VOLTIMA VSP Series User manual

User Manual
VOLTIMA
PURE SINE
POWER INVERTER
VSP Series
Pure Sine Wave Inverter

1. Introduction
2. Important Safety Instructions
3. Protection Features
4. Location
5. Inverter Materials List and Indication
6. The Inverter’s Output Waveform
7. Choose the Battery
8. Connections and Installation
9. Operating the AC Appliances
10. Trouble Shooting
11. Maintaining the Inverter
12. Dispose Instruction
13. Warranty
Thanks for your purchasing our VSP series power inverter.
Our power inverters are compact and high efficient inverters, and it is the leader in the field of high
frequency inverters.
Our power inverter converts low voltage, direct current (12V DC) in pure sine wave alternating current
(230V AC).
By connecting the power inverter directly to the 12V battery, you can turn your vehicle into a mobile
office, or have power to run entertainment electronics.
Read this guide before install and use the power inverter, and please reserve it for future reference.
Important: Read and save this owner’s guide for future reference.
This chapter contains important safety and installation instructions for our VSP series power inverters.
Each time, before using the power inverter, read all instructions and cautionary marking on or provided
with inverter and all appropriate sections of this guide.
WARNING!
ELECTIRCAL SHOCK HAZARD
▪Do not expose the inverter to rain, snow, spray, or bilge water. This inverter is designed for
indoor use only.
▪Do not operate the inverter if it has received a sharp blow, been dropped, has cracks.
▪Do not disassemble the inverter. Internal capacitors remain charged after all power is
disconnected.
▪Disconnect both AC and DC power from the inverter before attempting any maintenance or
cleaning or working on any circuits connected to the inverter. See note below.
▪Do not operate the inverter with damaged or substandard wiring.
▪Make sure that all wiring is in good condition and is not undersized.
Failure to follow these instructions will result in death or serious injury.
Notes:Turning off the inverter using the ON/OFF switch on the front panel will not reduce an electrical
shock hazard.
1.
Introduction
2.
Important Safety Intructions

WARNING!
FIRE AND BURN HAZARD
▪Do not cover or obstruct the air intake vent openings and / or install in a zero-clearance
compartment.
▪Do not use transformer less battery chargers in conjunction with the inverter due to
overheating.
Failure to follow these instructions will result in death or serious injury.
WARNING!
EXPLOSION HAZARD
▪Charge only properly rated (Such as 12V) lead-acid (GEL, AGM, Flooded, or lead-calcium)
rechargeable batteries because other battery types may explode and burst.
▪Do not work in the vicinity of lead-acid batteries. Batteries generate explosive gases during
normal operation.
▪Do not installand / or operate in compartments containing flammable materials or in locations
that require ignition-protected equipment.
Failure to follow these instructions will result in death or serious injury.
Notes:
1. Follow these instructions and those published by the battery manufacturer and the
manufacturer of any equipment you intend to use in the vicinity of the battery. Review
cautionary markings on these products and on the engine.
2. The inverter contains components which tend to produce arcs or sparks.
3. Locations include any space containing gasoline-powered machinery, fuel tanks, as well as
joints, fittings, or other connections between components of the fuel system.
RISK OF DAMAGE TO THE INVERTER
▪Never allow battery acid to drip on the inverter when reading gravity, or filling battery.
▪Never place the inverter unit directly above batteries, gases from a battery will corrode and
damage the inverter.
▪Do not place a battery on top of the inverter.
▪The inverter will not operate high Wattage appliances over the output power limit or surge
power limit.
▪This is not a top –keep away from children.
Failure to follow these instructions can damage the unit and/or damage other equipment.
Our power inverters are equipped with numerous protection features to guarantee safe and trouble-free
operation:
Low Battery Alarm
Alerts you if the battery has become discharged to 10.5V
or lower.
Low Battery Voltage Shutdown
Shuts the inverter down automatically if the battery
voltage drops below 9.5 volts. This feature protects the
battery from being completely discharged.
High Battery Voltage Shutdown
Shuts the inverter down automatically if the input
voltage rises to 15.5 volts or more.
Over Load Shutdown
Shuts the inverter down automatically if the loads
connected to the inverter exceed the inverter’s
operating limits
Over Thermal Shutdown
Shuts the inverter down automatically if its internal
temperature rises above an unacceptable level.
Output Short Circuit Shutdown
Shuts the inverter down automatically if a short circuit is
detected in the circuitry connected to the inverter’s
output
Reverse Polarity Protection
If wrong polarity connection, the internal fuse shall blow
out.
Earth Fault Protection
The inverter complies with the standard current leakage
allowance. When large current leakage to earth terminal
occurs, the protection circuit activated and shut down
the inverter, which prevent electric shock to human.
Turn off the inverter, unplug the fault AC appliances and
then turn ON is the way to restart it.
Notes: All protection is automatically recovered. To protect the battery, if the unit needs to be restarted
after lower voltage protection, the voltage of DC input factory setting: pure sine wave inverter is 12.6 V
3.
Protection Features

