manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Valor
  6. •
  7. Furnace
  8. •
  9. Valor 502CN User manual

Valor 502CN User manual

9
aIor
Direct
Vent
Wall
Furnace
MODEL
502CN
For
use
with
Natural
Gas
PLEASE
LEAVE
THESE INSTRUCTIONS
WITH
THE
OWNER
Vous
pourrez
vous
procurer
un
exempiaire
en
langue Francaise
de
cette
brochure
chez
votre
concessionaire.
R
APPROVE
VALOR
HEATING
ERDINGTON,
BRMNGHAM
824
9QP
ENGLAND
Distnbuted
by
HSINDUSTRiES
LTD
829
Third
Street
West
NORTH
VANCOUVER
BC.
V7P3K7
Phone (6O4
9843496
INSTALLATION
INSTRUCTIONS
FOR
YOUR
SAFETY
Do
not
store
or
use
gasoline
or
other
flammable
vapors
and
liquids
in
the
vicinity of
this
or
any
other
appliance.
FOR
YOUR
SAFETY
If
you
smell
gas:
1.
Open
windows.
4.
Immediately
call
your
gas
2.
Don’t
touch
electrical
supplier.
switches.
3.
Extinguish
any
open
flame.
AOOKRR9/(t9
1,
INSTALLATION
1.1
GENERAL
This
fireplace
is
certified
bythe
Canadian
Gas
Association
for
installation
on
an
outside
wall
and
for
use
with
Natural
Gas.
The
installation
must
conform with
local
codes.
In
the
absence
of
local
codes,
the
installation
must
conform
with
the
current
CAN-lB
149.1
installation
code.
Only
qualified
personn
iould
install
the
appliance.
1.2
SUPPLY
GAS
This
fireplace
must
only be
used
with
Natural
Gas
having
a
pressure
at
the
appliance
inlet
between
a
maximum
of
8in.
W.C.
and
a
minimum
of
5in.
W.C,
1.3
LOCATION
The
fireplace must
be
located
on
an
outside
wall.
1.3.1
THE
WALL
The
vent
reach
from
the
outside
surface
of
the
wall
to
the
back
of
the
fireplace
must
be
between
4”
minimum
and
16”
maximum.
The
vent
clearance
hole
in
the
wall
is
7/8”
diameter.
1.3.2 OUTSIDE
THE
WALL
This
fireplace
is
designed
to
operate when
an
undisturbed
air
flow
hits
the
outside
vent
terminal
from
any
direction.
Minimal
clearances
to
external
obstruct
ions
which
could
disrupt
the
air
flow
are shown
in
fig.
1.
In
addition
the
vent
outlet should
not
terminate
within
3
feet
of
a
building opening
or
the
combustion
air
inlet
of
another
appliance.
This
clearance
may
be
reduced
to
9
inches
with
the
approval
of
the
authority
having
jurisdiction.
The
vent
outlet
should
not
terminate
within
6
feet
of
a
mechanical
air
supply
to
a
building.
The
vent
outlet
should
be
positioned
where
it
will
not
be
covered
by
any
snowdrifts.
If
the
outside
ventterminal
isto
be
located
where
it
will
be
accessible
to
any
person,
we
recommend
that
a
guard
is
fitted
over
the
terminal
to
prevent damage
to
the
vent
and
to
prevent
it
being
touched.
The
terminal
gets
very
hot
in
use
and
could
cause
burns.
A
suitable
optional
guard
is
available
from
your
supplier
-
ask
for
guard
part
#
235.
1.3.3
INSIDE
THE
WALL
A
fireplace
cavity
maintaining
the
dimensions
shown
in
fig.
2
is
required.
As
the
unit
installs
after
the
wall
finish
is
applied,
the
depth
must
always
be
measured
from
a
finished
surface.
Minimum
clearances
to
combustible materials
inside
the
room
must
be
no
less
than
those
shown
in
fig.
3.
Combustible
materials
within
the
framing
(such
as
insulation
etc.>
must
not
be
closer
to
the
outside
surfaces
of
the
fireplace
metal
