Vicon V1400X-DVC-3 User manual

V1400X-DVC-3 Instruction Manual
V1400X-DVC-3 System Console
Warning: To reduce a risk of fire or electric shock, do not expose this product to rain or moisture.
Vicon Industries Inc. does not warrant that the functions contained in this equipment will meet your requirements or that the
operation will be entirely error free or perform precisely as described in the documentation. This system has not been
designed to be used in life-critical situations and must not be used for this purpose.
Copyright © 2001 Vicon Industries Inc. All rights reserved.
Product specifications subject to change without notice.
Vicon and its logo are registered trademarks of Vicon Industries Inc.
Vicon Part No. 8009-8090-00-00 Section 9 Rev 501

This page intentionally left blank.


FCC Notice
Note: Complies with Federal Communications Commission Rules & Regulations Part 15, Subpart B for a
Class A digital device.
WARNING
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in
strict accordance with the manufacturer’s instruction, may cause interference to radio and television reception.
It has been type tested and found to comply with the limits for a Class A computing device in accordance with
the specification in subpart B of part 15 of the FCC rules, which are designed to provide reasonable protection
against such interference in a commercial installation. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause interference to radio and television reception,
which can be determined by turning equipment off and on, the user is encouraged to try and correct the
interference by one or more of the following measures:
• Reorient the receiving antenna.
• Relocate the equipment with respect to the receiver.
• Relocated the equipment away from the receiver.
• Plug the equipment into a different electrical outlet so that the equipment and receiver
are on different branch circuits.
If necessary, the user should consult the dealer or an experienced radio/television technician for additional
suggestions.
The user may find the following booklet prepared by the Federal Communications Commission helpful:
“Interference Handbook, Bulletin CIB-2”
This booklet is available from the U.S. Government Printing Office, Superintendent of Documents, Mailstop
SSOP, Washington, D.C. 20402-9328, ISBN 0-16-045542-1.
Warning: Power must be removed from this unit before removing circuit modules or ribbon cables.
Caution: This unit contains circuit cards with integrated circuit devices that can be damaged by static
discharge. Take all necessary precautions to prevent static discharge.

XX090 Rev 501 System Console Contents •i
Contents
Introduction......................................................................................................................... 1
Installation: Standalone System ....................................................................................... 4
Installation: AURORA/VCR ONLY ..................................................................................... 6
Installation: NOVA/AURORA/VCR..................................................................................... 8
Installation: MSS/NOVA/AURORA/VCR .......................................................................... 10
The V1400X-IFS Fail-Safe Device.................................................................................... 12
Joystick Devices...............................................................................................................14
Passcodes & User IDs...................................................................................................... 16
Preliminary Steps ............................................................................................................. 18
Communication Settings ................................................................................................. 21
System Settings................................................................................................................25
Alarms ............................................................................................................................... 30
Operation: 1300 & 1400 Series........................................................................................ 32
Operation: 1300 Series Only............................................................................................ 36
Operation: V1400 Series Only ......................................................................................... 38
Operation: Multiplexers ................................................................................................... 40
Operation: VCRs............................................................................................................... 46
Operation: Macros............................................................................................................ 49
Diagnostics....................................................................................................................... 51
Maintenance...................................................................................................................... 52
Reference.......................................................................................................................... 53
Technical Information ...................................................................................................... 56
Shipping Instructions....................................................................................................... 58
Index.................................................................................................................................. 59

ii •Important Safeguards XX090 Rev 501 System Console
Important
Safeguards
GRAPHIC SYMBOL EXPLANATION
The lightning flash with arrowhead symbol, within an
equilateral triangle, is intended to alert the user to the
presence of uninsulated “dangerous voltage” within the
product’s enclosure that may be of sufficient magnitude
to constitute a risk of electric shock.
CAUTION
RISK OF ELECTRIC SHOCK
DO NOT OPEN
TO REDUCE THE RISK OF ELECTRICAL SHOCK,
DO NOT REMOVE COVER (OR BACK). NO USER-
SERVICEABLE PARTS INSIDE. REFER SERVICING
TO QUALIFIED SERVICE PERSONNEL.
CAUTION:
The exclamation point within an equilateral triangle is
intended to alert the user to the presence of important
operating and maintenance (servicing) instructions in
the literature accompanying the unit.
1. Read Instructions - All the safety and operating
instructions should be read before the video product is
operated.
2. Retain Instructions - All the safety and operating
instructions should be retained for future reference.
3. Heed Warnings - All warnings on the video product
and in the operating instructions should be adhered to.
4. Follow Instructions - All operating and use
instructions should be followed.
5. Cleaning - Step aapplies to equipment that can be
disconnected from the CCTV system without seriously
jeopardizing security. Step b applies to equipment that
must operate continuously such as video switching
equipment at military installations.
a. Disconnect this video product from its power
source before cleaning. Do not use caustic,
abrasive, or aerosol cleaners. Use a damp cloth for
cleaning.
b. Use a damp cloth to clean the equipment. Do not
allow moisture or liquids to enter any vents. Do not
use caustic, abrasive, or aerosol cleaners.
6. Attachments - Do not use attachments not
recommended by Vicon as they may cause hazards.
7. Water and Moisture - Do not use this video product
in any location where it may be exposed to water or
moisture. This does not apply to outdoor camera
housings, outdoor pan-and-tilt drives, and other
equipment designed for direct exposure to outdoor
environments.
8. Accessories - Do not place this video product on
any unstable surface or table. The video product may
fall, causing serious injury to a person and serious
damage to the video product. Use only with a mounting
accessory recommended by Vicon, or sold with the video
product. Any mounting of the video product should
follow Vicon’s instructions, and a mounting accessory
recommended by Vicon should be used.
9. Ventilation - Slots and openings in the cabinet are
provided for ventilation and to ensure reliable operation
of the video product and to protect it from overheating,
and these openings must not be blocked or covered.
The openings should never be blocked by placing the
video product on a rug or other similar surface. This
video product should never be placed near or over a
radiator or heat register. This video product should not
be placed in a built-in installation such as a bookcase or
rack unless proper ventilation is provided or Vicon’s
instructions have been adhered to.
10. Power Sources - This video product should be
operated only from the type of power source indicated
on the marking label. If you are not sure of the type of
power supplied to your installation site, consult your
Vicon dealer or local power company. For video
products intended to operate from battery power, or
other sources, refer to the operating instructions.
11. Grounding - This applies to video products
equipped with a 3-wire grounding-type plug, a plug
having a third (grounding) pin. This plug only fits into a
grounding-type power outlet. This is a safety feature. If
you are unable to insert the plug into the outlet, contact
your electrician to replace your obsolete outlet. Do not
defeat the safety purpose of the grounding-type plug.
12. Power-Cord Protection - Power supply cords
should be routed so that they are not likely to be walked
on or pinched by items placed upon or against them,

