Aiolos HybriCool Flat-V User manual

HYBRICOOL FLAT-V
Installation Operation Manual
HFVIOM180722.001

HYBRICOOL FLAT-V INSTALLATION AND OPERATION MANUAL
1
Index
FOREWORD ............................................................................................................................................. 4
HYBRICOOL FLAT-V BASIC EQUIPMENTS................................................................................................. 5
HYBRICOOL FLAT-V AIR CONDITIONING UNIT TECHNICAL SPECIFICATIONS .......................................... 6
1. SECURİTY PRECAUTIONS ................................................................................................................. 7
1.1. General.................................................................................................................................... 7
1.2. Applications............................................................................................................................. 7
1.3. Warning Labels........................................................................................................................ 7
2. Transportation and Lifting Directives.............................................................................................. 8
2.1. General.................................................................................................................................... 8
2.2. Transportation and Storage .................................................................................................... 8
2.3. Carrying and Lifting ................................................................................................................. 9
2.4. Horizontal Carrying.................................................................................................................. 9
3. MOUNTING INSTRUCTIONS............................................................................................................. 9
3.1. General.................................................................................................................................... 9
3.2. Security.................................................................................................................................... 9
3.3. Mounting Steps ..................................................................................................................... 10
3.4. Exploded View....................................................................................................................... 12
4. COMMISSIONING CHECKLIST ........................................................................................................ 13
4.1. Checklist ................................................................................................................................ 13
4.2. Commissioning Checkpoints.................................................................................................. 13
5. COMISSIONING AND OPERATION INSTRUCTIONS ........................................................................ 15
5.1. Casing .................................................................................................................................... 15
5.2. Body Panels ........................................................................................................................... 15
5.3. Door, Access and Enclosure Covers....................................................................................... 15
5.4. Grounding.............................................................................................................................. 15
5.5. Air Conditioning Unit Installation and Connection ............................................................... 15
5.6. Drainage ................................................................................................................................ 15
5.7. Air Damper ............................................................................................................................ 16
5.8. Air Filters ............................................................................................................................... 16
5.9. Heaters .................................................................................................................................. 16
5.9.1. General.............................................................................................................................. 16
5.9.2. Electric Heater................................................................................................................... 16
5.10. Cooling Coil........................................................................................................................ 17
5.11. Adiabatic Cooling System .................................................................................................. 17
5.12. EC Fan................................................................................................................................ 17

INSTALLATION AND OPERATION MANUAL HYBRICOOL FLAT-V
2
5.13. Sensors .............................................................................................................................. 17
5.14. Control System .................................................................................................................. 18
5.14.1. Operation Scenarios.......................................................................................................... 18
5.14.2. Controller........................................................................................................................... 20
5.14.2.1. Controller Specifications ............................................................................................... 20
5.14.2.1.1. General...................................................................................................................... 20
5.14.2.1.2. Universal Inputs......................................................................................................... 20
5.14.2.1.3. Flexible I/O Points...................................................................................................... 21
5.14.2.1.4. Relay Board Extension............................................................................................... 21
5.14.2.1.5. Sedona FrameworkTM ................................................................................................ 21
5.14.2.2. Wiring Schema............................................................................................................... 21
5.14.3. Programmable Room Controller ....................................................................................... 21
5.14.3.1. Room Controller Usage Interface.................................................................................. 21
5.14.3.2. Wiring Schema............................................................................................................... 23
5.14.3.3. Model Selection............................................................................................................. 23
5.14.3.4. Power Supply Options ................................................................................................... 23
6. MAINTENANCE CHECKLIST............................................................................................................ 24
6.1. Checkpoints and Recommended Maintenance Intervals Checklist...................................... 24
7. MAINTENANCE INSTRUCTIONS..................................................................................................... 26
7.1. General.................................................................................................................................. 26
7.2. Storage .................................................................................................................................. 26
7.3. Body....................................................................................................................................... 26
7.4. Door, Access and Enclosure Covers....................................................................................... 26
7.5. Grounding.............................................................................................................................. 26
7.6. Dampers ................................................................................................................................ 26
7.7. Fresh Air Inlet ........................................................................................................................ 26
7.8. Air Filters ............................................................................................................................... 26
7.9. Heaters .................................................................................................................................. 27
7.9.1. Coils ............................................................................................................................... 27
7.9.2. Electric Heaters.............................................................................................................. 28
7.10. Coolers............................................................................................................................... 28
7.11. Adiabatic Cooling System .................................................................................................. 28
7.12. Fan..................................................................................................................................... 28
7.13. Control Panel..................................................................................................................... 28
7.14. Electric Panel ..................................................................................................................... 28
7.15. Cleaning............................................................................................................................. 28

