
SRH pg. 12
INLET AIR BOX
FRONT PANEL
OF INLET
AIR BOX
STUB
ADDITIONAL 4 IN. (10.2 CM) I.D.
COMBUSTION AIR SUPPLY
PIPING (NOT INCLUDED)
4 IN. (10.2 CM) I.D. FLEX DUCT
18 IN. (46 CM) LONG
SUPPORT
PIPING AS
NECESSARY
INLET AIR SLEEVE
(SEAM TO BE AT TOP)
OPTIONAL INLET
AIR SLEEVE
(SEAM TO BE AT TOP)
TWO HOSE CLAMPS
INLET AIR
COLLAR (COMES
WITH BURNER)
COMBUSTION AIR SUPPLY
WARNING This heater is NOT an explosion-proof heater. Where the possibility of exposure to
volatile or low flash point material exists, it could result in severe personal injury, death,
and/or property damage. Consult your local fire marshal or insurance agency to
determine the classification of the building to be heated.
•Atmospheric air for combustion may come from either outdoors or indoors (within the building).
•Installation of combustion air supply must comply with the instructions, drawings, and installation notes provided in this
section. OUTDOORS INDOORS
•When combustion air is to be taken from inside a tightly
sealed or closed building, an opening must be installed
to supply the burner with sufficient air for combustion.
•The opening must be made so that for every 1,000
BTUH (293W) of the total input of all gas-fired
equipment, one square inch (6.5cm2) or more of free
area opening is provided.
•If combustion air is supplied from the space to be
heated, it must be free of contaminants that may
interfere with the proper and safe operation of the
heater. Some contaminants like halogenated
hydrocarbons or other corrosive elements may shorten
the life of the heater.
IMPORTANT
•In buildings contaminated with excessive dust or dirt,
containing substances which when combined with flame
and exhaust products result in corrosive gases, or those
under a negative pressure, combustion air must be
taken from outdoors.
•Outdoor air supply may be accomplished by bringing air
inside through piping from either the roof or wall as
shown below.
•The inlet air roof venting cap (roof) or inlet air box (wall)
must be located at least (3) three feet (1m) away from
any vent termination and in a manner preventing
blockage by snow.
•Components used to bring in outdoor air, when supplied
by others, must be identical to those specified in this
manual and be Metalbestos brand or equal. NO
SUBSTITUTIONS.
•Single wall 4” (10.2cm) I.D. galvanized pipe of 20 gauge
(.035” or 0.9mm) or schedule 40 PVC is recommended
for combustion air supply piping.
•For all systems, total linear (straight) pipe run must not
exceed (35) thirty-five feet (11m) within the building.
•A 90-degree elbow is equivalent to (10) ten linear feet
(3m).
•No more than (2) two 90-degree elbows are permitted.
•It may be necessary to insulate the inlet air supply
piping to eliminate condensation from warm inside air
on the piping.
•In very extreme cases, for protection against any
exterior contaminants, a blower enclosure may be
installed. The outdoor air supply piping is then attached
to the enclosure.
•DO NOTuse collapsible material such as dryer duct as
a substitute for single wall galvanized or PVC pipe. It
will restrict air flow to the burner causing improper
operation.
•Inlet air piping must be well supported since additional
stress may be encountered due to be expansion during
heater operation.
•Outdoor air must be free of contaminants.
•A minimum of (3) three feet (1m) is required between
the inlet air roof venting cap and the nearest vertical
vent terminal on a roof.
•If the inlet air roof venting cap is within (10) ten feet
(3m) of a vertical vent terminal on a roof, the vertical
vent terminal must be at least (12) twelve inches
(30.5cm) higher than the inlet air roof venting cap.
THRU-THE-WALL THRU-THE-ROOF