XX090 Rev 501 System Console Important Safeguards •iii
paying particular attention to cords at plugs,
convenience receptacles, and the point where they exit
from the video product.
13. Outdoor Cable Grounding - If an outside cable
system is connected to the video product, be sure the
cable system is grounded so as to provide some
protection against voltage surges and built-up static
charges. Section 810 of the National Electrical Code,
ANSI/NFPA 70-1984, provides information with respect
to proper grounding of the lead-in wire to an antenna
discharge unit, size of grounding conductors, location of
antenna-discharge unit, connection to grounding
electrodes, and requirements for the grounding
electrode.
14. Lightning - For added protection for this video
product when it is not used for long periods of time,
disconnect it from its power source and from the cable
system. This prevents damage to the video product due
to lightning and power-line surges.
15. Power Lines - An outside cable system should not
be located in the vicinity of overhead power lines or
other electric light or power circuits, or where it can fall
into such power lines or circuits. When installing an
outside cable system, extreme care should be taken to
keep from touching such power lines or circuits as
contact with them might be fatal.
16. Overloading - Do not overload wall outlets and
extension cords as this can result in a risk of fire or
electric shock.
17. Object and Liquid Entry - Never push objects of
any kind into this video product through openings as
they may touch dangerous voltage points or short out
parts that could result in a fire or electric shock. Never
spill liquid of any kind on the video product.
18. Servicing - Do not attempt to service this video
product yourself as opening or removing covers may
expose you to dangerous voltage or other hazards.
Refer all servicing to qualified service personnel.
19. Damage Requiring Service - Disconnect this video
product from its power source and refer servicing to
qualified service personnel under the following
conditions. Note that step cdoes not apply to outdoor
camera housings, outdoor pan-and-tilt drives and other
equipment specifically designed for direct exposure to
outdoor environments.
a. When the power-supply cord or plug is damaged.
b. If liquid has been spilled, or objects have fallen into
the video product.
c. If the video product has been exposed to rain or
water.
d. If the video product does not operate normally by
following the operating instructions. Adjust only
those controls that are covered by the operating
instructions, as an improper adjustment of other
controls may result in damage and will often require
extensive work by a qualified technician to restore
the video product to its normal operation.
e. If the video product has been dropped or the cabinet
has been damaged.
f. When the video product exhibits a distinct change in
performance - this indicates a need for service.
20. Replacement Parts - When replacement parts are
required, be sure the service technician has used
replacement parts specified by Vicon or that have the
same characteristics as the original part. Unauthorized
substitutions may result in fire, electric shock, or other
hazards.
21. Safety Check - Upon completion of any service or
repairs to this video product, ask the service technician
to perform safety checks to determine that the video
product is in proper operating condition.

XX090 Rev 501 System Console Introduction •1
Introduction
Note: Read all of the instructions completely before installing or operating this equipment.
The information in this manual covers installation, programming and operation for the V1400X-DVC-3
System Console. The installation procedures should only be performed by a qualified technician using
approved materials in accordance with national, state and local wiring codes. The unit complies with FCC
standards for a Class A device and with European Community EMC Directive 89/336. The product was
subjected to the testing outlined in European Normalization Standard EN 50081-1 (Electromagnetic
Compatibility - General Emissions Standard Part 1: Residential, Commercial and Light Industry), and EN
50082-1 (Electromagnetic Compatibility - Generic Immunity Standard Part 1: Residential, Commercial,
and Light Industry).
The V1400X-DVC-3 System Console is a central control station capable of controlling camera stations
connected to Vicon’s NOVACPU-based matrix control systems, digital multiplexers and video cassette
recorders (VCRs). The menu-based LCD display changes to display the proper functionality for the
selected control system. Selections are made using fiber optic backlit soft keys and the system console
keyboard. Multicolored, oversized keys and a hand rest, as well as user-defined macros and an on-line
help system are just a few of the features that make the system console easy to use. Refer to Figure 1
(hand rest not shown).
123
?
4 5
F1 F2
F3 F4 6
AUX
789
PRE
0
CLEAR MONITOR
F5 F6
F7 F8
CAMERA
Figure 1
V1400X-DVC-3 System Console
Fiber optic backlit soft
keys are used to make
selections based on the
selected NOVA control
system.
The LCD menu
system is easy
to navigate and
features pop-up
on-line help.
Function keys
are used to
access the
macro screens.
You may have
64 macros,
each with up to
16 keystrokes.
Any camera in
the system may
be quickly
selected.
A detailed multi-page
help system contains
instructions on system
console functions.
Oversized monitor and
camera keys are
conveniently located.

