SDU-Lon InstallationInstructions
SDU-LonInstallationInstructionsTG200599Issue1/C20/11/06
6
Mount Unit
14
Standard UK pattress wall box
or panel 60 mm
46 mm
50 mm
Ø 4 mm
(M3.5
screw)
Ø 4 mm
(M3.5
screw)
60 mm
2 off (M3.5 x 35 mm)
screws provided
Install on Lon Management Tool
12 If other IQ System devices on LonWorks are installed on LonWorks Management Tool.
WheninstallingSDU-LONonLonWorkManagementTool,pushservicepinbuttonwhenrequested.
S P E N G
1 2 3 4
See LonWorks network management tool
manual. See IQ System LonWorks Products
Engineering Manual (TE200292). LonWorks
System integrator must have LonWorks
engineeringexpertise.
SDUDataSheetTA200559
for LonWorks network
variables (NVs)
The SDU must also be associated with its IQL using the LMT
The following network variables need to be set up using the LMT:
nciInstallState: set to CFG_EXTERNAL
nciHostNodeAddr: set to associated IQL LonWorks node address
nciSubnetAddr: set to associated IQL LonWorks subnet address
nciMsgCode: set message code of associated IQL
nciDomainIndex: set to domain index of associated IQL
service pin button
Associate SDU with its IQL
13
ab
not if installed on LonWorks Management Tool
SP ENG
1234
Conn ect to IQ
“Connect to IQ”
SP ENG
1234
Press IQL Ser vic e PIN
“Press IQL
Service Pin”
cd
4 secs
EitheruseIQLTool2runinginSETandconnectedtoLonWorksusingLCIorusebuttonsasfollows:
3 Installation(Continued)
24Vac
I Q
L
+
O / S
L A N
L O N
N I D
S t r a t e g y
: : : : :
D O 1 I N 1
D O 2 D O 3
~
D O 4 D O 5 IN 2 I N 3
2 4 V
C O M
24V
C O M
~
C O M
service pin button