Van Air Systems AC-50 Owner's manual

PRINTED IN THE U.S.A. PAGE 1
JULY 2005
REV. A
P/N 32-0225
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
AIR-COOLED AFTERCOOLER
FOR COMPRESSED AIR SYSTEMS
MODELS AC-50 thru AC-130
(ALL VOLTAGES)
WARNING
BEFORE STARTING INSTALLATION OR MAINTENANCE PROCEDURES, TURN OFF ELECTRICAL POWER AND COMPLETELY
DEPRESSURIZE THE UNIT. FAILURE TO HEED THIS WARNING MAY RESULT IN SERIOUS PERSONAL INJURY AND/OR DAMAGE TO
THE UNIT.
NEVER REMOVE, REPAIR, OR REPLACE ANY ITEM ON THIS UNIT WHILE IT IS UNDER PRESSURE.
WHEN INSTALLING THIS UNIT, ALWAYS COMPLY WITH THE NATIONAL ELECTRICAL CODE AND ALL OTHER APPLICABLE FEDERAL,
STATE AND LOCAL CODES.
NEVER OPERATE THIS AFTERCOOLER IF THERE IS A LEAK IN THE CORE. IMMEDIATELY TAKE THE UNIT OUT OF SERVICE AND FIX
OR REPLACE THE CORE.
NEVER OPERATE THE AFTERCOOLER ABOVE THE MAXIMUM RATED OPERATING CONDITIONS, AS OUTLINED IN SECTION 3.1.
NEVER REMOVE THE FAN GUARD WHILE THE AFTERCOOLER IS OPERATING. CONTACT WITH THE ROTATING FAN BLADE(S) MAY
RESULT IN SERIOUS PERSONAL INJURY.
DURING NORMAL OPERATION, THE INLET PIPING MAY REACH TEMPERATURES OF 150oF TO 400oF. CONTACT WITH THE PIPING MAY
RESULT IN SERIOUS PERSONAL INJURY.
1.1 HANDLING THE AFTERCOOLER
CAUTION
NEVER LIFT THE AFTERCOOLER BY THE CORE OR INLET
AND OUTLET.
WHEN MOVING OR LIFTING THE UNIT, PROTECT THE
CORE FROM ACCIDENTAL DAMAGE.
Take extreme care when unpacking, moving or installing. The core is
exposed. Damage to the core or fins may render the unit inoperable.
HANDLING INSTRUCTIONS SECTION 1
1.2 EQUIPMENT CHECK
Inspect the aftercooler for any damage that may have occured
during shipment. Inspect all items shipped with the unit.
IF THE UNIT HAS BEEN DAMAGED DURING SHIPMENT:
(1) Notify carrier immediately
(2) DO NOT operate the unit before consulting factory

PAGE 2 PRINTED IN THE U.S.A.
ASSEMBLY, LEG INSTALLATION SECTION 2
2.1 INSTALLING THE LEGS
This unit was shipped without the legs installed. The legs should be
installed before placing the aftercooler in the piping system. Carefully lift
and support the unit several feet from the floor.
Position the legs against the unit and fasten them in place using the
fasteners provided. Make sure the fasteners are tightened in place.
FIGURE 1 LEG INSTALLATION DETAIL
SPECIFICATIONS AND DIMENSIONS SECTION 3
3.1 SPECIFICATIONS
WEIGHT
AC-50 ...................... 110 LBS AC-100 .................. 140 LBS
AC-60 ...................... 110 LBS AC-110 .................. 145 LBS
AC-70 ...................... 120 LBS AC-120 .................. 200 LBS
AC-80 ...................... 120 LBS AC-130 .................. 300 LBS
AC-90 ...................... 140 LBS
DIMENSIONS .............. See Section 3.2
INLET/OUTLET CONNECTIONS
AC-50 .............. 1" NPT (F) AC-100 ........ 1-1/2" NPT (F)
AC-60 .............. 1" NPT (F) AC-110 ........ 1-1/2" NPT (F)
AC-70 .............. 1-1/2" NPT (F) AC-120 ........ 2" NPT (F)
AC-80 .............. 1-1/2" NPT (F) AC-130 ........ 2" NPT (F)
AC-90 .............. 1-1/2" NPT (F)
MAXIMUM WORKING PRESSURE
ALL MODELS .................. 250 PSIG
MAXIMUM WORKING TEMPERATURE
ALL MODELS .................. 350OF
MATERIALS OF CONSTRUCTION
CABINET ......................... Galvanized steel
FAN GUARD ................... Steel with baked enamel finish
FAN ................................. Heavy gauge aluminum with steel hub
CORE .............................. Aluminum fins on copper tubes
MOTOR ........................... Open vented
MOTOR SPECIFICATIONS AND DATA
See Wiring Diagram, Figure 5 on page 6.