2 •Introduction XX090 Rev 501 System Console
System Configurations
There are four general system configurations using the V1400X-DVC-3 System Console: Standalone,
NOVA/AURORA/VCR, MSS/NOVA/AURORA/VCR and AURORA/VCR ONLY. In a standalone system,
there is no control system (CPU). You may connect receivers directly to the system console in this
configuration. In installations with control systems, receivers are connected to the control system. The
same is true for a matrix switcher (without CPU card); you may connect one directly to the system console
in standalone configuration, but you would connect the switcher to the control system in
NOVA/AURORA/VCR or MSS/NOVA/AURORA/VCR configurations. Like standalone systems,
AURORA/VCR ONLY systems do not include a control system. AURORA/VCR ONLY systems allow you
to control multiplexers and VCRs. When using VCRs, you must also use Vicon's Multi-Output Interface
devices (MIU). Multiple keyboards may be connected in all configurations except for standalone.
In a MSS/NOVA/AURORA/VCR system, you will need the V1400X-MSS Multi-System Selector. The
master system console can be used to select each of the control systems using the system console
V1300 or V1400 Series Control screen. A NOVA/AURORA/VCR system does not require the multi-system
selector, as control system selection is not relevant (there is only one control system).
The V1400X-IFS Fail-Safe Device is used to daisy-chain system consoles. Refer to page 12 for
illustrations of daisy-chained system consoles. The system console must be used with the fail-safe device
to ensure continuous communication with all consoles should one console become inoperable.
Two control (or “pointing”) devices are available for use with the system console, the V1400X-JST Joystick
Keypad and the V1400X-DJT Desk-Top Joystick. Only one device may be used at a time. The joystick
keypad may be customized for left- or right-handed users using a conveniently located switch. A trackball,
with an optional trackball shaft, is used to control receiver functions. Buttons are used to control lens
functions. The desk-top joystick contains one button used to control all lens functions and LEDs to indicate
which function is active. A traditional joystick is used for receiver control. Both the joystick keypad’s
trackball and the V1400X-DJT’s joystick are used to make choices in the AurorA99/AurorA or AurorA2000
menu system.
V1400X-DJT Desk-Top Joystick
V1400X–DJT
ZOOM
TILT
PAN
FOCUS
IRIS
FOCUS
FAR
IRIS
CLOSE ZOOM
OUT
FOCUS
NEAR
IRIS
OPEN ZOOM
IN
V1400X-JST Joystick Keypad

XX090 Rev 501 System Console Introduction •3
Installation and Programming Overview
The installation pages in this manual are set up in four sections, to reflect the four installation
configurations. In addition to choosing the correct installation configuration, you must also define your
system correctly using the system console software. The following steps will enable you to decide which
configuration is appropriate for your CCTV site and direct you to the corresponding programming sections.
1. Your first step is to choose the installation configuration (mode) for your system. Use the following
guidelines:
If you have… then the appropriate configuration is…
• no control system (CPU) and want to control receivers and
use a matrix switcher to switch video • Standalone mode, refer to page 4
• no control system (CPU) and want to control multiplexers
and VCRs • AURORA/VCR ONLY mode, refer to
page 6
• one NOVA control system (CPU) and want the ability to
control multiplexers and VCRs • NOVA/AURORA/VCR mode, refer to
page 8
• more than one NOVA control system (CPU) and want the
ability to control multiplexers and VCRs • MSS/NOVA/AURORA/VCR mode,
refer to page 10
2. If you have more than one system console, refer to pages 11 and 12 for star and daisy-chain
configurations.
3. If you will use the V1400X-DJT Desk-Top Joystick or V1400X-JST Joystick Keypad, refer to page 14.
4. Refer to page 16 to begin programming the system console software, continuing to define your
settings until you reach the chapter titled Communication Settings. If you chose standalone mode,
skip to the next step. If you chose any other mode and will use multiplexers in your system, you must
choose a protocol (A2000 or A99). "A2000 Protocol" refers to Vicon's proprietary 2-wire RS-485
AurorANet protocol. You may connect AurorANet devices directly to the System Console. Examples of
typical devices employing AurorANet are the AurorA2000 multiplexer, this version of the System
Console and the A2K-KBD Remote Keyboard. "A99 Protocol" refers to devices which do not have
AurorANet protocol, such as the AurorA/AurorA99 multiplexer and earlier versions of the System
Console. To use these devices, you must use an MIU, as discussed in the MIU instruction manual.
Refer to
Setting Keypad Addresses
on page 21 and choose the protocol.
5. Continue with the System Settings chapter, using the following to reference the correct section. You
will only define one system (standalone, NOVA/AURORA/VCR, MSS/NOVA/AURORA/VCR or
AURORA/VCR ONLY), so disregard the other sections under
Defining the Mode
.
If you have… refer to…
Standalone mode
Defining the Mode, Standalone
, page 26
AURORA/VCR ONLY mode
Defining the Mode, AURORA/VCR ONLY
, page 27
NOVA/AURORA/VCR mode
Defining the Mode, NOVA/AURORA/VCR
, page 26
MSS/NOVA/AURORA/VCR mode
Defining the Mode, MSS/NOVA/AURORA/VCR
, page 26
6. If you have chosen any mode except standalone, you may have multiplexers in your system. If so,
refer to page 29.
7. Refer to page 28 if you have VCRs in your system. VCRs cannot be used in standalone mode.
8. Continue with the programming chapters, referring to the Reference chapter if necessary.

