Thomas&Betts RZ405 User manual

Mfg No. 164771, Page 1
APPLIESTO: Installation
ModelCAUA
Gas-Fired, Indoor, Vertical (Upflow)
Power-Vented Heater
INSTALLATIONFORMRZ405(VersionB)
ObsoletesFormRGM405(VersionA)
Table of Contents
InstallationandOperation ...........................Paragraphs1-18 .... Pages 1-18
OptionalAccessories ................................ Paragraphs19-21 .. Pages 19-21
CheckInstallationandStart-Up ........................Paragraph22 .. Pages 22-23
FORYOURSAFETY
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
otherappliance.
Index ByPageNo.
Belt Drive ............................................. 15
Blower Motor and Drive ...................... 15
Check/Test/Start-Up ............................. 22
Clearances ................................................ 2
Combustion Air ...................................... 4
Combustion Air Proving Switch ........... 15
Concentric Adapter............................ 2, 5
Condensate Drain .......................... 14
Confined Space Installation .................. 10
Cased Cooling Coil (Model ACU)..... 2, 19
Control Location Illustration ................. 15
Dimensions ............................................. 3
Index ByPageNo.
Motor Amps......................................... 16
Mounting the Heater .............................. 2
Start-Up................................................. 22
Thermostat ........................................... 14
Uncrating and Preparation ...................... 2
Vent and Combustion Air ....................... 4
Determine Type of Vent ........................ 4
Power Vent Only Installation .........10-11
Separated-Combustion Installation ... 5-9
Warranty .................................................. 2
WiringDiagrams .............................. 17-19
Index ByPageNo.
Discharge Plenum (Optional) ............ 2, 21
Duct Connections ................................. 12
Electrical Supply and Connections....... 14
Filter Cabinet (Optional) .................. 2, 20
Gas Piping and Pressures ..................... 13
Gas Valve .............................................. 16
General .................................................... 1
Hazard Intensity Levels ......................... 2
Ignition System..................................... 16
Inlet Base (Optional) ......................... 2, 21
Installation Codes ................................... 2
Mixing Cabinet (Optional) .............. 2, 21
FORYOURSAFETY
What to do if you smell gas:
• Donottryto light any appliance.
• Donottouchanyelectrical switch; do not
useany phoneinyourbuilding.
• Immediatelycallyour gas supplierfroma
neighbor'sphone.Followthegassupplier's
instructions.
• Ifyoucannotreachyourgassupplier,call
yourfiredepartment.
WARNING:Improperinstallation,adjustment,
alteration, service, or maintenance can cause
property damage, injury, or death. Refer to this
manual.Forassistanceoradditionalinformation,
consulta qualifiedinstaller,serviceagency, orthe
gassupplier.
WARNING: Gas-fired appliances are not
designed for use in hazardous atmospheres
containingflammablevaporsorcombustibledust.
See Hazard Levels, page 2.
GENERAL
Installationshould bedoneby aqualifiedagency inaccordance with the
instructions in this manual and in compliance with all codes and re-
quirements of authorities having jurisdiction. The instructions in this
manual apply to the heater model shown below.
Model Description
CAUA Gas-Fired,
Power-Vented,
Vertical(Upflow)
Heater
C E R T I F I E D
REFERENCES:
Operation/Maintenance/Service Manual, Form RZ 405-OMS
Installation Manual for Model ACU Cooling Coil, RZ 405-CC
Gas Conversion Instructions for Model CAUA, RZ 405-GC
Model CAUA heaters are design-certified by the Canadian Standards
Association (CSA) to ANSI Z83.6 and CGA 2.6-M96 for industrial/
commercial installations in the United States and Canada. Heaters are
available for use with either natural or propane gas. The type of gas, the
firing rate, and the electrical characteristics are on the unit rating plate.
A Model CAUA heater requires installation of an inlet air duct or an
optional inlet air base and a supply duct or an optional discharge ple-
num. This heater may be installed as a separated-combustion system
(taking combustion air from outside) or as a power-vented system
(taking combustion air from the space where the heater is installed).
Installation Manual for Optional Filter Cabinet, RZ 405-FC
Installation Manual for Optional Mixing Box, RZ 405-MB
Installation Instructions for Optional Inlet Base, RZ 405-IB
Installation Instructions for Optional Discharge Plenum, RZ 405-DP

Form 405, Page 2
Separated-combustion units are designed to separate the air for com-
bustion and the flue products from the environment of the building in
which the unit is installed. Separated-combustion appliances are rec-
ommendedfor usein dust ladenand somecorrosive fume environments
or in buildings with negative pressure (up to .15" w.c.). If installed as a
separated-combustion system, the heater must be equipped with both
combustion air and exhaust piping to the outdoors. All Model CAUA
heaters must be vented to the outdoors.
WARNING:Shouldoverheatingoccur,orthegas
supplyfailtoshutoff,shutoffthemanualgasvalve
totheappliancebeforeshuttingofftheelectrical
supply.
WARNING:Do notusethisappliance ifanypart
hasbeenunderwater.Immediatelycallaqualified
service technician to inspect the appliance and
replace any gas control which has been under
water.
CAUTION: Do not locate the heater where it may
be exposed to water spray, rain or dripping water.
HAZARD INTENSITY LEVELS
1.DANGER:Failuretocomply willresultinsevere
personalinjuryordeathand/orpropertydamage.
2.WARNING:Failureto complycouldresultinsevere
personalinjuryordeathand/orpropertydamage.
3.CAUTION:Failureto complycouldresultinminor
personalinjuryand/orpropertydamage.
1. Installation Codes
Theseunits mustbeinstalled inaccordancewith localbuilding codes. In
the absence of local codes, in the United States, the unit must be in-
stalled in accordance with the National Fuel Gas Code ANSI Z223.1a
(latest edition). A Canadian installation must be in accordance with the
CAN/CGA B149.1 and B149.2 Installation Code for Gas Burning Ap-
pliances and Equipment. These codes are available from CSA Informa-
tion Services, 1-800-463-6727. Local authorities having jurisdiction
should be consulted before installation is made to verify local codes and
installation procedure requirements.
2. Warranty
Refer to the limited warranty information on the Warranty Card in the
"Owner's Envelope".
Warrantyisvoidif...
a. Wiring is not in accordance with the diagram furnished with the
heater.
b. The unit is installed without proper clearance to combustible
materials.
3. Uncrating and Preparation
This unit was test operated and inspected at the factory prior to crating
and was in operating condition. If the heater has incurred any damage in
shipment, file a claim with the transporting agency.
Checkthe ratingplate for thegas specificationsand electrical character-
istics of the heater to be sure that they are compatible with the gas and
electric supplies at the installation site.
Read this booklet and become familiar with the installation require-
ments of your particular heater. If you do not have knowledge of local
GENERAL (Cont'd)
5. Mounting
the Heater
Check the supporting structure to be used to verify that it has suffi-
cient load-carrying capacity to support the weight of the unit. The
heater must be level.
ApproximateNetWeight(lbs)
Size 150 200 250 300 350 400
Weight (lbs) 288 300 380 394 445 460
WARNING: Unit must be level for proper
operation.Donotplaceoraddadditional weight
to the heater. See Hazard Levels, page 2.
Determine the position of the heater with regard to venting, combus-
tion air, gas supply connection, electrical supply connection, and inlet
air opening. Either cut out the inlet air opening (requires tin snips or
aviation shears) now or when attaching ductwork or filter cabinet. Use
caution when cutting the opening as the cut edges of the metal will be
sharp. NOTE: If ordered with an optional inlet base, the heater is
shipped with a bottom inlet air opening.
requirements, check with the local gas company or any other local
agencies who might have requirements concerning this installation.
Before beginning, make preparations for necessary supplies, tools, and
manpower.
Shipped-Separate Accessories
•ConcentricAdapter andVent Terminal- If the heater is installed
as a separated-combustion system, a concentric adapter assembly
is required. The concentric adapter and parts are shipped in a sepa-
rate carton. Be sure that the shipped-separate carton is at the instal-
lation site. See Paragraph 7A.
•Filter Cabinet - The return air filter cabinet is shipped separately
for field installation over the inlet air opening of the heater. The inlet
air opening location is determined by the application. The filter
cabinet can attach at the opening on either the rear, the left side, or
right side of the unit. Follow the installation instructions included
with the cabinet.
•Cased Cooling Coil - Model ACU cooling coils are designed for
the Model CAUA heaters. The coil cabinet is shipped separately
for installation over the discharge opening of the heater.
•Mixing Cabinet - If outside air is desirable, a mixing cabinet with
dampers is available. The mixing cabinet is field attached to the rear
of the unit. Check to be sure that the mixing box is the configuration
ordered. Follow the installation instructions included with the
shipped-separate package.
•Inlet Base - If an optional inlet base is included, follow the instruc-
tions included with the inlet base to select the location. The heater
mounts on the inlet base; heater has a bottom inlet air opening.
•Discharge Plenum - The discharge plenum is shipped separately
for installation over the discharge opening of the heater. If the dis-
charge plenum and a cased cooling coil are part of the installation,
the discharge plenum is factory attached to the cooling coil casing.
Also, shipped with the heater are the parts needed to install a conden-
sate drain (needed if installing a cooling coil). Other shipped-separate
options could include a gas shutoff valve, a thermostat, a thermostat
guard, and/or a vent cap. Make sure all parts are at the site before
beginninginstallation.
4. Clearances
Unit must be installed so that
the clearances in the table are
provided for service and in-
spection and for proper spac-
ing from combustible con-
struction.
Required Clearances
(AllSizes)
Right Side 0" (0mm)
Left Side 0" (0mm)
Front 36" (914mm)
Rear 0" (0mm)
Bottom 0" (0mm)
Flue Connector 6" (152mm)
Top 1" (25mm)

Mfg No. 164771, Page 3
Corner indicators for cutting
inlet air opening
J
2-1/2 (64mm)
2-1/8 (54mm)
16
(406mm)
-5/8 (92mm)
1 (25mm)
1 -1/4
( 7mm)
Alternate
Gas
Connection
16
(406mm)
2-1/8 (54mm)
1-1/2 ( 8mm)
Corner indicators for
cutting inlet air opening
K
6. Dimensions
Figure1 -DimensionsofModelCAUA
NOTE: Composite drawings are
not proportional for all sizes.
Dimensions (inches + or - 1/8")
Size A B C D E F G H J K M N P
150 38 34-3/4 36 21 7-1/4 3-3/4 12-1/2 24 33 31 19 34 4-5/8
200 38 34-3/4 36 21 7-1/4 3-3/4 12-1/2 24 33 31 19 34 4-5/8
250 50 34-3/4 48 21 7-1/4 4-3/8 12-3/4 27-1/4 45 31 16 46 4-3/4
300 50 34-3/4 48 21 7-1/4 4-3/8 12-3/4 27-1/4 45 31 16 46 4-3/4
350 50 49-3/4 48 34 7 4-3/8 14-1/8 26-3/4 45 44 32 46 4-7/8
400 50 49-3/4 48 34 7 4-3/8 14-1/8 26-3/4 45 44 32 46 4-7/8
TopView
FrontView
Right
Side
View
Rear
View
Bottom
View
Dimensions (mm +or- 3)
Size A B C D E F G H J K M N P
150 965 883 914 533 184 95 318 610 838 787 483 864 117
200 965 883 914 533 184 95 318 610 838 787 483 864 117
250 1270 883 1219 533 184 111 324 692 1143 787 406 1168 121
300 1270 883 1219 533 184 111 324 692 1143 787 406 1168 121
350 1270 1238 1219 864 178 111 359 679 1143 1118 813 1168 124
400 1270 1238 1219 864 178 111 359 679 1143 1118 813 1168 124
Air Opening Dimensions
Supply Air (Discharge with duct flange) C x D
Inlet Air Opening (location selected by installer)
Right Side of Heater K x 16" (406mm)
Left Side* of Heater K x 16" (406mm)
Rear of Heater J x 16" (406mm)
Bottom of Heater M x N
*Right side is illustrated; corner indicators for open-
ing are the same on the left side.
A
C Plenum Opening
D
Plenum
Opening
B
EF
G
H
Electrical
(supply voltage)
Gas
4-1/8
(105mm)
6- /8
(162mm)
Combustion Air Cutout
150, 200 - 5 (127mm);
250, 00, 50, 400 - 6 (152mm)
Venter Outlet
150, 200, 250 -
5 (127mm);
00, 50, 400 -
6 (152mm)
2- /8 (60mm)
46-1/2
(1181mm)
24- /8
(619mm)
22-1/4
(565mm)
1/2 (1 mm)
Control Door
Blower Door
BOTTOM VIEW
Corner indicators for
cutting inlet air opening.
Control Side of Hater
M
N
P
2
(51mm)