MAXIMUM CAPACITY (SCFM)
Rated capacities are based on the following conditions: Inlet and approach temperature at inlet pressures 80 to 125 PSIG.
Approach Temperature: The number of degrees above the temperature of the cooling medium (in this case ambient air) to
which the aftercooler reduces the compressed air. A higher approach does not mean better performance.
INLET TEMP.
APPROACH
TEMP. OF
MODEL
AC-50
AC-60
AC-70
AC-80
AC-90
AC-100
AC-110
AC-120
AC-130
15
58
79
99
119
140
190
220
380
440
10
42
58
73
87
102
138
160
275
318
5
25
34
42
50
60
81
92
160
184
20
73
99
125
150
177
235
270
425*
480*
5
18
25
32
40
48
61
73
120
145
10
31
43
55
69
81
105
125
207
250
15
43
59
77
94
112
142
172
285
345
20
53
74
95
117
140
177
215
355
430
5
15
21
27
34
43
51
63
100
125
10
25
36
47
59
73
87
110
175
217
15
35
50
65
80
100
120
150
240
300
20
44
62
81
100
124
150
187
300
375
5
13
18
24
30
38
43
55
84
110
10
22
31
41
52
64
75
95
145
190
15
30
42
57
71
87
102
130
204
257
20
37
52
71
89
110
127
160
250
320
5
11
16
22
28
34
40
50
78
100
10
19
27
37
47
59
69
86
135
175
15
26
38
52
65
81
94
120
185
240
20
32
47
65
82
100
116
148
231
300
150OF 200OF 350OF250OF 300OF
MAXIMUM PRESSURE DROP LESS THAN 3 PSI.
* Maximum ratings restricted by pressure drop: actual thermal capacities are higher.
FAN DATA (AMBIENT AIR FLOW)
AC-50 THRU AC-80 ........ 1375 SCFM
AC-90 THRU AC-100 ...... 2450 SCFM
AC-110 ............................ 2350 SCFM
AC-120 ............................ 4600 SCFM
AC-130 ............................ 4700 SCFM
ELECTRICAL REQUIREMENTS
AC-50-1 thru AC-130-1 .......... 115-1-60 w/ ODP motor
AC-50-2 thru AC-130-2 .......... 115-1-60 w/ TEFC motor
AC-50-3 thru AC-130-3 .......... 230-1-60 w/ TEFC motor
AC-50-4 thru AC-130-4 .......... 230-3-60 w/ TEFC motor
AC-50-5 thru AC-130-5 .......... 460-3-60 w/ TEFC motor

PRINTED IN THE U.S.A. PAGE 3
SPECIFICATIONS AND DIMENSIONS SECTION 3
3.2 DIMENSIONS AND COMPONENT LOCATIONS
N IN/OUT
1" NPT
1" NPT
1-1/2" NPT
1-1/2" NPT
1-1/2" NPT
1-1/2" NPT
1-1/2" NPT
2" NPT
2" NPT
INSTALLATION SECTION 4
level to allow proper drainage of fluids from the outlet manifold.
The aftercooler must be installed at least 1 foot from walls or obstruc-
tions. It is important for the unit to have an adequate air supply for
cooling at all times. If more than one unit is to be installed in the same
area, allow at least 1 foot between them.
Aftercoolers equipped with an ODP motor must be installed indoors.
All others can be installed indoors or outdoors. If the unit is to be
installed outdoors or in an area where ambient temperatures can fall
below 35oF, precautions must be made to prevent freeze-up and
damage to the unit. The drain lines and separator must be heat traced
and/or insulated and the unit should be protected from the wind.
