Tranberg TEF 1060 User manual

Tranberg AS | P.O. Box 8033 | N-4068 Stavanger | Norway | Tel.: (47)51 57 89 00 | Fax.: (47)51 57 89 50
Tranberg Systems | Hjulmagervej 15C | 7100 Vejle | Denmark | Tel.: (45) 75 85 83 80
TEF 1060
HIGH VOLTAGE ENCLOSURE
WITH A-BLOCK SOLUTIONS
USER MANUAL
IMPORTANT
Read this instruction carefully before installing the
product
Danger! High Voltage!
Do not open when engergized!
TUM5461 REV. A25.05.2016

TEF 1060 HIGH VOLTAGE ENCLOSURE WITH A-BLOCK USER MANUAL
INTRODUCTION
Thank you for purchasing this product!
For installation, maintenance and assurance of a long life
of this product, please follow this manual.
MAINTENANCE / REPAIR / MODIFICATION
Before opening the enclosure make sure that the power is
disconnected. In case of intrinsically safe circuits, working
is permitted while voltage applies.
Before starting Maintenance, repair or modification, remove
safety cover (see figure 1) and measure that there is no high
voltage on the terminals.
Servicing the enclosure is done by checking the intactness
of the enclosure, gasket and glands. If necessary lubricate
the lid bolt threads or the quick lock closing with grease
type Renolit Unitemp 2 from Fuchs or equal.
If repair or overhaul is necessary this may only be done with
Tranberg spare parts.
Modification of the enclosure or change of design are
not permitted, except for installing additional glands and
terminals according to the approval of the enclosure.
APPROVALS
SAFETY INSTRUCTION
Tranberg High Voltage A-block series 1060 enclosures, are
suitable for use in hazardous areas zone 1-2, and also in
safe areas.
Changes made to the product which do not confirm to
the approvals of this equipment, is a safety violation. The
manufacturer is under no circumstances responsible for
personal injuries, death or any other damage caused by
such activities. For replacement and repair of the enclosure
only Tranberg AS spare parts may be used. Repair that
effects the explosion protection, may only be carried out
by Tranberg AS, or a qualified electrician in compliance with
the respective national regulation.
Fig. 1
Marking to 2014/34/EU:
II 2 G Ex eb IIC T4, T5, T6
IECEx PRE 14.0001
Presafe 14ATEX4124
Enclosure solutions with optional technical specifications
upon request. These solutions are subject to unit verifica-
tion certifications or field certifications.
Notified Body: DNV Nemko Presafe A/S, Norway

No spare parts, tools, measuring equipment or any other
item shall be stored inside the high voltage enclosure. The
inside of the enclosure, terminals and cables shall be clean
and dry. If dust or water is present, the enclosure shall be
disconnected, earthed, cleaned and measures shall be
taken to prevent further ingress of dust or water. Measures
should be taken to prevent condensation inside the enclo-
sure.
An equipotential bonding wire should always be connected
to the enclosure. This is to ensure any fault current shall be
lead safely to earth, and that the enclosure in no way may
be dangerous to touch. The bonding wire should be of a
suitable cross section so that it may safely lead the fore-
seen fault-current to the ground.
Installation is to be performed by skilled personnel, fa-
miliar with high voltage installations and regulations,
“Ex” regulations, the ATEX Directive and/or IECEx
norms and standards. This includes but is not limited to:
IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 60079-14, com-
pany routines and national and international regulations.
Ferrules shall always be used on fine-stranded cables.
All clearance and creepage distances shall be according to
IEC/EN 60079-7 after installation.
Regardless of the regulations taking precedence in any in-
stallation, a dielectric strength test is highly recommended
after installation, before the equipment is put in service. In
most cases, this test will be mandatory.
Disposal/Recycling: When the apparatus is disposed of,
the respective national regulations shall be observed.
Mounting
The 1060 enclosure must be fastened by 4 pcs. of M10
bolts, or M8 bolt at holes in back of enclosure
TEF 1060 HIGH VOLTAGE ENCLOSURE WITH A-BLOCK USER MANUAL
INSTALLATION
Connection
In order to maintain the mode of protection, the conductors
will have to be connected with special care. The insulation
must reach up to the terminal and the conductor must not
be damage. All screw and nut of the terminals, also those
remaining vacant, must be tighten down. For earth connec-
tion to stud or bar, cable shoes will have to be used.
Only certified cable entries and blinds may be used. Gland
has to be chosen according to cable diameter used.
To ensure the required minimum protection category glands
has to be tighten properly and unused holed has to be
closed with certified blinds according to hole diameter.
Close and lock door / lid. In case of bolt tight these firmly
with suitable tool by hand force. Over tightening may impair
the protection category.
Important
The panel must be mounted vertically to a wall or structure.
Make sure to use all four (and sometimes more) fixing
points, as the weight of the panel with components inside
may be considerable.
It is also very important that the rear of the panel stays level,
meaning that the fixing points on the structure must be in
the same plane. If one or more of the fixing points are out of
line, the panel is likely to be bent when fixed to the structure.
If the panel is bent it may result in several problems, such
as:
• Fault on IP degree of ingress protection, due to
certificate.
• Water intrusion (uneven pressure on door gaskets)
• Doors may not close completely or become difficult to
open
• The load on the fixing bolts may not be fully distributed
(excessive load on some points)
• Permanent deformation of the panel

