Sonnen-batterie Eco Series User manual

Sonnenbatterie eco
Operation and Installation Instructions
KD 129 - Version 1.04-1-EN
Subject to amendment and additions

0
Manufacturer
Sonnenbatterie GmbH
Am Riedbach 1
87499 Wildpoldsried / Germany
Emergency-Hotline: + 49-(0)8304-92933-444
info@sonnenbatterie.de
Service
◮For service contact one of the following in this order:
•The contractor that installed your storage system.
You can find details of how to contact the contractor on the inside of the door of the storage system or in the
installation and startup report.
•Your Sonnenbatterie service partner.
You will find them on the Internet page www.sonnenbatterie.de.
◮Enter your postal code in the window on the start page.
Then you will see details of how to contact the service partner.
These operation and installation instructions are for use
with the following hardware and software versions:
Hardware version: 7.00
Software version: 3.07
Publication date of these operation and installation instructions:
August 14, 2015
2 von 88 KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN

0Contents
Contents
1 About these instructions 5
1.1 Target groups ................ 5
1.2 Designations used in document ....... 5
1.3 Explanation of symbols ........... 5
2 Safety 6
2.1 Proper use .................. 6
2.2 Incorrect use ................. 6
2.3 Requirements of personnel ......... 6
2.4 General safety instructions ......... 6
2.4.1 What to do in case of fire / impor-
tant information for fire-fighters . . 7
2.5 Warnings ................... 7
3 Product description 9
3.1 Technical data ................ 9
3.2 Nameplate .................. 9
3.3 Energy flow in household .......... 9
3.4 Operating principle ............. 10
3.5 Feed-in power limitation ........... 11
3.6 Intelligent charge management ....... 12
4 Storage and transport 14
4.1 Storage .................... 14
4.1.1 Ambient conditions for storage . . . 14
4.1.2 Storing battery modules ....... 14
4.2 Transport .................. 14
4.2.1 Ambient conditions for transport . . 14
4.2.2 Transporting battery modules . . . . 14
4.2.3 Inspecting for transport damage . . 15
4.2.4 Compensating temperature after
transport ............... 16
4.2.5 Placing storage system ....... 16
5 Assembly 17
5.1 Delivery package ............... 17
5.2 Tools needed ................. 18
5.3 Unpacking storage system .......... 18
5.4 Choosing location .............. 18
5.4.1 Requirements of location . . . . . . 18
5.4.2 Minimum spacing .......... 18
5.5 Assembling storage system ......... 19
5.5.1 Attachment material ........ 19
5.5.2 Drilling holes ............ 20
5.5.3 Fitting wall bracket ......... 20
5.5.4 Joining cabinets ........... 21
5.5.5 Placing levelling mat . . . . . . . . 21
5.5.6 Suspending storage system in wall
bracket ................ 21
5.5.7 Screwing storage system in place . . 22
5.5.8 Attaching edge guard ........ 22
5.5.9 Flachband-Erder anbringen . . . . . 23
5.5.10 Fitting screwed cable glands . . . . 23
5.5.11 Fitting/removing side wall ..... 24
6 Electrical connection 25
6.1 Working on electrical installation distributor 25
6.1.1 Placing components in distributor . 25
6.1.2 Wiring components in distributor . . 26
6.2 Routing cables into storage system . . . . . 27
6.3 Connecting Ethernet cable ......... 27
6.4 Electrical connection of storage system . . . 28
6.5 Connecting Modbus cable .......... 29
6.5.1 Setting power meters ........ 33
6.6 Using extra connections ........... 34
6.6.1 Connecting battery emergency stop
switch ................ 34
6.6.2 Connecting self-consumption switch 35
6.6.3 Connecting combined heat and
power unit .............. 35
6.6.4 Connecting heat pump ....... 36
6.6.5 Connecting PV reduction . . . . . . 38
6.6.6 Connecting PV cutout ....... 39
6.6.7 Emergency power .......... 39
6.7 Installing battery modules .......... 40
6.8 Subsequent battery add-on ......... 44
7 Starting up 45
7.1 Startup checklist ............... 45
7.2 Activating storage system .......... 45
7.3 Adapting software settings ......... 46
7.3.1 Data for PV system ......... 46
7.3.2 Setting postal code for PV forecast . 46
7.4 Selftest .................... 46
7.4.1 Addressing battery modules . . . . . 47
7.4.2 Cabling battery modules . . . . . . 47
7.4.3 Number of battery modules . . . . . 47
7.5 Startup report ................ 48
7.6 Automatic full charging ........... 48
7.6.1 Automatic full charging earlier . . . 48
7.6.2 Automatic full charging later . . . . 48
KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN 3 von 88

