actionair ESP PLATINUM ERQ2-14AS User manual

INSTALLATION & COMMISSIONING GUIDE - INDOOR
Copyright © 2017 Actron Engineering Pty. Ltd. All rights reserved.
This manual is a controlled document which contains condential and proprietary information.
Distribution, modication, copying and/or reproduction are prohibited without written consent from Actron Air.
Please Read This Guide
Congratulations on your purchase of an
Actron Air air conditioning unit. This unit has
been designed and manufactured with the
highest quality standard in mind.
Please read this guide thoroughly and keep it
near the unit for future reference.
INDOOR UNITS
ESP PLATINUM
ERQ2-14AS
ERQ3-17AS
ERQ4-19AS
ESP PLATINUM QUE SPLIT DUCTED UNIT

Installation & Commissioning Guide - ESP Platinum ID Split Ducted Units
Doc. Part No. 0525-052 Rev. 4.0 180302
Page 2 of 16
TABLE OF CONTENTS
INTRODUCTION
CONGRATULATIONS on your purchase of an Actron
Air Platinum Series air conditioning unit ! This unit has
been designed and engineered to provide optimum air
conditioning and to achieve maximum energy efciency.
Your air conditioning system has been manufactured from
the highest quality materials. Numerous “in house” and
“external” inspection and test procedures were conducted
to your air conditioning to ensure satisfactory operation.
INFORMATION ABOUT THIS GUIDE
This guide provides installation instructions, specic
to your split ducted indoor unit. Read this manual
thoroughly and take into consideration all specications
and instructions to insure correct installation and safe
operation of your air conditioning system.
Keep this document near the unit for future
reference. Ensure that all technicians that work
on the unit can refer to this manual at any time.
PRODUCT INSPECTIONS
Fully check your air conditioning unit and all items
against the bill of loading upon receiving your shipment.
Inspect the unit, components and accessories for any
sign of shipping damage. If there is any damage to the
unit, contact Actron Air Customer Care Department
immediately on: 1800 522 722.
Check the unit nameplate to verify the model, serial
number, electrical rated specications and details are
correct.
CODES, REGULATIONS AND STANDARDS
The installer and/or contractor assumes responsibility
to ensure that unit installation complies with the
relevant council, state / federal codes, regulations and
building code standards. All electrical wiring must be in
accordance with current electrical authority regulations
and all wiring connections to be as per electrical diagram
provided with the unit.
SAFETY INSTRUCTIONS
1. Only licensed HVAC technicians*should install and
service this air conditioning equipment. Improper
service or alteration by unqualied technician could
result in signicant and major damage to the product
or property which may render your warranty null
and void. Such unqualied service could also lead
to severe physical injury or death. Follow all safety
instructions in this literature and all warning labels
that are attached to the equipment.
2. Prevailing WH&S regulations must be observed
and will take precedence to the safety instructions
contained on this manual. Safe work practices and
environment must be the paramount importance in
the performance of all the service procedures.
3. Ensure that unit installation complies with relevant
council regulations and building code standards.
4. All electrical wiring must be in accordance with
current electrical authority regulations and all wiring
connections to be as per electrical diagram provided.
5. Secure the fans against accidental contact. Beware
of pinch point and sharp edges which can cause
cutting injury.
6. Always wear appropriate PPE, remove any dangling
jewellery and protect long hair by wearing a cap.
7. Make sure that safety guards and panel covers are
always rmly secured and not damaged.
8. This appliance is not intended for use by young
children or inrm persons unless they have been
adequately supervised by a responsible person to
ensure that they can use the appliance safely. Young
children should be supervised to ensure that they do
not play with the appliance.
9. Installer must incorporate a means of electrical
disconnection (isolator) in the sub mains xed
wiring in accordance with the Australian wiring rule
(AS3000).
10. Secure the power cords and control cables that goes
in/out the unit. Use the cable ties provided in the
control box.
*Qualications required will be appropriate Electrical,
Refrigeration and Refrigerant Handling License & Training,
dependent on local State/Territory regulations.
This indoor unit is designed to match only with ActronAir
outdoor unit as specied in the Technical Selection
Catalogue.
This unit is designed for use with R410A refrigerant
only.
The unit is supplied with factory charged dry air. Beware
of the pressurised air charge when purging. Remove
the caps from the connection points and purge the
system only when the eld pipes connection are ready
to be completed.
IMPORTANT NOTES TO THE INSTALLER
Introduction ....................................................................
Safety Instructions..........................................................
Components Overview...................................................
Unit Dimensions and Clearances ..................................
Two-Piece Fan Coil .......................................................
Installation Instructions .................................................
Unit Lifting Procedures ..................................................
Condensate & Safety Tray Drainage Instructions .........
Zone Barrels Mounting Instructions ..............................
Wiring Diagram..............................................................
Maximum Cable Lengths...............................................
Maintenance Frequency Checklist ................................
Key Parts List ................................................................
2
2
3
4
6
7
8
9
10
11
12
14
15