HYBRICOOL FLAT-V INSTALLATION AND OPERATION MANUAL
3
7.16. Mechanical Cleaning.......................................................................................................... 29
7.17. Wiring ................................................................................................................................ 29
7.18. Compressor, Evaporator and Condenser .......................................................................... 29
8. TAKING AIR CONDITIONING UNIT OFF.......................................................................................... 30
8.1. Turning Unit Off..................................................................................................................... 30
8.2. Disassembling the Unit.......................................................................................................... 30
8.3. Recycling Components .......................................................................................................... 30
8.4. Recycling Fluids ..................................................................................................................... 30
8.5. Recycling of Electric and Electronic Components ................................................................. 30
8.6. Disposal of Filters .................................................................................................................. 30

INSTALLATION AND OPERATION MANUAL HYBRICOOL FLAT-V
4
FOREWORD
AIOLOS AIR HybriCool Flat-V vertical type air conditioning units with 100% fresh air and adiabatic cooling system are used in
the areas such as classrooms, offices, cafes, shops, common and individual living areas by supplying 100% fresh air and by
this way make the areas, where it is used healthier and more comfortable.
Cooling the air is a process that requires much more costs and hardware compared to heating. At this point HybriCool Flat-V
vertical type air conditioning units with 100% fresh air and adiabatic cooling system cool the outside air by using the
evaporation energy of water. This process reduces additional costs, equipment for air conditioning and brings the initial
investment and operation cost significantly down.
HybriCool Flat-V vertical type air conditioning units can adapt itself to every kind of environments by providing a wide range
of solutions in accordance with the use and purposes. In addition to natural cooling, an integrated compressor, condenser,
and evaporator can meet the indoor cooling requirements with cooling and heating with heat pump without any additional
equipment by supplying 100% fresh air in the area, where it is used. It is also possible to use HybriCool Flat-V unit by adding
chilled water coil (CWC) and / or hot water coil (HWC) in areas, where a central cooling and / or hot water supply are provided.
AIOLOS AIR HybriCool Flat-V Air Conditioning Unit is proposed to provide the most appropriate solution to your use and
location, standard equipment are as follows:
•On the fresh air side G2 (ISO Coarse) Filter + F7 (ISO ePM1) Filter
•Proportional speed-controlled EC Fans
•Adiabatic cooling system
•MCC panel, factory mounted automation hardware
•Communication with building automation system via BACnet MS/TP, Modbus RTU
Optional equipment are as follows:
•Cooling and/or heating with integrated DX compressor, condenser, and evaporator
•Electrical heater
•Chilled water coil (CWC)
•Hot water coil (HWC)
•Compact water softening unit
HybriCool Flat-V vertical type air conditioning unit with adiabatic cooling can be controlled and managed via its independent
software with help of well positioned internal sensors and via room controller. In addition, all to this, pollution status of filters
to be seen, daily, weekly time schedule can be done.
We bring together the solutions of the 21st century varying and developing ventilation and energy efficiency needs more
efficiently with less energy. As AIOLOS AIR family, we appreciate you preferring us.

HYBRICOOL FLAT-V INSTALLATION AND OPERATION MANUAL
5
HYBRICOOL FLAT-V BASIC EQUIPMENTS
Part Number
Description
1
Fresh Air G2 (ISO Coarse) Filter
2
F7 (ePM1) Compact Filter
3
Return Air G2 (ISO Coarse) Filter
4
Preheater
5
Heat Exchanger
6
Compressor system
7
Automation Panel
Supply Air
Fresh Air
Return Air
Exhaust Air

INSTALLATION AND OPERATION MANUAL HYBRICOOL FLAT-V
6
HYBRICOOL FLAT-V AIR CONDITIONING UNIT TECHNICAL
SPECIFICATIONS
HybriCool Flat-V Models
HF-V 10
Air Volume (m3/h)
1000
Out of Unit Static Pressure (Pa) @Nominal Air Volume
300
EER Adiabatic Modul (kW/kW)
6,5
EER Adiabatic + DX (kW/kW)
3,8
Adiabatic System Summer Operation Data
Air Entrance Temperature (°C)
35
Air Outlet Temperature (°C)
21,1
Cooling Capacity (kW)
4,8
Water Consumption (l/h)
3
Water Supply (l/h)
6
Heat Recovery Heat Exchanger Winter Operation Data
Air Entrance Temperature (°C)
-3
Air Outlet Temperature (°C)
16,9
HR Capacity (kW)
7
HR Heat Exchanger Efficiency (%)
82
Filtering
Pre-Filtering
G2 ISO Coarse
Final Filtering
F7 ISO ePm1%50
Integrated DX Cooling
Compressor Type
Hermetic
Cooling Refrigerant
R 134a
Cooling Capacity (kW)
7,2
Air Outlet Temperature (°C)
14
Condenser, Evaporator Cooling Water Supply (l/h)
6
Electrical Specifications
Fan Motor Power (kW) x Pieces (with Cooling)
0,78 x 2
Fan Motor Power (kW) x Pieces (Only HR)
0,50 x 2
Fan Power Consumption (kW) @ 0 Pa
0,37
Compressor Power Consumption (kW)
2,37
Electrical Power Supply
230V / 1PH @50 Hz
Control
24V AC
Operation Conditions and Dimensions
Operation Temperature Range (°C)
-20 - +50
Operation Humidity Range (R.H.)
%10 - %90
Width x Length x Height (mm)
1600x600x1981
Note: AiolosAir A.Ş. reserves the right all the values in the table to make a change without information.
Technical specifications of HybriCool Flat-V unit can vary according to usage conditions. Please confirm
the specifications of the product you have ordered from AiolosAir A.Ş.

