Westric IW Series User manual


76-5276-05 Page 2 of 82

76-5276-05 Page 3 of 82
Table of Contents
Description
Page
Unit Model Identification
5
Safety Information
7-8
General features
9
Control Panel
10
Different air flow configurations
11
IW – 005/006 Dimensions
12 - 15
Technical data sheet
16 - 18
Temperature and Humidity working range
18
Internal/External Components
19 - 24
Checking of unit upon receipt
25-26
Installation and Assembly
27-28-29
Electrical Wiring
30
Phase monitoring relay
31
Maximum distances and diameters of copper tubing
32 - 34
Maintenance
35
EC Fans Troubleshooting
36
System Operation
37-39
Danfoss Controller
40
Operation Panel - Display and keys
41-42
PLC Screens
43-52
Operation Panel - Display and keys configuration
52
TCP / IP Link (Web Server) (Optional)
53-65
Controller Troubleshooting
65
Carel Humidifier Maintenance (Optional)
66-68
Humidifier Technical data
69
Humidifier Troubleshooting
70 - 72
Drain Pump (Optional); Humidity Sensor
73
Troubleshooting Guide
74
Electrical Diagrams
75-81

76-5276-05 Page 4 of 82

76-5276-05 Page 5 of 82
Unit Model Identification
X
X
-
X
X
X
X
X
X
X
X
X
X
Special features
S= Standard
V= Standard with drain pump
H= Standard with humidifier
J= Standard with drain pump and humidifier
R= Standard with Electrical Heater
B= Standard with Electrical Heater and drain pump
M= Standard with humidifier and electrical heater
K= Standard with humidifier,electrical heater and drain pump
Refrigerant
P= R-410A
A= Chilled Water
Power Supply
A= 220V – 50Hz – 1ph
B= 380V – 50Hz – 3ph
D= 220V – 60Hz – 1ph
G= 380V – 60Hz – 3ph
Stages
Air Direction
For Indoor Units
For Outdoor Units
5 RT
F= Front and Back Return
L= Side and Back Return
D= Right Side an Back Return
I= Left Side an Back Return
H= Horizontal
6 to 15 RT
A= Upflow
Controller
For Indoor Units
For Outdoor Units
C= Controller
C= Controller
DX Units Only (IW Series)
Indoor Unit
Outdoor Unit
C= Scroll compressor inside
M= Variable Capacity compressor
inside.
I= Without Compressor
R= Without Compressor
E= With Scroll Compressor
V= With Variable Capacity compressor
CW Units Only (ID Series)
A = Fan Coil
Nominal Capacity : Ref Tons
InterRack type Precision Air Conditioners
IW = DX Units (Indoor/Outdoor).
ID = CW Units.
VALID ONLY FOR IW or ID.

76-5276-05 Page 6 of 82

76-5276-05 Page 7 of 82
Safety Information
Read the instructions carefully to become familiar with the equipment before trying to install, operate, service, or maintain
it. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or
to call attention to information that clarifies or simplifies a procedure..
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious
injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or
moderate injury.
NOTICE
NOTICE addresses practices not related to physical injury including certain environmental hazards,
potential damage or loss of data.

76-5276-05 Page 8 of 82
Safety Notices for While Installing This Equipment
Read and adhere to the following important safety considerations when working with this equipment. Follow all local and
national regulations when handling refrigerants.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E or CSA Z462.
• This equipment must be installed and serviced by qualified personnel only.
• Turn off all power supplying this equipment before working on or inside the equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors, and covers before turning on power to this equipment.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD FROM MOVING PARTS
Keep hands, clothing, and jewelry away from moving parts. Check the equipment for foreign objects
before closing the doors and starting the equipment.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF EQUIPMENT FALLING OVER
• Use two or more persons at all times to move or turn this equipment.
• Always push, pull, or turn while facing the front and rear of this equipment. Never push pull, or turn while
facing the sides of this equipment.
• Slowly move this equipment across uneven surfaces or door thresholds.
• Lower leveling feet to floor when this equipment is at rest.
• Lower leveling feet and attach joining brackets to adjacent racks when this equipment is in final position.
Failure to follow these instructions will result in death or serious injury.
NOTICE
The interconnection pipes must be isolated throughout the line, in order to avoid loss of performance and
ensure the proper functioning of the equipment.
Failure to follow these instructions will result in death or serious injury.