4 •Installation: Standalone System XX090 Rev 501 System Console
Installation: Standalone System
Warning: Do not apply power to any unit until all connections are properly made.
Make connections as shown in the figure and tables below. Refer to page 53 for cable recommendations.
You may use the supplied RJ45 Termination Box to organize your cable runs and provide easy wiring from
the receiver or distribution line control. Using the termination box is not required. The termination box has
eight labeled connecting screws. To determine which connection to make to which screw, refer to the
table in Figure 2.
250V SB
2A 10-12VAC
RISK OF FIRE REPLACE
FUSEAS MARKED
CAUTION PWR/COMM JOYSTICK CONTROL OUT
+AC –
Connect to switcher
card cage's Control
In connector.
Connect to RS-485* or RS-232**
device(s). Connect to auxiliary
devices.
Pin No.
RS-485
RS-232
Signal Name
RS485 + (A)
RS485 – (B)
Ground
1
6
7
Pin No.
Auxiliary Devices
Signal Name
Ground
Aux 1
Aux 2
7
8
9
Pin No. Signal Name
TxD
RxD
RTS
CTS
Ground
2
3
4
5
7
Power supply with cable supplied.
Cable supplied in accessory kit.
RS232/RS485
AUX
RS232
RS485
AUX
System Console "RS232,
RS485, AUX" Connector.
1
Connect to receiver
OR distribution line
control.
System Console
Signals RJ45 Termination
Box: Screw Number
8
N/A
6
5
4
N/A
N/A
1
Command Out +
N/A
ground
Response In –
Command Out –
N/A
N/A
Response In +
Pin 1: Command In +
Pin 2: N/A
Pin 3: ground
Pin 4: Response Out –
Pin 5: Command In –
Pin 6: – 12VAC
Pin 7: + 12VAC
Pin 8: Response Out +
RJ45 Termination Box
Input from Receiver/Dist.
Line Control & power sup.
RJ45 Termination
Box (supplied)
RECEIVER
SYSTEM CONSOLE REAR PANEL
Connect the appropriate power
supply to this connector:
V1400X-PS for 120 VAC
V1400X-PS-230 for 230 VAC.
Connect to
V1400X-DJT or
V1400X-JST.
Figure 2
Standalone Installation
You may connect:
• 255 receivers
• 1 matrix switcher
• 1 joystick device
• 2 auxiliary devices
• 1 RS-232 device
You may have to look closely at
the RJ45 Termination Box to
see the screw numbers (they
are embossed in the plastic).
Pin 1 is shown below, with
numbers increasing clockwise.
1
N/A

XX090 Rev 501 System Console Installation: Standalone System •5
V1400X-DJT
V1400X-JST
System Console
Switcher Card Cage
(without CPU card)
RS-232
RS-422
AUX
Device
1
AUX
Device
2
RS-232
Device
Distribution Line Control
ReceiverReceiver Receiver Receiver Receiver Receiver
V1400X–DJT
ZOOM
TILT
PAN
FOCUS
IRIS
123?
4 5
F1 F2
F3 F4 6 AUX
789PRE
0CLEAR MONITOR
F5 F6
F7 F8
CAMERA
FOCUS
FAR
IRIS
CLOSE ZOOM
OUT
FOCUS
NEAR
IRIS
OPEN ZOOM
IN
OR
Figure 3
Sample Standalone System