HYBRICOOL FLAT-V INSTALLATION AND OPERATION MANUAL
7
1. SECURİTY PRECAUTIONS
1.1. General
HybriCool Flat-V air conditioning units with adiabatic
cooling system are manufactured and assembled by
following AiolosAir quality directives. To ensure the
safe operation and use of the unit, please read this
document carefully and follow the instructions and
consider the alerts on this unit. Any changes in the
design and / or assembly of HybriCool Flat-V air
conditioning unit without giving an information to
AiolosAir or written permission of AiolosAir will
eliminate the warranty and the one who makes the
change will be responsible from any possible
damages.
1.2. Applications
HybriCool Flat-V Air Conditioning Unit is designed for
the purpose of conditioning and directing air unless
the project is decided in the projecting phase.
1.3. Warning Labels
Electric Voltage
These labels indicate that there is a dangerous
electrical current, which may be dangerous for the
user or installer behind these access doors, covers or
panels. Only the authorised personnel should be
allowed to work on these parts. These labels can be
found on the control panel of electric heater.
Lifting Place
These labels show the points of unit to be lifted by a
crane. The unit must be connected to crane with a
rope, which passes under the wooden pallet. If the
unit is desired to be lifted or carried with a forklift,
hand forklift or pallet jack under the wooden pallet.
Grounding
This label shows the connection points, from which
the unit must be grounded and located on the
electric panel.
- It is necessary to ground the electrical parts in the
air conditioning unit.
- The electrical assembly of the unit must be
connected to each other according to national
standards, where the unit to be used.
Rotating Components
This label indicates that there is a rotating
component behind the access door, cover or panel,
which may cause an injury. Fan section is indicated
by this label.
Hot Surfaces
This label shows that there are hot surfaces behind
these access covers, doors, or panels, which may
cause to heavy burns if any contact occurs.
Some equipment, such as steam humidifiers, vapour
coil, electrical heater and compressor’s surface,
copper piping line to the condenser with the models
with compressor may have hot surfaces. If there is a
component with hot surface behind any access
covers, doors, or panels, so have a potential risk is
marked by this label.
Fan Cell Access Door
This label is found on the fan section’s door or cover
and explains, that before opening the access door,
cover of the fan cell, minimum two minutes before
the power should be cut off.
Notice: All access doors, covers or panels must be
closed before the unit is activated.

INSTALLATION AND OPERATION MANUAL HYBRICOOL FLAT-V
8
Product Label
On this label the information about the unit and its
order are written. This label is generally found on the
fan section access door or on unit, where easy to see.
Lifting and Transportation
A label, which shows how to lift, and transport will
be done, is found on the cover of air conditioning
unit. Detailed information about this section is
described on the following capital. Packaging
materials should be discarded in accordance with
the relevant regulations.
2. Transportation and Lifting
Directives
2.1. General
Transportation and lifting of the HybriCool Flat-V air
conditioning unit must always be carried out in
accordance with the instructions below. Failure to
follow these instructions may cause irreparable
damage to the device and endanger the lives of
people in the vicinity of the device. AiolosAir does
not assume any liability for the consequences
resulting from failure to comply with these
instructions.
Carrying and transportation activities should be
carried out by expert personnel. Lifting must be
carried out in accordance with the relevant
regulations using certified lifting equipment.
2.2. Transportation and Storage
Air conditioning units should only be lifted by using
the specified lifting methods. In according to the
lifting conditions if it is unable to lift it up, the unit
can be lifted with a pallet jack, hand forklift or a
crane by passing through under the wooden pallet,
which is located under the unit’s foot. The carrying
and lifting are only allowed, when the required
instruction, which are described in chapter 2.4 are
followed. This situation is also valid for the storage
and marked by a warning label.
Lifting by hand forklift
Carrying by pallet jack
Lifting and carrying by forklift
Units are shipped to the field in one piece. If the
protective packaging on the units is removed, dirt
may enter the parts of the unit.
Necessary precautions should be taken in the
construction site environment and protective
packaging should not be removed until the units are
installed.
Filters of units waiting outside for a long time lose
their properties in case of exposure to the sun. For
this, the filters should be stored in the shade and in
places free from moisture.