Contents 0
8 Shutting down 49
8.1 Shutting down storage system ....... 49
8.1.1 Shutting down in emergency . . . . 49
8.1.2 Ramping down storage system . . . 49
9 Operation 50
9.1 Operating status ............... 50
9.1.1 Standby operating status . . . . . . 50
9.1.2 Charge operating status ....... 50
9.1.3 Discharge operating status . . . . . 50
9.2 Operating mode ............... 51
9.2.1 Automatic mode ........... 51
9.2.2 Manual mode ............ 51
10 Software 52
10.1 Operating touch panel ............ 52
10.1.1 Navigating in touch panel . . . . . . 52
10.2 Description of screen pages ......... 52
10.2.1 Start page .............. 52
10.2.2 Overview page ............ 53
10.2.3 Menu page .............. 53
10.2.4 Operating mode page ........ 54
10.2.5 Switch consumer page ....... 54
10.3 Making settings ............... 55
10.3.1 Enabling changed settings . . . . . . 55
10.3.2 Operating entry window ....... 56
10.3.3 Screen page Settings – Storage sys-
tem – Product info ......... 57
10.3.4 Screen page Settings – Storage sys-
tem – Pattern ............ 57
10.3.5 Screen page Settings – Charge pat-
tern – General ............ 58
10.3.6 Screen page Settings – Charge pat-
tern – Service ............ 58
10.3.7 Screen page Settings – Generator –
PV – General ............ 59
10.3.8 Screen page Settings – Generator –
CHP ................. 59
10.3.9 Screen page Settings – Consumer . 60
10.3.10 Screen page Settings – BMS – Gen-
eral .................. 60
10.3.11 Screen page Settings – Touch panel
– Time and language . . . . . . . . 60
10.3.12 Screen page Settings – Touch panel
– Screen ............... 61
10.3.13 Installing software update . . . . . . 62
11 Internet access 63
11.1 Connecting to Internet ........... 63
11.2 Internet portal ................ 63
11.2.1 Logging in on portal ......... 63
11.2.2 Overview page ............ 64
11.2.3 Status page ............. 64
11.2.4 Control page ............. 64
11.2.5 Pattern ............... 66
11.2.6 Forecast ............... 68
11.3 Smartphone app ............... 69
11.3.1 Installation and configuration . . . . 69
11.3.2 Operating smartphone app . . . . . 69
12 Maintenance and service 70
12.1 Maintenance ................. 70
12.1.1 Maintenance of battery modules . . 70
12.2 Performance check ............. 70
12.3 Servicing storage system .......... 70
12.3.1 Cleaning screen ........... 70
12.3.2 Cleaning cabinet ........... 70
13 Troubleshooting 71
13.1 Fault display on screen ........... 71
14 Recycling and certificates 72
15 Overview plans 73
15.1 Connections of storage system ....... 73
15.2 Electrical connection ............ 75
15.2.1 Electrical connection with three-
phase PV inverter or generator . . . 75
15.2.2 Modbus connection ......... 77
15.2.3 Connection of DC leads ....... 78
15.2.4 Connection of BMS communication
leads ................. 80
16 Appendix 83
16.1 Startup report ................ 83
4 von 88 KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN

1CHAPTER 1. ABOUT THESE INSTRUCTIONS
1 About these instructions
These instructions explain installation and operation of the
Sonnenbatterie eco. Note the following:
◮Read the instructions carefully before starting to use
the battery.
◮Keep the instructions close to the battery for ready
reference.
1.1 Target groups
This document is intended for the following groups of per-
sons:
•Operators of the storage system
•Qualified electricians (7→ 2.3 p. 6)
Certain activities may only be carried out by qualified elec-
tricians. The sections in the document referring to this are
indicated as follows:
Qualified electrician!
1.2 Designations used in document
Full designation Designation in document
Sonnenbatterie eco Storage system
1.3 Explanation of symbols
Warnings
SIGNAL WORD
Warning indications in this document are
marked by a warning triangle.
Additional signal words indicate the nature and
severity of consequences if measures to avert a
hazard are not observed.
The following signal words are used in the document:
•CAUTION means a possible threatening hazard.
Moderate to fairly serious bodily injury can result.
•WARNING means a possible threatening hazard.
Serious to critical bodily injury can result.
•DANGER means an immediate hazard. Serious to
critical bodily injury can result.
Material damage
Attention
The possibility of material damage is indicated in this doc-
ument by the signal word Attention.
Important information
Important information not concerning hazards
for humans or material is indicated by this sym-
bol.
Other symbols
Symbol Meaning
◮Step of action
1. 2. 3. Steps of action in defined sequence
a) b) c) Step of action in defined sequence (second level)
•Bullet / Accentuation
- Bullet / Accentuation (second level)
7→ Pointer to elsewhere in document
KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN 5 von 88