6 •Installation: AURORA/VCR ONLY XX090 Rev 501 System Console
Installation: AURORA/VCR ONLY
Warning: Do not apply power to any unit until all connections are properly made.
Make connections as shown in the figure and tables below. Refer to page 53 for cable recommendations.
You may use the supplied RJ45 Termination Box to organize your cable runs. Using the termination box is
not required. The termination box has eight labeled connecting screws. To determine which connection to
make to which screw, refer to the table in Figure 4.
250V SB
2A 10-12VAC
RISK OF FIRE REPLACE
FUSEAS MARKED
CAUTION PWR/COMM JOYSTICK RS232/RS485
AUX
CONTROL OUT
+AC –
Connect to RS-485* or RS-232**
device(s). Connect to auxiliary
devices.
Pin No.
RS-485
RS-232
Signal Name
RS485 + (A)
RS485 – (B)
Ground
1
6
7
Pin No.
Auxiliary Devices
Signal Name
Ground
Aux 1
Aux 2
7
8
9
Pin No. Signal Name
TxD
RxD
RTS
CTS
Ground
2
3
4
5
7
System Console "RS232,
RS485, AUX" Connector.
RS232
RS485
AUX
1
SYSTEM CONSOLE REAR PANEL
* For A99 Protocol: Connect to MIU(s) to use VCRs and/orAurorA99/AurorA
multiplexers.
* For A2000 Protocol: Connect directly to RS-485 devices using Vicon's
AurorANet protocol. Note that the V800MIU-3 uses AurorANet protocol and
must be used to connect to AurorA99/AurorA multiplexers and VCRs.
Note: You must choose A2000 or A99 protocol during programming. You may
not mix both protocols on one System Console.
** Connect to a printer, host computer or other RS-232 device.
Connect the appropriate power
supply to this connector:
V1400X-PS for 120 VAC
V1400X-PS-230 for 230 VAC.
Connect to
V1400X-DJT or
V1400X-JST.
This connector is not
used in AurorA/VCR
Only mode."
Figure 4
AURORA/VCR ONLY Installation
You may connect:
• 1 joystick device
• 2 auxiliary devices
• 1 RS-232 device
• Using A99 protocol:
7 additional V1400X-
DVC/V1400X-DVC-G
System Consoles, 8 MIUs,
each connected to up to 4
AurorA99/AurorA
multiplexers and/or VCRs.
• Using A2000 protocol:
79 additional AurorANet
devices, such as
AurorA2000 multiplexers
(maximum of 32),
V1400X-DVC-3 System
Consoles and A2K-KBD
Remote Keyboards
(maximum of 16). You
may also connect the
V800MIU-3 to use VCRs
and AurorA/AurorA99
multiplexers. Repeaters are
required for more than 32
devices on the AurorANet.

XX090 Rev 501 System Console Installation: AURORA/VCR ONLY •7
▲
▲
▲
▲
AurorA Multiplexer
▲
▲
▲
▲
AurorA2000 Multiplexer
System Console
System Console
VCR
▲
▲
▲
▲
AurorA99 Multiplexer
VCR
V800MIU-3
A2K-KBD
RS-485 AurorANet
AUX
Device
1
AUX
Device
2
RS-232
Device
V1400X-DJT
V1400X–DJT
ZOOM
TILT
PAN
FOCUS
IRIS
1 2 3 ?
4 5
F1 F2
F3 F4 6 AUX
7 8 9 PRE
0CLEAR MONITOR
F5 F6
F7 F8
CAMERA
OR
V1400X-JST
FOCUS
FAR
IRIS
CLOSE ZOOM
OUT
FOCUS
NEAR
IRIS
OPEN ZOOM
IN
▲
▲
▲
▲
AurorA Multiplexer
System Console
System Console
VCR
▲
▲
▲
▲
AurorA99 Multiplexer
VCR
V800MIU-3
A2K-KBD
AUX
Device
1
AUX
Device
2
RS-232
Device
V1400X-DJT
V1400X–DJT
ZOOM
TILT
PAN
FOCUS
IRIS
1 2 3 ?
4 5
F1 F2
F3 F4 6 AUX
7 8 9 PRE
0CLEAR MONITOR
F5 F6
F7 F8
CAMERA
OR
V1400X-JST
FOCUS
FAR
IRIS
CLOSE ZOOM
OUT
FOCUS
NEAR
IRIS
OPEN ZOOM
IN
Figure 5
Sample AURORA/VCR ONLY Systems
V800KBD
Using AurorANet "A2000" Protocol Using "A99" Protocol

8 •Installation: NOVA/AURORA/VCR XX090 Rev 501 System Console
Installation: NOVA/AURORA/VCR
Warning: Do not apply power to any unit until all connections are properly made.
Make connections as shown in the figure and tables below. Refer to page 53 for cable recommendations.
You may use the supplied RJ45 Termination Box to organize your cable runs. It also provides easy wiring
from the control system, as control systems do not include RJ45 connectors. Using the termination box is
not a required installation step. The termination box has eight labeled connecting screws. To determine
which connection to make to which screw, refer to the table in Figure 7.
250V SB
2A 10-12VAC
RISK OF FIRE REPLACE
FUSEAS MARKED
CAUTION PWR/COMM JOYSTICK RS232/RS485
AUX
CONTROL OUT
+AC –
Connect the appropriate power
supply to this connector:
V1400X-PS for 120 VAC
V1400X-PS-230 for 230 VAC.
Connect to
V1400X-DJT or
V1400X-JST.
Connect to NOVA
control system's
RS-422 connector.
Connect to RS-485* or RS-232**
device(s). Connect to auxiliary
devices.
* For A99 Protocol: Connect to MIU(s) to use VCRs and/orAurorA99/AurorAmultiplexers.
* For A2000 Protocol: Connect directly to RS-485 devices using Vicon'sAurorANet
protocol. Note that the V800MIU-3 uses AurorANet protocol and must be used to
connect to AurorA99/AurorA multiplexers and VCRs.
Note: You must choose A2000 or A99 protocol during programming. You may not mix
both protocols on one System Console.
** Connect to a printer, host computer or other RS-232 device.
System Console
Signals RJ45 Termination
Box: Screw Number
8
N/A
6
5
4
3
2
1
Command Out +
N/A
ground
Response In –
Command Out –
– 12VAC
+ 12VAC
Response In +
Pin 1: Command In +
Pin 2: N/A
Pin 3: ground
Pin 4: Response Out –
Pin 5: Command In –
Pin 6: – 12VAC
Pin 7: + 12VAC
Pin 8: Response Out +
RJ45 Termination Box
Input from NOVA Control
System and power supply
Pin No.
RS-485
RS-232
Signal Name
RS485 + (A)
RS485 – (B)
Ground
1
6
7
Pin No.
Auxiliary Devices
Signal Name
Ground
Aux 1
Aux 2
7
8
9
Pin No. Signal Name
TxD
RxD
RTS
CTS
Ground
2
3
4
5
7
System Console "RS232,
RS485, AUX" Connector.
Power supply with cable supplied.
RJ45-RJ45 cable supplied.
RS232
RS485
AUX
1
RJ45 Termination
Box (supplied)
SYSTEM CONSOLE REAR PANEL
Note: To connect a video printer,
connect Aux 1(pin8) to the tip of a
stereo 1/8” jack. Connect GND (pin 7)
to the sleeve of a stereo 1/8” jack.
Insert the 1/8” jack into the “Remote 2”
jack on the back of the video printer.
Figure 6
NOVA/AURORA/VCR Installation
You may connect:
• 1 NOVA control system
(CPU)
• 1 joystick device
• 2 auxiliary devices
• 1 RS-232 device
• Using A99 protocol:
7 additional V1400X-
DVC/V1400X-DVC-G
System Consoles, 8 MIUs,
each connected to up to 4
AurorA99/AurorA
multiplexers and/or VCRs.
• Using A2000 protocol:
79 additional AurorANet
devices, such as
AurorA2000 multiplexers
(maximum of 32),
V1400X-DVC-3 System
Consoles and A2K-KBD
Remote Keyboards
(maximum of 16). You
may also connect the
V800MIU-3 to use VCRs
and AurorA/AurorA99
multiplexers. Repeaters
are required for more than
32 devices on the
AurorANet.
•
You may have to look closely at
the RJ45 Termination Box to see
the screw numbers (they are
embossed in the plastic). Pin 1
is shown below, with numbers
increasing clockwise.
1
N/A N/A N/A