TEF 1060 HIGH VOLTAGE ENCLOSURE WITH A-BLOCK USER MANUAL
CONNECTION DATA FOR PHOENIX CONTACT UT TERMINALS
Connection type: Screw connection, Connection in acc.Standard : IEC 60947-7-1
UT Terminal type UT 2,5 UT 4 UT 6
Min./ max. Solid conductor cross section 0,14 mm² - 4 mm² 0,14 mm² - 6 mm² 0,2 mm² - 10 mm²
Min./max. Conductor cross section AWG 26 - 12 26 - 10 24 - 8
Min./max. Stranded conductor diameter 0,14 mm² - 4 mm² 0,14 mm² - 6 mm² 0,2 mm² - 10 mm²
Conductor cross stranded AWG min 26 26 24
Conductor cross flexible AWG max 12 10 8
Min./max. Conductor cross section stranded,
with ferrule without plastic sleeve
0,14 mm² - 2,5 mm² 0,14 mm² - 4 mm² 0,25 mm² - 6 mm²
Min./max. Conductor cross section stranded,
with ferrule with plastic sleeve
0,14 mm² - 2,5 mm² 0,14 mm² - 4 mm² 0,25 mm² - 6 mm²
Two conductors with same cross section,
solid min./max.
0,14 mm² - 1,5 mm² 0,14 mm² - 1,5 mm² 0,2 mm² - 2,5 mm²
Two conductors with same cross section,
stranded min./max.
0,14 mm² - 1,5 mm² 0,14 mm² - 1,5 mm² 0,2 mm² - 2,5 mm²
Two conductors with same cross section, stranded,
TWIN ferrules with plastic sleeve min./max.
0,5 mm² - 1,5 mm² 0,5 mm² - 2,5 mm² 0,5 mm² - 4 mm²
Two conductors with same cross section, stranded,
ferrules without plastic sleeve min./max.
0,14 mm² - 1,5 mm² 0,14 mm² - 1,5 mm² 0,25 mm² - 1,5 mm²
Connection in acc. standard IEC/EN 60079-7 IEC/EN 60079-7 IEC/EN 60079-7
Min./ max. Solid conductor cross section 0,14 mm² - 4 mm² 0,14 mm² - 6 mm² 0,2 mm² - 10 mm²
Conductor cross section AWG min. / max. 26 - 12 26 - 10 24 - 8
Min./ max. stranded conductor diameter 0,14 mm² - 2,5 mm² 0,14 mm² - 4 mm² 0,2 mm² - 6 mm²
Stripping length 9 mm 9 mm 10 mm
cylindrical gage A3 A4 A5
Screw size M3 M3 M4
Tightening min. 0,5 Nm 0,6 Nm 1,5 Nm
Torque max. 0,6 Nm 0,8 Nm 1,8 Nm