Form 405, Page 4
7. Venting and Combustion Air
WARNING: The vent must be installed in
accordance with national and local regulations.
Failuretoprovideproperventing could result in
death,seriousinjuryand/orpropertydamage.This
unitmustbeinstalledwitha venttothe outsideof
thebuilding.Safe operation ofanypower-vented
gas-firedequipmentrequiresaproperlyoperating
ventsystem, correctprovisionforcombustionair,
andregular maintenanceandinspection.
WARNING: Units installed in multiples require
individual vent pipe runs and vent caps.
Manifolding of vent runs is not permitted due to
possiblerecirculationofcombustionproductsinto
the building and back pressure effects on the
combustionairprovingswitch.
Ventingmust bein accordance withthe NationalFuel Gas CodeZ223.1
or CAN/CGA B149.1 and B149.2, Installation Code for Gas Burning
Appliances and Equipment, and all local codes. Local requirements
supersede national requirements. Combustion air for this heater may be
either taken from the space or may be ducted from the outside using the
STEP 1 - Decide which Venting System to Install:
concentric adapter combustion air/vent system. Flue products must
always be vented to the outdoors.
Installation should be done by a qualified agency in accordance with
these instructions. The qualified service agency installing the vent or
vent/combustion air system is responsible for the installation.
Theventing orventing/combustionair systemsillustratedin thismanual
are the only ones approved for a Model CAUA heater. However, since
more than one system is approved and requirements vary depending on
the type of installation, the first step must be deciding which vent or
vent/combustion air system is going to be installed. Review the follow-
ing matrix of vent types and installation requirements. If there is any
doubt as to what type of vent is required, contact the equipment dis-
tributor before beginning installation.
Hazards of Chlorines - The presence of chlorine vapors in the com-
bustion air of gas-fired heating equipment presents a potential corro-
sion hazard. Chlorine will, when exposed to flame, precipitate from the
compound, usually freon or degreaser vapors, and go into solution with
any condensation that is present in the heat exchanger or associated
parts. The result is hydrochloric acid which readily attacks all metals
including 300 grade stainless steel.
Care should be taken to separate these vapors from the combustion
process. This may be done by installing a separated combustion sys-
tem and/or wise location of the furnace with regard to exhausters or
prevailing wind direction. Chlorine is heavier than air. This fact should
bekept in mindwhendetermininginstallation locations ofheatingequip-
ment and building exhaust systems.
Type of
Installation Type of Vent System
(Description/Instructions) Vent Configuration/Options
Required Type of VENT Pipe* Required
Horizontal Vent / Option CC6
(includes concentric adapter box,
exhaust terminal, and inlet air guard)
Vertical Vent / Option CC2
(includes concentric adapter box,
exhaust terminal, and combustion air
inlet)
Horizontal Vent / Option CC1
Vent Cap or field-supplied
equivalent (see page 11)
Use either vent pipe approved for a Category III
appliance OR appropriately sealed 26-gauge
galvanized steel or equivalent single-wall pipe. If
local code requires, the terminal section may be
double-wall pipe with a single-wall vent run.
Vent pipe listed above for a horizontal power-
vented system may be used, OR vent pipe
approved for a Category I heater may be used.
Single-wall pipe or double-wall (Type B) vent
pipe are suitable for use with a Category I heater.
If local code requires, the terminal section may be
double-wall pipe with a single-wall vent run.
Use either vent pipe approved for a Category III
appliance OR single-wall, 26-gauge or heavier
galvanized (or a material of equivalent durability
and corrosion resistance) vent pipe.
Power-Vented (uses a power
venter to draw combustion air
from the indoor space and
exhaust flue products to the
outdoors) - (follow
Instructions in Section 7B)
COMMERCIAL/
INDUSTRIAL
(Harmonized
ANSI Z83.8-1996
and Canadian
Standard
CAN/CGA2.6-
M96)
Separated-Combustion
(uses a power venter to duct
combustion air from outdoors
and exhaust flue products to
the outdoors) - (follow
Instructions in Section 7A)
At least 1/2 of the Equivalent
Vent Length is Vertical / Option
CC1 Vent Cap or field-supplied
equivalent (see page 11)
STEP 2 - Follow the instructions that apply to the type of vent being
installed
•Separated-Combustion -- requires air inlet pipe, exhaust vent pipe, and concentric adapter kit (Option CC2 or CC6)
Usingrequiredpipe(SeeTableabove), FOLLOW INSTRUCTIONS IN SECTION 7A
•Power Vent -- requires vent pipe and vent cap (Option CC1 or field-supplied Type L Breidert Air-x-hauster®or equivalent vent
cap) Usingrequiredpipe(SeeTableabove), FOLLOW INSTRUCTIONS IN SECTION 7B

Mfg No. 164771, Page 5
2 (51mm)
2 (51mm)
6 (152mm)
H
E
G
D
C
B
Figure2-AttachCombustionAirPipe
1) Remove door panel.
2) Cut out the hole.
3) Slide pipe down through hole.
4) If collar is oval, form pipe to fit. Attach pipe to collar with
sheetmetal screws and seal the connection.
Collarfor
connecting
combustionair
pipe
Usetinsnips
tocutout
holefor
combustion
airpipe
Venter
Outlet
3. Concentric Adapter
If installed as a separated-combustion unit, a concentric adapter
is required.
•Option CC2 and CC6 - The concentric adapter is a
metal box that attaches to the inside of the building. See
the illustrations and dimenstions in Figures 3A and 3B.
Option CC6 is horizontal; Option CC2 is vertical. (Op-
tion kits also include a vent terminal and combustion air
inlet or guard.)
Figure3A-ConcentricAdapterAssemblyinOptionsCC2andCC6
Figure3B-ConcentricAdapterBox
Dimensions-inches (mm)
CAUA 150,200 250,300,350,400
A5 (127) 6 (152)
B4 (102) 5 (127)
C4 (102) 4 (102)
D7-1/2 (191) 7-1/2
E5 (127) 5 (127)
F4 (102) 5 (127)
G16-1/2 (419) 16-1/2 (419)
H8 (203) 10 (254)
J6 (152) 8 (203)
7A. Venting and Combustion Air Requirements for Separated-Combustion
Installation (must use either Option CC2 or CC6)
Specific Requirements (read all before installing)
Comply with the specific requirements and instructions in the following paragraphs and illustrations.
1. Combustion Air Inlet
Diameter is 5" for Sizes 150 and 200 and 6" for Sizes 250, 300,
350, and 400.
Use tin snips or aviation shears to cut out the hole in the top of
the heater (See Figure 2). Insert the pipe through the hole and
attach it to the collar inside the heater. Seal the joint. (Larger size
heaters have oval collars. If the collar is oval, form the pipe to fit
the collar.)
2. Venter Outlet
The venter outlet size is 5" for Sizes 150, 200, and 250 and 6" for
Sizes 300, 350, and 400. A minimum length of 12" of straight
pipe is required at the venter outlet.
Side View - Sideofthe
AdapterBoxthatConnects
totheHeater
End View
Field-supplied vent
pipe passes
through the
rubber seal on the
concentric adapter
box, extending out
both sides of the
box
A = Diameter of the
Collar for attaching
the inside
Combustion Air Pipe
from the Heater
Top View oftheConcentricAdapter
BoxShowingAirFlow
= Combustion Air Flow
= Exhaust (Vent) Gas Flow
J = Diameter of the
Collar for attaching the
"Outside" Portion of the
Combustion Air Pipe
ViewofHeaterConnectionSide ViewofVentTerminalConnectionSide
Collar for outside portion of the
combustion air pipe (vent pipe
extends through the box
internally concentric to the
outside portion of the combustion
air pipe)
Collar for
connecting
indoor portion
of the
combustion
air pipe Install rubber seal
for vent pipe

Form 405, Page 6
Instructions and Requirements for Installing
Horizontal
Vent Terminal/Combustion Air Inlet
Option CC6
4. Pipe Diameter and Length
MaximumPipeLengthfromHeatertoConcentricAdapter-
minimumlengthis fivefeet(1524mm)
Model Pipe Diameter Maximum 90° Elbow 45° Elbow
CAUA Vent Inlet Air Length Equals* Equals*
150-200 5" 5" 40 ft 5 ft 2.5 ft
12.2 M 1524 mm 762 mm
250 5" 6" 50 ft 5 ft 2.5 ft
15.2 M 1524 mm 762 mm
300-400 6" 6" 50 ft 5 ft 2.5 ft
15.2 M 1524 mm 762 mm
*Reduce maximum length by this amount for each elbow.
7. Venting and Combustion Air (cont'd)
7A. Venting and Combustion Air Requirements for Separated-Combustion
Installation (must use either Option CC2 or CC6) (cont'd)
OptionCC6Package includes:
Qty Description 150, 250, 300,
200 350, 400
1 Complete Horizontal Vent Kit 157158 82131
(Same as Option CC6)
1 Concentric Box Assembly 155392 68404
(See Figures 3A and 3B)
1 Screened 155096 53316
Exhaust Assy
1 Inlet 151755 124940
Guard
4 #10-16x1/2" lg Screws (to 37661 37661
attach the inlet guard)
1 Rubber seal for vent pipe opening 164492 164493
in concentric adapter
1 Tube of high temperature (450°F) 53335 53335
silicone sealant
Concentric Pipes (the vent pipe runs concentric through the out-
door portion of the combustion air pipe) - Sizes 150 and 200 require
a 6" diameter combustion air pipe for outdoor portion and a 4" diam-
eter vent pipe through the concentric adapter to the terminal; Sizes
250-400 require an 8" diameter combustion air pipe for the outdoor
portion and a 5" diameter vent pipe through the concentric adapter to
the terminal.
Length depends on building construction; specific requirements are
included with the concentric adapter kit instructions.
5. Joints
Determined by type of pipe - Provide field-supplied vent pipe as
specified in the Table on page 4.
•If using single wall, 26-gauge or heavier galvanized pipe, secure
slip-fit connections using sheet metal screws or rivets. Seal all
joints. Seal combustion air pipe with pressure sensitive tape ordi-
narily used for warm-air ductwork. Seal flue exhaust pipe with
Either collar
or smaller
diameter pipe
Taper-type Connector
Secure joints with sheetmetal
screws and seal.
Field-supplied installation requirements:
• Thimble (a thimble is not required if wall is of non-combus-
tible construction)
• Flashing
• Vent pipes (see requirements on pages 4 and 6)
• Combustion air pipes (see requirements on pages 4 and 6)
Installation Instructions for Option CC6
1. Determine the location on the outside wall for the vent terminal
(Applies to all horizontal vent kits). In most applications, the terminal
would be on a level with the heater mounting height. Allow 1/4" per foot
downward pitch toward the terminal for draining of condensation.
The distance of the termination of the horizontal vent from adjacent public
walkways, adjacent buildings, openable windows, and building openings
must be in accordance with local codes or, in the absence of local codes,
must conform with National Fuel Gas Code. Local codes supersede all
provisions in these instructions and in the National Fuel Gas Code. Mini-
mum clearances for the horizontal vent terminal are as shown in the table on
page 7.
Products of combustion can cause discoloration of some building finishes
and deterioration of masonry materials. Applying a clear silicone sealant
that is normally used to protect concrete driveways can protect masonry
materials. If discoloration is an esthetic problem, relocate the vent or install
a vertical vent.
WARNING: All vent terminals must be positioned or
located away from fresh air intakes, doors and
windows to preclude combustion products from
entering occupied space. See Hazard Levels, page 2.
Reducer
Airflow
Figure4- Whenjoiningdifferentpipe diameters,usetaper-
typepipeconnectors
either tape suitable for 550°F (such as Option FA1, P/N 98266) or
high-temperature (450°F) silicone sealant.
•If using Category III vent pipe, follow the pipe manufacturer's in-
structions for joining pipe sections.
In Concentric Pipes (outdoor portion) from Concentric Adapter
Box to Air Inlet and Vent Terminal - Follow the installation instruc-
tions for the specific option (CC6 for horizontal vent; CC2 for vertical
vent).
Joints Requiring Taper-type Connections (See Figure 4) - When
the diameter of the pipe in the vent pipe run is different from the vent
pipe in the terminal section, the joint must be made with a taper-type
pipe connector. Install the connector no more than 6" (152mm) from the
concentric adapter box. A 5" to 4" reducer is required in the vent pipe on
Sizes 150 - 200; a 6" to 5" reducer is required on Sizes 300 - 400.
6. Support
Support horizontal runs every six feet (1829mm); do not rely on the
heater or concentric adapter for support of either horizontal or vertical
pipes.
7. Clearance
Clearance from the vent pipe to combustibles is 6" (152mm). Do not
enclose the vent pipe.
• Mounting brackets for concentric adapter box (or box may be
mounted flush, depending on building construction)
• Taper-type reducers as required (see requirements above)