XX090 Rev 501 System Console Installation: NOVA/AURORA/VCR •9
.
▲
▲
▲
▲
AurorA Multiplexer
V1400X-DJT
V1400X-JST
NOVA V1422
RS-422RS-485
System Console
AUX
Device
1
VCR
▲
▲
▲
▲
AurorA99 Multiplexer
VCR
V800MIU-3
AUX
Device
2
RS-232
Device
V1400X–DJT
ZOOM
TILT
PAN
FOCUS
IRIS
123
?
4 5
F1 F2
F3 F4 6
AUX
789
PRE
0
CLEAR MONITOR
F5 F6
F7 F8
CAMERA
FOCUS
FAR
IRIS
CLOSE ZOOM
OUT
FOCUS
NEAR
IRIS
OPEN ZOOM
IN
OR
▲
▲
▲
▲
AurorA Multiplexer
V1400X-DJT
V1400X-JST
NOVA V1422
RS-422
System Console
AUX
Device
1
VCR
▲
▲
▲
▲
AurorA99 Multiplexer
VCR
V800MIU-3
AUX
Device
2
RS-232
Device
V1400X–DJT
ZOOM
TILT
PAN
FOCUS
IRIS
123
?
4 5
F1 F2
F3 F4 6
AUX
789
PRE
0
CLEAR MONITOR
F5 F6
F7 F8
CAMERA
FOCUS
FAR
IRIS
CLOSE ZOOM
OUT
FOCUS
NEAR
IRIS
OPEN ZOOM
IN
OR
▲
▲
▲
▲
AurorA2000 Multiplexer
A2K-KBD
RS-485 AurorANet
Figure 7
Sample NOVA/AURORA/VCR
Using "A99" Protocol
Using "A2000" Protocol