REFERENCE Section 4.5 for details.
4.2 MOUNTING THE UNIT
After selecting the proper location as outlined above, the aftercooler
should be mounted to the installation surface. Mounting holes are
provided on the leg support braces. Reference Section 3.2 for
mounting hole locations and dimensions. Use hardware (not supplied)
sized for the mounting holes.
MODEL
AC-50
AC-60
AC-70
AC-80
AC-90
AC-100
AC-110
AC-120
AC-130
A
30.50"
30.50"
30.50"
30.50"
43.50"
43.50"
43.50"
47.63"
51.68"
B
46.50"
46.50"
46.50"
46.50"
46.50"
46.50"
46.50"
49.50"
55.50"
C
50.50"
50.50"
50.50"
50.50"
50.50"
50.50"
50.50"
53.50"
59.50"
M
2.17"
2.17"
2.17"
2.17"
2.17"
2.17"
2.79"
2.85"
2.83"
L
18.29"
18.29"
18.29"
18.29"
18.29"
18.29"
18.29"
18.23"
18.50"
K
28.12"
28.12"
28.12"
28.12"
41.12"
41.12"
41.12"
40.80"
44.80"
J
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
H
10.75"
10.75"
10.75"
10.75"
10.75"
10.75"
10.75"
10.75"
10.75"
G
19.09"
19.09"
19.09"
19.09"
32.09"
32.09"
32.09"
32.09"
36.09"
F
14.75"
14.75"
14.75"
14.75"
14.75"
14.75"
14.75"
14.75"
14.75"
E
22.00"
22.00"
21.50"
21.50"
21.50"
21.50"
22.00"
22.00"
22.00"
D
22.50"
22.50"
22.50"
22.50"
22.50"
22.50"
22.50"
25.50"
31.50"
4.1 LOCATION
CAUTION
DO NOT LOCATE THIS AFTERCOOLER WHERE PERSONNEL
MAY CONTACT THE INLET PIPING UNLESS THE UNIT IS
PROTECTED BY WARNING SIGNS AND/OR A BARRIER.
DURING NORMAL OPERATION, THE INLET PIPING MAY
BECOME EXTREMELY HOT (150OF TO 400OF). CONTACT
MAY RESULT IN SERIOUS PERSONAL INJURY.
DO NOT INSTALL THIS UNIT IN AN ENVIRONMENT OF
CORROSIVE GASES OR CHEMICALS. MAKE SURE THAT
THE MATERIALS USED IN THIS UNIT (listed on the previous
page) ARE COMPATIBLE WITH THE ATMOSPHERIC
CONDITIONS.
The aftercooler should be located far enough away from the compres-
sor so that there are no vibrations transmitted from the compressor. A
FLEXIBLE HOSE MUST BE INSTALLED IN THE PIPING TO
VALIDATE THE WARRANTY AND TO PREVENT DAMAGE TO THE
AFTERCOOLER FROM VIBRATION IN THE PIPING! REFERENCE
Section 4.3 for instructions.
The location should be level and capable of supporting the aftercooler
and all components and piping to be installed. The aftercooler must be

PAGE 4 PRINTED IN THE U.S.A.
INSTALLATION SECTION 4
MAXIMUM WORKING PRESSURE
MODEL
AC-50 & AC-60
AC-70 THRU AC-110
AC-120 THRU AC-130
70OF
525 PSIG
450 PSIG
400 PSIG
300OF
460 PSIG
395 PSIG
350 PSIG
400OF
435 PSIG
370 PSIG
330 PSIG
FIGURE 2 FLEXIBLE HOSE DETAILS
WEIGHT
2.0 LBS
3.0 LBS
4.5 LBS
DIMENSIONS
A
12"
16"
18"
B
1" NPT
1-1/2" NPT
2" NPT
PART NO.
83-0735
83-0736
83-0737
HOSE
FH-1
FH-1-1/2
FH-2
If the aftercooler is to be installed in an existing piping system, clean
the piping to remove accumulated dirt, pipe scale, oil, and other
contaminants before installing the unit.