TEF 1060 HIGH VOLTAGE ENCLOSURE WITH A-BLOCK USER MANUAL
Connection type: Screw connection, Connection in acc.Standard : IEC 60947-7-1
UT Terminal type UT 10 UT 16 UT 35
Min./ max. Solid conductor cross section 0,5 mm² - 16 mm² 1,5 mm² - 25 mm² 1,5 mm² - 50 mm²
Min./max. Conductor cross section AWG 20 - 6 16 - 4 16 - 10
Min./max. Stranded conductor diameter 0,5 mm² - 16 mm² 1,5 mm² - 25 mm² 1,5 mm² - 50 mm²
Conductor cross stranded AWG min 20 16 16
Conductor cross flexible AWG max 6 4 1
Min./max. Conductor cross section stranded,
with ferrule without plastic sleeve
0,5 mm² - 10 mm² 1 mm² - 16 mm² 1,5 mm² - 35 mm²
Min./max. Conductor cross section stranded,
with ferrule with plastic sleeve
0,5 mm² - 10 mm² 1 mm² - 16 mm² 1,5 mm² - 35 mm²
Two conductors with same cross section,
solid min./max.
0,5 mm² - 4 mm² 1 mm² - 6 mm² 1,5 mm² - 16 mm²
Two conductors with same cross section,
stranded min./max.
0,5 mm² - 4 mm² 1 mm² - 6 mm² 1,5 mm² - 10 mm²
Two conductors with same cross section, stranded,
TWIN ferrules with plastic sleeve min./max.
0,5 mm² - 6 mm² 0,75 mm² - 10 mm² 1,5 mm² - 16 mm²
Two conductors with same cross section, stranded,
ferrules without plastic sleeve min./max.
0,5 mm² - 2,5 mm² 1 mm² - 6 mm² 1,5 mm² - 10 mm²
Connection in acc. standard IEC/EN 60079-7 IEC/EN 60079-7 IEC/EN 60079-7
Min./ max. Solid conductor cross section 0,5 mm² - 16 mm² 1,5 mm² - 25 mm² 1,5 mm² - 50 mm²
Conductor cross section AWG min. / max. 20 - 6 16 - 4 16 - 10
Min./ max. stranded conductor diameter 0,5 mm² - 10 mm² 1,5 mm² -16 mm² 1,5 mm² - 35 mm²
Stripping length 10 mm 14 mm 18 mm
cylindrical gage A6 A7 B9
Screw size M4 M5 M6
Tightening min. 1,5 Nm 2,5 Nm 3,2 Nm
Torque max. 1,8 Nm 3 Nm 3,7 Nm
CONNECTION DATA FOR PHOENIX CONTACT UT TERMINALS

Tranberg AS | P.O. Box 8033 | N-4068 Stavanger | Norway | Tel.: (47)51 57 89 00 | Fax.: (47)51 57 89 50
Tranberg Systems | Hjulmagervej 15C | 7100 Vejle | Denmark | Tel.: (45) 75 85 83 80
TEF 1060 HIGH VOLTAGE ENCLOSURE WITH A-BLOCK USER MANUAL
TECHNICAL DATA
Housing: Acid proof stainless steel
Max voltage: 11000V AC/DC
IP-rating: IP66
Note: IP-classification may be different, determinated by
components used in enclosure.
Tamb: -20°C - +40°C
Silicone gasket: -50°C to 60°C
Certification: IECEx PRE 14.0001
Presafe 14ATEX4124
Enclosure solutions with optional technical specifications upon
request. These solutions are subject to unit verification certifications
or field certifications.
Compliance with: EN 60079-0:2012
EN 60079-7:2007
IEC 60079-0:2011
IEC 60079-7:2011
Area of use: Zone 1, Zone 2 and safe area
Table of contents
Other Tranberg Enclosure manuals