ActronAir is constantly seeking ways to improve the design of it’s products, therefore specications are subject to change without notice.
Copyright © 2017 Actron Engineering Pty. Ltd. Page 3 of 16
COMPONENTS OVERVIEW
INDOOR UNIT COMPONENTS OVERVIEW
Indoor
Unit
EC Motor
ID Fans
ID Coil
8Z-VAQ Module
Lid - Control Panel
Indoor
Control Panel
SRD175C / SRD175E
TECHNICAL & SELECTION DATA
UNIT FEATURES
Digital Scroll Compressor•
10-100% Variable Refrigeration Capacity•
Multiple Speed Outdoor Fans•
Louvre Outdoor Coil Guard•
Pre-charged with R410A Refrigerant•
AM7-D8 Wall Controller Supplied as Standard•
20 m of Data Cable Included•
EXV (Electronic Expansion Valve)•
Integral Fan Coil Safety Tray with Drain Kit •
Indoor Coil Overheat Protection•
Indoor Coil Anti-Freeze Protection•
Smart Defrost Function•
CONTROL FEATURES (AM7-D8)
7-Day Programmable Controller with 2 Events/Day •
24- Hour ON/OFF Timer•
Auto, Heat & Cool Modes•
Auto/Continuous Indoor Fan Operation•
3 Speed Indoor Fan Setting•
Hot Start Feature•
Home/Building Automation ON/OFF Capability•
CONTROL OPTIONS
Remote Temperature Sensors•
Zone Kit for Control up to 8 Zones •
(See Integrated Zones, Barrels & Plenums Section)
Secondary Wall Controller with Mimic Logic•
PLENUMS (Optional)
Supply Air Plenums are Available in a 2 way or 3 way•
Con guration (See Integrated Zones, Barrels and Plenums
Section for details of Spigots availability)
Return Air Plenums are Available with 2 x 400 mm Spigots• or
2 x 450 mm Spigots
SPECIFICATION SUMMARY
TOTAL * NETT **
COOLING CAPACITY (kW) *** 18.12 17.40
SENSIBLE CAPACITY (kW) *** 14.81 14.09
HEATING CAPACITY (kW) ^ 17.60 18.30
COOLING INPUT POWER (kW) ^^ 6.07
HEATING INPUT POWER (kW) ^^ 5.44
EER 2.99 2.87
COP 3.24 3.37
INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^ 740 / 920 / 1100
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH 52.0 / 54.0
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH 69.0 / 71.0
POWER SUPPLY - OUTDOOR 240 V / 1 Ph / 50 Hz
POWER SUPPLY - INDOOR 240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ** 22.0 / 3.1 / 25.1
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^ 32.6 / 4.0 / 36.6
CIRCUIT BREAKER AND CABLE AMPS 40.0
APPROXIMATE STARTING AMPS <45.0
WEIGHT (kg) -- INDOOR / OUTDOOR 75.0 / 180.0
OUTDOOR UNIT MODEL SRD175C
INDOOR UNIT MODEL SRD175E
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 27
0
C DB / 19
0
C WB entering air temperatures and 35
0
C ambient.
At 20
0
C DB entering air temperature and 7
0
C DB / 6
0
C WB ambient.
Input power includes indoor fan kW.
Max. - Min. airow application range.
Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.
See Speci cations sheet for Cable Size and Circuit Breaker Size details.
Note: Use input power to estimate running cost.
*
**
***
^
^^
^^^
^^^^
ActronAir is constantly seeking ways to improve the design of it’s products, therefore speci cations are subject to change without notice, Please check prior to purchase. SRD175C-0100 / SRD175E-0100 -P1- 090326
R
R410A
DIGITAL SCROLL
COMPRESSOR
ESP SPLIT DUCTED UNIT
Indoor Unit
Control Board
EMC Filter