10 •Installation: MSS/NOVA/AURORA/VCR XX090 Rev 501 System Console
Installation: MSS/NOVA/AURORA/VCR
Warning: Do not apply power to any unit until all connections are properly made.
Make connections as shown in the figure and tables below. Refer to page 53 for cable recommendations.
You may use the supplied RJ45 Termination Box to organize your cable runs and provide easy wiring from
the Multi-System Selector. Using the termination box is not a required installation step. The termination
box has eight labeled connecting screws. To determine which connection to make to which screw, refer to
the table in Figure 9.
Connect to
V1400X-MSS J10
“Control In” connector.
250V SB
2A 10-12VAC
RISK OF FIRE REPLACE
FUSEAS MARKED
CAUTION PWR/COMM JOYSTICK RS232/RS485
AUX
CONTROL OUT
+AC –
Connect to
V1400X-MSS J9
connector.
Connect to RS-485* or RS-232**
device(s). Connect to auxiliary
devices.
System Console
Signals RJ45 Termination
Box: Screw Number
8
N/A
6
5
4
N/A
N/A
1
J9 Pin 1: Command Out +
N/A
J9 Pin 2: ground
J9 Pin 3: Response In –
J9 Pin 6: Command Out –
N/A
N/A
J9 Pin 7: Response In +
Pin 1: Command In +
Pin 2: N/A
Pin 3: ground
Pin 4: Response Out –
Pin 5: Command In –
Pin 6: – 12VAC
Pin 7: + 12VAC
Pin 8: Response Out +
RJ45 Termination Box
Input from V1400X-MSS
and power supply
Power supply with cable supplied.
Cable supplied.
RS232
RS485
AUX
1
RJ45 Termination
Box (supplied)
MSS
SYSTEM CONSOLE REAR PANEL
* For A99 Protocol: Connect to MIU(s) to use VCRs and/orAurorA99/AurorA
multiplexers.
* For A2000 Protocol: Connect directly to RS-485 devices using Vicon's
AurorANet protocol. Note that the V800MIU-3 uses AurorANet protocol and
must be used to connect to AurorA99/AurorA multiplexers and VCRs.
Note: You must choose A2000 or A99 protocol during programming. You may
not mix both protocols on one System Console.
** Connect to a printer, host computer or other RS-232 device.
Connect the appropriate power
supply to this connector:
V1400X-PS for 120 VAC
V1400X-PS-230 for 230 VAC.
Connect to
V1400X-DJT or
V1400X-JST.
Pin No.
RS-485
RS-232
Signal Name
RS485 + (A)
RS485 – (B)
Ground
1
6
7
Pin No.
Auxiliary Devices
Signal Name
Ground
Aux 1
Aux 2
7
8
9
Pin No. Signal Name
TxD
RxD
RTS
CTS
Ground
2
3
4
5
7
System Console "RS232,
RS485, AUX" Connector.
Note: To connect a video printer,
connect Aux 1(pin8) to the tip of a
stereo 1/8” jack. Connect GND (pin 7)
to the sleeve of a stereo 1/8” jack.
Insert the 1/8” jack into the “Remote 2”
jack on the back of the video printer.
Figure 8
MSS/NOVA/AURORA/VCR Installation
You may have to look closely at
the RJ45 Termination Box to see
the screw numbers (they are
embossed in the plastic). Pin 1 is
shown below, with numbers
increasing clockwise.
1
You may connect:
• 1 V1400X-MSS Multi-
System Selector, which
may be connected to up to 8
NOVA control systems or 1
V1400X-MSSV, which may
be connected to up to 32
NOVA control systems
• 1 joystick device
• 2 auxiliary devices
• 1 RS-232 device
• Using A99 protocol:
7 additional V1400X-
DVC/V1400X-DVC-G
System Consoles, 8 MIUs,
each connected to up to 4
AurorA99/AurorA
multiplexers and/or VCRs.
• Using A2000 protocol:
79 additional AurorANet
devices, such as
AurorA2000 multiplexers
(maximum of 32),
V1400X-DVC-3 System
Consoles and A2K-KBD
Remote Keyboards
(maximum of 16). You
may also connect the
V800MIU-3 to use VCRs
and AurorA/AurorA99
multiplexers. Repeaters are
required for more than 32
devices on the AurorANet.
N/A
1

XX090 Rev 501 System Console The V1400X-IFS Fail-Safe Device •11
▲
▲
▲
▲
AurorA Multiplexer
V1400X-DJT
V1400X-JST
RS-422
System Console
AUX
Device
1
VCR
▲
▲
▲
▲
AurorA99 Multiplexer
VCR
V800MIU-3
AUX
Device
2
RS-232
Device
▲
▲
▲
▲
AurorA2000 Multiplexer
A2K-KBD
RS-485 AurorANet
V1400X–DJT
ZOOM
TILT
PAN
FOCUS
IRIS
1 2 3
?
4 5
F1 F2
F3 F4 6 AUX
7 8 9 PRE
0CLEAR MONITOR
F5 F6
F7 F8
CAMERA
FOCUS
FAR
IRIS
CLOSE ZOOM
OUT
FOCUS
NEAR
IRIS
OPEN ZOOM
IN
OR
POWER
V1400X-MSS Multi-System Selector
Connects to a Maximum of 8 NOVA Control Systems (CPUs)
▲
▲
▲
▲
AurorA Multiplexer
V1400X-DJT
V1400X-JST
RS-422RS-485
System Console
AUX
Device
1
VCR
▲
▲
▲
▲
AurorA99 Multiplexer
VCR
V800MIU-3
AUX
Device
2
RS-232
Device
V1400X–DJT
ZOOM
TILT
PAN
FOCUS
IRIS
1 2 3
?
4 5
F1 F2
F3 F4 6
AUX
7 8 9
PRE
0
CLEAR MONITOR
F5 F6
F7 F8
CAMERA
FOCUS
FAR
IRIS
CLOSE ZOOM
OUT
FOCUS
NEAR
IRIS
OPEN ZOOM
IN
OR
POWER
V1400X-MSS Multi-System Selector
Connects to a Maximum of 8 NOVA Control Systems (CPUs)
V800KBD
Figure 9
Sample MSS/NOVA/AURORA/VCR
Installation
Using "A99" Protocol
Using "A2000" Protocol