Mfg No. 164771, Page 7
2. Prepare clearance hole through the outside wall for a 6"
diameter pipe (Size 150 or 200) or an 8" diameter pipe
(Size 250, 300, 350, or 400). Outside wall construction
thicknessshould bebetween 1" (25mm)minimum and30"
(762mm) maximum. The larger diameter combustion air
pipe serves as clearance for the exhaust pipe on non-com-
bustible construction. A thimble may or may not be re-
quired depending on wall construction and/or local codes.
3. Prepare the concentric adapter box.
3a) Determine whether field-supplied brackets are
required. The box must be positioned so that the
distance from the outside of the wall to the box is a
minimum of 12" (305mm). Maximum distance is 60"
(1524mm). If brackets are used, box should be angled
slightly to allow for downward pitch of pipes. If used,
attach brackets securely; do not leave any unsealed
holes in the adapter box.
If brackets are not used, when the box is installed,
position it tight against the wall.
3b)Install the rubberseal andthe ventpipe. Locate the
vent pipe opening (no collar) and place the rubber seal
around and over the edge of the metal.
Determine the length of the section of vent pipe by
adding the requirements. On the heater side of all Sizes
except CAUA 250, the vent pipe must extend no more
than 6" (152mm) (length limit does not apply to Size
250 because the pipe diameter does not change); plus
6" (152mm) through the box; plus bracket length; plus
the width of the wall; plus a minimum of 18" (457mm)
on the outside (if
the inlet air pipe
extends recom-
mended 2"
(51mm) beyond
the wall).
Lubricate the seal
and pipe with liq-
uid soap or a rub-
ber lubricant. (In-
stallation Tip:
Spray cooking oil
works well as a lubricant for this task.)
Being sure the pipe is in the proper flow direction,
slide the end through the box and push it out through
the rubber seal. Push evenly using caution not to dis-
place the seal from its position on the edge of the hole.
If the rubber seal moves, slide the pipe back slightly,
re-position the seal, and slide the pipe through again.
Position the vent pipe so that it will extend a minimum
of 16" past the end of the combustion air pipe. See
2 (51mm)
approx plus
wall thickenss
Vent Pipe - when a taper-type
reducer is required in
the vent pipe; the connection
must be no more than 6
(152mm) from the box.
Seal the seam in the vent pipe.
16 (406mm) minimum
Combustion air pipe
ield-supplied
mounting brackets
Collar for
combustion
air pipe.
Concentric Adapter Box
Install rubber seal in
vent pipe opening.
Vent low
Combustion
Air low
5A
Figure 5A. On all Sizes except 250, no more than 6" (152mm) of vent pipe
should extend out the heater side. Any time the pipe is re-positioned, re-check
the seal to be sure that it has not rolled. Adjust the pipe and seal until the pipe is
the correct length on each side of the box and the seal is over the edge of the hole
and tight to the entire circumference of the pipe.
3c) Attach the outside portion of the combustion air pipe to the box. Determine
the length by measuring the bracket length (if brackets are used), plus the wall
thickness, plus 2" (51 mm). The inlet pipe should extend beyond the outside
wall approximately 2" (51mm). Attach the inlet air pipe to the collar of the
concentric adapter with sheetmetal screws being careful not to penetrate the
vent pipe.
4. Attach the concentric adapter box to the wall. Insert
the vent pipe and combustion air pipe through the wall.
Push the concentric adapter box flush against the inside
wall or attach to the wall with the field-supplied brackets.
Caulk or flash inlet air pipe on the outside wall. Flashing is
field supplied.
5. Slide the inlet guard over the end of the vent pipe
and position it on the end of the combustion air pipe. See
Figure 5B. Attach the guard to the inlet air pipe with the
four 1/2" lg screws provided.
6.Position the ventcap onthe end ofthe ventpipe. Align the cap so that its baffle
strips are positioned on the horizontal and vertical centerlines (See Figure 5C).
Attach the exhaust cap to the vent pipe with sheetmetal screws.
Structure
Forced air inlet within 10 ft
(3.1m) 3 ft (0.9m) above
Combustion air inlet of
another appliance 6 ft (1.8m)
4 ft (1.2m) horizontally
4 ft (1.2m) below
1 ft (30cm) above
Electric meter, gas meter *
and relief equipment 4 ft (1.2m)
horizontally
Gas regulator * 3 ft (0.9m)
Adjoining building or parapet 6 ft (1.8m)
Adjacent public walkways 7 ft (2.1m) above
Grade (ground level) 7 ft (2.1m) above
Minimum Clearances for Vent
Termination Location (all
directions unless specified)
*Do not terminate
the vent directly
above a gas meter
or service regulator.
Door, window, or gravity air
inlet (any building opening)
Flashorcaulk
theinletair pipe
onthe outside
wall
5B
IMPORTANT: Install
exhaust cap with baffles
positioned on horizontal and
vertical centerlines as illustrated.
InletAirGuard 5C
First,attachtheinlet air guard;
Second,attachtheexhaustcap
7. Horizontal vent terminal/combustion air inlet Option CC6 is installed and ready
for connection to the heater.
8. Connect the Concentric Adapter Box to the Heater - Use the pipe specified
and joints required for type of pipe. If collar or opening at the heater or adapter are
different diameters from the pipe (use only diameters allowed on page 6), make joint
connection with field-supplied taper-type reducer or enlarger.
A minimum of 12" (305 mm) of straight pipe is required at the venter outlet.
Due to the high temperature, do not enclose the exhaust pipe or place pipe closer
than 6" (152 mm) to combustible material.
Installation of the horizontal vent and combustion air system on your separated-
combustion unit is complete. Refer to Figure 5D and verify that all installation
requirements are met. Continue to Paragraph 8.
Worksheet - Determine Length of
Vent Pipe through the Box
inches mm
Heater Side (max if + 6 152
diameterchanges)
Width of Box + 6 152
Bracket Length + __ ___
Width of Wall + __ ___
Terminal Side(min) + 18 457
Length of Pipe =

Form 405, Page 8
Figure5D-InstallationofaTypicalSeparated-
CombustionUnitwithHorizontalVentandCombustion
AirPipes(OptionCC6)
Building Overhang
3 ft (914mm)
minimum
6-15/16 (176mm)
Vent Pipe
- PITCH
TO
DRAIN
Adjoining
Building
3 ft (914mm)
minimum
Thimble Wall
16(406mm)
minimum
24(610mm)
minimum
IMPORTANT NOTE: Exhaust cap must be installed so the baffles
are positioned on horizontal and vertical centerlines.
Building Projection
6ft (1829mm)
minimum
Concentric Adapter Box
Combustion Air Pipe
(PITCH TO DRAIN)
"Through-the-Wall"Viewofatypical
installationofa horizontalvent/inletair
terminalandconcentricadapter
(OptionCC6)
7. Venting and Combustion Air (cont'd)
7A. Venting and Combustion Air Requirements for Separated-Combustion
Installation (must use either Option CC2 or CC6) (cont'd)
Instructions and Requirements for Installing a
Vertical
Vent Terminal/Combustion Air Inlet
(Requires Concentric Adapter Kit, Option CC2)
VerticalVentTerminal/CombustionAir Package
(OptionCC2)includes:
Field-supplied installation requirements:
•Thimble (a thimble is not required if wall is of non-
combustible construction)
•Flashing
•Vent pipes (see requirements on pages 4 and 6)
•Combustion air pipes (see requirements, pages 4 and 6)
•Mounting brackets for concentric adapter box (or box
may be mounted flush, depending on building construc-
tion)
•Taper-type reducers as required (see requirements on
page 6)
Qty Description 150, 250,300,
200 350,400
1 Complete Vertical Vent Kit 157156 54444
(Same as Option CC2)
1 Concentric Box Assembly 155392 68404
1 Exhaust 155631 53326
Terminal
1 Combustion 155635 53330
Air Inlet
1 Rubber seal for vent pipe 164492 164493
opening in concentric adapter
1 Tube of High Temperature 53335 53335
(450°F) Silicone Sealant
SideView
Screened
Exhaust
Cap
Inlet Air
Guard
Wall
Vent ( lue Exhaust) Pipe
Seal joints; see Require-
ment No. 5 on page 6.
Combustion Air Pipe
Seal Joints
Concentric Adapter
Maximum Length (See Requirement
No. 4 on page 6.)
Minimum length is 5 ft (1.5M)
60 (1524mm) maximum
12 (305mm) minimum
Top
View
Worksheet - Determine Length of
Vent Pipe through the Box
inches mm
Heater Side (max if + 6 152
diameterchanges)
Width of Box + 6 152
Bracket Length + __ ___
Width of Roof + __ ___
Inlet Pipe Height + __ ___
Terminal Side(min) + 22 559
Length of Pipe =
2. Prepare the concentric adapter box.
2a) Determine whether field-supplied brackets are required. If used, attach
brackets securely; do not leave any unsealed holes in the adapter box.
If brackets are not used, when in-
stalled,the box shouldbe tight against
the roof.
2b) Install the rubber seal and the
ventpipe. Locate the vent pipe open-
ing and place the rubber seal around
and over the edge of the metal.
Determine the length of the section of
vent pipe by adding the requirements.
On the heater side of all Sizes except
CAUA 250, the vent pipe must ex-
tendno more than6"(152mm)(length
limit does not apply to Size 250 be-
Installation Instructions for Option CC2
1. Determine the location for the vent terminal on the roof, allowing room for the
concentric adapter box inside. A thimble may or may not be required depending
on building construction and/or local codes. Prepare a hole through the roof for
the combustion air pipe (Sizes 150 and 200, pipe is 6"; Sizes 250-400, pipe is 8").
The air inlet pipe must be flashed or sealed to the roof. Flashing is to be supplied
by the installer as required by roof construction and/or codes.
WARNING: All vent terminals must be positioned or
located away from fresh air intakes, doors and windows to
preclude combustion products from entering occupied
space. See Hazard Levels, Page 2.

