SGM LEKTRA AGRITHERM T5 User manual

AGRITHERM T5
Display unit for small plants
technical documentation GB Rev. of 05/03/2021

Page 2 of 24 www.sgm-lektra.com
AGRITHERM T5 - index
INDEX
1-WARRANTY
2-PRODUCT
3-TECHNICAL FEATURES
4-DIMENSIONS
5-INSTALLATION
6-ELECTRIC CONNECTIONS
7-DISPLAY
8-SETTING
9-SETTING UPDATE
10-FACTORY TEST AND QUALITY CERTIFICATE
page 3
page 4
page 5
page 6
page 7
page 9
page 17
page 19
page 21
page 24

Page 3 of 24
www.sgm-lektra.eu
Products supplied by SGM LEKTRA are guaranteed for a period of 12 (twelve) months from delivery date
according to the conditions specified in our sale conditions document.
SGM LEKTRA can choose to repair or replace the Product.
If the Product is repaired it will maintain the original warranty terms, whereas if the Product is replaced it will have
12 (twelve) months of warranty. The warranty will be null if the Client modifies, repairs or uses the Products for
other purposes than the normal conditions foreseen by instructions or Contract.
In no circumstances shall SGM LEKTRA be liable for direct, indirect or consequential or other loss or damage
whether caused by negligence on the part of the company or its employees or otherwise howsoever arising out of
defective goods.
1-WARRANTY
AGRITHERM T5 - warranty

Page 4 of 24 www.sgm-lektra.com
AGRITHERM T5 - product
2-PRODUCT
2.1 IDENTIFICATION
Every instrument is supplied with an adhesive plate with the main data:
2
Model: AGRITHERMT5
Input power: 24 Vdc ±20%
Max: 400mA @ 24Vdc,Class2
Serial number: TM0041800103
1. Model
2. Power supply
3. Serial Number
12 3 4
5
1. Ethernet
2. USB Host
3. COM1 RS-232, RS-485 2W/4W
COM3 RS-485 2W
4. Removable power connector
5. Skintop M20x1.5
1
2
3
VERSION FRONT PANEL VERSION WALL OR DIN RAIL

Page 5 of 24
www.sgm-lektra.eu
3-TECHNICAL FEATURES
Display
4.3” TFT color LCD resistive touch screen, 480 x 272 resolution, LED backlight (Life Time >30000h)
Digital port
USB 2.0 (1x) for set up upload. COM port: COM1 RS485 Isolated Half Duplex for TM probes connection or MUX02
RTC battery
Integrated
Power supply
Version “A” 24Vdc ±20%
Version “B” 85-230Vac (50/60Hz) ; 24Vdc/ac
Consumption
Version “A” Max 500mA, 12W@24Vdc
Version “B” Max 14W (display + with 10 points)
Dimensions l x h x w (mm)
Version “A” 128x102x32
Version “B” 183.5x250x126
Drilling template for panel mounting version “A” (mm)
119x93
Mounting
Version “A” front panel
Version “B” wall or DIN rail, with ABS enclosure with transparent lid
Frontal IP rating
Version “A” IP65 / NEMA4 - Version “B” IP66
Storage temperature
-20°÷60°C
Working temperature
0÷50°C
Relative humidity
10÷90% (not condensing)
Power supply for optional relay module
20.4÷28.8Vdc
Power consumption for optional relay module
2.5W
Mounting for optional relay module
DIN rail
Optional relay module output
< 250Vac, 30Vdc - 2A for single contact
Optional relay module storage temperature
-25°÷+70°C
Optional relay module working temperature
5÷55°C
Optional relay module Relative humidity
5÷95% (not condensing)
AGRITHERM T5 - technical features

Page 6 of 24 www.sgm-lektra.com
AGRITHERM T5 - dimensions
4-DIMENSIONS
4.1 MECHANICAL DIMENSIONS VERSION “A/D”
102mm
128mm
92mm
118mm
32mm
126mm 183.5mm
250mm
4.2 MECHANICAL DIMENSIONS VERSION “B/E”

Page 7 of 24
www.sgm-lektra.eu
AGRITHERM T5 - installation
5.1 PANEL MOUNTING VERSION “A/D”
Secure the instrument into the arranged hole (119x93mm) using the provided brackets and screws.
(Screw torque: 0.3÷0.45 Nm for reaching waterproof eect and preventing the panel from being deformed)
5-INSTALLATION

Page 8 of 24 www.sgm-lektra.com
AGRITHERM T5 - installation
5.2 WALL OR DIN RAIL MOUNTING VERSION “B/E”
• Installation must be only performed by qualified personnel and in accordance with local governing regulations.
• Make sure that the housing material is compatible with environmental conditions. In case of outdoor installation it is
recommended to protect the unit from the direct sunlight and from the rain.
• An improper use of the unit can cause serious injuries to operators and damages to the product and to the connected
equipments.
125mm
183.5mm
35mm
149mm