The power inverter must only be installed in a location that is:
Dry:
The inverter must be installed in a dry location not subject to moisture especially rain, spray, or splashing
bilge water.
Cool:
The inverter should not be exposed to metal fillings or any other form of contamination.
Ventilated:
The ambient air temperature should be between 0 - 40°C for best performance
Safe:
Ventilation openings on the inverter must not be obstructed. If the inverter is mounted in a tight fitting
compartment, the compartment must be ventilated with cut-outs to prevent the inverter from
overheating.
Close to battery:
The inverter is not ignition-protected equipment, so it cannot be installed in areas containing gasoline
tanks or fittings which require ignition –protected equipment. We recommend that it is safest not to
install any kind of electrical equipment including the inverter in these areas.
Protected from battery gases:
The inverter should be installed as close as possible to the batteries, but not in the same compartment to
prevent corrosion. Avoid excessive cable lengths and use the recommended wire sizes. We recommend
that installing with battery cables sized to achieve less that 3% voltage drop on battery cables under full
load. This will maximize the performance of the inverter.
Materials List
There are power inverter unit, user manual, DC cables and spare fuse inside of packing.
Figure 1 (6.1, 6.2, 6.3)
6.1 Pure sine wave inverter 300W - 600W
6.2 Pure sine wave inverter 1000W
6.3 Pure sine wave inverter 1500W - 3000W
4.
Location
5.
Inverter Materials List and Indication

Indication:
1. AC outlets are used to power loads.
2. ON/OFF Switch turns the inverter on and off.
3. Fault light (red) indicates that the inverter has shut down due to inverter overload, over temperature,
short circuit, leakage or fault happen.
4. Power light (green) indicates the inverter is operating.
5. USB Port it output DC 5V 500mA or 2.1A connect the USB external appliance to USB port and switch it
on. The USB output on the power inverter provides a supply of 5V DC power for USB external appliances
(e.g. lights, fans, radios).
The USB output is permanently on when the power inverter is connected to a 12V battery input voltage.
Warning:
The USB port on the power is not designed for transferring data.
•Do not Connect memory sticks, MP3 players or similar data storage external appliances.
•Do not connect any data transfer cables to the USB port!
6. Negative DC input terminal (-) always connects to the negative terminal of the battery via a negative
DC input cable (black battery cable). The negative DC input terminal is colored black.
7. Positive DC input terminal (+) always connects to the positive terminal of the battery via a positive DC
input cable (red battery cable). The positive DC input terminal is colored red.
Warning:
Do not reverse polarity connection, the wrong connection will result in a blown fuse and may cause
permanent damage to the inverter
8. Chassis ground screw grounding the earth by use wire.
9. High –Speed Cooling fan must not be obstructed for the proper operation of the inverter. When the
inverter is mounted, then ventilation opening on the DC panel must not point up or down.
10. DC cable with ring, please you can connect the ring in red cable to red terminal on inverter and the
ring in another side to battery. Do same way in black cable.
11. DC cable with clip, you can use it connect the battery and inverter by connecting the clips in cable to
battery, and the ring in another side to inverter.
Warning: Symptoms of low battery power can result from cables that are either excessively long or an
insufficient gauge. Substantial power loss and reduced battery operating time results from inverters
installed with cables that are not able to supply full power.
Notes: The installer/operator should be especially aware of the requirements to maintain secure, tight,
water-resistant electrical connections and to provide for strain relief for DC cables and appliances wiring.
Cable insulation must be the appropriate type for the environment.
The AC output waveform of the VSP series inverter output waveform is “pure sine wave”.
Figure 2
Modified sine wave and pure sine wave comparison
6.
The inverter’s Output Waveform