Mfg No. 164771, Page 9
Collar for combustion
air pipe.
Vent Pipe - when a taper-type reducer
is required in the vent pipe; it must be no
more than 6 (152mm) from the box.
Seal the seam in
the vent pipe.
Concentric
Adapter Box
Combustion
air pipe
ield-supplied
mounting brackets
Install seal
in vent pipe
opening
Install the vent pipe
by inserting it into the
terminal side of the
box and pushing it out
through the seal on the
heater side.
NOTE: Be sure flow
direction is correct.
Vent low
Combustion
Air low
22"
(559mm)
minimum
Snow
Clearance
6C 1)Slide combustion
air inlet over the
vent pipe
Install field-supplied
flashing at roof
opening (flashing not
illustrated).
cause the pipe diameter does not change); plus bracket length;
plus the width of the roof; plus the length of the outer inlet air
pipe; plus a minimum of 22" (559mm).
Lubricate the seal and pipe with liquid soap or a rubber lubri-
cant. (Installation Tip: Spray cooking oil works well as a lubri-
cant for this task.) Being sure the pipe is in the proper flow
direction, slide the end through the box and push it out through
the rubber seal. Push evenly using caution not to displace the
seal from its position on the edge of the hole. If the rubber seal
moves, slide the pipe back slightly, re-position the seal, and
slide the pipe through again.
Position the vent pipe so that it will extend a minimum of 22"
(559mm) past the end of the combustion air pipe. See Figure
6B.
A maximum of 6" (152mm) of vent pipe should extend out the
heater side. Any time the pipe is re-positioned, re-check the
seal to be sure that it has not rolled. Adjust the pipe and seal
until the pipe is the correct length on each side of the box and
the seal is over the edge of the hole and tight to the entire
circumference of the pipe.
"Through-the-Roof"Viewofatypicalinstallation
ofaverticalvent/inletairterminal andconcentric
adapter(OptionCC2)
lue
Exhaust
(Vent )
Pipe
Vent
Termina
l
Combustion
Air Inlet
Seal with high
temperature silicone
rubber sealant supplied
with the kit.
lashing
(field supplied)
Roof
Vent
Pipe
Combustion Air Pipe
Concentric
Adapter
9-3/8
(238mm)
12 (305mm) 6 ft (1829mm)
minimum
11 (279mm)
18(457mm)
minimum
Wall or
Adjoining
Building
lashing
(field supplied)
Roof
Concentric
Adapter Thimble
5 ft (1524mm)
maximum (Size
according to
anticipated
snow depth.
SideView
"X" is the length of combustion air
pipe required through and above
the roof
"X" must equal roof thickness
plusclearance required for
anticipated snow
plus ridge and/or
parapet clearance
"X" must not
exceed60"
(1524mm)
6A 6B
2c)Attach theoutside portion ofthecom-
bustion air pipe to the box. Determine
the length of the combustion air pipe so
that dimension "X" (Figure 6A) is equal
to the roof thickness, plus snow depth
and ridge or parapet clearance, but does
not exceed 60" (1524 mm). Attach the
combustion air pipe to the collar with
sheetmetal screws being careful not to
penetrate the vent pipe.
3. Attach the concentric adapter. Insert
the vent pipe and combustion air pipe up
through the roof and secure the adapter box.
Flash the combustion air pipe to the outside
of the roof as required.
4. Slide the combustion air inlet over the
vent pipe and fasten the collar
to the end of the combustion air
pipe with sheet metal screws
(See Figure 6C). Seal joint at top
between vent pipe and combus-
tion air inlet with silicone seal-
ant to prevent water leakage.
5. Attach the exhaust termi-
nalwith sheet metal screws (See
Figure 6D).
6.Verticalventterminal/combus-
tionair inlet is installedandready
for connection to the heater.
7.ConnectConcentricAdapter
Box to the Heater - Use the pipe speci-
fied and joints required for type of pipe.
If collars at the heater or adapter are dif-
ferent diameters from the pipe (use only
diameters allowed on page 6), make con-
nection with field-supplied taper-type re-
duceror enlarger.
A minimum of 12" (305 mm) of
straight pipe is required at the venter
outlet. Due to the high temperature, do
not enclose the vent pipe or place pipe
closer than 6" (152 mm) to combustible
material.
Installation of the vertical vent and combustion air system on your sepa-
rated-combustion unit is complete. Refer to Figure 6E and verify that all
installation requirements are met.
Exhaust
Terminal
6D
12"(305mm)
minimum
Combustion
AirInlet
2)Fasten to the end
of the combus-
tion air pipe
3)Seal the top joint
with silicone
Figure6E- Installationof Separated-CombustionUnitwithVerticalVentandCombustionAirPipes(OptionCC2)
Rear
View

Form 405, Page 10
4) Vent System Support
Lateral runs should be supported every six feet (1.8M) using a non-combus-
tible material, such as strap steel or chain. Do not rely on the heater for
support of either horizontal or vertical vent pipe.
Figure8 -Alternate
VentDirections
SpecificVenting Requirements(readall
before installing)
1) Venter (Flue) Outlet
Venter
Outlet
Size:
Ventinany
positionabove
horizontal Aminimumof12"of
straightpipeis required
beforeanelbow
Model Size 150, 200, 250 300, 350, 400
Outlet Diameter 5" 6"
Venter Outlet Attachment Requirements:
•A minimum of 12" of straight pipe is required at the venter
outlet before installing an elbow in the vent system. An elbow
should never be attached directly to the venter. An elbow
attached to the straight pipe can be in any position at or above
horizontal. See Figure 8.
7B. Venting and Combustion Air Requirements for Power Vent Drawing
Combustion Air from THE INSIDE SPACE and Venting Flue Products to
the Outdoors (vent cap is required)
If the environment has a positive pressure and is such that it is
not detrimental to combustion air, this system may be installed.
To provide combustion air to the heater sufficient air must enter
the equipment location to replace that exhausted through the
heater vent system. In the past, the infiltration of outside air
assumed in heat loss calculations (one air change per hour) was
assumed to be sufficient. However, current construction methods
using more insulation, vapor barriers, tighter fitting and gasketed
doors and windows, weather-stripping, and/or mechanical ex-
haustfans maynow require theintroduction of outsideair through
wall openings or ductwork to the equipment room.
The requirements for combustion and ventilation air depend upon
whether the unit is located in a confined or unconfined space. An
"unconfined space" is defined as a space whose volume is not less
than 50 cubic feet per 1000 BTUH of the installed appliance.
Under all conditions, enough air must be provided to ensure
there will not be a negative pressure condition within the equip-
ment room or space. Follow the specific requirements below for
a confined space installation.
Confined Space Installation - Do not install a unit in a con-
fined space without providing wall openings leading to and from
the space. Provide openings near the floor and ceiling for ventila-
tion and air for combustion as shown in Figure 7, depending on
the combustion air source as noted in Items 1, 2, and 3 below.
Figure7-ConfinedSpace:
Add total BTUH of all appliances in the confined space and
divide by figures below for square inch free area size of each (top
and bottom) opening.
1. Air from inside the building -- openings 1 square inch free
area per 1000 BTUH. Never less than 100 square inches free area
for each opening. See (1) in Figure 7.
2. Air from outside through duct -- openings 1 square inch free
area per 2000 BTUH. See (2) in Figure 7.
3.Air directfromoutside -- openings 1 square inch free area per
4000 BTUH. See (3) in Figure 7.
NOTE: For further details on supplying combustion air to a
confined space, see the National Fuel Gas Code ANSI Z223.1a
(latest edition).
Aspacewhose
volumeislessthan
50cubicfeetper
1000BTUHofthe
installedappliance
inputrating
7. Venting and Combustion Air (cont'd)
•Do not install dampers or any other type of flue restrictor device.
2) Vent Pipe Diameter and Length
Maximum Vent Length - minimum length is 5 ft (1.5M)
CAUA Pipe Maximum 90°Elbow 45°Elbow
Diameter Length Equals* Equals*
150-250 5" 50 ft (15.2M) 5 ft (1.5M) 2.5 ft (.8M)
300-400 6" 50 ft (15.2M) 5 ft (1.5M) 2.5 ft (.8M)
*Reduce by this amount for each elbow.
Note: If the system contains all vertical pipe or a combination of horizontal
and vertical vent pipe, the Maximum Permissible Vent Length may be in-
creased one foot (305mm) for each foot (305mm) of vertical rise up to a
maximum increase of ten feet (3M).
3) Vent Pipe and Joints
Provide field-supplied vent pipe as specified in the Table on page 4.
•If using single wall, 26-gauge or heavier galvanized pipe, secure slip-fit
connections using sheet metal screws or rivets. Seal pipe joints either with
tape suitable for 550°F (such as Option FA1, P/N 98266) or high-tem-
perature silicone sealant.
•If using Category III vent pipe, follow pipe manufacturer's instructions
for joining pipe sections. When attaching Category III pipe to the venter
outlet or the vent cap, make secure, sealed joints following a procedure
that best suits the style of Category III pipe being used.
•If using double-wall (Type B) vent pipe (at least 1/2 of the equivalent vent
length must be vertical), follow pipe manufacturer's instructions for join-
ing pipe sections. For joining double-wall pipe to the venter outlet collar,
single-wall pipe, and/or the vent cap, follow the instructions below:
Instructions for attaching double-wall (Type B) vent pipe to the ven-
ter outlet, a single-wall pipe run, or to the vent cap (use these in-
structions for either full length double-wall or terminal only):
Hardware and Sealant Required: 3/4" long sheetmetal screws; and a tube of
high temperature silicone sealant
1) Look for the "flow" arrow on the vent pipe; attach according to the
arrow. Slide the pipe so that the venter outlet, the single-wall pipe, or the
vent cap is inside the double-wall pipe.
2) Drill a hole through the pipe into the outlet collar, the single-wall pipe,
or the vent cap. (Hole should be slightly smaller than the sheet metal
screw being used.) Using a 3/4" long sheet metal screw, attach the pipe.
Do not overtighten. Repeat, drilling and inserting two additional screws
evenly spaced (120°apart) around the pipe.
3) Use silicone sealant to seal any gaps. If there is an annular opening, run
a large bead of sealant in the opening. The bead of sealant must be large
enough to seal the opening, but it is not necessary to fill the full volume
of the annular area.

Mfg No. 164771, Page 11
5) Condensation
Any length of single-wall vent pipe exposed to cold air or run
through an unheated area or an area with an ambient temperature
of 45°F or less must be insulated along its entire length with a
minimum of 1/2" foil-faced fiberglass, 1-1/2# density insulation.
Where extreme conditions are anticipated, install a means of con-
densate disposal.
6) Vent Terminal (Pipe and Vent Cap)
The vent system must be terminated with the type of vent cap
approved for use with this heater. The vent cap must be the same
size as the vent pipe. Use either a vent cap available from the
Roof or Building Overhang
3 (1M)
minimum
12
(305mm)
minimum
6 (2M)
minimum
Wall
Parapet or Adjoining Building
Approved clearance
thimble for single-wall
vent pipe is required
when flue pipe extends
through combustible
materials.
Note position of vent
cap openings.
Pitch flue pipe down toward outlet
1/4 per foot for condensate drainage.
(NOTE: Applies to entire horizontal
vent run.)
Adjoining Building
Parapet or
Roof or Building Overhang
6 (2M)
minimum
3 (1M)
minimum
12
(305mm)
minimum
Wall
Approved clearance
thimble for single-wall
vent pipe is required
when flue pipe extends
through combustible
materials. ollow
the requirements
of the double-wall
pipe manufacturer.
Pitch flue pipe down toward
outlet 1/4 per foot for con-
densate drainage.
(NOTE: Applies to entire
horizontal vent run.)
Note position of
vent cap openings.
6 (152mm) minimum
ollow instructions on page 10 to join single
and double-wall pipe and to seal the connection.
Figure8 -HorizontalVentTerminals
Single-WallVent
RunandSingle-
Wall Terminal
Single-Wall
VentRun
andDouble-
Wall
Terminal
Horizontal Vent Terminal Clearances
Structure Minimum Clearances for Vent Termination
Location (all directions unless specified)
Forced air inlet within 10 ft (3.1m) 3 ft (0.9m) above
Combustion air inlet of another appliance 6 ft (1.8m)
Door, window, or gravity air inlet 4 ft (1.2m) horizontally
(any building opening) 4 ft (1.2m) below
1 ft (30cm) above
Electric meter, gas meter* and relief 4 ft (1.2m) *Do not terminate the vent
equipment horizontally directly above a gas meter
Gas regulator* 3 ft (0.9m) or service regulator.
Adjoining building or parapet 6 ft (1.8m)
Adjacent public walkways 7 ft (2.1m) above
Grade (ground level) 7 ft (2.1m) above
heater manufacturer (Option CC1) or a field-supplied cap. If the vent cap is
field-supplied, use a Type L Breidert Air-x-hauster®or equivalent vent cap.
(Type L Air-x-hauster®is a trademark of The G. C. Breidert Company.) Use
of a vent cap supplied by the pipe manufacturer is not permitted; the vent
cap must be the type approved for use with this heater. A different style
vent cap could cause nuisance problems or unsafe conditions.
See the illustrations in Figures 9A and 9B for requirements of vertical and
horizontal vent termination. The vent terminal pipe may be either single-
wall or double-wall (Type B). If double-wall pipe is used in the vent termi-
nal with a single-wall vent run, follow the instructions on page 10 to attach
the vent cap and to connect the double-wall pipe to the single-wall vent pipe
run.
A vent cap is required. Maintain a clearance
of 12" from the wall to the vent terminal cap
for stability under wind conditions.
Products of combustion can cause discolora-
tion of some building finishes and deteriora-
tion of masonry materials. Applying a clear
silicone sealant that is normally used to pro-
tect concrete driveways can protect masonry
materials. If discoloration is an esthetic prob-
lem, relocate the vent or install a vertical vent.
6 (2M) minimum 6 (2M) minimum
Approved clearance thimble
for single-wall vent pipe is
required when flue pipe
extends through
combustible materials.
Parapet or Adjoining Building
Vertical flue extension to
be 6 (152mm) higher than
anticipated snow depth but
no less than 2 feet (610mm)
above the roof.
Vertical pipe extension
must be insulated.Roof lashing
Roof - pitched
from 0 to 45°
Vertical flue extension
to be 6 (152mm) higher
than anticipated snow
depth but no less than
2 feet (610mm) above the
roof.
6 (152mm) minimum
Roof lashing
Roof - pitched
from 0 to 45°
Approved clearance thimble
for single-wall vent pipe is
required when flue pipe extends
through combustible materials.
ollow the requirements of the
double-wall pipe manufacturer.
ollow instructions on page 10
to join single and double-wall
pipe and to seal the connection.
Parapet or Adjoining Building
Figure9 - VerticalVentTerminals
Single-WallVent
RunandSingle-
Wall Terminal
Single-Wall Vent
RunandDouble-
WallTerminal