HYBRICOOL FLAT-V INSTALLATION AND OPERATION MANUAL
9
2.3. Carrying and Lifting
Air conditioning units are manufactured as a single,
independently of considering the required size from
worksite and transported to the field. Before starting
the transportation and installation of the unit, be
sure to review the documents containing the
dimensions, weights, and assembly sequence of the
unit.
The weight for each transport segment is given on
the unit. The points to be used for transportation are
marked with the relevant labels on the body.
The following method is recommended for vertical
lifting and moving of the air conditioning unit:
Application
Slip the carrying rope through the wooden pallet,
which is under the unit and connect rope to crane,
then lift it up. Take the necessary precautions to
avoid damages on unit.
Lifting by crane
Note: For all uninstalling methods, make sure that
the load is balanced during lifting.
2.4. Horizontal Carrying
For horizontal transportation of unit, a suitable
forklift, hand forklift or pallet jack can be used in
accordance with the instructions. FOR THE
HORIZONTAL CARRYING ALWAYS LIFT WITH
SUITABLE TRANSPORTATION VEICHLE BY IT’S
FORKS ARE PASSING THROUGH THE WIDTH OF
UNIT ACCORDING TO THE WARNING SIGNS.
The following method is recommended for
horizontal lifting and moving of the air conditioning
unit:
Application
The forks of lifting vehicle should pass through the
wooden pallet and by this way unit can be carefully
and balanced done. Lifting and carrying work should
be carried out by experts. AIOLOS AIR IS NOT
RESPONSIBLE FOR DAMAGES OR INJURIES CAUSED
BY NON-SPECIALIST PERSONNEL OR CAUSED BY AN
INCORRECT FORKLIFT SELECTİON.
Carrying by pallet jack
Not: The forklift must be selected in accordance with
the weight and dimensions of the air conditioning
unit.
3. MOUNTING INSTRUCTIONS
3.1. General
The Area, where HybriCool Flat-V unit is going
to be mounted, has been considered as an
indoor, so the floor should carry the weight of
unit, ventilation duct system should be installed
properly and drain precautions should be also
taken. The ground concrete body must be made
smoothly and, in the scales, to prevent a
problem while the operation of the unit.
1
Supply Air Outlet
3
Return Air Inlet
2
Fresh Air Inlet
4
Exhaust Air Outlet
3.2. Security
This Section provides an overview of all important
safety aspects for protection against person.
Power Cable
•Do not lay nearby any heater.
•Do not put under any heavy objects, which
might change the cross section of power cable.
•Use the given voltage, otherwise it may lead to
fire and electric strike.

INSTALLATION AND OPERATION MANUAL HYBRICOOL FLAT-V
10
•Do not use device, if power plug or power cable
is damaged.
•Before maintenance cut the electricity of
device.
Intended Usage
•Intended use also includes compliance with all
information in this manual.
•Any use that goes beyond the intended use or
that is different counts as misuse.
•Any modification to the device or the use of
non-original spare parts will void the warranty
and the manufacturer's liability.
Operation Limitations
Operation voltage
230V 50 Hz
Operation Current
On the Product Label
Data
Value
Environment Temperature (°C)
5 to +30
Relative Humidity (%)
10 to 90
Air Intake Temperature (°C)
-20 to +50
Electric Current Hazards
DANGER!
Danger of death through electric current
Any contact with live parts poses an intermediate
risk of fatal injury from electric shock. Damage to
the insulation or individual components can be
fatal.
➢Only authorised electricians are
allowed to work with electrical
components.
➢Any damages to the insulation of
power supply must be repaired
immediately.
➢Keep away humidity from live parts. It
may cause short circuit.
➢Must be grounded properly.
Transportation, Storage and Packaging
Air conditioning units should only be lifted by
using the specified lifting methods. According to
the lifting conditions if it is unable to lift it up,
the unit can be lifted with a pallet jack, hand
forklift or a crane by passing through under the
wooden pallet, which is located under the unit’s
foot. The carrying and lifting are only allowed,
when the required instructions, as described in
the second chapter under Transportation and
Lifting Directives are followed. This situation is
also valid for the storage and marked by a
warning label.
Units are shipped to the field in one piece. If the
protective packaging on the units is removed,
dirt may enter the parts of unit. Necessary
precautions should be taken in the construction
site environment and protective packaging
should not be removed until units are installed.
If unit’s filters are waiting outside for a long
time, they lose their properties in case of
exposure to the sun. For this, filters should be
stored in the shadow and inner places free from
moisture.
3.3. Mounting Steps
Fixing to Wall
In order to a proper mounting of unit,
installation’s process has to follow these steps:
1. Stand the unit in front of the wall, where it is
going to be fixed.
2. Adjust the height of unit by turning feet.
3. Mount wall fixing part to wall (above yellow
parts)
4. Adjust the required distance from wall by
moving unit with wall fixing parts (down yellow
parts)
5. Fix these yellow parts to each other by using
two M8x20 hex headed bolts with four rings
and two hex headed nuts for each unit.
Distance from Side Walls
Recommended minimum distance from the
inner surface of wall