case
than
the
points
of
the
“V”
shaped
spacing
strips
on
the
sides
and
back
of
the
case.
Apart
from
this
requirement,
no
clearances
to
combustible
materials
inside
the
framing are
required.
1.4
GAS
FEED
LINE
The
fireplace
case
contains
3
alternative
gas
line
access
panels
-
two
panels
in
the
case
back
and one
in
the
right
side.
The
position
of
the
openings
is
shown
in
fig.
3.
The
gas
feed
line
should
be
extended
so
that
connection
to
the
appliance
can
be
through
one
of
these
panel
openings.
The
gas
connection
point
to
the
appliance
firebox
is
at
the
right
side.
It
will
therefore
be
preferable
if
the
feed
line
can
enter
the
fireplace
case
through the
right
side
access
panel.
See
section
1
.1
2
for
gas
supply
connection
details.
12
min
24’
mn
vertical
view
N
FIG.
1
MINIMUM
OUTSIDE CLEARANCES
1
28”
from
finished
hearth
level.
(Installed
unit
covers
28%
Mm
29’/”
Max)
CENTER
LINE
OF
FIREPLACE
Lç
f
GAS
UNE
ACCESS
OPENINGS
FIG.
2
FRAMING
36”
Mm.
4’’ 11
!‘
1 1
‘/2’
4”
2’’,’’
FINISHED
HEARTH
LEVEL
SACK
OF
FiREPLACE
FIG. 3
CLEARANCES
TO
COMBUSTIBLE MATERIALS
&
GAS
LINE
AREAS
12”
2
1.5
FIREPLACE
PACK
CONTENTS
The
pack
contains:
1
Fireplace
unit (Comprising
of
the
outer
case
complete
with
assembled
firebox
unit
and
front
facia
unit).
1
Top
front
grille.
1
Facia
strip
for
bottom
front.
1
Thin
Sealing
ring
for
vent
to
case
sealing.
1
Thick
Sealing
ring
for
vent
to
case
sealing.
1
Thick
Sealing
ring
for
vent
to
outside
wall
plates
sealing.
5
Ceramic
logs
in
styrofoam
pack.
2
Ceramic
side
cheeks.
1
Air
intake
&
vent
tube
unit.
3
Vent
tube
locating
plates.
1
Outer vent
shield
tube.
1
Bag
containing
fixing
screws
&
plugs.
1.5.1
REMOVE
THE
FRONT
FACIA
(SEE
FIG.
4)
Remove
the
front facia
by
withdrawing
the
two
screws
situated
near the
bottom
corners
of
the
facia.
Lift
the
facia
forward
to
clear
the
control
knob
and
expose
the
rear
of
the
piezo
ignitor
unit.
Detach
the
leads
from
the
body
of
the
piezo
ignitor
unit
then
lift
the
facia
completely
clear
and
store
in
a
safe
place.
The
vent
unit,
ceramic
parts
and
most
other
loose
items
will
be
found
inside
the
fireplace
outer
case.
Check
that
all
the
contents
listed
are
in
the
pack
and
are
undamaged.
1.5,2
REMOVE
THE
(SEE
FIG. 5)
(a)
Remove
the
3
screws
holding
each
side
pillar.
(b)
Lift
up
the
top
cross
unit
to
free
the
side
pillars.
To
prevent
them
falling
out and
getting
lost,
remove
the
2top
support brackets
located
in
the
slots
in
the
side
pillars.
Put
the
pillars
and
support
brackets
in
a
safe
place.
1.6
PREPARING
THE
VENT
HOLE
IN
WALL
Before
cutting
the
vent
hole
in
the
wall,
make
sure
that
the
finished
hearth
level
is
established.
Once
the
vent
hole
is
cut
in
the
wall,
it
will
not
be
possible
to
alter
the
position
of
the heater
without
re
cutting
the
wall.
(a)
Place
dust
sheets
on
the
floor.
(b)
Mark
the
position
of
the
center
of
the
vent
on
the
wall
(see
fig.
6).
Top
Support
Bracket
___J
3
Screws
each
side
FIG.
5
SIDE
PILLAR
REMOVAL
SIDE
PILLARS
7/’
dia,
FIG.
4
FACIA
REMOVAL
212
FINISHED
HEARTH
.4
/
/
///
/
//
/7
FIG.
6
VENT
HOLE CENTER
////
3
(c)
Cut
73
/a”
dia.
hole
through
the
wall
making