76-5276-05 Page 9 of 82
Application Field
WESTRIC IW precision air handling units have been developed to be installed in rack computing centers to act directly on
the hot spots, and save energy thanks to their EC fans.
Its function is to control the temperature and humidity of the racks 24/7, making decisions in order to maintain at all times,
the programmed conditions
General features
IW units are manufactured using galvanized, pre-painted steel sheets, ensuring a long service life of the cabinet housing
without the need of repainting or other maintenance procedures.
To enable its cooling operation under low outdoor temperatures, WESTRIC air conditioners with air-cooled condensation
are equipped with electronically-controlled modulating condensation, allowing complete control of the operating conditions.
The evaporator section has a large coil and a high air flow which ensure high performance under sensible heat.
The electrical heaters accelerate the dehumidifying process by reheating the air.
Stainless steel drain pan. Stainless steel made, collects the condensate and funnels it to the drain line
Deshumidification. In case dehumidification is necessary, this will be done by reducing the fan speed of the air
handling unit. This function acts automatically thanks to variable capacity EC fans and factory programming.
Air Filters. 30/30 medium-efficiency filters ensuring the cleanliness of air circulating through the evaporator.
EC Fans. High efficiency EC fans, modulate their speed through the controller to obtain the necessary air flow for each
moment of the refrigeration cycle, in this way they increase the energy saving.
Clogged-Air Filter Switch This device acts when the accumulated dirt on the filter decreases the air flow, which is
transmitted to the controller, the system first gives a warning alarm and if the filters is not replaced the controller leaves
the unit out of service, this causes the units in the same network increases its flow to try to replace the out of order unit.
Klixon Thermal Protections. This thermal protector will disconnect the heating system in case of blower motor failure.
Each set of resistors has its own independent protection.
Electric heater for heating Their electrical output is practically equivalent to the one of the compressor, so that power
consumption during cooling or heating operations is the same.
WARNING
- THIS APPLIANCE IS NOT DESIGNED FOR USE BY PERSONS, INCLUDING CHILDREN, WITH REDUCED PHYSICAL,
SENSORY OR MENTAL CAPACITIES, OR LACK OF EXPERIENCE AND KNOWLEDGE, UNLESS THEY HAVE BEEN
SUPERVISED OR INSTRUCTED ABOUT THE USE OF THE APPLIANCE BY PERSONS RESPONSIBLE FOR THEIR USE
SECURITY.
- CHILDREN MUST BE SUPERVISED TO ENSURE THAT THEY DO NOT PLAY WITH THE APPLIANCE
- THIS UNIT MUST BE INSTALLED ACCORDING TO NATIONAL, STATE AND / OR MUNICIPAL SAFETY REGULATIONS

76-5276-05 Page 10 of 82
Control Panel
The units are controlled by a built-in panel. The panel houses the controller, which are connected to other units via
interconnection terminals.
Therefore, the operation of the unit is entirely automatic.
The controller has a Flash memory which records the operating program and it also has multiple inputs and outputs. The
unit receives data from sensors and controls different elements of the system.
Using the display and keypad built into the controller makes it possible not only to obtain data about the conditions in the
room, but also the fault data log. Using an access code or password the user can enter the menu to change temperature
or humidity set points, cycling parameters, etc.
The control panel is able to receive the signal from a power-free contact from a fire control room; this signal is used to
switch off the units in case the fire alarm is triggered.
Main elements of unit panel:
Microprocessed controller
Power Supply Transformer
General circuit breaker
Air inlet/outlet temperatura sensors
Relative Humidity Sensor
Phase monitoring relay
Terminal blocks
Controller. Each system is controlled by a dedicated controller for air conditioners.
Temperature sensor. This sensor sends information to the Controller about changes in room temperature.
Humidity sensor. This sensor sends analog information to the Controller about changes in room humidity.
Controller alarm outputs. The system has alarm outputs which are triggered when one or more units are out of
service.
Phase monitoring relay. This sensor is used to detect under- or overvoltage conditions, missing phase or phase
asymmetry.