Form 405, Page 12
Combustion Air Knockout Venter Outlet
Electrical
Gas
6-3/8
(162mm)
4-1/8
(105mm)
2-3/8 (60mm)
A
B
8. Duct Connections and
Ductwork
Both inlet air ductwork and supply air discharge ductwork are required
unless the heater is equipped with an optional inlet base and/or an
optional discharge plenum. IMPORTANT NOTE: If a Model ACU
cased cooling coil is part of the installation, it must be installed before
attaching discharge ductwork. Installation of a filter cabinet is rec-
ommended when a cooling coil is installed.
Discharge Duct Connection - The discharge duct connects to the top
of the heater or to the outlet of the optional cooling coil cabinet. See
Figures 10 and 11. Connect the ductwork plenum to the duct flange as
illustrated in Figure 11.
1) The duct connection on the top of the heater has a 90°flange.
2) The duct may either have no flange or a 90°flange.
3) Position ductwork around the outside of the heater flange.
4) If the ductwork has a flange, drill holes vertically through duct
flange into the top of the heater and secure with sheetmetal
screws. If the ductwork does not have a flange, drill holes hori-
zontally through the ductwork and the heater flange; secure with
sheetmetal screws.
Inlet Air Ductwork - The location of the inlet air duct connection
depends on the installation. Corner indicators for the opening are pro-
vided on the right side, the left side, and the rear of the heater. (See
DimensionsinFigure 1, page 3.)Determinewherethe inlet air opening(s)
should be and cut out using tin snips or aviation shears. CAUTION:
Figure12- Duct OpeningforConnectingthe InletAir
Ducttothefield-installedFilterorMixingCabinet
Depending on the heater size and whether the cabinet is on the side
or the rear, the inlet opening may be either vertical (on the top of the
filter cabinet) or horizontal (on the side of the filter cabinet.)
AttachtoDuct
Flange
Removable
Access Panel in
theDuctwork-
6" x 10"
(152mmx
254mm)
minimum
Figure11 - ConnectingDischargeDuctwork
Heater
Figure 10 - Top View showing Discharge Duct
ConnectionDimensions(inches)
ilter Cabinet Inlet Opening
150, 200 - Rear or Side ilter Cabinet - 32 (813mm)
250, 300 - Side ilter Cabinet - 32 (313mm)
250, 300 - Rear ilter Cabinet - 45-1/8 (1146mm)
350, 400 - Rear or Side ilter Cabinet = 45-1/8 (1146mm)
16
(406mm)
Inlet
Opening
Requirements and Suggestions for Connecting
and Installing Ducts
•Type of Ductwork - The type of duct installation to be used de-
pends in part on the type of construction of the building.
•Ductwork Material - Rectangular duct should be constructed of
not lighter than No. 26 U.S. gauge galvanized iron or No. 24 B & S
gaugealuminum.
•Ductwork Structure - All duct sections 24 inches or wider, and
over 48 inches in length, should be cross broken on top and bottom
and should have standing seams or angle-iron braces. Joints should
be S and drive strip, or locked.
•Through Masonry Walls - No warm air duct should come in con-
tact with masonry walls. Insulate around all air duct through ma-
sonry walls with not less than 1/2" (1" is recommended) of insula-
tion.
•Through Unheated Space - Insulate all exposed warm air ducts
passing through an unheated space with at least 1/2" (1" is recom-
mended) of insulation.
•Duct Supports - Suspend all ducts securely from buildings mem-
bers. Do not support ducts from unit duct connections.
•Duct Sizing - Proper sizing of the supply air ductwork is neces-
sary to ensure a satisfactory heating installation. The recognized
authority for such information is the Air Conditioning Contractors
Association, 1228 17th Street N.W., Washington, D.C. 20036. A
manual covering duct sizing in detail may be purchased directly
from them.
CAUTION: An external duct system static pressure
not within the limits shown on the rating plate, or
improper motor pulley or belt adjustment, may
overload the motor. See Hazard Levels, page 2.
•Removable Panels - The ducts should have removable access pan-
els on both upstream and downstream sides of the furnace. These
openings must be accessible when the furnace is in service and
should be a minimum of 6" x 10" in size so smoke or reflected light
may be observed inside the casing to indicate the presence of leaks
in the heat exchanger. The covers for the openings must be attached
in such a manner as to prevent leakage. See Figure 11.
The cut edges of the metal will be sharp.
If installing an optional filter or filter/mixing cabinet shipped with the
heater, attach the cabinet at the "cutout" opening (See Optional Acces-
sories, Paragraph 18 or 19). Depending on the cabinet and how it is
installed, the inlet opening may be horizontal or vertical.
Attach the ductwork to the heater or to the inlet cabinet.
Size 150, 200 250, 300 350, 400
A36" (914mm) 48" (1219mm) 48" (1219mm)
B21" (533mm) 21" (533mm) 34" (864mm)

Mfg No. 164771, Page 13
Sizing a Gas Supply Line
9. Gas Piping and Pressures
WARNING: This appliance is equipped for a
maximum gas supply pressure of 1/2 pound, 8
ounces, or 14 inches water column. Supply
pressure higher than 1/2 pound requires
installation of an additional lockup-type service
regulatorexternalto the unit.
PRESSURETESTINGSUPPLYPIPING
Test Pressures Above 1/2 PSI: Disconnect the heater and manual
valve from the gas supply line which is to be tested. Cap or plug the
supply line.
Test Pressures Below 1/2 PSI: Before testing, close the manual
valve on the heater.
All piping must be in accordance with requirements outlined in the
National Fuel Gas Code ANSI Z223.1a (latest edition) or CAN/CGA-
B149.1 and B149.2 (See Paragraph 1). Gas supply piping installation
should conform with good practice and with local codes.
Unit heaters are orificed for operation with natural gas having a heating
value of 1000 (± 50) BTUH per cubic ft or propane gas with a heating
value of 2550 BTUH per cubic ft. If the gas at the installation site does
not meet these specifications, consult the factory for proper orificing.
Pipe joint compounds (pipe dope) shall be resistant to the action
of liquefied petroleum gas or any other chemical constituents of
the gas being supplied.
Install a ground joint union and manual shutoff valve upstream of the
unit control system as shown in Figure 13. The 1/8" plugged tapping in
the shutoff valve provides connection for a supply line pressure test
gauge. The National Fuel Gas Code requires the installation of a trap
with a minimum 3" drip leg. Local codes may require a minimum drip
leg longer than 3" (typically 6"). Bleed gas lines of trapped air.
Gas connection is either 1/2" or 3/4" depending on size and type of gas.
Size Gas Gas Connection
150-200 Natural 1/2"
250-400 Natural 3/4"
150-400 Propane 1/2"
Leak-test all connections by brushing on a leak-detecting solution.
WARNING: All components of a gas supply
system must be leak tested prior to placing
equipment in service. NEVER TEST FOR
LEAKS WITH AN OPEN FLAME. Failure to
complycouldresultin personalinjury, property
damageordeath.
Manifold or Orifice Pressure Settings
Measuring manifold gas pressure cannot be done until the heater is in
operation. It is included in the steps of the "Check-Test-Start" proce-
dure in Paragraph 22. The following warnings and instructions apply.
WARNING: Manifold gas pressure must never
exceed 3.5" w.c. for natural gas or 10" w.c. for
propanegas.
For Natural Gas: Manifold gas pressure is regulated by the combina-
tion valve to 3.5" w.c. Inlet pressure to the valve must be a minimum of
5" w.c. or as noted on the rating plate and a maximum of 14" w.c.
ForPropane Gas:Manifold gas pressure is regulated by the combina-
tion valve to 10" w.c. Inlet pressure to the valve must be a minimum of
11" w.c. and a maximum of 14" w.c.
Before attempting to measure or adjust manifold gas pressure, the inlet
rom Gas Supply
rom
Gas
Supply
6 Drip Leg
NOTE:
Connections
shown are by
the installer.
To Controls
Manual
Gas Valve
Immediately upstream of the gas
supply connection, install a manual
shutoff valve with a 1/8 NPT
plugged tap accessible for test
gauge connection.
Ground Joint Union
Figure 13 -
SupplyPiping
Connection
Capacity of Piping - Cubic Feet per Hour based on 0.3" w.c. Pressure Drop
Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)
Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)
Length Diameterof Pipe
of 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"
Pipe Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane
20’92 56 190 116 350 214 730 445 1100 671 2100 1281
30’73 45 152 93 285 174 590 360 890 543 1650 1007
40’63 38 130 79 245 149 500 305 760 464 1450 885
50’56 34 115 70 215 131 440 268 670 409 1270 775
60’50 31 105 64 195 119 400 244 610 372 1105 674
70’46 28 96 59 180 110 370 226 560 342 1050 641
80’43 26 90 55 170 104 350 214 530 323 990 604
90’40 24 84 51 160 98 320 195 490 299 930 567
100’38 23 79 48 150 92 305 186 460 281 870 531
125’34 21 72 44 130 79 275 168 410 250 780 476
150’31 19 64 39 120 73 250 153 380 232 710 433
175’28 17 59 36 110 67 225 137 350 214 650 397
200’26 16 55 34 100 61 210 128 320 195 610 372
Note: When sizing supply lines, consider possibilities of future expansion and increased requirements.
Refer to National Fuel Gas Code for additional information on line sizing.