Installation & Commissioning Guide - ESP Platinum ID Split Ducted Units
Doc. Part No. 0525-052 Rev. 4.0 180302
Page 4 of 16
INDOOR UNIT DIMENSIONS / CLEARANCES ERQ2-14AS / ERQ3-17AS
UNIT MODEL NUMBER
UNIT
WEIGHT
(kg)
ERQ2-14AS 59
ERQ3-17AS 62
MINIMUM SERVICE ACCESS CLEARANCES
NOTES :
1.Do not scale drawing. All dimensions are in mm unless specied.
2.Refer Field Pipe connection details on specications sheet.
3.Service Clearances given are suggested minimum based on the condition that the
spaces around the units are free from any obstructions and a walkway passage of
1000mm between the units or between the unit and the outside perimeter is available.
4.Minimum service access clearances are responsibilities of the installer, ActronAir®will
not be held liable for any extra charges incurred due to lack of access.
THIRD ANGLE
PROJECTION
STACKING OF UNITS
ONE IN FRONT OF THE OTHER
(DISTANCE BET. A& B)
SIDE BY SIDE
(DISTANCE BET. A& C)
DUCT WORK 800 mm
HEIGHT CLEARANCE = 340
B
DC
A
DUCT WORK
DUCT WORK
800 mm
SERVICE
CLEARANCE
800 mm
SERVICE
CLEARANCE
(ELECTRICAL)
EC
ID FAN
EC
ID FAN
INDOOR COIL
OVERALL NOMINAL DIMENSION (H x W x D)
= 412 x 1290 x 615
SUPPLY DUCT (H x W) = 300 x 715
RETURN DUCT = 340 x 1100
DRAIN CONNECTION = 20mm OD
1100
80
715
20 20
INDOOR COIL
412
O/A
615 O/A
1250
40
300
72
40
340
22
50
115
247.5 247.5
575
SUPPLY
AIR
RETURN
AIR
1290 O/A
40
535
70
50
EC
INDOOR
FAN
EC
INDOOR
FAN
SUPPLY AIR
TOP VIEW
FRONT VIEW SIDE VIEW

ActronAir is constantly seeking ways to improve the design of it’s products, therefore specications are subject to change without notice.
Copyright © 2017 Actron Engineering Pty. Ltd. Page 5 of 16
INDOOR UNIT DIMENSIONS / CLEARANCES ERQ4-19AS
UNIT MODEL NUMBER
UNIT
WEIGHT
(kg)
ERQ4-19AS 76
MINIMUM SERVICE ACCESS CLEARANCES
NOTES :
1.Do not scale drawing. All dimensions are in mm unless specied.
2.Refer Field Pipe connection details on specications sheet.
3.Service Clearances given are suggested minimum based on the condition that the
spaces around the units are free from any obstructions and a walkway passage of
1000mm between the units or between the unit and the outside perimeter is available.
4.Minimum service access clearances are responsibilities of the installer, ActronAir®will
not be held liable for any extra charges incurred due to lack of access.
THIRD ANGLE
PROJECTION
OVERALL NOMINAL DIMENSION (H x W x D)
= 435 x 1420 x 680
SUPPLY DUCT (H x W) = 300 x 715
RETURN DUCT = 360 x 1140
DRAIN CONNECTION = 20mm OD
TOP VIEW
FRONT VIEW SIDE VIEW
SUPPLY
AIR
715310 310
1420 O/A
114080 120
630
20 20
435
O/A
INDOOR COIL
1375
90
130
SUPPLY AIR
59040 50
680 O/A
360
50
25
110
300
25
RETURN
AIR
EC
INDOOR
FAN
EC
INDOOR
FAN
HEIGHT CLEARANCE = 410
DUCT WORK
DUCT WORK
800 mm
SERVICE
CLEARANCE
800 mm
SERVICE
CLEARANCE
(ELECTRICAL)
EC
ID FAN
EC
ID FAN
INDOOR COIL
B
DC
A
STACKING OF UNITS
ONE IN FRONT OF THE OTHER
(DISTANCE BET. A& B)
SIDE BY SIDE
(DISTANCE BET. A& C)
DUCT WORK 800 mm
This manual suits for next models
2
Table of contents
Other actionair Air Conditioner manuals
Popular Air Conditioner manuals by other brands

Fujitsu
Fujitsu ASYG 09 LLCA installation manual

York
York HVHC 07-12DS Installation & owner's manual

Carrier
Carrier Fan Coil 42B Installation, operation and maintenance manual

intensity
intensity IDUFCI60KC-3 installation manual

Frigidaire
Frigidaire FAC064K7A2 Factory parts catalog

Sanyo
Sanyo KS2432 instruction manual

Mitsubishi Electric
Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Panasonic
Panasonic CS-S18HKQ Service manual

Panasonic
Panasonic CS-E15NKE3 operating instructions

Gree
Gree GWH18TC-K3DNA1B/I Service manual

Friedrich
Friedrich ZoneAire Compact P08SA owner's manual

Daikin
Daikin R32 Split Series installation manual