sure
that
it
is
straight
and
level.
1.7
PREPARE
THE
VENT
UNIT
(See
fig.
7)
(a>
Measure
the
total
wall
depth
from
finished interior
to
finished
exterior
surfaces.
(b)
Mark
the
vent
unit
at
a
length
equal
to
the
total
wall
depth
plus 5in.
measured
from
the
outside
end
of
the
vent
cap.
(C>
Insert
the
styrofoam
support
and
cut
off
the
vent
tubes
squarely
at
this
marked position.
IMPORTANT:
MAKE
SURE
THAT
ALL
STYROFOAM
IS
REMOVED
FROM
THE
VENT
UNIT
AFTER CUTTING.
1.8
FIT
THE
VENT
UNIT
(a)
Insert
the
cut
end
of
the
vent
unit
through
the
hole
in
the
rear
of
the
case.
Make
sure
that
the
seam
on
the outer
vent
tube
is
not
at
the
bottom.
Push
the
vent
unit
on
to
the
two
collars
at
back
of
the
firebox.
IMPORTANT WARNING:
MAKE
SURE
THAT
THE VENT
UNIT
IS
FULLY
PUSHED
HOME
ONTO
BOTH
COLLARS.
FAILURE
TO
SECURELY
INSTALL
THE
VENT
COULD
RESULT
IN
A
HAZARD
TO
THE
USER.
(b)
A
#6
x
/“
thread
tapping
screw
is
supplied
to
help
secure
the vent
unit
to
the
fireplace
outlet.
Insert
a
/32”
drill
through the
hole
in
the
vent
securing
bracket
(situated
above
the
outer
collar
(see
fig.
8).
Drill
into
the
vent
outer
tube and
secure
with
the
screw.
(c)
Fit
one
thin and
one thick
soft
ceramic
sealing
ring
over
the
vent
unit,
The
thin
ring
must
be
on
the
inside
and
the
thick
ring
outside
-
see
figs
7
&
9.
Push
the
seals
up
to
the
back
of
the
firebox.
(d)
Fit
one
of
the
vent
tube
locating
plates
over
the
vent
unit.
Push
the
plate
uptotheoutercase.
Make
sure
that
the
ceramic
seals
are
located
in
the
well
in
the
plate
and
up
to
the
firebox
back
and
that
they
are
not
trapped
between
the
locating
plate
and
the outer case.
(e)
Secure
the
locating
plate
to
the
back
of
the
outer
case
using
the
seven
#
8
thread
tapping
screws
provided
(see
fig.
9).
1.9
INSTALL
THE
FIREPLACE
(a)
Position
the
fireplace
(with
vent
attached)
into
the
framed
enclosure.
Push
the
fireplace
right
up
to
the
wall
with
the
vent projecting
through
the
wall.
Make
sure
that
the
dished
ring
on
the
vent locating
plate
at
the
back
of
the
fireplace
is
fully
centralized
with
the
vent
hole
in
the
wall.
Wall
IL;9i
Thick
_____________________________
sealing
f
ring
1
—
NJ
=1=
__
Thin
seahng
,,,,..—‘
Vent
ring
Unit
Wall
depth
+
5”
FIG.
7
VENT
UNIT
INSTALLATION
eahng
ring
FIG. 9
VENT LOCATION
TO
CASE
fit
#
6
screw
FIG.
8VENT
SECURING
4
(b)
Fix
the
fireplace
to
the
framing
enclosure
using two
of
the
wood
screws
supplied
through
each
side
flange
of
the
metal
case
(see
fig.
10).
(c)
Replace
the
two
side
pillars
by
lifting
up
the
top
cross
unit
and
inserting
the
side
pillars.
Fix
the
pillars
to
the
fireplace
case
with
the
three
screws
each
side
previously
removed.
Re
locate
a
top
support
bracket
in
one
of
the
slots
in
each
side
pillar.
There
are four
slots
in
each
pillar
giving
a
choice
of
height
for
the
top
unit.
Make
sure
that
the
top
cross
unit
is
properly
located
over
the
side
pillars
and
rests
on
the
support
brackets
(see
fig.
11).
1.10
PREPARE
THE
OUTER
VENT
SHIELD
TUBE
(a)
The
outer
vent
shield
tube
is
supplied
coiled
round
the
vent
unit.
Flatten
it
and
cut
at
a
length
of
wall
depth
plus
1
/
2
1n.
Make