A properly sized pressure relief valve should be installed after the
compressor and before any block valves. The relief valve should be
installed in compliance with any applicable federal, state, or local
codes.
To isolate the aftercooler for maintenance, install bypass piping around
the aftercooler and separator (if installed). Reference Figure 3.
Connect the inlet piping to the top of the aftercooler. Make sure that
the flexible hose is properly installed before the aftercooler inlet.
Provide supports wherever necessary to prevent stress on the
aftercooler. Supports should be installed close to the inlet and outlet
manifolds. Use either overhead or stiff-leg type supports.
4.5 FREEZE PROTECTION
If the aftercooler is to be installed in a location where ambient tempera-
tures may fall below 35oF, heat tracing and/or insulation must be used
on the outlet piping to the separator, the separator, and the drain
piping. The aftercooler must be protected from the direct wind, i.e. a
roof and/or walls.
The aftercooler should be turned off when ambient temperatures fall
below 35oF.
FIGURE 3 RECOMMENDED INSTALLATION DETAIL
4.3 FLEXIBLE HOSE INSTALLATION
IMPORTANT
A FLEXIBLE HOSE MUST BE INSTALLED BETWEEN THE
COMPRESSOR AND AFTERCOOLER TO VALIDATE THE
WARRANTY ON THE AFTERCOOLER.
The flexible hose must be installed perpendicular to the direction of
vibration from the compressor.
If a flexible hose was not ordered with the aftercooler, one can be
ordered from your Van Air distributor. Figure 2 lists the hose required
for each aftercooler model.
4.4 PIPING INSTALLATION
CAUTION
ALL PIPING MUST BE ADEQUATELY SUPPORTED AND
ISOLATED FROM VIBRATION. EXCESSIVE STRESS OR
VIBRATION IN THE PIPING WILL CAUSE DAMAGE TO THE
AFTERCOOLER CORE.
TO ENSURE PROPER OPERATION, MAKE SURE THAT THE
INLET AND OUTLET PIPING ARE CORRECTLY CONNECTED
TO THE UNIT. REFERENCE FIGURE 3.

PRINTED IN THE U.S.A. PAGE 5
INSTALLATION SECTION 4
FIGURE 4 SEPARATOR DETAILS
MODEL
S-10-AD
S-20-M
S-30-M
A
10.00"
12.10"
16.10"
B
4.75"
4.38"
4.38"
C
1.00"
2.30"
2.30"
D
1" NPT
1" NPT
1-1/2" NPT
E
1/8" NPT
1/4" NPT
1/4" NPT
MWP
(PSIG)
250
250
250
MAX
120
160
400
MIN
11
11
60
FLOW (SCFM)
AFTERCOOLER
AC-50 thru AC-90
AC-100 & AC-110
AC-120 & AC-130
SEPARATOR
S-10-AD
S-20-M
S-30-M
PART NO.
83-0744
83-0745
83-0746
DRAIN
FD-1
FD-1
FD-1
PART NO.
83-0751
83-0751
83-0751
4.7 ELECTRICAL CONNECTIONS
CAUTION
TURN OFF MAIN POWER SUPPLY BEFORE WIRING TO THE
AFTERCOOLER.
MAKE SURE THAT ALL USER SUPPLIED WIRING IS
PROPERLY SIZED TO HANDLE THE AMPERAGE REQUIRED
BY THE AFTERCOOLER AND ANY ADDITIONAL
EQUIPMENT.
WHEN WIRING TO THIS UNIT AND ANY OTHER
ELECTRICAL COMPONENTS, ALWAYS COMPLY WITH THE
NATIONAL ELECTRICAL CODE AND ALL APPLICABLE
FEDERAL, STATE AND LOCAL CODES.
IF THE AFTERCOOLER IS TO BE INSTALLED OUTDOORS
OR IN AN EXTREMELY HUMID ATMOSPHERE, MAKE SURE
THAT ALL WIRING AND COMPONENTS ARE PROPERLY
RATED.