INTERFERENCE WITH SOME EQUIPMENT
Buzz in Audio Equipment
Some inexpensive stereo systems may emit a buzzing noise from their loudspeakers when operated from
the inverter. This occurs because the power supply in the audio System does not adequately filter the
modified sine wave produced by the inverter.
The only solution is to use a sound system that has a high quality power supply.
Television Reception
When the inverter is operating, it can interfere with television reception on some channels. If interference
occurs, try the following:
1. Make sure that the chassis ground screw on the rear of the inverter is solidly connected to the ground
system of your vehicle or home.
2. Make sure that the television antenna provides an adequate (“snow-free”) signal and that you are using
good quality cable between the antenna and the television.
3. Keep the cables between the battery and the inverter as short as possible, and twist them together
with two to three twists per foot. (this minimizes radiated interference from the cables.)
4. Move the television as far away from the inverter as possible.
5. Do not operate high power loads with the inverter which the television is on.
Battery Requirements
Battery type and battery size strongly affect the performance of the power inverter. Therefore, you need
to identify the type of loads your inverter will be powering and how much you will beusing them between
charges. To determine the minimum battery size that you need to operate appliances, follow these steps:
1. Determine the wattage of each appliance and/or tool you will need to simultaneously operate from the
inverter. To do this, read the labels on the requirement to be operated. Usually, power consumption is
shown in watts. If it is shown in amps, multiply by 230V to determine the wattage.
2. Estimate the number of hours the equipment will be in use between battery recharges.
3. Determine the total watt-hours of energy use, the total running time and the average power
consumption power (in watts) by 10 if 12V system, by 20. If 24V system, by 40 if 48V system.
To calculate the approximate power in amps a 24 volt battery bank has to supply you need to know the
current, or amps required for powering the continuous AC load. A shortcut method is to divide the
continuous AC load. A shortcut method is to divide the continuous AC load wattage by 20.
For example, the continuous AC load is 2000 watts, the current (amps) is: 2000/20 or 100amps at 24V DC.
Add to the load any DC appliances that may be powered by the battery bank.
Notes: Some appliances required high surge power to start, then consumer less power. And some
appliances are not operating for long periods of time. For example, a typical home-use coffee maker
draws 500watts during its brew time of 5 minutes, but it maintains the temperature of the pot at about
100watts. Typical use of a microwave is only a few minutes, sometimes at lower power; some exceptions
to brief operating times are lamps, TVs and computers.
Important: The power inverter must be connected only to batteries with a normal output voltage of 12V
when you use a 12V inverter. The unit will not operate from a 6V battery, and will sustain permanent
damage if connected to a 24V battery.
Caution: Loosen connectors may cause overheated wires and melted insulation. Check to make sure you
have not reversed the polarity. Reverse polarity connection will result in a blown fuse and may cause
permanent damage to the inverter.
The calculation of the Battery’s Back Up Time
The battery’s back up depends on the battery capacity (Ah) and your appliances power (Watt)
The method to calculate the backup time:
Battery capacity (Ah) * Input voltage (Volt)/Loads power (Watt)
For example:
Battery capacity = 150Ah
Input voltage = 12Volt
Loading power = 600Watt
So:
(150Ah*12V)/600Watt = 3 Hours
Note: the time calculated by this way is a theory value; the actual using time may short than this value
Recharging Batteries
When possible, recharge your batteries when they about 50% discharged or earlier. This gives the
batteries a much longer life cycle than recharging when they are more deeply discharged.
Our inverter has a battery low voltage shutdown around 10V DC. With moderate to heavy loads, this will
protect against over-discharging the battery. If the inverter is running only light loads it is advisable to
recharge before the inverter low voltage shutdown point is reached.
7.
Choose the Battery