Page 9 of 24
www.sgm-lektra.eu
AGRITHERM T5 - electrical connection
6.1 ELECTRICAL CONNECTION VERSION “A/D” (PANEL MOUNTING)
CONNECTION TO TM PROBES (n.5 max) VIA MODBUS PORT
MODBUS connection to TM probes must be made with 2 wires in COM1 [RS485]:
• Pin 1 > B
• Pin 2 > A
6-ELECTRICAL CONNECTION
B
A
+
-
SCH
B
A
+
-
SCH
B
A
+
-
SCH
TM 1 TM 2
B
A
+
-
SCH
TM 25
B
A
+
-
SCH
B
A
+
-
SCH
24Vdc
0V
SCH
24Vdc supply - min. 500mA
Female connector 9 pin
5
4
3
21
GND
678 9
6.2 POWER SUPPLY CONNECTION 24VDC
24Vdc power supply must be connect to the removable power connector.
Ground
0V
+24Vdc
B
A
MUX02
5
4
3
21
GND 678 9

Page 10 of 24 www.sgm-lektra.com
AGRITHERM T5 - electrical connections
6.3 TERMINAL CONNECTION VERSION “B”
1) Separate the power cables of the Agritherm T5 from the signal cables
2) Remove the plugs of the cable glands and open the lid unscrewing the screws.
3) Insert the cables into the transmitter through the cable glands.
4) Close the lid and tighten the cable glands.
6.4 HUMIDITY INFILTRATIONS
In order to avoid humidity infiltrations inside the enclosure it is recommended:
- to use a cable with outer diameter of 6÷12mm and to fully tighten the M20 cable glands.
- to close the lid well
- to position the cable so that it forms a downward curve at the M20 output; in this way the
condensate and/or the rain water will tend to drip from the bottom curve.

Page 11 of 24
www.sgm-lektra.eu
AGRITHERM T5 -electrical connection
6.5 ELECTRIC CONNECTIONS VERSION B (WALL MOUNTING)
We suggest to connect TM probes (n.25 max) to AgrithermT5 as shown below.
In case of number of probes greater than 25, it’s necessary to provide an external 24Vdc power supply.
B
A
+
-
SCH
B
A
+
-
SCH
B
A
+
-
SCH
TM 1 TM 2
B
A
+
-
SCH
TM 25
B
A
+
-
SCH
B
A
+
-
SCH

Page 12 of 24 www.sgm-lektra.com
AGRITHERM T5 - electrical connections
It is possible to make an electric star connection with max. 3 TM probes, but the max. cable length between
AgrithermT5 and TM must be 25m.
B
A
+
-
SCH
B
A
+
-
SCH
B
A
+
-
SCH
B
A
+
-
SCH
B
A
+
-
SCH
B
A
+
-
SCH
TM 1 TM 2 TM 3

Page 13 of 24
www.sgm-lektra.eu
AGRITHERM T5 - electrical connections
B
A
MUX02
B
A
MUX02
B
A
MUX02
It’s possible to make a star connection with max 3 MUX02, but the maximum length of the connection cable between
AGRITHERT5 and MUX02 must not exceed 25m.

Page 14 of 24 www.sgm-lektra.com
AGRITHERM T5 - electrical connections
6.6 ELECTRICAL CONNECTIONS FOR WALL MOUNT (“E” VERSION)WITH EXTERNAL
OPTIONAL RELAY MODULE
We suggest to connect TM probes (n.25 max) to AgrithermT5 as shown below. In case of number of probes greater
than 25, it’s necessary to provide an external 24Vdc power supply for probes and relay module.
B
A
+
-
SCH
B
A
+
-
SCH
B
A
+
-
SCH
TM 1 TM 2
B
A
+
-
SCH
TM 25
B
A
+
-
SCH
B
A
+
-
SCH
+ - S/S X0 X1 X2 X3 X4 X5 • •
C0 Y0 Y1 C2 Y2 Y3 • •• •
24VDC IN
B1-10MR2-D24
+
-
SCH
B1-CM5
+
-
+
-24Vdc

Page 15 of 24
www.sgm-lektra.eu
AGRITHERM T5 - electrical connections
+ - S/S X0 X1 X2 X3 X4 X5 • •
C0 Y0 Y1 C2 Y2 Y3 • •• •
24VDC IN
B1-10MR2-D24
+
-
SCH
B1-CM5
+
-
+
-24Vdc
B
A
MUX02
B
A
MUX02
B
A
MUX02
B
A
B
A
B
A
The series connection between MUX02 and AGRITHERMT5 is recommended, as shown in the following wiring diagram.