CHAPTER 2. SAFETY 2
2 Safety
2.1 Proper use
Incorrect or improper use can endanger the life of the user
or a third party, impair the working of the product, or cause
damage to property.
•Use the storage system only to store electrical energy.
It is not intended for any other purpose.
•Proper use also includes observing and following
these operation and installation instructions plus all
accompanying product documentation.
Failure to observe the warranty terms and the
information contained in these operation and
installation instructions cancels entitlement to
all warranty and guarantee claims.
2.2 Incorrect use
◮Do not use the storage system in vehicles.
◮Do not use the storage system in potentially explosive
areas (flour dust, sawdust, etc).
◮Do not expose the storage system to direct sunlight.
◮Do not use the storage system in areas in which the
ammonia content of the air exceeds 20 ppm.
◮Do not use the storage system in areas where corrosive
gases are present.
◮Do not operate the storage system at an altitude of
more than 2000 meters (asl).
◮Do not operate the storage system outside the permissi-
ble ambient temperature range of 5
➦
C to 30
➦
C.
◮Do not operate the storage system outside the permissi-
ble humidity range of max. 90 %, non-condensing.
2.3 Requirements of personnel
Installation and startup of the storage system following
the operation and installation instructions may only be per-
formed by qualified electricians. The electrician conducting
the work must satisfy all the following criteria:
•Electrician from an installation company certified by
Sonnenbatterie GmbH.
•Electrician properly acquainted with applicable direc-
tives and standards.
•Electrician who has participated in certification train-
ing of Sonnenbatterie GmbH.
2.4 General safety instructions
◮Only use the storage system in its original state without
unauthorized alterations and in perfect technical condition.
◮Ensure adherence to the following when fitting and con-
necting the storage system and PV system:
•National directives and regulations
•Specifications of professional associations, associa-
tion for technical inspection (T¨
UV), association for
electrical, electronic and information technologies
(VDE)
•Technical connection requirements (TAB) of the par-
ticular power utility
•National and international rules and specifications
◮Make sure all protective devices work correctly.
◮Observe requirements of the place of installation.
(7→ 5.4.1 p. 18)
◮Carefully read these operation and installation instruc-
tions.
6 von 88 KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN

2CHAPTER 2. SAFETY
2.4.1 What to do in case of fire / important
information for fire-fighters
Despite all the care that goes into electrical design it is
still possible for a fire to occur. Or a fire in the vicinity can
cause the storage system to catch fire. A fire can release
substances contained in the battery modules.
◮Observe the warning Risk of injury / burns through es-
caping electrolyte (7→ p. 8).
Consequently you should proceed as follows in the event of
a fire in the storage system or its surroundings:
◮Only firemen wearing proper protective clothing (includ-
ing gloves, masks, breathing apparatus) may enter the
room with the burning storage system.
◮A fire in the storage system can be extinguished by con-
ventional agents.
◮The use of water is advisable to cool the battery mod-
ules and thus prevent the thermal runaway of modules that
are still intact.
Information on battery modules:
•The battery modules have a rated voltage of 51.2
Vdc and are thus in the range of protective extra-low
voltage (below 60 Vdc).
•The battery modules contain no metallic lithium.
2.5 Warnings
This section deals with warnings that must always be ob-
served when working with the product.
DANGER
Danger to life through electric shock!
If the door to the cabinet is open, there is dan-
ger to life through electric shock if you touch
components inside the storage system.
◮Do not remove any plastic covers or sealed
parts.
◮By no means reach under covers.
DANGER
Danger to life through electric shock!
Observe the following if conducting any electri-
cal work on the storage system:
◮Disconnect the storage system.
◮Disconnect the back-up fuse.
◮Follow the five safety rules.
◮Have electrical jobs only carried out by qual-
ified persons.
WARNING
Danger to life through electric shock!
Even if the power supply from the public grid
is interrupted, parts of the electrical installation
can still be live. The storage system continues
to deliver electrical energy (using the optional
emergency power supply), so it has to be dis-
connected separately.
◮Cut out the electricity in the house.
◮Disconnect the storage system.
Attention
Damage to battery modules through exhaustive dis-
charge!
If not connected to the public grid the battery modules can
be damaged by exhaustive discharge.
◮Do not disconnect the storage system from the public
grid for an extended period.
KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN 7 von 88

CHAPTER 2. SAFETY 2
WARNING
Risk of burns!
Very high shortcircuit currents are possible!
Observe the following when working with
battery modules:
When the fused connector is plugged in, a
battery module is active. So there is voltage
across the plus and minus contacts of the
battery module (rated voltage of battery
modules 51.2 Vdc). Unplugging the fused
connector deactivates the battery module.
Here there is no voltage across the plus and
minus contacts of the battery module. So
you can work on a battery module without
risk if all interconnected battery modules are
deactivated.
Working on DC circuit:
◮Take off metal jewellery of any kind that
could cause a shortcircuit.
◮Disconnect the storage system.
◮Disconnect the back-up fuse.
◮Remove the orange-coloured fused connector
on all battery modules.
WARNING
Risk of injury / burns through escaping elec-
trolyte
The battery modules fitted in the storage sys-
tem are guarded by a number of security de-
vices for safe operation. Despite diligent con-
struction battery cells inside the battery mod-
ules can still degrade or pyrolyze in the event
of mechanical damage, heat or a fault. The
possible effects are:
•High development of heat on the surface
of battery cells.
•Electrolyte can escape.
•Escaping electrolyte can ignite and pro-
duce an explosive flame.
•Smoke from burning battery modules
can irritate skin, eyes and throat.
Consequently proceed as follows:
◮Do not open battery modules.
◮Do not damage battery modules mechani-
cally (puncture, deform, take apart, etc).
◮Do not modify battery modules.
◮Keep battery modules away from water (ex-
cept to extinguish a fire in the storage system).
◮Do not allow battery modules to heat up and
only operate them in the allowed temperature
range (7→ 5.4.1 p. 18).
◮Do not shortcircuit battery modules / bring
them into contact with metal.
◮By no means continue to use a battery mod-
ule after a short.
◮Do not exhaustively discharge battery mod-
ules.
If contents escape:
◮Do not enter the room.
◮Avoid by all means contact with the escap-
ing electrolyte.
◮Contact your fire department.
◮Contact the following
Emergency hotline: +49-(0)8304-92933-444
8 von 88 KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN

3CHAPTER 3. PRODUCT DESCRIPTION
3 Product description
3.1 Technical data
Sonnenbatterie eco 246
Usable capacity 2,0 kWh 4,0 kWh 6,0 kWh
Cell chemistry Lithium-iron phosphate
Size HxWxD in cm 90/62/36 90/62/36 160/62/36
Weight 110 kg 140 kg 200 kg
Rated power 1500 W 2500 W 3000 W
Rated voltage 230 Vac 230 Vac 230 Vac
Rated current 6,5 Aac 11 Aac 13 Aac
IP rating IP 21
Safety class I (ground conductor)
Ambient temperature 5
➦
C to 30
➦
C
Max. humidity 90 % - non-condensing
Sonnenbatterie eco 8 10 12
Usable capacity 8,0 kWh 10,0 kWh 12,0 kWh
Cell chemistry Lithium-iron phosphate
Size HxWxD in cm 160/62/36 160/62/36 160/62/36
Weight 230 kg 260 kg 290 kg
Rated power 3300 W 3300 W 3300 W
Rated voltage 230 Vac 230 Vac 230 Vac
Rated current 14,5 Aac 14,5 Aac 14,5 Aac
IP rating IP 21
Safety class I (ground conductor)
Ambient temperature 5
➦
C to 30
➦
C
Max. humidity 90 % - non-condensing
Sonnenbatterie eco 14 16
Usable capacity 14,0 kWh 16,0 kWh
Cell chemistry Lithium-iron phosphate
Size HxWxD in cm 160/62/36 160/62/36
Weight 310 kg 340 kg
Rated power 3300 W 3300 W
Rated voltage 230 Vac 230 Vac
Rated current 14,5 Aac 14,5 Aac
IP rating IP 21
Safety class I (ground conductor)
Ambient temperature 5
➦
C to 30
➦
C
Max. humidity 90 % - non-condensing
3.2 Nameplate
The nameplate, properly identifying the storage system, is
on the left side. You need the details from this nameplate
for correct use and if you have questions for service. The
nameplate shows the following:
•Model designation
•Model number
•Version (hardware)
•Technical data of storage system
3.3 Energy flow in household
The Sonnenbatterie eco is an intelligent storage system
that registers and controls energy flow in the household,
that in the following illustration being of importance:
1
43
5
6
2
Figure 3.1: Energy flow
[1] Generation
[2] Consumption
[3] Charging
[4] Discharging
[5] Feed-in
[6] Import
The storage system can directly influence the following en-
ergy flow:1
•Charging: Charging conducts energy into the bat-
tery.
•Discharging: During discharging part of the energy
intermediately stored in the battery is given off.
1Generation can also be influenced (throttled) to satisfy the constraint of a feed-in limit.
KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN 9 von 88

CHAPTER 3. PRODUCT DESCRIPTION 3
•Consumption: Consumption can be increased by
connection of loads.
The purpose of controlling energy flow is to minimize en-
ergy import and optimize energy consumption.
3.4 Operating principle
The following is an example of operation of the storage
system together with a PV system. Instead of the latter it
is possible to connect other sources like a combined heat
and power unit.
PP
5
6
2
1
4
7
8
3
Figure 3.2: Schematic
[1] PV system or other source
[2] Inverter of PV system
[3] Generated power meter
[4] Consumed power meter
[5] Battery
[6] Inverter of storage system
[7] Household supply
[8] Up/down meter
The DC current generated by a PV system [1] is converted
into AC current by an inverter [2]. The meters [3] and [4]
register momentary electric power in watts (W). Meter [3]
registers momentary power generation, meter [4] momen-
tary power consumption in a household [7]. If generation
is higher than consumption, excess electric power is saved
in the storage system. The battery [5] is charged. When it
is charging, the inverter of the storage system [6] converts
the fed AC current into DC current for the battery [5]. If
generation is less than consumption, electric power comes
from the storage system. The battery [5] is discharged, and
the inverter of the storage system [6] converts DC current
from the battery [5] into AC current. The up/down meter
[8] calculates the electric energy fed into the public grid
and that drawn from it in kilowatt hours (kWh).
10 von 88 KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN

3CHAPTER 3. PRODUCT DESCRIPTION
3.5 Feed-in power limitation
Depending on when a photovoltaic system was installed, it
may be subject to what is called feed-in power limitation.
Meaning that the power fed in from a photovoltaic system
is limited at the point where it ties to the grid.
Example
Rated power of PV system 10 kWp
Power limitation to 60%
Maximum feed-in power 6 kW
In this example the feed-in power must not exceed 6 kW.
The following illustration is an example of generation by a
PV system in the course of the day.
76 %
Autarkie
letzte7Tage
P
t
60%
12:00
1
23
4
Figure 3.3: Example: feed-in power limitation to 60 % of rated
power
[1] First measure: charging of storage system.
[2] Second measure: connection of peak loads by wireless socket.
[3] Third measure: connection of loads linked to self-consumption
switch.
[4] Midday peak that may not be fed into grid.
To avoid throttling of generation – and thus loss of en-
ergy – the surplus is first saved in the storage system [1]
and consumption is increased by connecting loads [2] and
[3]. Generation is only throttled if these measures do not
produce the desired limitation.
Feed-in power limitation is activated by your electrician
when installing the system according to Settings – Genera-
tor – PV – General (7→ 10.3.7 p. 59).
In what follows you can read details of the steps to imple-
ment feed-in power limitation. Follow the steps one after
the other. Only move on to the next step if a particular
step does not lead to the wanted reduction.
1. Charging of battery
Surplus energy is fed into the battery, which there-
fore needs sufficient capacity. So on sunny days it
is often advisable to reduce charging power in the
morning hours to leave enough battery capacity for
midday. For this reason there is intelligent control of
charging pattern (7→ 3.6 12).
2. Connection of loads linked to wireless sockets (op-
tional). ). These loads must be marked as peak loads
through the portal (7→ 11.2.4 p. 64). The loads are
activated as soon as the feed-in limit is exceeded.
Loads are deactivated again if the limit drops after 3
minutes.
3. Activation of self-consumption switch (7→ 10.3.9
p. 60)so that loads possibly on the hardwired switch-
ing output are connected.
4. Reduction of PV power over integrated switching
contact on inverter. This limits the photovoltaic in-
verter to set power output. The requisite is support
of the inverter for power reduction over a switching
contact or an external solution (e.g. a solar data log-
ger). Configuration and connection are by a qualified
electrician.
5. Cutout of photovoltaic system if all the steps have
no effect (exceeding of maximum feed-in power de-
spite activation of all points on average 10 minutes).
The photovoltaic system remains separated from the
grid for a period of at least 5 minutes (configured by
electrician) and is afterwards automatically released.
KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN 11 von 88

CHAPTER 3. PRODUCT DESCRIPTION 3
3.6 Intelligent charge management
Charge management means intelligent control of the charg-
ing pattern of the storage system. The purposes of this
intelligent control are as follows:
•Storage of the midday peak in the storage system
(sufficient storage capacity must be available).
•Full charging of the storage system by the evening
(to provide sufficient energy for the nighttime).
Intelligent charge management only works in storage sys-
tems operated together with PV systems, and in which
feed-in power limitation is activated.
Operating principle of intelligent charge man-
agement
The storage system is connected over the Internet to a
server. This produces a generation and consumption fore-
cast for the particular day. The generation forecast is based
on the following data:
•Forecast weather data
•Rated power of PV system
•Orientation of PV system
The consumption forecast is calculated from consumption
in recent weeks. The following illustration is an example
of such a consumption and generation forecast.
P
t
60%
12:00 13:00 14:00 15:00 16:00 17:0011:0010:00
9:008:00
7:006:00
10 kW
9 kW
8 kW
7 kW
6 kW
5 kW
4 kW
3 kW
2 kW
1 kW
0 kW
Figure 3.4: Generation and consumption forecast
[yellow] Forecast generation
[blue] Forecast consumption
Here, for example, average consumption of 0.5 kW is ex-
pected between 10:00 and 11:00 h plus generation of ap-
prox. 9 kW. Subtracting consumption from generation pro-
duces the forecast surplus (here 8.5 kW). In the following
illustration the consumption bars are shifted to the top of
the generation bars.
P
t
60%
12:00 13:00 14:00 15:00 16:00 17:0011:0010:00
9:008:00
7:006:00
10 kW
9 kW
8 kW
7 kW
6 kW
5 kW
4 kW
3 kW
2 kW
1 kW
0 kW
Figure 3.5: Forecast surplus
[yellow] Forecast generation
[blue] Forecast consumption (shown on forecast generation)
In this example, feeding in the entire surplus at midday
would violate the feed-in power limitation (at 6 kW). So
it is best if as much energy surplus as possible above the
feed-in limit is used to charge the battery.
Without intelligent charge management the storage system
would immediately save the surplus (through to maximum
charging power – see Technical data) in the battery.
P
t
60%
12:00 13:00 14:00 15:00 16:00 17:0011:0010:00
9:008:00
7:006:00
10 kW
9 kW
8 kW
7 kW
6 kW
5 kW
4 kW
3 kW
2 kW
1 kW
0 kW
Figure 3.6: Charging pattern without intelligent charge manage-
ment
[yellow] Forecast generation
[blue] Forecast consumption
[green] Charging of storage system
In the example looked at here, this pattern would mean
that the storage system was fully charged before midday.
So the subsequent surplus above the feed-in power limita-
tion could no longer be stored in the battery. To satisfy the
feed-in power limitation (7→ 3.5 p. 11) the power of the
PV system would have to be reduced. That would mean
both a financial and an energy loss.
12 von 88 KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN

3CHAPTER 3. PRODUCT DESCRIPTION
Intelligent charge management tries to prevent such prema-
ture full charging of the battery. So early in the morning
the server sends a daily charging plan to the storage sys-
tem. Intelligent charge management tries to prevent such
premature full charging of the battery. So early in the morn-
ing the server sends a daily charging plan to the storage
system.
P
t
60%
12:00 13:00 14:00 15:00 16:00 17:0011:0010:00
9:008:00
7:006:00
10 kW
9 kW
8 kW
7 kW
6 kW
5 kW
4 kW
3 kW
2 kW
1 kW
0 kW
Figure 3.7: Charging pattern with intelligent charge manage-
ment
[yellow] Forecast generation
[blue] Forecast consumption
[green] Charging of storage system
In the example, charging of the storage system is avoided
in the morning hours. At midday the storage system is
charged just enough to satisfy the feed-in power limitation.
Adaptation of intelligent charge manage-
ment
After starting up, intelligent charge management has to
match to local conditions. The generation forecast de-
pends for example on the weather forecast, on orientation
and roof angle, shadowing, etc of the PV system. A con-
sumption forecast depends on your energy use and your
electric loads or household appliances. Enabling intelligent
charge management to adapt to this complexity of factors
calls for consumption and generation statistics. None of
the data needed are present after installation of the stor-
age system, so they need to be collected. For this reason
intelligent charge management takes approx. 7 days to cal-
ibrate. During this time there may be unwanted charging.
After the 7 days intelligent charge management will have
adapted to your personal generation and consumption pro-
file.
Limits of intelligent charge management
The effectiveness of intelligent charge management de-
pends on how accurate generation and consumption fore-
casts are.
•The wrong weather forecast will mean a poor gener-
ation forecast.
•A consumption forecast depends on figures of recent
weeks. So heavily fluctuating consumption has a neg-
ative effect on the quality of the forecast. The more
constant your consumer pattern, the preciser is the
consumption forecast.
KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN 13 von 88

CHAPTER 4. STORAGE AND TRANSPORT 4
4 Storage and transport
4.1 Storage
Storage is the condition where the energy storage system
is not connected to the public grid and there can be no
automatic charging of battery modules.
4.1.1 Ambient conditions for storage
◮Ensure the following ambient conditions for storage of
the energy storage system and battery modules:
•Ambient temperature must be between
0 and 40
➦
C.
•Otherwise maintain the same ambient conditions as
at the point of operation (7→ 5.4.1 p. 18).
4.1.2 Storing battery modules
Attention
Damage / destruction of battery modules through ex-
haustive discharge!
Battery modules discharge to a minimum degree by them-
selves during storage. But exhaustive discharge can damage
or destroy them. So only store battery modules for a lim-
ited period.
◮When put into storage battery modules must have 85 %
charge (as delivered).
◮Do not store battery modules for longer than 6 months.
◮At the latest after 6 months fit battery modules into the
storage system and start it up.
◮During storage the orange-coloured fused connector must
not be plugged into a battery module. 1
4.2 Transport
4.2.1 Ambient conditions for transport
◮Ensure the following ambient conditions for transport of
the energy storage system and battery modules:
•Ambient temperature must be between
-15 and 40
➦
C.
•Otherwise, if possible, maintain the same ambient
conditions as at the point of operation
(7→ 5.4.1 p. 18).
4.2.2 Transporting battery modules
Lithium-ion batteries rank as hazardous goods, so take the
following precautions when transporting battery modules:
◮Observe general regulations of the transport carrier and
all legal regulations.
◮Seek advice from an external hazardous goods consul-
tant.
Data of battery modules relevant for transport:
•Hazardous goods class: 9
•UN number: UN3480 ”
lithium-ion batteries“
•Weight of battery module: 29 kg
1When delivered (original packaging), the orange-coloured fused connector is not plugged in.
14 von 88 KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN

4CHAPTER 4. STORAGE AND TRANSPORT
4.2.3 Inspecting for transport damage
The haulier can be held responsible for transport damage
if it is possible to prove that the damage was caused dur-
ing actual transport. Therefore it is important to strictly
follow these instructions.
Transport damage is categorized as open or hidden. Open
damage is when damage to the goods in transit or their
packing is visible externally. Hidden damage is when the
packing looks undamaged but the contents are then found
to be damaged.
A complaint of open transport damage must be lodged
with the haulier immediately. For hidden transport dam-
age a complaint must be lodged as follows:
Haulier Complaint at latest
Deutsche Post / DHL / parcel services 24 hours
Forwarder 7 days
1Checking freight documents
◮Check the address of the recipient and number of pieces
in the presence of the haulier.
2Checking freight for open damage
◮Check the packing and transported goods for external
damage in the presence of the haulier.
If damage is determined:
◮Check the freight also for hidden damage in the presence
of the haulier.
◮Check the shockwatch attached to the packing of the
main cabinet in the presence of the haulier.
Figure 4.1: Shockwatch
If blue powder appears in the arrow of the shockwatch, the
storage system was not transported properly.
◮In this case you should refuse to accept the freight.
3Checking freight for hidden damage
Conduct this also in the presence of the haulier.
◮Unpack the delivery and inspect it for hidden damage
(not immediately visible).
◮Do not continue to unpack if you determine transport
damage.
◮Immediately photograph the damage.
◮Refuse to accept the freight if it is heavily damaged.
4Documenting damage
◮Note the damage you find as ”
Conditional acceptance“
on the bill of consignment and have this confirmed by the
signature of the haulier. The registration number of the
delivering vehicle on the bill of consignment should also be
documented.
5Complaining of damage
◮Complain of damage immediately to the responsible
haulier and the manufacturer.
◮Send the bill of consignment / waybill with confirma-
tion of damage by the haulier plus photographic evidence
by e-mail to the manufacturer.
It is not possible to settle a claim for damages
without submission of the above papers within
deadlines for complaints.
Inspecting battery modules
CAUTION
Risk of injury by using damaged battery
modules!
Using these can cause the release of substances
injurious to health.
◮Unpack battery modules immediately after
transport and check them for transport dam-
age.
If deformation, damaged casing, leaking con-
tents, etc is determined:
◮Do not use the battery modules under any
circumstances.
◮Contact the service point.
KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN 15 von 88

CHAPTER 4. STORAGE AND TRANSPORT 4
4.2.4 Compensating temperature after
transport
Attention
Damage to storage system by condensation
If the temperature of the storage system upon delivery is
less than the ambient temperature of the room, condensa-
tion may form inside the storage system and damage it.
◮Check the inside of the storage system for condensation
before installing it.
◮Only install the storage system if there is no condensation
on the outside surfaces.
If the storage system was transported at a temperature less
than 0
➦
C, proceed as follows:
1. Set up the storage system at a suitable location
(7→ 5.4.1 p. 18).
2. Open all cabinet doors.
3. Leave the storage system standing with opened cab-
inet doors for at least 24 hours.
4. Only then should you put the storage system into
operation.
4.2.5 Placing storage system
Qualified electrician!
WARNING
Risk of injury by lifting storage system!
The storage system is heavy.
◮Wear steel-toe boots when setting it up.
◮Ensure a firm stand.
◮Observe the correct tilting positions.
◮Use a manual or electric trolley to cross
steps.
Figure 4.2: Suitable trolley for placement
Permitted tilting
◮The storage system may be tilted by a maximum angle
of 90
➦
. The screen must always face upwards.
90°
Figure 4.3: Correct (left) and wrong (right) tilting
16 von 88 KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN

5CHAPTER 5. ASSEMBLY
5 Assembly
5.1 Delivery package
◮Check that the delivery package is complete:
11 1 4 7
3 6 9
2
1
kvarh
N L1 L2 L3
EINGÄNGE
1x 1x 2x
2x 1x 3x
11 1 4 7
3 6 9
2
1
kvarh
N L1 L2 L3
EINGÄNGE
1x
3x
1x
2x
6x
3x
4x
5x
2x 1x
6x
30345 30346 10491 1049210441 10955 10503
10996 10969 600106 10257
20586
10557
10920 10922
52081
1056210448
10924
1x
B+
B
-
IJ1101MNB(SY)
140822
3000862
ON
1 2 34
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
I/F(1) I/F(2)
45003
1x
11082 11040
45001
1x
45002
1x
10921 10923
2x 1x
1x
1x
10928
1x
10929
1x
11041
1x
1x
20769
20837
1x
20838
1x
600034
2x
10870 11123 10551
1x 1x 1x
20878
1x
20878
1x
Scope of delivery - main cabinet
18 2519 20 21 22 23 24 26 3427 28 29 30 31 32 33
38 39 40
41 3
235 36 37
5 6 7 8 9 10 11 12 1713 14 15 16
20844
1x
Scope of delivery - extension cabinet Scope of delivery - battery module
2x
600232
1x
10368
1x
10369
Figure 5.1: Delivery package
[10257] Wire end ferrule, insulated 0.25 mm2
[10368] Stopper for screwed cable gland M16
[10369] Stopper for screwed cable gland M20
[10441] Terminal block
[10448] Hexagon socket-head screw M6 x 16
[10491] Fuse holder
[10492] End plate
[10551] Spring washer M6
[10557] Shield transition incl. cable tie
[10562] Washer M6
[10870] Hexagon nut M6
[10924] Seal insert, double
[10920] Screwed cable gland M16 x 1.5
[10921] Check nut M16 x 1.5
[10922] Screwed cable gland M20 x 1.5
[10923] Check nut M20 x 1.5
[10928] Screwed cable gland M25 x 1.5
[10929] Check nut M25 x 1.5
[10955] Fine-wire fuse 315 mA, slow-blow
[10969] Wire end ferrule, bare 4 mm2
[10996] Screw anchor W-SA 7.5
[11040] Screen page communication lead, short
[11041] Screen page communication lead, long
[11082] Fused connector
[11123] Contact washer
[20586] Wall bracket
[20769] Levelling mat
[20837] DC lead, black
[20838] DC lead schwarz
[20844] Socket connector set for terminal strip X1
[20878] Sticker numbering battery modules
[30345] Generated power meter
[30346] Consumed power meter
[45001] Main cabinet
[45002] Add-on cabinet
[45003] Battery module
[52081] File with operation and installation instructions and access data
[600034] Edge protection strip
[600106] Wire end ferrule, insulated 0.75 mm2
[600232] Cable tie 2.5 x 100 mm
KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN 17 von 88