VERIFY THAT THE POWER SOURCE MATCHES THE
AFTERCOOLER ELECTRICAL REQUIREMENTS BEFORE
MAKING ANY CONNECTIONS. REFERENCE EQUIPMENT
DATA TAG AND FIGURE 4 FOR INFORMATION.
TO PREVENT POSSIBLE ELECTRICAL SHOCK, IT IS
IMPORTANT THAT THIS UNIT IS GROUNDED. ALWAYS USE
THE PROVIDED GROUNDING SCREW.
The aftercooler electrical requirements are listed on the
equipment data tag and in Figure 5. If there are any discrepan-
cies between the data tag and Figure 5, use the information on
the tag.
Remove the cover from the electrical junction box on the
aftercooler motor. Using FIGURE 5 as reference, make the
necessary wiring connections. Several ways to wire the unit
are listed below. Make the connections for the pertinent
application(s).
1. DEDICATED POWER SUPPLY AND DISCONNECT
Install a properly sized fused disconnect before the
aftercooler. Make the necessary wire connections and re-
install the junction box cover.
2. INTERLOCKED WITH COMPRESSOR MOTOR STARTER
The aftercooler can be interlocked with the air compressor
starter. This allows the aftercooler to operate only when the
air compressor is operating.
If a set of auxiliary, normally open contacts is available on
the air compressor magnetic starter, make necessary wiring
connections from the contacts to the aftercooler.
If a set of auxiliary contacts is not available, use a properly
sized contactor. Wire the contactor's holding coil in parallel
with the air compressor starter holding coil. Make the
necessary wiring connections from the contactor to the
aftercooler.
4.7-1 FAN MOTOR ROTATION
The rotation of the fan motor(s) is important. Units with 3
phase power should be checked for proper rotation after
installation.
Energize the unit. Observe the rotation and air flow direction.
Reference Section 3.2 for air flow direction. If the fan(s) do
not pull the air across the core, turn off the unit and switch
two of the main power legs.
4.6 SEPARATOR INSTALLATION
CAUTION
IF THE SEPARATOR DRAIN IS TO BE CONNECTED INTO A
REMOTE OR COMMON DRAIN LINE, MAKE SURE THAT IT IS
VENTED.
THE DISCHARGE FROM THE SEPARATOR MAY CONTAIN
COMPRESSOR LUBRICANTS. COMPLY WITH ALL
REGULATIONS CONCERNING DISPOSAL OF SUCH FLUIDS.
When the system air is cooled by the aftercooler, moisture in
the compressed air condenses and accumulates in the outlet of
the aftercooler. To efficiently remove this liquid from the air
system, a separator with an FD-1 float drain must be installed
immediately downstream of the aftercooler.
Install the separator as outlined in the Installation, Operation,
and Maintenance Instructions supplied with the component. If
a separator was not ordered with the aftercooler, one can be
ordered from your VAN AIR distributor.

PAGE 6 PRINTED IN THE U.S.A.
5.3 REPAIRING LEAKS
INSTALLATION SECTION 4
FIGURE 5 WIRING DIAGRAM

PRINTED IN THE U.S.A. PAGE 7
5.1 START UP INSTRUCTIONS
Pressurize the compressed air system. If the aftercooler was
interlocked with the compressor, the aftercooler will begin to
operate immediately. If the aftercooler was wired on a sepa-
rate electrical source, turn on the source.
Open the inlet and outlet isolation valves on the aftercooler (if
installed). Close the bypass valve. The aftercooler is ready for
operation.
5.2 OPERATING INSTRUCTIONS
The operation of the aftercooler is simple. The fan rotates,
moving ambient air across the core. The ambient air flow cools
the compressed air inside the core. The aftercooler will
automatically operate as long as electrical power is supplied to
the unit.
OPERATION SECTION 5
MAINTENANCE and REPLACEMENT PARTS SECTION 6
6.3 MOTOR LUBRICATION
This unit is equipped with a sleeve bearing motor. The sleeve
bearings will require lubrication at least every 6 months. Add a few
drops of S.A.E. 20 oil to each bearing.