sure
that
the
cutting
line
is
at
least
1
inch
away
from
the
nearest
bolt
hole
(see
fig.
12).
(b)
Form
the
shield
into
a
tube
with
the
holes
aligned.
Fasten
using
the
10
bolts
and
nuts
provided,
with
the
bolt
heads
outside.
(c)
Insert
the
shield tube
into
the
wall
from
the
outside
wall.
Push
the tube
firmly
in
so
that
it
locates
fully
over
the
dished
ring
of
the
vent
location
plate
on
the
fireplace
back.
Trim
the
tube
if
necessary
(see
fig.
1
3).
1.11
FIT
OUTSIDE
VENT
LOCATION
PLATES
(a)
Fit
a
wall
plate
over
the outside
wall
end
of
the vent
unit
with
the
dished
projection
to
the
inside.
Push
the
pJate
up
to
the
wall
so
that
the
dished
projection
locates
inside
the
outer
vent
shield
tube.
Mark
the
location
plate
fixing
holes
on
the
wall.
Remove
the
plate.
(b)
Drill
the
fixing
holes
in
the
wall
and
insert
wall
plugs
if
necessary.
FIG.
10
FIREPLACE
FIXINGS
FIG.
11
SIDE
PILLAR
AND
TOP
UNIT
REPLACEMENT
o
o
Cutting
Line
-—
—
o
0
Wall
Depth
o
0
/4
Mm
Clear
1’
(a>
If
cutting
line
distance
from
tube
edge
is
at
least
1
from
bolt
hole.
FIG.
12
OUTER
VENT
SHIELD
TUBE
Cut
Both
Edges
to
Maintain
1
Clearance
From Bolt
Holes
(b>
If
cutting
line
distance
from
tube
edge
is
less
than
1’
from
bolt
hole.
5
(c)
Replace
the
location
plate
making
sure
that
it
sits
firmly
inside
the
outer
shield
tube.
(d)
Fit
a
thick
sealing
ring
over
the
vent
unit
and
push
in
to
the
location
plate.
(e) Fit
the remaining
vent
location
plate
over
the
vent
unit
with
the
dished
projection
to
the
outside.
Line
up
the
screw
holes and
start
the
fixing
screws.
Apply
a
clear
silicone
rubber
sealant
under
the
edges
of
the
wall
plate
and
tighten
the
screws.
Apply
a
bead
of
silicone
sealant
around
the
vent
tube
where
it
exits
the
wall
plate
(see
fig. 14).
1.12
CONNECT
THE
GAS
SUPPLY
The
gas
connection
point
on
the
appliance
is
at
the
right
side
of
the
firebox
inside
the
outer
case.
The
connection
is
/8”
N.P.T.
We
recommend
using
only
new
black iron
or
steel
pipes.
Copper
tubing
may
be
acceptable
-
Check
local
codes.
The
gas
supply
line
must
be
sized
and
so
installed
to
provide
a
supply
of
gas
sufficient
to
meet
the
maximum
demand
of
the
fireplace
without undue
loss
of
pressure.
Sealants
used
must
be
resistant
to
the
action
of
all
gas
constituents
including
liquified
petroleum
gas.
Sealants
should
be
applied
lightly
to
male
threads
to
ensure
excess
sealant
does
not
enter the
gas
lines.
The
supply
system
should
include
an
accessible manual
shut
off
valve
and
union
in
the
line
so
that
the fireplace
can
be
disconnected
for
servicing. Unions
in
the
gas
line
should
be
of
ground
joint
type.
A
plugged
¼”
N.P.T.
tapping
must
be
installed
in
the
line.
The
tapping
should
be
accessible
for
test
gauge
connections
upstream
of
the
gas
supply
connection
to
the
furnace.
The
fireplace
is
designed
for
the
supply
feed
line
to
enter
the
appliance
through
one
of
the
two
access
openings
in
the
back
of
the
outer
case.
These
openings
are
covered
by
metal
plates.
Remove
the
cover
plate
from
the
chosen
access
opening
by
unfastening
the
fixing
screws.
Cut
out
sufficient
of
the
cover
plate
to
allow
the
