alphainnoTec L8 SPLIT User manual

MOS GB 1539-3
331457
SPLIT
INSTALLATION AND MAINTENANCE INSTRUCTIONS
SPLIT
L8 SPLIT/L12 SPLIT, HM 8-12 SPLIT, EHZK 90 SPLIT/WWS 300 SPLIT/WWS 500 SPLIT
LEK
LEK
LEK
LEK
LEK
LEK

EHZK 90 SPLIT
LEK
LEK
LEK
LEK
LEK
WWS 300 SPLIT
LEK
WWS 500 SPLIT
LEK
HM 8-12 SPLIT

LEK
LEK
LEK
L8 SPLIT
LEK
LEK
L12 SPLIT


For Home Owners
General
3
3Installation data
Information about the installation
5Product information
5Features of SPLIT
5Principle of operation SPLIT
Front panel, indoor module
7How to use the front panel
7Menu types
7Quick movement
7Key lock
Comfort setting heating
8General
8Operating status
8Changing the room temperature manually
9Default setting
10Readjusting the default settings
Comfort setting cooling
11General
11
Cooling operated from the outdoor sensor in operating
mode AutoK
11Controlling cooling mode using the room sensor
Comfort setting hot water
12Available volume
12Prioritizing
12Extra Hot Water
Maintenance
14Checking the safety valves
14
Pressure gauge in EHZK 90 SPLIT, WWS 300 SPLIT, WWS
500 SPLIT
15Emptying the coil in the water heater
15Emptying the vessel
15Maintenance of L8 SPLIT/L12 SPLIT
15Saving tips
Dealing with comfort disruption
17Operating mode "Add. heat only"
17Emergency mode
Alarm indications
18
What happens when an alarm appears on my sys-
tem?
18Recommended actions
18Acknowledging alarms
For the Installer
General information for the installer
19Transport and storage
19Supplied components
20Assembly
20Dimensioning expansion vessel
21Manual shunting
21Emptying the vessel
21Recommended installation order
Pipe installation
22General
22System requirements
22Dimensions and pipe connections
23Pump capacity diagram
23Connecting HM 8-12 SPLIT to tank
24Connecting the climate system
24Connecting the hot water heater
25Connection of external heat source
25Waste exchanger part
25Connecting refrigerant pipes (not supplied)
29Dockings
Electrical installation
33General
33Electrical components
35Connecting the supply
35Miniature circuit-breaker
35Temperature limiter
35
Connection between HM 8-12 SPLIT and L8 SPLIT/L12
SPLIT
36
Connection between HM 8-12 SPLIT and EHZK 90 SPLIT,
WWS 300 SPLIT, WWS 500 SPLIT
37Setting max power, electrical addition
37Setting max boiler temperature
37EBV board, terminal and wiring diagram
37Connecting the outside sensor
37
Connecting the temperature sensor hot water char-
ging
37Connecting the current limiter
38Connection of centralised load control/tariff
38Connecting external contacts
38Alarm outputs
38Docking specific connection
Start-up and inspection
40Preparations
40Commissioning
40Setting system flow heating
40Setting system flow cooling
40
Commissioning HM 8-12 SPLIT without L8 SPLIT/L12
SPLIT connected
41
Checking external addition with internal immersion
heater blocked
41
Checking external addition (not controlled by HM 8-12
SPLIT) with internal immersion heater as backup
41Inspection of the installation
41Cleaning the particle filter
41Secondary adjustment
42Checklist: Checks before commissioning
1SPLIT
Table of Contents

Miscellaneous
Control
43Display
43Menu types
43Menu management
44Menu tree
52Main menus
531.0 [N] Hot water temp.
532.0 [N] Supply temp.
553.0 [N] Supply temp. 2
564.0 [N] Outdoor temp.
565.0 [N] Heat pump
576.0 [N] Room temperature*
577.0 [N] Clock
588.0 [N] Other adjustments
599.0 [S] Service menus
Alarm list
65Acknowledging alarms
65Alarm with automatic reset
65Temperature limiter alarm
65HM 8-12 SPLIT alarm
66L8 SPLIT/L12 SPLIT alarm
68Hot water alarm
68Supply alarm
69Outdoor sensor alarm
69Circulation pump alarm
Electrical circuit diagram
70HM 8-12 SPLIT
76L8 SPLIT
76L12 SPLIT
Component positions
78HM 8-12 SPLIT
80EHZK 90 SPLIT, WWS 300 SPLIT, WWS 500 SPLIT
82Outdoor unit
Temperature sensor
84Sensor placement
84Data for sensor in L8 SPLIT/L12 SPLIT
85Data for sensor in HM 8-12 SPLIT
Dimensions
86Indoor unit
90Outdoor unit
Technical specifications
94Performance, HM 8-12 SPLIT and L8 SPLIT
94Performance, HM 8-12 SPLIT and L12 SPLIT
95Sound pressure levels
96Standard test, EN14511
96Standard test, L8 SPLIT
96Standard test, L12 SPLIT
Energy labelling
97Information sheet
97Data for energy efficiency of the package
98Technical documentation
Accessories
100
Safety precautions
101Caution
101Care
102Especially for units intended for R410A
103Index
SPLIT2
Table of Contents