Form 405, Page 14
4
2
1
(supply) pressure must be within the specified range for the
gas being used both when the heater is in operation and on
standby. Incorrect inletpressure could causeexcessive mani-
fold gas pressure immediately or at some future time.
Instructions to Check Manifold
Pressure (when unit is operating):
1) With the manual valve positioned to prevent flow to the
main burners, connect a manometer to the 1/8" pipe outlet
pressure tap in the valve. NOTE: A manometer (fluid-filled
gauge) is recommended rather than a spring type gauge due
to the difficulty of maintaining calibration of a spring type
gauge.
2) Open the valve and operate the heater. Measure the gas
pressure to the manifold. Normally adjustments should not
be necessary to the factory preset regulator.
If adjustment is necessary, set pressure to correct settings
by turning the regulator screw IN (clockwise) to increase
pressure. Turn regulator screw OUT (counterclockwise) to
decrease pressure.
1) Assemble the brass nut, the sealing washer, and the 90°fitting.
2) Position the threaded fitting up through the hole so that the hose barb is
toward the bushing in the side of the cabinet. Attach using the silver-colored
locknut.
3) Under the burner, push the tubing onto the hose barb, being sure that it is
secure. Maintaining a downward slope, extend the hose out through the
cabinet side.
4) Just after exiting the cabinet, create a trap in the line by making a loop in
the hose. Secure the loop with the wire ties.
5) Continue downward with the tubing, connecting it into the coil drain pipe.
Figure14- BurnerCondensateDrainConnection
10. Burner Condensate
Drain
If an optional cooling coil is installed on a Model CAUA
heater (either now or at a later time), a burner condensate
drain line must be installed.
The following parts to install the drain line are packaged and
shipped with all Model CAUA heaters.
Qty P/N Description
1 165955 6-ft length of 3/8" I.D. Tubing
1 165952 90° Nylon Fitting, 1/4" NPT x 3/8"
tubing
1 110628 1/4" NPT Brass Nut
1 171527 1/4" Locknut, Hex, T& B 139
1 165953 SealingWasher
2 20913 Nylon Wire Ties, T&B #TY-24M
1 87556 Snap Bushing, Heyco SB 625-8
Instructions for Installing the Burner
Condensate Drain (Figure 14)
1. Remove the burner compartment door.
2. The burner box cover is in two sections. On the left side
of the burner box cover, disconnect the flame sensor wire
and the flame rollout switch wires. Disconnect the sili-
cone tubing from the static tap. Remove the left section
of the burner box cover.
3. Determine which side of the cabinet will be most conve-
nient for the drain line. Remove the hole plug on that side
and insert the snap bushing from the package.
4. Locate the hole in the bottom center of the burner pan
andremove theplug. Follow theinstructions inFigure 14
to install the drain. Complete all steps as listed in the
illustration.
When installation of the burner condensate drain is com-
plete, re-assemble the heater.
11. Electrical Supply and Connections
All electrical wiring and connections, including electrical grounding, MUST be
made in accordance with the National Electric Code ANSI/NFPA No. 70 (latest
edition)or, inCanada, the CanadianElectrical Code, PartI-C.S.A. Standard C22.1.
In addition, the installer should be aware of and comply with any local ordinances
or gas company requirements.
Check the rating plate on the heater for the supply voltage and current require-
ments. A separate line voltage supply with fused disconnect switch should be run
directly from the main electrical panel to the heater. All external wiring must be
within approved conduit and have a minimum temperature rise rating of 60°C.
Conduit from the disconnect switch must be run so as not to interfere with the
service panels of the heater.
The electrical supply and control wiring enter at the top of the heater (See Figure
1, page 3) and connect to the terminal strip behind the gas valve (See Figure 15).
Consult the wiring diagram supplied with your heater. Typical wiring diagrams are
on pages 17 and 18.
CAUTION:Ifanyoftheoriginalwireassuppliedwiththe
appliancemustbereplaced,itmustbereplacedwithwiring
material having a temperature rating of at least 105°C,
except for sensor lead wires which must be 150°C. See
Hazard Levels, page 2.
12. Thermostat and Connections
A thermostat is not standard equipment but is an installation requirement. Use
either an optional thermostat available with the heater or a field-supplied 24-volt
thermostat. Install according to the thermostat manufacturer's instructions. Con-
trol wiring enters on the right side of the heater and connects to the terminal strip
in the control compartment; see Figure 15.
Make sure that the heat anticipator setting on the thermostat is in accordance with
the amperage value noted on the wiring diagram of your heater.
WARNING:Ifyouturnoff thepowersupply,turnoffthe
gas. See Hazard Levels, page 2.
!!
!!
!HexLocknut(silver)
—Burner Bottom Pan—
""
""
"Sealing Washer
##
##
#Brass Nut
$$
$$
$90°NylonFitting
9. Gas Piping and
Pressures (cont'd)
Manifold Pressure Settings (cont'd)

Mfg No. 164771, Page 15
Limit Control
Supply Wiring Terminal Block
(behind the gas valve)
(Line voltage enters the control
compartment through a hole in
the top of the heater cabinet.)
Thermostat
Terminal Strip
(Thermostat wires enter
the control compartment
through a hole in the right
side of the heater cabinet.)
Contactors
Gas
Valve
Ignition Control
Module
Terminal Strip
Transformer
Pressure Switch
Venter
3/4 (19mm)
Figure 16 -
Check Belt
Tension
Figure15-Control
Locations
14. Blower Motor and Drive
Model CAUA units are equipped with either direct drive motor(s) and
blower(s) or adjustable belt-drive blower(s) and motor.
Direct Drive
All direct drive blower motors are 1 horsepower. Sizes 150-200 have a
single motor. Size 150 has a 12-9 blower; Size 200 has a 12-12 blower.
Sizes 250-400 have dual motors with dual 12-9 blowers.
Belt Drive
The motor horsepower on a belt drive unit is whatever was specified on
the order ranging in size from 1/4 HP to 5 HP. Check the heater rating plate
and the motor rating plate.
As part of the start-up procedure, check belt tension. Proper belt tension
is important to the long life of the belt and motor. A loose belt will cause
wearand slippage. Too much tensionwill cause excessivemotorand blower
bearing wear. Adjust the belt tension by turning the adjusting screw on the
motor base until the belt can be depressed 3/4". (See Figure 16.) After
correct tension is achieved, re-tighten the locknut on the adjustment screw.
Be sure that the belt is aligned in the pulleys.
13. Combustion Air Proving
Switch
The combustion air proving switch is a pressure sensitive switch
that monitors air pressure to ensure that proper combustion air is
available.
The switch is single pole/double throw with the normally open
contacts closing when the proper airflow is sensed in the system.
On start-up when the heater is cold, the sensing pressure is at the
most negative level, and as the heater and flue system warm up, the
sensingpressure becomes lessnegative. After thesystemhas reached
equilibrium (about 20 minutes), the sensing pressure levels off.
If a restriction or excessive flue length or turns cause the sensing
pressure to be outside the switch setpoint, the pressure switch will
function to shut off the main burners. The main burners will remain
off until the system has cooled and/or the flue system resistance is
reduced. The table below lists the approximate water column nega-
tive pressure readings and switch setpoints for sea level operating
conditions.
Model Start-Up Equilibrium SetPoint SetPoint
Size Cold “OFF”“ON”
150 1.45 1.05 .75 .90
200 1.50 1.05 .75 .90
250 1.55 1.10 .75 .90
300 1.60 1.15 .75 .90
350 1.30 1.05 .75 .90
400 1.20 1.00 .75 .90
DANGER: Safe operation of this unit requires
proper venting flow. NEVER bypass the com-
bustionair proving switchorattempt tooperate
the unit without the venter running and the
proper flow in the vent system. Hazardous
conditionscould result.SeeHazard Levels,page
2.
Most blower motors are equipped with thermal overload protection of the
automatic, reset type. If the motor is not equipped with thermal overload
protection, the unit will be equipped with a starter. The adjustable setting
on the starter will be factory set to match the amp draw of the motor and
sealed. No change should be made to the starter setting unless the original
motor is replaced. Starters are equipped with a manual reset. If an overload
condition is experienced, the condition must be corrected and the starter
must be manually reset.
After the installation is complete including all ductwork, the amp draw of
the motor should be checked with an amp meter to verify that the motor
amp rating on the motor nameplate is not being exceeded. Amps may be
adjusted downward by reducing the blower speed or by increasing the duct
system static pressure. The temperature rise must be within the range
specified on the unit rating plate.

Form 405, Page 16
Adjusting Blower Speed
The blower speed may be adjusted to achieve the desired outlet tem-
perature, as long as the adjustment is within the temperature rise and
the static pressure limits shown on the heater rating plate. Direct drive
motors are factory set at medium speed for heating and high speed for
cooling (if ordered). Belt drive motors are factory set between maxi-
mum and minimum blower speeds.
If the duct resistance is low, the blower may deliver too high an air
volume. If the resistance is very low, the blower may deliver excess air
to overload the motor, causing the overload protector to activate. Re-
ducing the blower speed will correct these conditions. If ductwork is
added to an installation, it may be necessary to increase the blower
speed.
Direct drive motors have multi-speed taps for speed adjustment. If
your installation requires an adjustment of the blower speed, the motor
may be re-wired to an alternate tap by following these instructions.
1. Turn off the gas and electric power.
2. Remove the blower door panel.
3. Consult the wiring diagram on the heater and follow the chart below
to choose the wiring for the desired adjustment. Units are wired at
high speed for cooling (if ordered) and medium speed for heating.
Model Sizes Speed Use these two motor wires:
150, 200, 250, 350 High White and Black
Medium White and Blue
Low White and Red
300 and 400 High White and Black
Medium White and Blue
4. Cut the crimped cap for the end of the wire that you intend to use
and strip the insulation.
5. Disconnect the factory-wired connectionandre-wire,using the newly
stripped wire.
6. Put a wire nut on the end of the blower motor wire that was discon-
nected.
7. Replace the heater door panel. Turn on the gas and electric. Check
for proper operation.
Belt drives have an adjustable pulley which permits adjustment of the
blower speed. Follow these instructions to adjust blower speed.
1. Turn off the gas and the electric power.
2. Loosen belt tension and remove the belt.
3. Loosen the set screw on the side of the pulley away from the motor.
4. To increase the blower speed, turn the adjustable half of the pul-
ley inward. To decrease the blower speed, turn the adjustable half
of the pulley outward. One turn of the pulley will change the speed
8-10%.
5. Tighten the set screw on the flat portion of the pulley shaft.
6. Replace the belt and adjust the belt tension. Adjust tension by
turning the adjusting screw on the motor base until the belt can be
depressed 3/4". (See Figure 16.) Re-tighten the lock nut on the
adjusting screw. Be sure that the belts are aligned in the pulley
grooves properly and are not angled from pulley to pulley.
7. Turn on the gas and electric. Light the heater following the instruc-
tions on the lighting instruction plate.
8. Check the motor amps with an amp meter. The maximum motor
amp rating on the motor nameplate must not be exceeded.
When service is complete, check for proper operation.
MotorAmps
Use an amp meter to check motor amps. The chart lists full load amps
for various HP's and voltages. Amps may be adjusted downward by
reducing blower RPM or increasing duct system static pressure.
The chart below can be used for sizing line wiring but should not be
interpreted as the exact motor amps. See the motor rating plate for exact
Full Load Amps - Blower Motors (Open)
HP 1/4 1/3 1/2 3/4 1 1-1/2 2 3 5
Direct-Drive Motors
230V 1PH -- -- -- -- 6.3 -- -- -- --
208V 1 PH 2.1 3.2 5.1 6.3 7.5 8.3 10.0 -- --
230V 1PH 2.3 2.8 4.4 5.5 6.5 7.5 10.2 -- --
208V 3 PH 1.1 1.4 3.0 2.9 3.7 5.6 7.0 9.0 13.4
230V 3PH 1.4 1.6 2.5 2.6 3.2 5.0 6.6 8.6 13.2
460V 3PH 0.75 0.8 1.0 1.3 1.6 2.7 3.5 4.3 6.6
575V 3PH -- -- -- -- 1.1 1.6 2.1 3.6 5.4
Optional Belt Drive Motors
motor specifications. At final adjustment, amperes should not ex-
ceed motor nameplate amp rating. The installation must be ad-
justed to obtain a temperature rise within the range specified on
the heater rating plate.
CAUTION: An external duct system static
pressure not within the limits shown on the rating
plate, or improper motor pulley or belt adjustment,
may overload the motor or cause the limit control
to activate. See Hazard Levels, page 2.
15. Gas Valve
The main operating gas valve is powered by the 24-volt control circuit
through the thermostat and safety controls. The main control valve is
of the diaphragm type providing regulated gas flow preset at the fac-
tory.
WARNING: The operating valve is the prime
safetyshutoff.All gassupplylinesmustbe freeof
dirtorscalebeforeconnectingtheunittoensure
positive closure. See Hazard Levels, page 2.
16. Ignition System
This heater is equipped with a direct spark integrated control system.
The system monitors the safety devices and controls the operation of
the blower and venter motors and the gas valve.
Ignition System Operating Sequence
On a call for heat from the thermostat, the system energizes the venter
motor and goes through a 10-second prepurge. The system verifies that
the pressure switch has changed states closing the normally open con-
tactor and that the high limit is in the closed state.
The gas valve is then energized, and the ignition system provides the
high voltage spark to the electrode to ignite the main burner gas. Burner
flame is electronically sensed by the control (minimum 1.0 microamps)
upon carryover of all burners. (A separate solid metal probe is used as
theflame sensingfunction.A low voltageelectrical signal isimposed on
the metal probe which is electrically isolated from ground. When the
flame impinges on the flame sensing probe, the flame acts as a conduc-
tion path to ground. The flame rectifies and completes the DC circuit,
and the ignition system acknowledges the flame.)
The blower motor is energized by the system after 30 seconds of flame
sensing.
After the thermostat has been satisfied, the system de-energizes the gas
valve, the venter motor goes through a 45-second post-purge, and the
blower motor remains energized for an additional 135 seconds.
NOTE: This is a three trial system. The unit will lockout for one hour
before initiating another trial for ignition. If the unit fails after one
recycle interval, the unit will go into hard lockout and must be reset by
interrupting power or resetting the thermostat. To initiate another trial
for ignition before the one hour interval, either reset the thermostat or
interrupt power to the unit for 30 seconds.
14. Blower Motor and Drive
(cont'd)