feed
line
to
pass
through
it.
Do
not
cut
away
more
than
is
necessary.
Refit
the
cover
plate
after
cutting
in
order
that
heat
losses
through
the
back
of
the
fireplace
are
minimised.
All
gas
piping
and
connections
must
be
tested
for
leaks
after
installation
or
servicing.
All
leaks
must
be
corrected
immediately.
When
testing
for
leaks:
(a)
Make
sure
that
the
fireplace
control
is
OFF
(The
knob
“OFF”
marking
should
be
at
the
top).
(b)
Open
the
manual
shut
off
valve.
(c)
Test
for
leaks
by
applying
a
liquid
detergent
to
all
joints.
Bubbles
forming
indicate
a
gas
leak.
NEVER
USE
AN
OPEN
FLAMETO
CHECK
FOR
LEAKS.
(d)
Correct
any leak
detected
immediately.
1.13
CHECK
PILOT
IGNITION
1.13.1
REMOVE
WINDOW
UNIT
Remove
the
firebox
window
unit
by
unscrewing the
twelve
wing
nuts.
Put
the
window
and
nuts
in
a
safe
place.
Remove
the
cardboard
packing
which
holds
the
ceramic
log
Outer
vent
shield
tube
N
Location
Li
plate
/
FIG.
13
OUTER
SHIELD TUBE
LOCATION
Sealing
Outer
Vent
Shield
Tube
g
Wall
Plate
==
I
Sealant
Wall
Plate
\
FIG.
14
VENT
OUTSIDE
WALL
FIXING
6
support
bed
in
position
during
transit.
Check
that
the
support
bed
is
correctly
located
with
its
front
edge
under
the
front
lip
of
the
firebox.
1.13.2
CONNECT
THE
PIEZO
IGNITOR
UNIT
Bring
the
facia
unit
close
to
the
fireplace
so
that
the
piezo
ignitor
unit
wires
can
be
connected
for
testing
before
fully
fitting
the
facia.
Connect
the
wires
as
shown
in
fig.
15.
1.13.3
CHECK PILOT
IGNITION
Pilot
ignition
is
initiated
by
a
piezo-electric spark
produced
by
depressing
the
ignitor
push
button
on
the
facia.
To
ignite
the
pilot
gas:
(a>
Push
in
the
control
knob
and
turn counter-clockwise
until
the
1/IGN
marking
is
at
the
top
(This
will
be
by
the
bright
stud
on
the
facia
when
the
facia
is
installed).
(b)
Hold
the
knob
in
for
a
few
seconds
to
allow
gas
to flow
to
the
pilot.
0.14”
(3.5mm)
FIG.
16
ELECTRODE
GAP
(c)
While
still
holding
in
the
control
knob,
depress
the
ignitor
button
several
times
until
the
pilot
lights.
If
the
pilot
does
not
ignite
(after
ensuring
that
all
air
has
been purged
from
the
gas
lines),
check
that
the
electrode
gap
is
set
as
shown
in
fig.
16.
(d)
Hold
the
control
knob
in
for
a
further
10
seconds
to
prevent
the
flame failure
detector
from
shutting
off
the
gas
while
its
thermocouple
probe
is
warming
up.
The
pilot
should
then
remain
lit.
(e)
Check
the
pilot
flame
-
See
figs
1
7a
&
1
7b.
(f)
Turn
off
by
pushing
in
the
knob
slightly
and
turning
clockwise
until
the
“OFF”
marking
is
at
the
top.
1,14
ASSEMBLE
THE
CERAMIC SIDE
CHEEKS
Unwrap
the
ceramic
side
cheeks
and
place
in
position.
The
cheeks
are
left
and
right
handed
(see
fig.
18).
FIG.
15
PIEZO IGNITOR
CONNECTON
FL
n
FIG.
1
7a
CORRECT
PILOT
FLAME
FIG,
17b
WRONG
PILOT
FLAME
7
Recess
B
Recess
D
Recess
G
1.15
ASSEMBLE
THE
CERAMIC
LOGS
In
order
to
obtain
the
correct
performance,
the
logs
must
be
positioned
as
described
in
these
instructions.
A
poor
flame
pattern
will
result
if
the
logs
are
positioned
other than
as
described
below.
Take
care
to
duplicate
the
positioning
as
shown
in
each illustration.
Each
log
has
a
number
stamped
on