Batteries Wiring
1. SERIES WIRING
Wiring batteries in a series increases the total battery bank output voltage. A series connection combines
each battery in a string until the voltage matches the inverter’s DC requirement. Even though there are
multiple batteries, the capacity remains the same. In the example below (Figure 4), two 6V DC/200Ah
batteries are combined into a single string-resulting in a 12V DC / 200Ah bank.
12V battery bank (total capacity = 200 Ah)
Figure 4, Series Battery Wiring
2. PARALLEL WIRING
Wiring the batteries in parallel increases the total run time the batteries can operate the AC loads. A
parallel connection combines overall battery capacity by the number of batteries in the string. Even
though there are multiple batteries, the voltage remains the same. In the example below (Figure 5), four
12V DC/100Ah batteries are combined into a single 12V DC/400AH battery bank.
12V battery bank (total capacity = 400 Ah)
Figure 5, Parallel Battery Wiring
2. SERIES –PARALLEL WIRING
A Series-parallel configuration increases both voltage (to match the inverter’s DC requirements) and
capacity (to increase run time for operating the loads) using smaller, lower voltage batteries. In the
example below (Figure 6), four 6V DC/200Ah batteries are combined into two strings resulting in a 12V
DC/400Ah battery bank.
12V battery bank (total capacity = 400 Ah)
Figure 6, Series-Parallel Battery Wiring
Best use of battery Power
Make sure any appliances are energy efficient and turned off after use. Use Compact Florescent Lamps.
Wherever possible, charge with solar panels or wind generators. Do not allow lead acid batteries to
remain discharged for long periods of time, they lose capacity (amps hours).
Mounting the Inverter
Warning: Keeping ventilation when using batteries. Batteries may generate flammable gas during
charging or discharging.
The inverter (1000W to 3000W models) has four slots in its mounting bracket that allow the unit to be
fastened against a bulkhead, floor, wall or other flat surface. Ideally, the mounting surface should be cool
to the touch.
It is more electrically efficient to use longer AC wiring than DC wiring, so install the inverter as close as
possible to the 12/24/48V DC power source (Battery).
8.
Mounting and Connecting the Inverter

The inverter can be operated in any position, however, if it is to be mounted on a wall, mount it
horizontally (Figure 7) so that indicators, switches, outlets and terminal blocks located on the front panel
are visible and accessible. If inverter is to be installed in a moving vehicle, we strongly recommend that
the inverter be shock-mounted either on the floor (in a clear, safe area) or on a secure flat surface.
Figure 7
System Connection
When you connect the battery with inverter, please remember to connect the correct volts (e.g. 12V
inverter connect with 12V batteries.
The inverter will provide you 230V AC when powered by a 12V DC source. This manual does not describe
all of the possible types of battery configurations, battery charging configurations and battery isolation
configurations. The figure 8 as below show the typical connection.
Figure 8
Note: For safety concern, you can connect a DC-rated fuse or a DC-rated circuit breakers on the positive
cable line in your power system, following these recommendations when you purchasing fuses or circuit
breakers.
Select a fuse or circuit breaker with a proper rating (e.g.: 1000W advice 150A DC, 1500W advice 200A DC)
Determine the short-circuit current rating of the battery and choose a battery fuses that withstand the
short circuit current that may be generated by the battery.
Connection and Installation Steps
1. Check to be sure the inverter’s power switch is turned off and that no flammable fumes are present.
2. Identify the positive (+) and negative (-) battery terminals.
3. Install a fuse holder or breaker close to the positive (+) terminal of the battery.
4. Connect a length of wire on one side of the fuse holder or circuit breaker. Connect the other end of the
wire to the positive (+) terminal of the inverter.
5. Connect a length of wire between the inverter’s negative (-) terminal and the battery’s negative (-)
terminal.
6. Connect a short length of wire to the other terminal of the fuse holder or circuit breaker. Mark it
“positive” or “+”.
7. Connect the free end of the fuse or breaker wire to the positive terminal of the battery.
8. Insert a suitable fuse in the fuse holder.
9. Check to be sure that all connections between battery clips, terminals and fuses are secure and tight.
Notes: Sparking is normal for the first connection.
Make sure you have good secure connections - Do not over tighten.
1. When you have confirmed that the AC appliances to be operated is turned off, plug an appliance cord
into the AC outlet on the front panel of the inverter.
2. Turn ON the inverter.
3. Turn the appliance on.
4. Plug in additional appliances and turn them on.
Notes:
1. Plug the cord from the AC appliances you wish to operate into the AC receptacle. When turn ON the
inverter. The Red and Green LED both lit for 3 - 5seconds then red LED not lit, green LED indicator lights
to indicate that the inverter is functioning. Make sure the combined load requirement of your equipment
does not exceed inverter’s output rating.
2. Turn OFF the inverter. The over load LED may briefly “blink” and the audible alarm may also sound a
short “Chirp”. This is normal. This same alarm may also sound when the inverter being connected to or
disconnect from the battery.
9.
Operating the AC Appliances