76-5276-05 Page 11 of 82
Different air flow configuration

76-5276-05 Page 12 of 82
IW – 005/006 Side Air Flow-Rear Air Return Indoor Unit Dimensions:

76-5276-05 Page 13 of 82
IW – 005/006 Front Air Flow/Rear Air Return Indoor Unit Dimensions:

76-5276-05 Page 14 of 82
IW – 005 Outdoor Unit Dimensions:

76-5276-05 Page 15 of 82
IW – 006 Outdoor Unit Dimensions:

76-5276-05 Page 16 of 82
Technical Data Sheet
DESCRIPTION
UNIT
IW-005
IW-006
CAPACITY @ 32 ºC DB / 19ºC WB (~ 28 % RH ) INDOOR
TYPE
-
STANDING
BRAND
-
WESTRIC
STANDARDS
-
ISO – 9001- 2015
ORIGIN
Country
ARGENTINA
POWER SOURCE
380 VAC – 50 HZ – 3 ph
POWER FACTOR
-
0,95
EER
-
3
3,4
POWER CONSUMPTION
KW
5,8
5,9
TOTAL CAPACITY
Kwf
17,6
20,2
SENSIBLE CAPACITY
Kwf
16,7
19,2
AIR FLOW
m3/min
60 - 34
66 - 40
INDOOR UNIT WIDTH
mm.
300
INDOOR UNIT HEIGHT
mm.
2.000 (2.070 with wheels)
INDOOR UNIT DEPTH
mm.
1.100
INDOOR UNIT WEIGHT
Kg.
170 (*) 210 (**)
OUTDOOR UNIT WIDTH
mm.
1160
771
OUTDOOR UNIT HEIGHT
mm.
757
945
OUTDOOR UNIT DEPTH
mm.
420
740
OUTDOOR UNIT WEIGHT
Kg.
75 (*) / 110 (**)
85(*) 120(**)
(*) WITHOUT COMPRESSOR – (**) WITH COMPRESSOR
COMPRESSOR
TYPE
-
SCROLL / VARIABLE CAPACITY SCROLL
QUANTITY
N
1
NOMINAL VOLTAGE
-
380 VAC – 50 Hz – 3 ph
QUANTITY
Kw
4,8
5,1
CURRENT DRAW
Amp.
8,4
8,9
OUTDOOR UNIT FAN
TYPE
-
AXIAL
DIAMETER
mm.
508
550
QUANTITY
N
1
DRIVE
-
DIRECT
OUTDOOR UNIT FAN MOTOR
NOMINAL VOLTAGE
Volts
220
QUANTITY
Nº
1
CURRENT DRAW
Amp.
2,7
1,7
POWER CONSUMPTION
Kw
0,56
0,36
DRIVE
-
DIRECT
EC INDOOR UNIT FAN
TYPE
-
EC
DIAMETER
mm.
220
QUANTITY
N
5
RPM MAX
n/min
3060
CONTROL
0 – 10 VCC
POWER CONSUMPTION
Kw.
0,095
CURRENT DRAW
Amp.
0,8
NOMINAL VOLTAGE
Volts
220
DRIVE
-
DIRECT
BEARINGS
BALL