it
which
corresponds
with
the
number
referred
to
in
these
instructions.
When
in
position
the numbers
on
these
logs
face
down.
Refer
to
figures
19,
20
&
21.
(a)
Place
Log
#
1
at
the
left
side
of
the
log
support
bed.
Locate
the
hole
at
the
front
edge
of
the
log
on
to
tab
“A”
on
the
front
log
support
rail
and
locate
the
projection
underneath
the
log
into
recess
“B”
in
the
ceramic
support
bed.
(b)
Place
Log
4
2
to
the
right
side
of
Log
4
1
and locate
the
hole
at
its
front
edge
onto
tab
“C”
on
the
front
support
rail.
Locate
the
rear
of
the
log
into
recess
“D”
in
the
support
bed.
(c)
Place
Log
4
3
at
the
right
side
of
the
support
bed.
Locate
the
hole
at
the
front
edge
onto
tab
“E”
of
the
front
support
rail,
Locate
the
underside
of
the
log
onto
the
recess
“G”
in
the
support
bed.
The
Logs
should
now
be
as
shown
in
fig.
19.
(d)
Place
Log
#4
between
Logs
4
2
&
4
3.
Locate
the
groove
(situated
under
the
front
edge
of
the
log>
onto
tab
“F”
on
the
front
support
rail.
Locate
projection
“H”
(situated
under
the
rear
of
the
log)
into
the
hole
in
Log
4
3
(see
fig.
20).
(e)
Place
Log
4
5
between
Logs
4
1
&
4
2
so
that
hole
“N”
(underneath
the
left
branch
of
Log
5)
locates
over
the
projection
“0”
in
the
middleof
Log
#1.
Locate
the depression
‘‘Lj’
(underneath the
long
branch
of
Log
#
5)
onto
the
projection
“M”
at
the
top
left
side
of
Log
4
2.
Place
the
bottom right
end
“J”
of
Log
4
5
onto
the
lower
left
side
of
Log
4
2
(position
“K”)
(see
fig.
21).
The
completed
log
assembly should
be
as
shown
in
fig.
22.
(f)
Replace
the
window
unit
and
re-fit
and
tighten
the
1
2
wing
nuts.
Tab
A
FIG.
18
LOG
SUPPORT
BED
&
SIDE
CHEEKS
TabC
TabF TabE
FIG
19
LOGS
41,
42
&
#3
LOCATION
Tab
F
FIG.
20
LOG
44
LOCATION
8
1.16
CHECK
CONTROL
OPERATION
&
FLAMES
Relight
the
pilot
as
described
above.
When
the
pilot
is
correctly burning,
push
the
control
knob
in
slightly
and
check
each
control
position
by
turning
progressively
counter-clockwise
until
the
marking
on
the
knob
for
the
position
to
be
checked
is
at
the
top.
Check
that
the
burners
are
as
in
the
table
below and
that
the
appearance
of
the
flames
is
correct
-
See
figs
23
&
24.
Turn
off
by
pushing
in
the
knob
slightly
and
turning
clockwise
until
the
“OFF”
marking
is
at
the
top.
Control
Main
Decorative
Position
Burner Burner
1/IGN
Off
Off
(Pilot
ig
n
it
i
on
position)
2
Low
Off
(Center
area
only_on>
3
Low
Center
area
(Center
area
only
on
only
on)
4
High
All
areas
(All
areas
on
on)
FIG.
23a
CORRECT
DECORATIVE
FLAME
FIG. 21
LOG
5
LOCATION
FIG.
22
COMPLETED
LOG
ASSEMBLY
FIG.
23b
WRONG
DECORATIVE FLAME
9
1.17
CHECK
THE
SYSTEM
PRESSURE
Maximum
heat
input
is
19,000
Btu/h.
The
fireplace
is
pre-set
to
give
the
correct
heat
input
with
natural
gas.
For
input
adjustment,
the
gas
supply
pressure
to
the
fireplace
inlet
must
be
a
minimum
of
5”
w.c.
The
maximum
inlet
gas
supply
pressure
is
8”
w.c.
The
burner
manifold
pressure
is
controlled
by
a
built-in
regulator.
The
manifold
pressure
must
be
4”
w.c.
and
should
be
checked
at
the
pressure
test
point
which
is
located
immediately
downstream
of
the
regulator.
The
pressure
check
should
be