3. When using an extension cord from the inverter to an appliance the extension cord should not be
longer than 15 meters.
4. When you plan to operate more appliances, please make sure plug and switch ON the biggest one first
and then smaller one.
Caution: The inverter is engineered to be connected directly to standard electrical and electronic
equipments. Do not connect the powerinverter to household or RV AC distribution wiring. Do not connect
the power inverter to any AC load circuit in which the neutral conductor is connected to ground (earth)
or to the negative of the battery source.
Warning: Do not connect to AC distribution wiring.
Operating Tips
Rated versus actual current draw of equipment
Most electrical tools, appliances and audio/video equipment have labels that indicate the power
consumption in amps or watts.
Be sure that the power consumption of the item you wish to operate is less than inverter’s rating power.
(if the power consumption is rated in amps, simply multiply by the AC volts (230V) to determine the
wattage). The inverter will shutdown if it is overloaded. The overload must be removed before the
inverter will restart.
Resistive loads are the easiest for the inverter to run. However, larger resistive loads, such as electric
stoves or heaters, usually require more wattage than the inverter can deliver. Inductive loads. Such as
TV’s and stereos, require more current to operate than do resistive loads of the same wattage rating.
Induction motors, as well as some televisions, may require 2 to 6 times their wattage rating to start up.
The most demanding in this category are those that start under load, such as compressors and pumps. To
restart the unit after a shutdown due to overloading, remove the overload if necessary turn the power
switch OFF then ON.
No AC output; red LED lit, green LED not lit:
Possible Cause
Suggested Solution
DC input below 10volts(battery low voltage)
Recharge or replace battery.
Inverter overheat -> thermal shutdown
Remove or reduce load, wait for inverter to cool.
No AC output; red & green LED not lit:
Possible Cause
Suggested Solution
Inverter fuses
Contact technical support.
Non-continuous AC output; red LED lit on or off, green LED lit:
Possible Cause
Suggested Solution
Inverter output power limited by overload/short circuit
protection circuit
Reduce load or remove short circuit
Reduce load or remove short circuit:
Possible Cause
Suggested Solution
The voltmeter you used not a true RMS meter
Change to use a true “RMS” voltmeter when you measure the AC
voltage output from modified sine wave inverter.
No AC output (latch up); red & green LED lit:
Possible Cause
Suggested Solution
Earth fault protection is activated by excessive current leakage
from the load
Unplug the faulted load.
The battery Backup time shorter than expect:
Possible Cause
Suggested Solution
The inverter you choose too small
Recharge or replace battery
Battery poor quality or damaged
Remove or reduce load, wait for inverter to cool.
Battery empty or lower voltage
Recharge for the battery, or use good quality charge to charge the
battery
No AC output; red LED lit, green LED not lit:
Possible Cause
Suggested Solution
The current dissipation too much in DC cables
Use heavy cables and shorten the cables
Low battery alarm sounds abnormal:
Possible Cause
Suggested Solution
Bad connection or wiring
Tighten all DC connections
Low battery alarm sounds:
Possible Cause
Suggested Solution
Low battery voltage
Recharge or replace battery
If appliances does not start, then appliance is drawing excessive
wattage and will not work with inverter.
Appliance too close to inverter
Keep inverter and antenna distant from each other. Use shielded
antenna cable. Connect antenna with amplifier.
10.
Trouble Shooting

