
Startco Engineering Ltd. Page 1
SE-701 Ground-Fault Monitor Rev. 4
Pub. SE-701-M, December 19, 2000.
1. GENERAL
The SE-701 is a microprocessor-based ground-fault
monitor for resistance-grounded and solidly grounded
systems. Its output relay can operate in the fail-safe or non-
fail-safe mode for undervoltage or shunt-trip applications,
and the output contacts are isolated for use in independent
control circuits. Additional features include LED and
fluorescent-flag trip indication, autoreset or latching trips
with front-panel and remote reset, self test, 0 to 5-V analog
output, inputs for standard and sensitive ground-fault
current transformers, CT verification for sensitive current
transformers, digital selector switches, switch-selectable
algorithms for fixed-frequency or variable-frequency
applications, and an inhibit that can be enabled to prevent
the output relay from operating during a high-current
ground fault.
Ground-fault current is sensed by a standard CT with a
1-A or 5-A secondary, or by a sensitive CT with a 5-A-
primary rating (EFCT-1 or EFCT-2). The trip level of the
ground-fault circuit is digital-switch selectable in 1%
increments from 1% to 99% of the CT-primary rating. Trip
time is digital-switch selectable with 10 settings from 0.05
to 2.5 s.
2. OPERATION
2.1 CONFIGURATION-SWITCH SETTINGS (See Fig. 1)
2.1.1 RELAY OPERATING MODE
The SE-701 has one output relay with isolated normally
open and normally closed contacts. Switch 1 is used to set
the operating mode of the output relay. In the fail-safe
mode, the output relay energizes when the ground-fault
circuit is not tripped. In the non-fail-safe mode, the output
relay energizes when a ground-fault trip occurs.
2.1.2 INHIBIT
Switch 2 is used to select Class I or Class II operation. In
the INHIBIT OFF position, high-current inhibit is off for
Class I operation. In the INHIBIT ON position, high-
current inhibit is on for Class II operation. If high-current
inhibit is on and ground-fault current escalates above eleven
times the CT-primary rating before the ground-fault circuit
trips, the output relay will not operate until ground-fault
current falls below eight times the CT-primary rating. This
feature allows the overcurrent protection to operate in
applications where the ground-fault current can be larger
than the interrupting capacity of the device tripped by the
SE-701.
2.1.3 CT VERIFICATION
Switch 3 is used to enable CT verification with the
EFCT-1 or EFCT-2. In the CT VERIFY ON position, a
trip will occur if the CT is disconnected. The red LED will
flash to indicate a trip initiated by a CT fault. Switch 3 must
be in the CT VERIFY OFF position when a 5-A- or 1-A-
secondary CT is used.
2.1.4 FILTER SELECTION
Switch 4 is used to select the filtering algorithm for a
fixed-frequency (50/60 Hz) or variable-frequency
application. The fixed-frequency algorithm allows lower
trip levels to be used by rejecting harmonics that can cause
nuisance tripping. The variable-frequency setting should be
used if the CT is located on the load side of a variable-
frequency drive.
2.1.5 AUTORESET
Switch 5 is used to select autoreset or latching trips. See
2.2.3.
2.2 FRONT-PANEL CONTROLS
2.2.1 GROUND-FAULT TRIP LEVEL
The % CT PRIMARY selector switches are used to set
the ground-fault trip level as a percentage of the CT-primary
rating. Protection against arcing ground faults in a solidly
grounded system requires a ground-fault CT that will not
saturate below the operating value of the overcurrent
protection. For reliable ground-fault detection, the ground-
fault trip level must be substantially below the prospective
ground-fault current. To avoid sympathetic tripping, the
trip level must be above the charging current of the largest
feeder; and to eliminate nuisance tripping, surge current
must not saturate the CT. See Startco Technical
Information 11.1 available at www.startco.ca.
2.2.2 GROUND-FAULT TRIP TIME
The TIME (s) selector switch is used to set the ground-
fault trip time for coordination with upstream and
downstream ground-fault devices. Coordination requires
the same trip level for all ground-fault devices in a system
and the trip time to progressively increase upstream. The
amount of equipment removed from the system will be a
minimum if the first ground-fault device to operate is the
one immediately upstream from the fault.
2.2.3 RESET
The reset circuit responds only to a momentary closure so
that a jammed or shorted switch will not prevent a trip. The
front-panel RESET switch is inoperative when the remote-
reset terminals (6 and 7) are shorted.