Mfg No. 164771, Page 17
TYPICALWIRING DIAGRAMS
Figure17-Typical WiringDiagramforModelCAUAwith Direct-DriveBlowerMotor(s)
208 OR 230/1/60
GRD
G
BK
OPTIONAL DISCONNECT SWITCH
CONTACTS
HEAT SPEED
W
MOTOR
BLOWER
L1
L2
PROTECTED
INHERENTLY
COOL SPEED CONTACTS
BL
BK
W
BL
W
BK
BK
W
INHERENTLY
PROTECTED
BLOWER
MOTOR
GGRD
BL BL
BK BK
W
W
WW
BK
BK
W
W
VENTER MOTOR
40 VA. CONTROL
BK
BL 24V
LINE VOLT
BR
TRANSFORMER
Y
CMB
ACB HEAT
LINE
GRO ND
VALVE
PSW
HI LIMIT
HI LIMIT
PRESS RE SWITCH HIGH
LIMIT
W
G
R
24VAC
DSI CONTROL
FLAME SENSING
PROBE
FLAME SENSE
IGNITOR
HV LEAD
LED CODES
SLOW FLASH NORMAL OPERATION - NO CALL FOR HEAT
FAST FLASH NORMAL OPERATION - CALL FOR HEAT
2 FLASHES SYSTEM LOCKO T - FAILED TO DETECT OR S STAIN FLAME
3 FLASHES PRESS RE SWITCH OPEN OR CLOSED
4 FLASHES HIGH LIMIT OPEN
5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED
STEADY ON INTERNAL FAIL RE (MICRO-CONTROLLER FAIL RE: SELF CHECK)
FIELD CONTROL WIRING
150'
250'
350'
75'
125'
175'
#18 GA. WIRE
#16 GA. WIRE
#14 GA. WIRE
TOTAL WIRE
LENGTH
DISTANCE FROM
NIT TO CONTROL
MIN. RECOMMENDED
WIRE G AGE
ROLLO T
LED
BK
BK
BL
BL
BL
BL
R
Y
Y
R
BR
BK OR BR
BK
BK OR BL
BR
R
FIELD WIRING
OPTIONAL FACTORY WIRING
FACTORY WIRING
WHITE - W
P RPLE - PR
BL E - BL
GREEN - G
YELLOW - Y
ORANGE - O
RED - R
BROWN - BR
BLACK - BK
WIRING CODE
BR
R
CHASSIS GRND.
B RNER GRO ND
IN
O T
VAC HOT
HOT
IN
BLWR A X
L2
L2
L2
L1
L1
1
1
1
7
7
7
7
Y
2
2
CNO
NC
FLAME
ROLLO T SWITCH
Y
CONTACTOR COIL
W
BK
ACB COOL
COOL SPEED
HEAT SPEED
CONTACTOR COIL
MAIN TERMINAL BLOCK
NIT TERMINAL STRIP
THERMOSTAT TERMINAL STRIP
BR
Y
3
DOOR SWITCH
BLBL
BL
Y1
Y2
W1
W2
SET ANTICIPATOR AT 0.6 AMPS
T87F THERMOSTAT Q539A S BBASE
W
Y
R
G
C
R
GY
BK
R
BL
R
BK
Y
BL
TERMINAL STRIP
THERMOSTAT
R
C
COOL RELAY COIL
C STOMER'S
MOTOR WIRE COLORS
WHITE - NE TRAL
BLACK - HIGH SPEED
BL E - MEDI M SPEED
RED - LOW SPEED
R R
(SEE NOTE #7)
(SEE NOTE #8)
W
(DO NOT SE WITH 208V)
(SEE NOTE)
BR
BL
BK
ALTERNATE W.R. OR ROBERTSHAW
BY-PASS GAS VALVE
PL G PILOT O TLET
P
MAIN
BL
PILOT
M
BR C
OR PV
TH-TR
TH OR
BK
BY-PASS GAS VALVE
HONEYWELL
PILOT
MV
PL G PILOT O TLET
MAIN
TR OR
PV-MV
AG1 - AK2 OR AK3 - CL10 - DIRECT DRIVE BABS
CA A SERIES 150 - 400 DWG. # B-164607 REV #1
OPERATING SEQ ENCE
1. SET THERMOSTAT SYSTEM SWITCH AT "OFF" POSITION, FAN SWITCH AT "A TO" POSITION.
2. T RN ON MAN AL GAS VALVE.
3. T RN ON POWER TO NIT.
5. THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.
6. VENTER PRESS RE SWITCH CLOSES, FIRING NIT.
7. B RNER FLAME IS SENSED, AND IN 30 SECONDS THE BLOWER MOTOR IS ENERGIZED.
8. IF THE FLAME IS EXTING ISHED D RING MAIN B RNER OPERATION, THE INTEGRATED CONTROL SYSTEM
CLOSES THE MAIN VALVE AND M ST BE RESET BY INTERR PTING POWER TO THE CONTROL CIRC IT
(SEE LIGHTING INSTR CTIONS).
NOTES
1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT
2. DOTTED WIRING AND COOL RELAY COIL INSTALLED BY OTHERS.
3. CA TION: IF ANY OF THE ORIGINAL WIRING AS S PPLIED WITH THE
APPLIANCE M ST BE REPLACED, IT M ST BE REPLACED WITH WIRING MATERIAL
HAVING A TEMPERAT RE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR
LEAD WIRE WHICH M ST BE 150° C.
4. SE 18 GA. WIRE FOR CONTROL WIRING ON THE NIT.
6. LINE AND FAN MOTOR BRANCH WIRE SIZES SHO LD BE OF A SIZE TO PREVENT
VOLTAGE DROPS BEYOND 5% OF S PPLY LINE VOLTAGE.
5. SE 14 GA. WIRE FOR LINE AND MOTOR WIRING ON NIT.
4. SET THERMOSTAT SYSTEM SWITCH AT "HEAT" POSITION; FAN SWITCH AT "A TO" POSITION.
9. SET THERMOSTAT SYSTEM SWITCH AT "COOL" POSITION, FAN SWITCH AT "A TO" POSITION.
(A) ON A CALL FOR COOLING, BLOWER MOTOR IS ENERGIZED AT HIGH SPEED AND COOLING
CIRC IT IS ENERGIZED.
11. SET THERMOSTAT SYSTEM SWITCH AT "OFF" POSITION, FAN SWITCH AT "A TO" POSITION, FOR SH TDOWN..
10. WHEN BLOWER DOOR IS OPENED, THE NIT IS SH TDOWN.
7. SECOND BLOWER MOTOR ON 250-400 NITS ONLY.
8. VENTER MOTOR ON 350-400 NITS HAS BROWN AND BL E WIRES.
9. ON 208/230V. NITS THE CONTROL TRANSFORMER HAS A D AL VOLTAGE PRIMARY.
FOR 208V. NITS SE BLACK AND RED LEADS (CAP YELLOW).
FOR 230V. NITS SE BLACK AND YELLOW LEADS (CAP RED).
10. WHEN PROVIDING OR REPLACING F SES IN THE F SIBLE DISCONNECT SWITCH
SE D AL ELEMENTS TIME DELAY F SES AND SIZE ACCORDING TO
TIMES THE MAXIM M TOTAL INP T AMPS.

Form 405, Page 18
Figure18-TypicalWiringDiagramforModelsCAUAwithBelt-DriveBlower Motor
40 VA. CONTROL
BK
BL 24V
LINE VOLT
BR
TRANSFORMER
Y
LINE
GRO ND
PSW
HI LIMIT
HI LIMIT
PRESS RE SWITCH HIGH
LIMIT
W
G
R
24VAC
FLAME SENSING
PROBE
FLAME SENSE
IGNITOR
HV LEAD
ROLLO T
LED
BK
BK
BL
BL
BL
BL
R
Y
Y
R
BR BR
R
BR
R
CHASSIS GRND.
B RNER GRO ND
IN
O T
VAC HOT
HOT
IN
DSI CONTROL
L2
L2
L2
L1
L1
1
1
1
7
7
7
Y
2
2
CNO
NC
FLAME
ROLLO T SWITCH
208 OR 230/1/60
GRD
G
BK
OPTIONAL DISCONNECT SWITCH
CONTACTOR
MOTOR
W
MOTOR
BLOWER
Y
MAIN TERMINAL BLOCK
NIT TERMINAL STRIP
THERMOSTAT TERMINAL STRIP
L2
BR
Y
L1
L2
3
DOOR SWITCH
BLBL
BL
Y1
Y2
W1
W2
SET ANTICIPATOR AT 0.6 AMPS
T87F THERMOSTAT Q539A S BBASE
W
Y
R
G
C
R
GY
BK
R
BL
R
BK
Y
BL
TERMINAL STRIP
THERMOSTAT
PROTECTED
INHERENTLY
BK
W
BK
W
R
GGRD
C
COOL RELAY COIL
C STOMER'S
VALVE
7
(SEE NOTE)
BR
BL
VENTER MOTOR
CONTACTOR COIL
(SEE NOTE #8)
BK OR BR
MOTOR
BK OR BL
BK
BK W
ACB COOL
BLWR A X
ACB HEAT
CMB
OR PV
TH-TR
TH OR
BK
BY-PASS GAS VALVE
HONEYWELL
PILOT
MV
PL G PILOT O TLET
MAIN
TR OR
PV-MV
BK
ALTERNATE W.R. OR ROBERTSHAW
BY-PASS GAS VALVE
PL G PILOT O TLET
P
MAIN
BL
PILOT
M
BR C
OPERATING SEQ ENCE
1. SET THERMOSTAT SYSTEM SWITCH AT "OFF" POSITION; FAN SWITCH AT "A TO" POSITION.
2. T RN ON MAN AL GAS VALVE.
3. T RN ON POWER TO NIT.
4. SET THERMOSTAT SYSTEM SWITCH AT "HEAT" POSITION; FAN SWITCH AT "A TO" POSITION.
5. THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.
6. VENTER PRESS RE SWITCH CLOSES, FIRING NIT.
7. B RNER FLAME IS SENSED, AND IN 30 SECONDS THE BLOWER
MOTOR IS ENERGIZED.
8. IF THE FLAME IS EXTING ISHED D RING MAIN B RNER OPERATION,
THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND
M ST BE RESET BY INTERR PTING POWER TO THE CONTROL CIRC IT
(SEE LIGHTING INSTR CTIONS).
NOTES
1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT
2. DOTTED WIRING AND COOL RELAY COIL INSTALLED BY OTHERS.
3. CA TION: IF ANY OF THE ORIGINAL WIRING AS S PPLIED WITH THE
APPLIANCE M ST BE REPLACED, IT M ST BE REPLACED WITH WIRING MATERIAL
HAVING A TEMPERAT RE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR
LEAD WIRE WHICH M ST BE 150° C.
4. SE 18 GA. WIRE FOR CONTROL WIRING ON THE NIT.
6. LINE AND FAN MOTOR BRANCH WIRE SIZES SHO LD BE OF A SIZE TO PREVENT
VOLTAGE DROPS BEYOND 5% OF S PPLY LINE VOLTAGE.
5. SE 14 GA. WIRE FOR LINE AND MOTOR WIRING ON NIT.
9. SET THERMOSTAT SYSTEM SWITCH AT "COOL" POSITION, FAN SWITCH AT "A TO" POSITION.
(A) ON A CALL FOR COOLING, BLOWER MOTOR IS ENERGIZED AND COOLING
CIRC IT IS ENERGIZED.
10. WHEN BLOWER DOOR IS OPENED, THE NIT IS SH TDOWN.
7. ON 208/230V. NITS THE CONTROL TRANSFORMER HAS A D AL VOLTAGE PRIMARY.
FOR 208V. NITS, SE BLACK AND RED LEADS (CAP YELLOW).
FOR 230V. NITS, SE BLACK AND YELLOW LEADS (CAP RED).
8. VENTER MOTOR ON 350-400 NITS HAS BROWN AND BL E WIRES.
11. SET THERMOSTAT SYSTEM SWITCH AT "OFF" POSITION, FAN SWITCH AT "A TO" POSITION, FOR SH TDOWN.
9. WHEN PROVIDING OR REPLACING F SES IN THE F SIBLE DISCONNECT SWITCH
SE D AL ELEMENTS TIME DELAY F SES AND SIZE ACCORDING TO 1.25
TIMES THE MAXIM M TOTAL INP T AMPS.
LED CODES
SLOW FLASH NORMAL OPERATION - NO CALL FOR HEAT
FAST FLASH NORMAL OPERATION - CALL FOR HEAT
2 FLASHES SYSTEM LOCKO T - FAILED TO DETECT OR S STAIN FLAME
3 FLASHES PRESS RE SWITCH OPEN OR CLOSED
4 FLASHES HIGH LIMIT OPEN
5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED
STEADY ON INTERNAL FAIL RE (MICRO-CONTROLLER FAIL RE: SELF CHECK)
FIELD CONTROL WIRING
150'
250'
350'
75'
125'
175'
#18 GA. WIRE
#16 GA. WIRE
#14 GA. WIRE
TOTAL WIRE
LENGTH
DISTANCE FROM
NIT TO CONTROL
MIN. RECOMMENDED
WIRE G AGE
FIELD WIRING
OPTIONAL FACTORY
WIRING
FACTORY WIRING
WHITE - W
P RPLE - PR
BL E - BL
GREEN - G
YELLOW - Y
ORANGE - O
RED - R
BROWN - BR
BLACK - BK
WIRING CODE
TYPICALWIRING DIAGRAMS (cont'd)