6.4 REPLACEMENT PARTS
Replacement Cores
AC-50 P/N 34-0733
AC-60 P/N 34-0734
AC-70 P/N 34-0735
AC-80 P/N 34-0736
AC-90 P/N 34-0737
AC-100 P/N 34-0738
AC-110 P/N 34-0739
AC-120 P/N 34-0740
AC-130 P/N 34-0741
Replacement 12" Dia. Fan Blade
AC-50 through AC-80 P/N 26-5906
Replacement 14" Dia. Fan Blade
AC-90 through AC-130 P/N 26-5907
Replacement Fan Guard
All models P/N 41-0208
Replacement 1/4 HP 115v Motor
AC-50-1 through AC-130-1 P/N 34-0744
5.3 SHUT DOWN INSTRUCTIONS
To shut down the aftercooler, turn off the electrical power
source. If the aftercooler was interlocked with the compressor,
the aftercooler will automatically turn off with the compressor.
Open the bypass valve and close the inlet and outlet isolation
valves (if installed).
6.0 MAINTENANCE INSTRUCTIONS
WARNING
BEFORE STARTING INSTALLATION OR MAINTENANCE
PROCEDURES, TURN OFF ELECTRICAL POWER AND
COMPLETELY DEPRESSURIZE THE UNIT. FAILURE TO
HEED THIS WARNING MAY RESULT IN SERIOUS PERSONAL
INJURY AND/OR DAMAGE TO THE UNIT.
NEVER REMOVE, REPAIR, OR REPLACE ANY ITEM ON THIS
UNIT WHILE IT IS UNDER PRESSURE.
NEVER REMOVE THE FAN GUARD WHILE THE
AFTERCOOLER IS OPERATING. PERSONAL CONTACT
WITH THE ROTATING FAN BLADE MAY RESULT IN
SERIOUS PERSONAL INJURY.
6.1 CORE EXTERIOR CLEANING
The core should be regularly cleaned. Accumulation of dirt or other
contaminants such as oils will greatly reduce the efficiency of the
aftercooler.
Normal accumulation of dirt can be removed by blowing off the core
with compressed air. If the core becomes contaminated with oil-laden
particles, it can be steam cleaned. Clean with extreme care. The
aluminum fins can be easily damaged.
6.2 CORE INTERIOR CLEANING
If the compressed air system contains excessive lubricating fluids,
build-up may occur. The interior of the core may be cleaned to
remove the deposits by circulating a mild cleaning solution through the
core. For most conditions, a mild alkaline solution such as OAKITE or
equal, is satisfactory. For extreme conditions, it might be necessary
to use a weak solution of INHIBITED hydrochloric acid.
Turn off the electrical power supply, depressurize the unit, and
disconnect it from the air system. Circulate the solution through the
core until it is clean. Make sure that the core is rinsed out thoroughly
before returning the unit to service.
When the core is cleaned, it is important that the full characteristics of
the fouling material and cleaning agent be known. Proper care must
be taken when handling and disposing of the solution. Always follow
the instructions supplied with the material.
CAUTION
NEVER USE SOLVENTS CONTAINING STRONG ACID OR
ALKALINE BASES TO CLEAN THE CORE. DAMAGE TO THE
CORE MAY OCCUR.

PAGE 8 PRINTED IN THE U.S.A.
2950 Mechanic Street
Lake City, PA 16423 USA
Phone: 800/840-9906
Corporate Fax: 814/774-0778
Order Entry Fax: 814/774-3482
www.vanairsystems.com
I. INSTALLATION.
Unless otherwise set forth in a quotation and/or acknowledgment, Seller shall not be responsible for
installation. Cost of and all risks of damage to the equipment and/or components thereof caused by
installation shall be the sole responsibility of Buyer. If supervision of installation and/or supervision
of start up of the equipment is to be provided by Seller, Buyer shall assume all costs incurred by Seller
in furnishing supervision. If supervision of installation and/or supervision of start up of the equipment
is provided by Seller, Seller shall only be responsible for any loss or damage growing out of a direct
negligent act or acts of Seller’s supervisor.
SELLER SHALL NOT BE RESPONSIBLE FOR IMPROPER OPERATION OF THE EQUIPMENT
DUE TO FAULTY ERECTION OR INSTALLATION.
