
508031-02Issue 2135Page 6 of 29
Unit Components
A80UH1EX & 80G1UHEX unit components are shown
in Figure 1. The gas valve, combustion air inducer and
burners can be accessed by removing the upper access
panel. Electrical components are in the control box (Figure
2) found in the blower section.
Electrostatic discharge can aect
electronic components. Take precautions
to neutralize electrostatic charge by
touching your hand and tools to metal
prior to handling the control.
CAUTION
Control Transformer (T1)
A transformer located in the control box provides power
to the low voltage section of the unit. Transformers on all
models are rated 40VA with a 120V primary and a 24V
secondary.
Door Interlock Switch (S51)
A door interlock switch is wired in series with line voltage.
When the blower door is removed the unit will shut down.
NOTE: The door interlock switch is a safety switch. Do not
by-pass or jumper switch.
DOOR INTERLOCK
SWITCH (S51)
INTEGRATED IGNITION
CONTROL
(A92)
TRANSFORMER
(T1)
CIRCUIT
BREAKER
(CB8)
Figure 2. Control Box
Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The
switch provides overcurrent protection to the transformer
(T1). The breaker is rated at 3A at 32V. If the current
exceeds this limit the breaker will trip and all unit operation
will shutdown. The breaker can be manually reset by
pressing the button on the face.
Integrated Control (A92)
Shock hazard.
Disconnect power before servicing. Control is not eld
repairable. If control is inoperable, simply replace entire
control.
Can cause injury or death. Unsafe operation will result
if repair is attempted.
WARNING
The hot surface ignition control system consisting of
an integrated control (Figure 3 with control terminal
designations in tables 1, 2 and 3), sensor and ignitor
(Figure 6). The integrated control and ignitor work
in combination to ensure furnace ignition and ignitor
durability. The integrated control, controls all major furnace
operations. The integrated control also features a RED
LED for troubleshooting and two accessory terminals rated
at (1) one amp. See Table 4 for troubleshooting diagnostic
codes. The nitride ignitor is made from a non-porous, high
strength proprietary ceramic material that provides long life
and trouble free maintenance.
Electronic Ignition (Figure 4)
On a call for heat the integrated control monitors the
combustion air inducer pressure switch. The control will
not begin the heating cycle if the pressure switch is closed
(bypassed). Once the pressure switch is determined to
be open, the combustion air inducer is energized. When
the dierential in the pressure switch is great enough, the
pressure switch closes and a 15-second pre-purge begins.
If the pressure switch is not proven within 2-1/2 minutes,
the integrated control goes into Watchguard-Pressure
Switch mode for a 5-minute re-set period.
After the 15-second pre-purge period, the ignitor warms
up for 20 seconds during which the gas valve opens at
19 seconds for a 4-second trial for ignition. The ignitor
remains energized for the rst 3 seconds during the 4
second trial. If ignition is not proved during the 4-second
period, the integrated control will try four more times with
an inter purge and warm-up time between trials of 35
seconds. After a total of ve trials for ignition (including the
initial trial), the integrated control goes into Watchguard-
Flame Failure mode. After a 60-minute reset period, the
integrated control will begin the ignition sequence again.