Mfg No. 164771, Page 19
17. OptionalCasedCoolingCoil,ModelACUA,ACUB,orACUC
This cased cooling coil is designed for use with the Model CAUA upflow heater. It is shipped separately for field installation over the discharge
opening of the heater. Before installing, verify that the coil cabinet is the same size as the heater cabinet.
Follow the installation instructions shipped with the cooling coil (Installation Form RZ 405-CC), the wiring diagram, and the instructions provided
by the compressor manufacturer.
Figure19-AModelACUcoolingcoilinstalledonaModelCAUAheaterandthelineconnectionsizes
ModelCAUA
Heater
ModelACU
Cased
CoolingCoil
Model ACUA ACUB ACUC
Size 060 072 090 090 120 150 120 150 180
Nominal Cooling Capacity (MBH) 60 72 90 90 120 150 120 150 180
Refrigerant Type R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22
Thermal Expansion Valves* 1 1 1 1 2 2 2 2 2
Approximate Weight (lbs) 83 86 105 110 122 140 176 180 188
No. of Intertwining Circuits 8 8 12 12 12 18 12 16 18
Face Area (sq ft) 7.79 7.79 9.38 14.04 11.67 13.70 17.13 15.38 17.13
Rows-Fins/Inch 2-10 2-12 3-10 2-12 3-10 3-12 2-12 3-10 3-10
Airflow (cfm) Low 1800 3000 4000
Nominal 2400 4000 5000
High 3000** 5000** 6000**
* - TXV's are factory supplied. Models with two TXV's have intertwined circuiting.
** - Airflow in excess of maximum values shown may result in blow-off of condensation.
Heater/Coil Cross-Reference
Table by Cabinet Size
Heater Model CAUA
150 200 250 300 350 400
ACUA ACUB ACUC
060 090 120
072 120 150
090 150 180
Burner Condensate Drain
When a system includes a cooling coil, a burner condensate drain must be installed. The parts required for the drain are shipped with the heater.
Instructions for installing the drain are in Paragraph 10, page 14.
Electrical Connections
Model Size Connections
ACUA 060/072 (1) 7/8" Suction Line
060 (1) 3/8" Liquid Line
072 (1) 1/2" Liquid Line
090 (2) 7/8" Suction Lines
090 (2) 3/8" Liquid Lines
ACUB 090/120/150 (2) 7/8" Suction Lines
090/120 (2) 3/8" Liquid Lines
150 (2) 1/2" Liquid Lines
ACUC 120/150/180 (2) 7/8" Suction Lines
120 (2) 3/8" Liquid Lines
150/180 (2) 1/2" Liquid Lines
Drain line connection is 3/4" for all sizes.
R
C
Y
1
Y
2
W
1
W
2
G
Thermostat
Connections
(Read thermostat
manufacturers
installation
instructions
before wiring.)
24V Supply *
Common
1st Stage Cooling
2nd Stage Cooling
1st Stage Heating
Optional 2-Stage Heating
an
Heater Terminal Strip
Common
1st stage cooling
24V control relay
2nd stage cooling
24V control relay
for Sizes 090, 120,
150, and 180
Condensing Unit
Connections
(Read
manufacturers
installation
instructions
before wiring.)
* A separate 24V control transformer may
be required for the condensing equipment controls
Install a jumper wire between RH and RC terminals
on the thermostat for single transformer operation.
Consult the thermostat manufacturers instructions.
Legend (field-supplied 24V wiring)
Thermostat wiring - 24V
ield control wiring - 24V
Figure20- Typical
LowVoltage Wiring
(field-supplied)
SuctionLine
Connection(s)
3/4"DrainLine
Connection
LiquidLine
Connection(s)
HoleforBurner
CondensateDrain
Tube (use this hole
or the one on the
opposite side) - see
Paragraph 10, page
14
OPTIONALACCESSORIES

Form 405, Page 20
OPTIONALACCESSORIES (cont'd)
18. Optional Filter Cabinet (return air only)
A filter cabinet designed for 2" pleated disposable or permanent metal filters is shipped separately for field assembly and installation. Depending on
the option selected, filters are either shipped with the cabinet or are field-supplied.
To adapt to a variety of applications, the heater cabinet is designed so that the filter cabinet can attach on either the right side, the left side, or the rear
of the heater. The larger filter cabinets (left two tables below) are uniquely designed so that the same cabinet can be field-assembled and installed with
either a horizontal or vertical air inlet. The smaller filter cabinet in the table on the right is limited to Sizes 150 and 200 and is available with a
horizontal inlet only. All cabinets have door panels for easy filter removal for changing or cleaning.
All of the filter cabinets have a duct flange for attaching the inlet air duct. For inlet duct dimensions, see Paragraph 8.
Follow the step-by-step instructions included with the filter cabinet package to assemble and attach it to the heater.
Figure 21 - Filter Cabinets with Filter Arrangements and Filter Sizes
Sizes of Permanent or Pleated 2"
Filters for Options CW4, CW5, or CW6
Size CFM FPM Filters
150 1800 281 (4) 16 x 16
2400 375 (4) 16 x 16
3000 469 (4) 16 x 16
200 2400 375 (4) 16 x 16
3000 469 (4) 16 x 16
250 3000 469 (4) 16 x 16
*4000 625 (4) 16 x 16
**5000 781 (4) 16 x 16
(4) 16 x 16
300 3000 469 (4) 16 x 16
*4000 625 (4) 16 x 16
**5000 781 (4) 16 x 16
(4) 16 x 16
350 4300 448 (6) 16 x 16
5000 521 (6) 16 x 16
*6000 625 (6) 16 x 16
400 4300 448 (6) 16 x 16
5000 521 (6) 16 x 16
*6000 625 (6) 16 x 16
NOTES:
* Requires 2" permanent filters.
** If using side inlets, two cabinets must be
installed, one on each side.
Sizes of Permanent or Pleated 2"
Filters for Options CW7, CW12, or
CW11
Size CFM FPM Filters
150 1800 281 (4) 16 x 16
2400 375 (4) 16 x 16
3000 469 (4) 16 x 16
200 2400 375 (4) 16 x 16
3000 469 (4) 16 x 16
250 3000 313 (6) 16 x 16
4000 417 (6) 16 x 16
5000 521 (6) 16 x 16
300 3000 313 (6) 16 x 16
4000 417 (6) 16 x 16
5000 521 (6) 16 x 16
350 4300 448 (6) 16 x 16
5000 521 (6) 16 x 16
*6000 625 (6) 16 x 16
400 4300 448 (6) 16 x 16
5000 521 (6) 16 x 16
*6000 625 (6) 16 x 16
Option CW4 with 2" Pleated Filters
Option CW5 with 2" Permanent Filters
Option CW6 for Field-Supplied Filters
•Attaches on Either Side of the Heater
•Vertical (Top) or Horizontal Inlet Opening
•"V" Filter Rack Arrangement
Filters for Options CW8, CW9, CW10
SizeCFM FPM 2" Filters
Pleated Permanent
150 1800 375 (2) 12 x 32 (4) 12 x 16
2400 500 (2) 12 x 32 (4) 12 x 16
*3000 625 -- (4) 12 x 16
200 2400 500 (2) 12 x 32 (4) 12 x 16
*3000 625 -- (4) 12 x 16
Figure21A-
Assembledwith
VerticalAir
InletOpening
Figure 21B -
Assembled
with
Horizontal
AirInlet
Opening
Figure21C-
SmallFilter
CabinetforSizes
150and200only
--HorizontalAir
InletOnly
Option CW7 with 2" Pleated Filters
Option CW12 with 2" Permanent Filters
Option CW11 for Field-Supplied Filters
•Attaches on the Rear of the Heater
•Vertical (Top) or Horizontal Inlet
Opening
•"V" Filter Rack Arrangement
Option CW8 with 2" Pleated Filters
Option CW9 with 2" Permanent
Filters
Option CW10 for Field-Supplied
Filters
•Attaches on either Side or the Rear
of a Size 150 or 200 Heater
•Horizontal Inlet Opening
•"V" Filter Rack Arrangement
19. MixingCabinet (Outsideand ReturnAir)
The optional mixing box for the Reznor®Model CAUA heater is designed
to provide the system with a supply air mixture of return air and outside
air. Any percentage of outside air can be supplied to the unit as long as the
air temperature entering the blower is 35°F or above. The mixing box is
available in an assortment of configurations with a selection of actuators
and controls. All mixing boxes are completely assembled at the factory for
field attachment to the rear of a Model CAUA heater.
Follow the instructions packed with the mixing box to cut out the opening
and attach the mixing box. If the mixing box has dampers, follow the
instructions for routing the damper motor wires, and connect the
wiresaccording tothewiring diagram.Ifthere areboth return airand
outside air dampers, follow the directions to adjust the damper
linkage.
Allmixing boxinletair openingshave duct flangesfor attachment of
ductwork. Ductwork must be attached to the outside air opening.
Removable door panels provide for filter access from either end of
the cabinet. If the box was ordered with optional filters, it is shipped
with the filters installed.
This manual suits for next models
7
Table of contents
Other Thomas&Betts Furnace manuals
Popular Furnace manuals by other brands

Nordyne
Nordyne SC Series installation instructions

Bryant
Bryant 396G installation instructions

Lennox
Lennox ML180UHA installation instructions

VERDER
VERDER Carbolite Gero SCF 24 Installation, operation and maintenance instructions

Payne
Payne PG95XAT Product data

Bryant
Bryant Legacy 912SA Series Product data

VERDER
VERDER HZS 12/900 Installation, operation and maintenance instructions

Carrier
Carrier 58VLR User's information manual

Lennox
Lennox EL296DFV SERIES User's information manual

Lennox
Lennox EL297UH045XV36B Unit information

Payne
Payne 349FAZ Quick manual

Carrier
Carrier N96MSN Installation, start-up, operating and service and maintenance instructions