II. PERFORMANCE.
Seller shall have no responsibility for the performance of its Goods when installed under conditions
varying materially from those under which the product is usually tested or operated under existing
industry standards.
III. WARRANTY
All AC Series Aftercoolers manufactured by Seller are guaranteed to be free from defective materials
and workmanship for a period of one (1) year from date of shipment.
The above warranties for all products described do not cover abuse, neglect, lack of normal
maintenance, accidents or other exceptional circumstances.
Date of shipment will be defined as the date of departure from the factory or from distributor stock.
A copy of the distributor invoice to the customer at time of shipment is required as verification of
shipment from distributor stock. Equipment start up will be verified by receipt of the product
registration card.
Seller’s obligation under this warranty may, at its option, be discharged by refunding the price of,
furnishing or repairing, without charge, FOB its factory, a similar part to replace any part of its own
manufacture which within the above specified periods, proves to have been defective, provided that
within a reasonable time for inspection after delivery, Seller is notified of such defects and the
equipment, material or part claimed to be defective is delivered pre-paid to Seller at Lake City,
Pennsylvania with evidence that it has been properly maintained and used in accordance with
instructions. If, in connection with such warranties, repairs are performed by the Buyer with the written
authorization of Seller, then the expense in connection with such repairs shall not exceed the cost
of material and direct labor If such repairs are performed by Buyer without the written authorization
of Seller. Seller will not assume any of the expenses in connection with such repairs and will
immediately void any remaining warranty on the Goods.
THE REPAIR OR REPLACEMENT WARRANTY HEREIN SET FORTH IS THE EXCLUSIVE
WARRANTY GIVEN BY SELLER FOR ITS GOODS. THIS WARRANTY IS GIVEN IN LIEU OF ANY
OR ALL WARRANTIES, WHETHER WRITTEN OR ORAL, EXPRESSED OR IMPLIED. ANY AND
ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR
PURPOSE ARE HEREBY EXPRESSLY EXCLUDED BY SELLER. SELLER NEITHER ASSUMES,
NOR DOES IT AUTHORIZE ANY OTHER PERSON TO ASSUME ON ITS BEHALF ANY OTHER
LIABILITY IN CONNECTION WITH THE SALE OF ITS GOODS.
IV. LIMITATIONS OF LIABILITIES AND INDEMNITIES.
IN NO CASE, WHETHER AS A RESULT OF BREACH OF CONTRACT, BREACH OF WARRANTY
OR TORT (INCLUDING SELLER’S OR BUYER’S NEGLIGENCE OR STRICT LIABILITY) SHALL
SELLER BE LIABLE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES INCURRED BY
BUYER, INCLUDING, BUT NOT LIMITED TO, LOSS OF SALES PROFIT, REVENUE, OR GOOD
WILL; LOSS OF USE OF GOODS OR ANY ASSOCIATED EQUIPMENT OR MATERIAL; COST OF
CAPITAL; COST OF SUBSTITUTE PRODUCTS, FACILITIES OR SERVICES; DOWN TIME COSTS;
ATTORNEY’S FEES; OR LOSSES OR CLAIMS OF CUSTOMERS OF BUYER FOR SUCH DAMAGES
BUYER HEREBY AGREES TO INDEMNIFY AND HOLD HARMLESS SELLER FROM ANY AND ALL
SUCH DAMAGES BUYER FURTHER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS
SELLER FROM ANY AND ALL CLAIMS, LIABILITY, DAMAGES OR EXPENSES (INCLUDING
ATTORNEY’S FEES) DUE TO PERSONAL INJURIES OR DEATH, TO BUYER, ITS EMPLOYEES,
AND THIRD PARTIES AND FROM PROPERTY DAMAGE RESULTING FROM THE NEGLIGENCE
OR STRICT LIABILITY OF BUYER NOT WITHSTANDING THE PROVISIONS OF ANY WORKER
COMPENSATION OR SIMILAR STATUTE
V. SERVICE, OPERATING PROCEDURE, WARNINGS.
Should Buyer request start up supervision by Seller, a maximum number of days required for this
supervision may be included and specified in the quotation and/or acknowledgment as a separate
price item. The specified days are only approximate, since start up. Supervision is contingent upon
equipment and work supplied by others and beyond the control of Seller, and Seller shall be paid for
any days actually worked in addition to those specified on a pro-rata basis.