12 •The V1400X-IFS Fail-Safe Device XX090 Rev 501 System Console
The V1400X-IFS Fail-Safe Device
Note: This section is not applicable for the AurorA/VCR Only mode (just connect any keypads to the
RS-485 network). This section is not applicable to standalone systems (you may only have one
keypad in a standalone system).
To daisy-chain system consoles, you will need one V1400X-IFS Fail-Safe Device for every two consoles.
These devices provide a continuous chain of communication in case one system console loses power or
communications. The V1400X-IFS is sold separately and includes two 8 ft (2.4 m) RJ-45 terminated
cables in its accessory kit.
Note: Use pins 7 (+12 VAC) and 9 (-12 VAC) on the 9-pin terminal block located on each fail-safe device
(pin 3 is ground) for power.
Figure 10 shows a block diagram for a daisy-chained system with two system consoles and Figure 11
illustrates the connections for this configuration.
DAISY-CHAIN CONFIGURATION
Two Keypads
System Console
1 2 3
?
4 5
F1 F2
F3 F4 6
AUX
7 8 9
PRE
0
CLEAR MONITOR
F5 F6
F7 F8
CAMERA
System Console
123
?
4 5
F1 F2
F3 F4 6
AUX
789
PRE
0
CLEAR MONITOR
F5 F6
F7 F8
CAMERA
V1400X-IFS
Figure 10
Block Diagram of Two System Consoles in a Daisy-Chain Configuration
250V SB
2A 10-12VAC
RISK OF FIRE REPLACE
FUSEAS MARKED
CAUTION
PWR/COMM JOYSTICK RS232/RS485
AUX
AUX
CONTROL OUT
+AC –
COMM IN
COMM IN 12 VAC
RESP OUT
GND
123456789
RESP OUT
12 VAC
–
++
+
–
–
LOOP OUTLOOP IN MAIN KEYPAD
250V SB
2A 10-12VAC
RISK OF FIRE REPLACE
FUSEAS MARKED
CAUTION
PWR/COMM JOYSTICK RS232/RS485CONTROL OUT
+AC –
Control System's
RS422 Keypad Connector
(See appropriate Instruction Manual.)
System Console
System Console
Fail-Safe Device (front) Fail-Safe Device (back)
Figure 11
Connections with Two System Consoles
------- Cable provided in V1400X-IFS Accessory Kit.

XX090 Rev 501 System Console The V1400X-IFS Fail-Safe Device •13
Daisy-chained connections for systems with more than two consoles require one less number of fail-safe
devices than there are system consoles in your installation. A block diagram is shown in Figure 12.
System Console System Console System Console System Console System Console System Console
Distribution Line Control
STAR CONFIGURATION
More Than Two Keypads
1 2 3
?
4 5
F1 F2
F3 F4 6
AUX
7 8 9
PRE
0
CLEAR MONITOR
F5 F6
F7 F8
CAMERA
123
?
4 5
F1 F2
F3 F4 6
AUX
789
PRE
0
CLEAR MONITOR
F5 F6
F7 F8
CAMERA
1 2 3
?
4 5
F1 F2
F3 F4 6
AUX
7 8 9
PRE
0
CLEAR MONITOR
F5 F6
F7 F8
CAMERA
123
?
4 5
F1 F2
F3 F4 6
AUX
789
PRE
0
CLEAR MONITOR
F5 F6
F7 F8
CAMERA
123
?
4 5
F1 F2
F3 F4 6
AUX
789
PRE
0
CLEAR MONITOR
F5 F6
F7 F8
CAMERA
System Console
System Console
System Console
123
?
4 5
F1 F2
F3 F4 6
AUX
789
PRE
0
CLEAR MONITOR
F5 F6
F7 F8
CAMERA
V1400X-IFS
123
?
4 5
F1 F2
F3 F4 6
AUX
789
PRE
0
CLEAR MONITOR
F5 F6
F7 F8
CAMERA
123
?
4 5
F1 F2
F3 F4 6
AUX
789
PRE
0
CLEAR MONITOR
F5 F6
F7 F8
CAMERA
V1400X-IFS
Figure 12
Block Diagram of More Than Two System Consoles in a Daisy-Chain Configuration
Connect the system consoles as shown in the following figure if you have more than two system consoles
in a daisy-chain configuration.
250V SB
2A 10-12VAC
RISK OF FIRE REPLACE
FUSEAS MARKED
CAUTION
PWR/COMM JOYSTICK
Control System's
RS422 Keypad Connector
(See appropriate Instruction Manual.)
RS232/RS485
AUX
RS232/RS485
AUX
RS232/RS485
AUX
CONTROL OUT
+AC –
COMM IN
COMM IN 12 VAC
RESP OUT
GND
123456789
RESP OUT
12 VAC
–
++
+
–
–
LOOP OUTLOOP IN MAIN KEYPAD
250V SB
2A 10-12VAC
RISK OF FIRE REPLACE
FUSEAS MARKED
CAUTION
PWR/COMM JOYSTICK CONTROL OUT
+AC –
250V SB
2A 10-12VAC
RISK OF FIRE REPLACE
FUSEAS MARKED
CAUTION
PWR/COMM JOYSTICK CONTROL OUT
+AC –
COMM IN
COMM IN 12 VAC
RESP OUT
GND
123456789
RESP OUT
12 VAC
–
++
+
–
–
LOOP OUTLOOP IN MAIN KEYPAD
Cable provided in V1400X-IFS Accessory Kit.
System Console
System Console
System Console
Fail-Safe Device (front)
Fail-Safe Device (front)
Fail-Safe Device (back)
Fail-Safe Device (back)
Figure 13
Connections with More Than Two System Consoles
Other manuals for V1400X-DVC-3
1
Table of contents
Popular Music Mixer manuals by other brands

Chilton
Chilton QM 3 Series operating instructions

SoundCraft
SoundCraft Spirit Live 4 user guide

AUSTRALIAN MONITOR
AUSTRALIAN MONITOR AMIS ZRM4 Service information

Sony
Sony SRP-X100 Features & specifications

Mackie
Mackie PPM1008 Bedienungshandbuch

Sound Devices
Sound Devices 633 User guide and technical information