HYBRICOOL FLAT-V INSTALLATION AND OPERATION MANUAL
11
Plenum Box Installation
1. Apply gasket to the connection surfaces to
prevent air leakage.
2. Place plenum box onto the unit.
3. Use six pieces of M6x20 socket head cap
screws for fixing plenum box to unit.
Base Plate Installation
1. Adjust the unit’s height
2. Place front and back plates and mount them
with 14 pieces of M6x20 pan cross headed
screws
3. At the same time install the drainage from left
of right side of the unit.
1. Green pipe indicates IEC water supply.
2. Red pipe indicates drainage outlet.
Note: The opening, which is shown by 1 is an option
for electrical connection from bottom.
Filter Installation
1. Check filters for the correct type and size
2. Place thin filters (G2 ISO Coarse) and thick
filters (F7 ePM1) as shown
3. To lock F7 filter push red locking plates
down. Vice versa is applied to remove F7
filter safely.
Vertical and Horizontal Louver Installation
1. Use Ø250 mm flex duct
2. Open holes in the wall
3. Place and fix indoor and outdoor mounting
plates as shown
4. Connect and fix flex duct with sleeve
5. Protect outside plate with cover and fix

INSTALLATION AND OPERATION MANUAL HYBRICOOL FLAT-V
12
Connection with Power Supply
1. Make sure all other connections and mountings are correctly and safely done.
2. 5-meter-long power cable is already placed inside the unit.
3. Take the power cable of unit and plug it in to the nearest 230V 50Hz power supply.
3.4. Exploded View

HYBRICOOL FLAT-V INSTALLATION AND OPERATION MANUAL
13
4. COMMISSIONING CHECKLIST
4.1. Checklist
General information about the planning required for commissioning the air conditioning unit is given in the table below.
Details about each part of this table will be given on the following pages.
4.2. Commissioning Checkpoints
FUNCTION
COMPONENTS
CHECKPOINTS
STATUS
General
Indoor Unit Assembly
Inner and Outer Panels
Damage
Connections
Connection according to regulation
Outdoor Unit Assembly
Door/Access and Enclosure
Covers
Damage / Must be closed before
operation
Grounding
Connection according to regulation
Dampers
Proper assembly
Damper Actuator
Proper assembly
Filters
Correct filter type and size
Deformation on surface
Pressure Differential Sensor /
Switch
Smooth operation / Automation
connection
Heaters
Leakage
Freezing thermostat operation
Hot Water coil
Correct assembly
Motorised Valve
Correct assembly
Correct automation connection
Electric Heater
Correct connection / Safety
equipment
Steam Humidifier
Correct connection / safety
equipment
Coolers
Leakage
Chilled Water Coil
Correct assembly
Motorised Valve
Correct assembly
Correct automation connection
Drift Eliminator
Proper placement
Drainage
Correct connection
Adiabatic Cooling system
Damage
Leakage
Nozzle
Congestion
Solenoid Valve
Correct automation connection
Leakage
Damage
Water Supply
Softened water
Fan
Damage
Correct electric connection
ATTENTION!
Before starting the air conditioning unit, make sure that all parts have the correct electrical voltage and make the
connections in accordance with the relevant regulations. The door and access / conservation covers should be closed, the
air conditioning unit should be grounded.