CHAPTER 5. ASSEMBLY 5
5.2 Tools needed
Tool
Stripping tool
Wire stripping pliers
Wire end ferrule crimping pliers
Concrete drill (6 mm)
Pencil
DC voltmeter
Hot-air gun
Hexagon socket spanner A/F 5
Phillips screwdriver PH 2
Folding meter stick
Trolley
Hammer drill
Screwdriver 0.4 x 2.5
Screwdriver 1 x 5.5
Spanner A/F 10
Spanner A/F 13
Spanner A/F 22
Spanner A/F 27
Spanner A/F 34
Shrink-on sleeve
Spirit level
Extra tools may be needed to modify the elec-
trical installation.
5.3 Unpacking storage system
◮Unpack the storage system.
◮Remove all protective foil.
5.4 Choosing location
5.4.1 Requirements of location
•Ambient temperature 5
➦
C to 30
➦
C
•Humidity max. 90 %, non-condensing
•Room for installation may be ventilated
•Altitude maximally 2000 meters asl
•Adequate fire prevention measures
(smoke alarm recommended)
•Free of dust
•Free of corrosive and explosive gases
•Free of vibration
•Level floor suitable for heavy weight
•Easy access for assembly team
•Observe any local building regulations
5.4.2 Minimum spacing
50cm 5cm
B+T
T
10cm
B
76 %
Autarkie
letzte7Tage
Figure 5.2: Minimum spacing
[B] Width of storage system (7→ 3.1 p. 9)
[T] Depth of storage system (7→ 3.1 p. 9)
If a standby generator is to be installed at a
later date, the minimum spacing between stor-
age system and ceiling is approx. 30 cm.
18 von 88 KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN

5CHAPTER 5. ASSEMBLY
5.5 Assembling storage system
WARNING
Risk of injury by lifting storage system!
The storage system is heavy.
◮Wear steel-toe boots when setting it up.
◮Ensure a firm stand.
◮Assemble the storage system upright.
◮Assemble the storage system in a team of at
least two.
•Place storage systems with an add-on cabinet on the
floor.
•Screw storage systems without an add-on cabinet to
the wall.
Figure 5.3: Standup (left) and suspended from wall (right)
5.5.1 Attachment material
WARNING
Risk of injury by inadequate attachment!
The storage system is heavy and calls for high-
quality attachment material, otherwise it could
fall and lead to injuries.
◮Use only the correct attachment material.
No liability can be accepted for damage or in-
juries as a result of inadequate attachment.
Attachment to concrete walls
•Only use the supplied screw anchors ([10996] in Fig-
ure 5.1 p. 17) on concrete walls.
•Only attach the suspended storage system to a con-
crete wall.
Specification of screw anchor
Manufacturer W¨
urth
Designation Screw anchor W-SA 7.5
Number 0901017502
Drill diameter 6 mm
Torque to anchor 15 Nm
Proceed as follows to attach screw anchors:
1. Drill a hole (diameter 6 mm).
2. Clean the hole.
3. Put the screw anchor in place.
4. Tighten the screw anchor (15 Nm torque).
Screw the anchor into the hole without any plas-
tic wall plug.
Attachment to non-concrete walls
•Here you must not use the supplied screw anchors.
•The storage system may not be suspended from the
wall, it must be stood on the floor.
•You can still use the wall bracket to prevent the stand-
ing storage system from toppling over.
KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN 19 von 88

CHAPTER 5. ASSEMBLY 5
5.5.2 Drilling holes
200 100100
110 110
620
1610
1532
838,5
710
1
2
128,5
822
900
10
3
Figure 5.4: Drilling template (all dimensions in mm)
[1] Drilled holes for wall bracket
[2] Additional drilled holes
[3] Levelling mat
Tools needed
Pencil
Spirit level
Folding meter stick
Hammer drill
Concrete drill (6 mm)
For main cabinet suspended from wall1:
◮Drill the holes labelled (1) and (2).
For standup storage system (consisting of main cabinet and
add-on cabinet):
◮Drill the holes labelled (1).
For a main cabinet suspended from the wall it
is still advisable to keep to the dimensions in
Figure 5.4. Because if you add to the storage
system at a later date you need not drill any
new holes.
5.5.3 Fitting wall bracket
Figure 5.5: Fitting wall bracket
Tools needed
Spanner A/F 13
◮Fit the bracket to the wall with the attachment material
(7→ 5.5.1 p.19).
1Suspension is only possible from concrete walls.
20 von 88 KD-129 Sonnenbatterie eco Manual Version 1.04-1-EN
Table of contents