Start up supervision and warranty supervision and warranty service time will include all elapsed time
during the standard working hours, as defined by Seller, or Seller’s representative from the time
Seller’s representative leaves his operating base or another customer’s plant.
Where the service to be performed is start up supervision. Seller should be notified approximately
30 days prior to start up Seller’s representatives may be required to have standard time verification
sheets approved by Buyer’s authorized representative, and the name and title of this representative
should be furnished to Seller with the notification.
Unless set forth in the quotation and/or acknowledgment, Seller shall not be obligated to provide
special operating manuals or operating procedures for the operation of its equipment or supply special
warning placards to be affixed to the equipment. If such manuals, procedures or placards are provided
by Seller, Buyer shall be responsible for payment of cost of furnishing such items, for instructing any
operator of the equipment as to the contents of such manuals and/or procedures; for requiring that such
procedures be abided by; for insuring that warning placards remain affixed to the equipment and for
requiring operators to abide by warning placards.
Any safety equipment required to be worn by any operator or maintenance person shall be provided
by Buyer, and the failure to provide such equipment or the failure to require the use thereof shall be
the Buyer’s sole responsibility. Buyer shall indemnify and hold Seller harmless for any liability with
respect thereto.
Seller shall not be responsible for providing safety devices and/or guarding of the equipment except
as provided for in the quotation and/or acknowledgment, and Buyer specifically assumes all
responsibility for supplying such safety devices and/or guarding necessary for the safe operation of
the equipment. If safety devices and/or guarding are specified in the quotation and/or acknowledgment,
Buyer shall be solely responsible for making certain that any operator of the equipment uses such
safety devices and/or guarding and Buyer shall indemnify and hold Seller harmless with respect to any
property damage and/or personal injury, including death, occasioned by any person by reason of such
failure on the part of Buyer and/or its operator.
8.0 WARRANTY
WARRANTY SECTION 8
TROUBLESHOOTING SECTION 7
7.0 TROUBLESHOOTING
1. FAN MOTOR NOT OPERATING
Motor failure - Check electrical power source. If power supply is okay, check the motor. Replace if necessary.
Power supply failure - Check electrical power source. Check contactors, fuses, or disconnects. Check incoming wiring for
damage. If aftercooler is interlocked with the compressor, check the compressor starter.
2. HIGH AFTERCOOLER OUTLET TEMPERATURES
Fan motor not operating - Reference Problem 1.
Plugged aftercooler core or restricted air flow - Inspect the core for deposits of dirt and/or oils. If the core is contaminated,
clean it as outlined in Sections 6.1 thru 6.2. Check for obstructions around the aftercooler. Remove if present.
3. INCREASED LIQUID (WATER) CONTENT IN THE COMPRESSED AIR SYSTEM DOWNSTREAM OF THE AFTERCOOLER
Plugged or damaged separator - Check the separator for damage and proper operation.
Separator installed incorrectly - If a separator was installed, check to make sure that it was installed properly. If no separator
was installed downstream of the aftercooler, one should be installed to remove the liquid from the air system.
Separator drain plugged or damaged - Check the drain for damage and proper operation.
4. EXCESSIVE PRESSURE DROP ACROSS THE AFTERCOOLER
Aftercooler core damaged or clogged - Inspect the core for damage or blockage. If the core is damaged, repair or replace.
If the core is plugged, flush it out as outlined in Section 6.2.
MAKING COMPRESSED AIR AND GAS WORK BETTER SINCE 1944.
This manual suits for next models
8
Table of contents
Popular Freezer manuals by other brands

AGT
AGT PSG BCR05 Installation Manual, Operating Manual, Maintenance Manual, Spare Part List

Gaggenau
Gaggenau RF 200 user manual

montpellier
montpellier MIFF7301F Installation and operating instructions

NEFF
NEFF GI781 Series user manual

Baumatic
Baumatic BZ550W instruction manual

Frigidaire
Frigidaire FFU11FC4BW Factory parts catalog