INSTALLATION AND OPERATION MANUAL HYBRICOOL FLAT-V
14
Grounding
Correct automation connection
Correct rotating direction
Compressor
Damage
Leakage
Correct automation connection
Proper gas charge pressure and
control
Condenser
Damage
Leakage
Correct assembly
Evaporatör
Damage
Leakage
Correct assembly
Control Panel
Correct automation connection
Sensors
Accurate measurement control
Correct automation connection
Electric Panel
Compliant connection with
regulations
Grounding
Maintenance Switch
Correct connection
Function test

HYBRICOOL FLAT-V INSTALLATION AND OPERATION MANUAL
15
5. COMISSIONING AND
OPERATION INSTRUCTIONS
5.1. Casing
Order code, unit type, serial number, etc. The label
containing the unit information is located on an
easily visible place on the unit. In this way, the
customer can easily read the unit information.
5.2. Body Panels
Check the panels of the air conditioning units for
damage. If there is, remove any dirt and stains from
the surfaces and eliminate the possibility of damage
in the long term. Check the sealing gaskets on the
unit, if any, and repair if necessary.
5.3. Door, Access and Enclosure
Covers
In addition to the door handle and locks, check the
overall operation of the nut and rivet system, and
then determine whether the hinges and movement
mechanisms are moving properly.
5.4. Grounding
Make sure that the air conditioning unit is properly
grounded and in accordance with the relevant
regulations. There is a label on the body or the
electrical panel indicating the grounding location of
the unit.
5.5. Air Conditioning Unit
Installation and Connection
Since the room where the air conditioning unit will
be installed is a wet place, it should be kept in mind
that the floor should be waterproof and drainage
measures should be taken. To avoid any problem in
the operation of the unit, the concrete base of the
device should be made smooth and in balance.
5.6. Drainage
A drainage system should be used at the drain outlet
of the unit to ensure a constant flow of water from
the drainpipe of the air conditioning unit.
Proper drainage application is important in order to
avoid air suction or leakage from the drain to the unit
and to discharge water inside the unit without
overflowing. In drainage dimensions, the static
pressure in the area where the drainage will be
applied should be taken into account. AIOLOSAIR IS
NOT RESPONSIBLE FOR FAILURES CAUSED BY
WRONG DRAINAGE USAGE.
Negative pressure drainage
At the pipe outlet of the condensation pan, the
minimum distance from the lower point of the pipe
to the floor, D [mm] is calculated with the following
formula:
P [Pa]: It is the negative pressure in the device and
the pressure value here should be used within the
absolute value.
Positive pressure drainage application
P [Pa]: It is the maximum pressure in the cooling coil
and H1 is calculated by the following formula:
H2= 50 mm
The inside of the positive pressure drainage must be
filled with water before the device is put into
operation, and the negative pressure drainage can
only be used in negative pressure drainage outlets.
If negative pressure drainage is not supplied from
the factory should be made according to the figure
below.

INSTALLATION AND OPERATION MANUAL HYBRICOOL FLAT-V
16
U-shaped negative pressure drainage application
P [Pa]: It is the maximum pressure in the cooling coil.
H1 and H2 are calculated by the following formulas:
Drainage outlets should not be raised along the
drainage drain line or at the end of the line. If the line
must be raised due to any obstacle on the floor, H2
height should be taken into account in the drainage
calculation. Drain line is generally designed ¾” scale.
Female connection on ¾” scale is ready for the male
connection with same size on both sided of casing.
Water supply, Drainage and Electrical cable showing
Water supply and electrical cable from right side
Water supply from left side, electrical cable from
right side as standard
5.7. Air Damper
Check if the damper is adjusted to the correct angle,
opened with the required angle, and works properly.
5.8. Air Filters
Check whether the appropriate size and correct
filters specific to the application are installed.
Check that the filters are placed properly and make
sure that they are protected under appropriate
conditions.
Set the filter impurity pressure switches or the filter
gauges if used
5.9. Heaters
5.9.1. General
i. Check and ensure that connections
meet the requirements according
to the sizing project.
ii. Leakage control must be done and
be ensure there is no leakage.
iii. Be sure that the heater produces
enough heat to prevent freezing.
Attention: In coils where water is used as a
heater or coolant, no water should be left in
the circuits to prevent damage to the coil
against the possibility of freezing at
temperatures below 0°C. It should be ensured,
that some precautions such as setting up hot
water boiler, circulation pump operation and
starting the freezing scenario of automation in
case when the temperature drops below under
5°C.
5.9.2. Electric Heater
i. Make sure that the electrical heater is
connected in accordance with the
manufacturer's instructions. The
wiring diagram is located inside the
electrical junction box.
ii. Check the current in the electrical
heater.
iii. Check whether the safety devices
shown in the electrical diagram are
installed.