76-5276-05 Page 17 of 82
INDOOR UNIT COIL
AREA
m2
0,58
ROWS
N
3
TUBE DIAMETER
mm.
9.52
FINS PER INCH
N
16
OUTDOOR UNIT COIL
AREA
M2
0,88
1,78
ROWS
N
2
1
TUBE DIAMETER
mm.
9.52
FINS PER INCH
N
13
16
ANTI FREEZING
TYPE
-
ELECTRONIC
BRAND
-
WESTRIC
MODEL
-
CVTR
ORIGIN
-
ARGENTINA
HIGH AND LOW PRESSURE SWITCHS
RANGE
HIGH
Kg / cm2/ PSI
30 – 43 / (420 – 610)
LOW
Kg / cm2/ PSI
3,5 – 6,4 / (50 – 90)
AIR FILTER
TYPE
-
Washable
DIMENSIONS
mm
920 x 215 x 8
QUANTITY
-
ELECTRICAL HEATING RESISTORS (OPTIONAL)
MODEL
-
3 x 800W
QUANTITY
Nº
1
NOMINAL VOLTAGE
Volts
380
STAGES
Nº
1
CURRENT DRAW
AMP.
3,6 A per PHASE
POWER CONSUMPTION
Kw
2,4
RECOMMENDED PIPE DIAMETERS FOR COMPRESSOR ON THE INDOOR UNIT
SUCTION
(inch)
½”
LIQUID
(inch)
3/8”
RECOMMENDED PIPE DIAMETERS FOR COMPRESSOR ON THE OUTDOOR UNIT
SUCTION
(inch)
¾”
LIQUID
(inch)
3/8”
LOGIC CONTROLLER
3/4” BPS
BRAND
-
DANFOSS
MODEL
-
MCX
ORIGIN
Pais
ROMANIA
DRAIN PUMP (OPTIONAL)
MAX. VERTICAL DISTANCE
m.
4
MÁX. HORIZONTAL DISTANCE
m.
10
HUMIDIFIER (OPTIONAL)
Flow Rate
Power
Nominal Voltage
Phases
Current Draw
3 Kg / h
2.25 Kw
380 VAC
3 Ph
3.2 (A)
-Components subject to availability.
-Specifications subject to change without notice.

76-5276-05 Page 18 of 82
CAPACIDAD @ 35ºC EXTERNAL TEMPERATURE
3/4” BPS
Unit
30ºC / 19wb
32ºC / 19wb
35ºC / 20,2wb
IW-005
TOTAL
CAPACITY
Kw
16,8
17,6
18,9
SENSIBLE
CAPACITY
Kw
15,7
16,7
18,9
IW-006
TOTAL
CAPACITY
Kw
19,4
20,2
21,5
SENSIBLE
CAPACITY
Kw
18,2
19,2
21,5
Temperature and Humidity Working Range
WARNING: If the indoor humidity is too high, the condensation effect around the coil can generate too much
condensed water, which could cause a water spill or trigger an alarm.
Nota: If it is in a not operable condition, use an auxiliary dehumidifier or an air conditioner to adjust the interior
temperature and humidity until it falls within an acceptable operating rang

76-5276-05 Page 19 of 82
IW-005/006 External Components
Item
Description
Item
Description
1
PLC Display
6
Rear Door
2
Front Door
7
Top or bottom pipe access
3
Swiveling Casters
8
Top or bottom wire access
4
Wheels
5
Removable Side Panel

76-5276-05 Page 20 of 82
IW-005/006 Internal Components (front view)
Item
Description
Item
Description
1
EC Fans (Qty. 5)
7
Evaporator Coil
2
Protection Grille
8
Service Valves
3
ON/OFF Lever
9
Filter Drier
4
Operation Manual Holder
10
Humidity and Temperature Sensor
5
Drain Pump (Optional)
11
Power Factor Correction Capacitor
6
Compressor
12
Dirty Filter Pressure Switch
This manual suits for next models
5