made
with
the
appliance
burning and
the
control
set
at
position
4.
1.18
DECORATIVE
FLAME
ADJUSTMENT
The
decorative
flame
burner
may
need
adjusting
to
suit
the
local
supply
gas.
To
adjust:
(a)
Remove
the
six
wing
nuts
from
the
burner
box
front
panel
(see
fig.
25).
(b)
Remove
the
cover
plate
and
seal.
Be
careful
not
to
damage the
seal.
(c)
Light
the
appliance
and
turn
to
control
setting
#
4.
(d)
Slide
the
aeration
sleeve
on
the
decorative
flame
burner
either
way
to
give
the
correct
flame
pattern
(see
fig.
26).
There
should
be
no
appreciable
deposits
of
carbon
on
the
logs.
(e)
Replace
the
seal,
cover
plate and
wing
nuts
and
tighten
securely.
1.19
FIT
FACIA,
FRONT
STRIP
&
GRILLE
(a)
Replace
the
facia
in
the
fireplace
case
checking
that
the
ignitor
wires
do
not
get
trapped.
Re-fit
and
tighten
the
two
screws
at
the
bottom
corners
of
the
facia.
(b)
Locate
the
bottom
front
facia
strip
over
the
two
location
brackets
as
shown
in
fig.
27.
FIG.
24
MAIN
BURNER
FLAME
FIG.
26
AERATION
ADJUSTMENT
Burner
Cover
FIG.
25
BURNER
COVER
REMOVAL
Gasket
FIG 27
FRONT
RACA
STRIP
LOCATION
10
(c)
Place
the
top
grille
in
position
at
the
top
of
the
facia.
The
projecting end
of
the
strip midway
along
the
grille
must
be
at
the
top
of
the
grille
and
point
into
the
fireplace
case.
The
bottom
of
the
grille
should
rest
in
the
“V”
channel
at
the
top
of
the
facia.
The
sides
of
the
grille
should
rest
against
the
stop
brackets
fixed
to
the
inside
of
the
case
sides
(see
fig.
28).
1.20
MAKE FINAL
CHECK
Re-check
the
ignition
and
operation
at
all
control
settings.
Instruct
the
owner
mentioning
the
following
points:
(a)
How
to
operate
the
fireplace
mentioning
that
the
control
knob
must
be
pushed
in
before
turning
counter-clockwise
and
that
the
knob
must
be
turned
to
1/IGN
and
the
ignitor
button
pushed
in
to
light.
(b)
Warn
that
if
the
ceramic
window
is
damaged
the
fireplace
must
be
turned
off
immediately
and
not
used
until
the
window
is
replaced.
(c)
If
necessary,
the
facia
and
window
may
be
removed
to
re-set the
logs
when
the fireplace
is
shut
off
and
cold
but
must
be
replaced
securely
before
operating
the
fireplace.
(d)
The
fireplace
may
smell
sfightlyfor
a
short
time
due
to
being new.
This
will
soon
disappear.
(e)
It
is
recommended
that
the
fireplace
has
a
service
check
at
least
once
a
year.
(f)
Point
out
the
location
of
the
supply
pipe
shut
off
valve and
its
operation.
(g)
Hand
over
the
instruction
booklets
to
the
owner.
2.
SERVICING
2.1
GENERAL
(a)
Repair
and
replacement
work
should
only
be
done
by
a
qualified
service
person.
(b)
Always
shut
off
the
gas
supply
and
make
sure
that the
fireplace
is
cool
before
commencing
any
servicing
operation.
(c)
Always
check
for
leaks
after
servicing.
(d)
Always
check
that
the
fireplace
area
is
clear
and
free
from
combustible
materials,
gasoline
and
other
flammable vapors
and
liquids.
2.2
PERIODIC
CHECKS
(a)
Examine
the
vent
system
periodically.
Check
that
the
tubes
and
cap
on
the
outside
wall
are
not
obstructed.
(b)
Check
the
flame
patterns
periodically
-
See
illustrations
in
installation section.
FIG.
28
TOP
GRILLE
LOCATION
11