HYBRICOOL FLAT-V INSTALLATION AND OPERATION MANUAL
17
iv. Check if the electric heater is
grounded in accordance with local
instructions.
v. The electric heater should only be
operated if the specified minimum air
volume rate is achieved.
vi. The electric heater must be turned off
at least 5 minutes before power is cut
from the air handling unit.
vii. Make sure that nothing is left in the
electric heater compartment.
viii. The following notices are posted on
the panel:
Electrical Voltage and Hot Surface.
5.10. Cooling Coil
i. Check the connections based on the sizing
projects and check the leakage and
tightness of the connections.
ii. If fins are damaged during the
transportation, fix them.
iii. Check if the drop eliminator behind the
cooler is properly connected.
iv. A substance that blocks water flow should
not be put into the ceiling.
v. Check that the condensed water is
drained, and the drainage is working after
a while after the cooling coil is switched
on. If necessary, clean the drainage.
Attention: In coils where water is used as a
refrigerant, against the possibility of freezing
at temperatures below 0°C, no water should be
left in the circuits to prevent damage to the
coils. If water is to be left, glycol must be added
at a rate that is safely calculated according to
the lowest possible air temperature. AiolosAir
is not responsible for water freeze damage
caused by failure to take precautions.
5.11. Adiabatic Cooling System
i. Check the nozzle valves on the module and
make sure that distilled, dirt-free and
demineralised water is supplied to the
system.
ii. Adiabatic module water inlet pressure
min. Check it is 3 bar.
iii. Check the water nozzles.
iv. Make sure that the air-tight heat
exchanger cover is tightly closed and
airtight.
v. Before the device is started, check that the
adiabatic module drainage drain is made
properly with proper drainage and pipe
connection.
Attention: When switched into winter
operation, the remaining water in the
adiabatic cooling module pipes must be
drained. For this, it should be checked that the
solenoid valve on the adiabatic cooling module
water supply is open and the water flows
through the pipes in reverse flow. AiolosAir is
not responsible for any damage caused by
failure to take precautions.
5.12. EC Fan
i. Check whether the fan can move freely
without getting caught in the mounting
frame, elastic connection, or wiring.
ii. Check the mains voltage of the electric
motor.
iii. Check and/or connect the engine
according to the relevant regulations and
with the help of the information provided
by the manufacturer and by authorized
persons.
iv. Check the fan rotation direction. This
direction should be the direction indicated
on the case.
v. Measure the current drawn by the electric
motor for all phases.
vi. The current drawn in all phases should be
approximately the same and match the
information on the product label.
vii. Check that the flexible connections are
properly fitted.
viii. Make sure that the grounding is done
correctly.
Attention: Before working on the fan, it must
be ensured that the electricity is cut off.
Warning signs regarding rotating parts,
electrical voltage and open doors are affixed to
the door.
5.13. Sensors
Sensors are hardware that allows the unit to be
monitored and interpreted in detail over a single
system.

INSTALLATION AND OPERATION MANUAL HYBRICOOL FLAT-V
18
i. Make sure that the temperature of the
inlet and outlet air is measured correctly.
ii. Check that the air volume is measured
correctly.
5.14. Control System
5.14.1. Operation
Scenarios
HybriCool Flat-V air conditioning units work at
maximum capacity in accordance with the
ready prepared scenarios via room controller.
General Operation Scenario
The general operation logic of AIOLOS AIR
HybriCool Flat-V vertical type air conditioning
unit with 100% fresh air and adiabatic cooling
system is described below:
IEC Operation System
High efficiency counter-flow heat exchangers
are used in HybriCool series. So, the heat
exchange will proceed at the highest level.
This heat exchange begins with the saturation
of exhaust, return, air right before entering the
heat exchanger. Fresh air, which passes through
heat exchanger and saturated return air make
heat exchange via lamella of heat exchanger
without physically mixing each other in
accordance with the thermodynamically. By this
way, the inlet air is cooled in summer and
heated in winter.
DX+ Heat Pump Operation System
Compressors with high COP values are used in
HybriCool series. So, the highest cooling
capacity with the lowest energy consumption is
provided.
A main factor in DX system is room
temperature. Operation systems of
compressors are depended on firstly room
temperature, then the set value of room
temperature. They keep working on the same
logic both summer and winter seasons.
Summer operation mode (Cooling): Let’s take
room temperature’s set value 22°C. Whenever
room temperature increases 2°C above this set
value (24°C) compressor starts working. If there
are more than one compressor, both starts
working. If system with two compressors
reaches the set value, (ex. 22°C), the first
compressor stops working. When the room
temperature decreases 1°C below the set value
(22°C), the second compressor also stops
working. If there is a system with single
compressor, when the room temperature
decreases 1°C below the set value, compressor
stops working.
Winter operation mode (Heat Pump): Let’s
take room temperature’s set value 24°C.
Whenever room temperature decreases 2°C
below this set value (22°C) compressor starts
working. If there are more than one
compressor, both starts working. If system with
two compressors reaches the set value, (ex.
24°C), the first compressor stops working.
When the room temperature increases 1°C
above the set value (24°C), the second
compressor also stops working (25°C). If there is
a system with single compressor, when the
room temperature increases 1°C above the set
value (25°C), compressor stops working.
6 minutes of brakes are necessary for each start
and stop of compressors.
Coil Operation System
HybriCool series can be adjusted into coil
system, if necessary.
Heating and cooling coils serve depending on
the operation scenarios of unit. In summer
mode cooling coil (CWC), in winter mode
heating coil (HWC) are activated.
Summer operation mode (Cooling): CWC coil is
activated on cooling mode. After setting up a
set value for room temperature (E.g. 24°C),
whenever room temperature increases above
this set value, CWC coil controls the room
temperature by increasing its capacity, which is
controlled by a proportional valve.
Winter operation mode (Heating): HWC coil is
activated on cooling mode. After setting up a
set value for room temperature (E.g. 22°C),
whenever room temperature decreases below
this set value, HWC coil controls the room
temperature by increasing its capacity, which is
controlled by a proportional valve.
Hot Gas Re-Heat Operation System
Hot gas re-heat system is used in HybriCool
series for controlling the humidity and
temperature in the room more sensitively. With
this application the humidity in the room can be
controlled much more sensitively. The working
principle of this system is almost the same as DX
+ Heat Pump system. With only one difference,
the supply air is cooled much more than
required by evaporator and is transferred to the
hot gas re-heat coil. Here, the supply air is
heated again by hot gas re-heat coil, which is