Specifications for VSP Series Inverter:
Model
VSP300
VSP600
VSP1000
VSP1500
VSP2000
VSP3000
VSP4000
Output
Rated Power (Watts)
300W
600W
1000W
1500W
2000W
3000W
4000W
Surge Power(few seconds)
600W
1200W
2000W
3000W
4000W
6000W
8000W
Voltage (AC)
220-240V AC (230V)
AC Voltage Regulation
±10%
Frequency (Hz)
50 Hz ±3
Waveform
Pure Sine Wave
USB port
5V 500mA or 2.1A
Efficiency
>= 90%
Input
Voltage (DC)
12V DC
Voltage Range (DC)
10 - 15.5V DC
Protection Function
Low Voltage Shutdown
12V
10.5±0.5V
24V
21±1V
48V
42V±2V
Low Voltage Alarm
11.5±0.5V
23±1V
46V±2V
Over Voltage Shutdown
15.5±0.5V
31±1V
62V±2V
Short Circuit Protection
Shutdown and cutout the output
Over Temperature Shutdown
Shutdown and cutout the output
Polarity Reverse Protection
By internal fuse open
Over Load Protection
Shutdown and cutout the output
Earth Leakage Protection
Shutdown and cutout the output
Operating Temperature Range
-20 +45°C
Soft Start
Yes, 3 - 5’S
Others
Cooling Fan
Factory default is by 10% - 20% AC load, temperature control is optional
Unit Dimensions (L*W*H)
21.5*15
*5.8cm
26*15*7.8c
m
29.3*15*9.8
cm
37.2*23*10.8cm
48.8*23*10.8c
m
53.8*23*10.8cm
Unit Weight (kg)
2
2.2
3.1
5.8
6
9
10.6

Minimal maintenance is required to keep your inverter operating properly, periodically you should:
‣Clean the exterior of the unit with a damp cloth to prevent the accumulation of dust and dirt.
‣Ensure that DC cables are secure and fasteners are tight.
‣Make sure the ventilation openings on the DC panel and bottom of the inverter are not clogged.
Home electronic equipment: If you no longer wish to use this appliance, please take it to the applicable
collection point or deliver it to a public recycling location for old electronic equipment. Electronic
equipment shall under no circumstances be disposed of in the same manner as normal household waste
(See the crossed-out garbage can symbol above).
Further disposal instructions: Hand over the appliance in a condition that will allow for safe recycling and
disposal. Remove all batteries from the appliance in advance and prevent any liquid containers from being
damaged. Electronic equipment may contain harmful substances. Improper use or malfunction caused by
damage may adversely affect human health and harm the environment during recycling.
This couplet and the purchasing invoice are both considered as the protection for fix warrantees, so please
reserve them carefully.
Feedback couplet
Product model number: ………………………… Product name: …………………………………………………….
Factory serial number: ………………………….. Purchase store: …………………………………………………..
Purchase date: ……………………………………… Invoice number: ………………………………………………….
Customer address: ……………………………………………………………………………………………………………………
Post codes: ………………………………………….. E-mail: ………………………………………………………………..
Protection to fix elucidation
According to the prescription, the period for protecting to fix our company’s inverter is two years, (from
the date when you have the invoice).
During this period, any belongs to under normal usage circumstance cause because of the product
quality’s problem of breakdown, our company will be responsible for give free maintain. In product fix
the period, if there is any breakdown which caused by the product’s own quality, customers can bring the
purchasing invoice and the customer couplet that has filled and get the free repair from the repair center
that has authorized by our company.
1. Those inverters that has refitted or added other functions by your own will not be accepted to repair.
2. Once the protection to fix card or purchasing invoice has been changed, the protection to fix
immediately expired.
3. This card and the purchasing invoice are both considered as the protection to fix warrantees, so please
reverse them carefully. Lose don’t repair.
Free maintain won’t be given under the following
circumstance:
1. Without protection to fix warrantees.
2. The breakdown caused by the manipulation that hasn’t follow the requests of the manual.
3. The breakdown caused by the dismantle movement of a non-our-company authorized maintainer.
4. The breakdown, row harm or damaged because of the move or drop.
5. The damage caused by customer inappropriate preservation maintain, or the usage.
6. Easy damaged pieces and present accessories are not concerned.
7. The breakdown and the damage caused by the force majeure.
11.
Maintaining the Inverter
12.
Disposal Instructions
13.
Warranty
This manual suits for next models
7
Table of contents
Other VOLTIMA Inverter manuals