Page 16 of 24 www.sgm-lektra.com
AGRITHERM T5 - electrical connections
6.7 ELECTRICAL CONNECTIONS FOR PANEL MOUNT (“D” VERSION)WITH EXTERNAL
OPTIONAL RELAY MODULE
B1-10MR2-D24 external relay module must be connected to COM3 port with connection interface B1-CM5
as shown below.
+ - S/S X0 X1 X2 X3 X4 X5 • •
C0 Y0 Y1 C2 Y2 Y3 • •• •
24VDC IN
B1-10MR2-D24
C0
Y0
R
Y1
R
Load
Load
Fuse
~
AC/DC
Power
B1/B1z -- PLC
+
-
SCH
B1-CM5
C2
Y2
R
Y3
R
Load
Load
Fuse
~
Female connector 9 pin
5
4
3
21
GND 678 9
Y0 = PRE-ALARM threshold contact
Y1 = ALARM threshold contact
Y2 = COMMUNICATION fault alarm contact
Y4 = Not used

Page 17 of 24
www.sgm-lektra.eu
AGRITHERM T5 - display
7.2 TEMPERATURES DISPLAY
The temperatures detected by the probes are automatically and cyclically shown on the display.
The system automatically scrolls the pages every 20 seconds.
The values in yellow indicate that the average temperature has been exceeded and the values in red
indicate that the maximum temperature has been exceeded.
Scrolling notices (in yellow and red) indicate which probe is detecting a temperature alarm.
7-DISPLAY
The operator can proceed with a manual scroll by Taping UP ARROW (next probe) and DOWN ARROW
(previous probe).
INFO key opens the pop up window of System Info. With LEFT ARROW the display will go back to previous page.
28.75
28.87
29.18
29.50
30.00
30.68
31.12
31.50
32.18
37.50
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
PROBE 1
59 PREALARM - PROBE 1 16:40:59
59 ALARM - PROBE 1 16:43:59
16:43:13 29/05/2018
7.1 KEYS LEGEND
UP ARROW DOWN ARROW LEFT ARROW
SETUP INFO ENTER

Page 18 of 24 www.sgm-lektra.com
Tap on SETUP button to enter the setting menu.
Password entering:
Open the drop-down list ▼ and select USER, then Tap on “password” field for the input keypad.
Digit the default password 12345 (which can be modified in the advanced settings) and Tap ENTER.
To enter the setting menu Tap ENTER again.
AGRITHERM T5 - setting
8-SETTING
Tap LEFT ARROW to go back to SET UP menu.
8.1 THRESHOLD
Tap on “THRESHOLD” to modify the displayed temperature alarm thresholds.
Tap on the grey value field to display the input keypad and digit the value. Tap ENTER to confirm.
Tap LEFT ARROW to go back to SET UP menu.
THRESHOLD PASSWORD
DATE/TIME LANGUAGE
SET UID TM BRIGHTNESS
INFOAUTO SCROLL
30.00
35.00
PREALARM TEMPERATURE
ALARM TEMPERATURE
TEMPERATURE ALARM THRESHOLDS
ALARM SILENCE
USERUSER
PASSWORD

Page 19 of 24
www.sgm-lektra.eu
AGRITHERM T5 - setting
8.2 DATE/CLOCK
Tap on “DATE/CLOCK” to modify day, month, year, hour, minutes or seconds.
Tap on the date field to display the input keypad and proceed with the modification.
Tap ENTER to confirm.
Tap LEFT ARROW to go back to SET UP menu.
8.3 SET UID TM
Push on “SET UID TM” to access UID address settings. (Only for UID from 9 to 35).
In order to set UID on TM probe, proceed as follow:
1) Disconnect the probe that needs new UID setting.
2) Set the first 4 dip switch ON, others on OFF.
3) Connect the probe to AGRITHERMT5 and turn on power supply.
4) Push on “STARTING THE PROCEDURE”.
5) Pushing on “NEW UID ADDRESS” a numeric keypad will appear. Set the UID value
6) The window “STORED UID ADDRESS?” will confirm the right setting.
The function “TM INITIALIZATION” is usefull in case of auto-setup for new electronic units of TM probes (E.g. electronic
parts replacement); for auto-setup proceed as follow:
1) Disconnect the probe that needs to be setted.
2) Set the first 4 dip switch ON, others on OFF.
3) Connect the probe to AGRITHERMT5 and turn on power supply.
4) Push on “START PROCEDURE”.
5) Push on “TM INITIALIZATION”.
Premendo su FRECCIA SINISTRA si torna alla pagina precedente.
8.4 AUTO SCROLL
Push on “AUTO SCROLL” to access the settings.
Act on switch to enable or disable the automatic pages scroll function.
8.1.2 ALARM SILENCE (ONLY FOR VERSION WITH RELAY ALARM MODULE)
Press the “ALLARM SILENCE” key to reset the relay alarm condition.

Page 20 of 24 www.sgm-lektra.com
AGRITHERM T5 - setting update
8.5 PASSWORD
Tap on “PASSWORD” to modify the default password.
Tap on the empty field to display the input keypad and digit the new password.
Tap “ENTER” to confirm, and then “ENTER” again to save it.
Tap LEFT ARROW to go back to SET UP menu.
USER
CHANGE PASSWORD
8.6 LANGUAGE
Tap on “LANGUAGE” and select the ag corresponding to the required language:
• Italian
• English
• French
• Spanish
• German
• Portuguese
• Russian
• Chinese
Tap LEFT ARROW to go back to SET UP menu.
8.7 BRIGHTNESS
Tap on BRIGHTNESS to adjust the display brightness.
Tap LEFT ARROW to go back to SET UP menu.
8.8 INFO
Tap on “INFO” to display the instrument data.
Tap LEFT ARROW to go back to SET UP menu.
Table of contents
Other SGM LEKTRA Monitor manuals