Other Valor Furnace manuals

Valor 737CN Installation instructions

Valor

Valor 737CN Installation instructions

Valor 936TTN Installation instructions

Valor

Valor 936TTN Installation instructions

Valor 936RTN Legend Instruction Manual

Valor

Valor 936RTN Legend Instruction Manual

Valor 502CP User manual

Valor

Valor 502CP User manual

Valor 837AN Installation instructions

Valor

Valor 837AN Installation instructions

Valor 134CN User manual

Valor

Valor 134CN User manual

Popular Furnace manuals by other brands

Stelpro ''SEF'' series installation guide

Stelpro

Stelpro ''SEF'' series installation guide

Drolet HEATMAX II Installation and operating instructions

Drolet

Drolet HEATMAX II Installation and operating instructions

VERDER CARBOLITE GERO HST 12/600 Installation, operation and maintenance instructions

VERDER

VERDER CARBOLITE GERO HST 12/600 Installation, operation and maintenance instructions

Lennox Merit Series installation instructions

Lennox

Lennox Merit Series installation instructions

MORTEX G18D SERIES installation instructions

MORTEX

MORTEX G18D SERIES installation instructions

Johnson Controls TM8V MP Series installation manual

Johnson Controls

Johnson Controls TM8V MP Series installation manual

Coleman DGAA installation manual

Coleman

Coleman DGAA installation manual

Empire Comfort Systems DV-20E-1 Installation instructions and owner's manual

Empire Comfort Systems

Empire Comfort Systems DV-20E-1 Installation instructions and owner's manual

Nortek VG7TC-FS user manual

Nortek

Nortek VG7TC-FS user manual

Carrier 58TN0B installation instructions

Carrier

Carrier 58TN0B installation instructions

Yukon Eagle SUPER JACK SJ125 owner's manual

Yukon Eagle

Yukon Eagle SUPER JACK SJ125 owner's manual

York TP9C Series installation manual

York

York TP9C Series installation manual

Lennox G40DF Series User's information manual

Lennox

Lennox G40DF Series User's information manual

Carrier 120 Series Installation, start-up, and operating instructions

Carrier

Carrier 120 Series Installation, start-up, and operating instructions

Bryant 330AAV User's information manual

Bryant

Bryant 330AAV User's information manual

Lennox EL280UH070P24A installation instructions

Lennox

Lennox EL280UH070P24A installation instructions

Olsen HTL-90D Installation, operation & maintenance manual

Olsen

Olsen HTL-90D Installation, operation & maintenance manual

Bryant 922SA Installation, start-up, operating and service and maintenance instructions

Bryant

Bryant 922SA Installation, start-up, operating and service and maintenance instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.