HYBRICOOL FLAT-V INSTALLATION AND OPERATION MANUAL
19
controlled proportionally, according to required
temperature and humidity values.
Electric Heater Operation System
HybriCool series are only equipped with electric
heater only for heating.
The Electric heater is used on the fresh air side
to protect heat exchanger against freezing,
defrost and as an additional heating capacity in
winter season.
Electric heater works below described
circumstances in winter season:
-If supply air temperature is under the set
temperature value, electric heater starts
working. When set value and supply air
temperature are equal, electric heater
switches into standby mode.
-If room or return air temperature is 5°C
lower than a room set temperature value,
electric heater starts working and
whenever both temperatures are equal,
stops working.
-Electric heater stays active during defrost
mode.
-Electric heater starts operating for 10
minutes when exhaust air temperature
decreases below 3°C on the models
without compressor, then stops working.
After an hour starts working again if the
necessary conditions occur.
Freezing Protection System
Although HybriCool series is optional, we have a
freeze protection, and we recommend that the
temperatures in winter are high or where the
risk of falling is high.
These freezing protections are possible to
separate into two parts: Firstly, the necessary
system protection against freezing on the heat
exchanger and then for the condenser on the
exhaust air side on the models with compressor.
Heat exchanger freezing protection: When the
outdoor temperature falls below -5°C, electric
heater, which is used for preheating, works for
10 minutes, and heats the cold outdoor air,
before entering the heat exchanger. So, this
process prevents the possible freezing in the
exchanger. This process repeats itself once in
each hour.
Condenser freezing protection: Frost and
freezing occur on the surface of condenser,
since the evaporation temperature of the
refrigerant passing through the condenser
decreases in winter. With the help of
temperature sensors on the condenser, the
freezing can be sensed, and the system works
for 15 minutes on defrost mode (ice melting).
During this period, compressors are on standby
mode, air volume is decreased to 25% of
nominal air volume and electric heaters are
activated. By this way the air temperature that
feeds the room works for a while at ambient
temperature levels and above temperatures. At
the end of defrost mode unit returns
automatically to its normal operating values.
Note: During defrost mode, it is unable to
provide normal heating capacity of the unit. At
design stage this situation must be considered.
Free Cooling System
Free cooling system is a standard for each
HybriCool series and provides fresh air into a
room without any power consumption except
EC fans (if there are any compressors, will be
shut down).
This system mostly works in spring and autumn.
When outside temperature is 6°C lower than
room temperature, the Damper will be opened
and fresh air passes through. But when outdoor
air decreases below 10°C, damper will be
closed, and unit returns to its normal operation
conditions.
Constant Air Volume and Variable
Pressure Control System
Air volume remains constant with the help of
pressure differential sensors on fans.
The values of these sensors can be tracked
dynamically and with the calculation below air
volume can be calculated manually:
This formula above is used for a single fan, if
there are more than one, this formula should be
multiplied by n:
Here: n is quantity of fans, k is fan constant, ∆P
describes pressure difference.
“k” values of fans are shown in the table below.
Model
HF-06
HF-12
HF-20
HF-30
HF-40
HF-50
K Factor
71
60
95
121
This manual suits for next models
1