General
SPLIT is a system for heating, cooling and producing hot water for small houses. The system consists of an outdoor module
(L8 SPLIT/L12 SPLIT), which utilises the energy in the outdoor air and sends it to the indoor module (HM 8-12 SPLIT), which
takes care of the regulation and heat distribution in the house.
In order to gain the greatest benefit from the SPLIT system, please refer to the 'For Home Owners' chapter within this In-
stallation and Maintenance Manual.
SPLIT is a quality system offering a long service life and reliable operation.
Installation data
Completed by the installation engineer when the sys-
tem is installed
Installation data and installation check list on page 42
must be filled in by the installer in order for the warranty
to apply.
Serial number, must always be stated in all correspondence with us.
Outdoor unit:Indoor unit:
Installation date:
Check list, page 42, filled in
Installation engineers:
Heating
Radiator Floor Fan convector
External heat source
Solar Gas Oil Wood Pellets Electricity
Accessories
KWS RBE SPLIT RFV SPLIT MG 2 SPLIT VK 2 SPLIT EP 2 SPLIT
Other.................................................................................................................
Settings
Enter deviations from default settings.
SettingMenuSettingMenu
..........................................................................................................................................................................................
..........................................................................................................................................................................................
..........................................................................................................................................................................................
..........................................................................................................................................................................................
Date __________ Signed __________________________________
3SPLIT
For Home Owners
General

This appliance can be used by children aged
from 8 years and above and persons with
reduced physical, sensory or mental capabil-
ities or lack of experience and knowledge if
they have been given supervision or instruc-
tion concerning use of the appliance in a
safe way and understand the hazards in-
volved. Children shall not play with the appli-
ance. Cleaning and user maintenance shall
not be made by children without supervision.
Rights to make any design or technical
modifications are reserved.
SPLIT4
For Home Owners
General

Information about the installation
Product information
SPLIT is a complete modern heat pump system that offers
effective energy saving and reduced carbon dioxide
emissions.
The heat is retrieved from the outdoor air by an outdoor
module (L8 SPLIT/L12 SPLIT), where the refrigerant, which
circulates in a closed system, transfers the heat from the
heat source (outdoor air) to the indoor module (HM 8-12
SPLIT). This eliminates the need for boreholes and coils in
the ground.
Features of SPLIT
■Optimal annual heating factor thanks to the inverter
controlled compressor.
■Outdoor unit with compact dimensions.
■Speed controlled circulation pump.
■Optimized operating costs. The speed of the compressor
is adjusted according to the demand.
■Supplemented with the tanks EHZK 90 SPLIT, WWS 300
SPLIT or WWS 500 SPLIT for the indoor module HM 8-12
SPLIT and outdoor module, L8 SPLIT or L12 SPLIT.
■Integrated clock for scheduling extra hot water and
temperature lowering/increasing the flow line temper-
ature.
■Prepared for control of two climate systems.
■Integrated active cooling function.
■Possible to connect external heat sources.
Principle of operation SPLIT
System without hot water, only heating (cooling)
Klimatsystem
BT 1
RG10/
RE10
CP1
Överströmnings-
ventil
HE 30
AMS 10-12
HBS 16
Climate system
Overflow valve
HM 8-12
SPLIT
L8 SPLIT /L12
SPLIT
RFV SPLIT/
RBE SPLIT
EHZK 90 SPLIT
System heating (cooling) and hot water
Klimatsystem
BT 1
RG10/
RE10
CP1 Erf. säker-
hetsutr.
FQ1
FL1
Överströmnings-
ventil
AMS 10-12
HBS 16
HEV 300/HEV 500
Extern tillsats
Climate system
Overflow valve
HM 8-12
SPLIT
L8 SPLIT /L12
SPLIT
RFV SPLIT/
RBE SPLIT
WWS 300 SPLIT/WWS 500 SPLIT
Required
safety devices
External additional
heat
Function
SPLIT is a system that can produce heating, hot water and
cooling.
The principle during heating can be simplified as follows:
1. The refrigerant in L8 SPLIT/L12 SPLIT retrieves heat
from the outdoor air then compresses it, which in-
creases the temperature further.
2. The hot refrigerant (now in gas state) is routed into
HM 8-12 SPLIT.
3. The refrigerant releases the heat for further distribu-
tion in the system.
4. The refrigerant (now in liquid state) is routed back to
L8 SPLIT/L12 SPLIT and the process is repeated.
By reversing the process, thereby allowing the refrigerant
in L8 SPLIT/L12 SPLIT to retrieve the heat from the water
and release it into the outdoor air, the heat pump can, if
necessary, cool instead.
HM 8-12 SPLIT determines when L8 SPLIT/L12 SPLIT is to
work and not to work, using the collated data from the
temperature sensor. In the event of extra heat demands,
HM 8-12 SPLIT can connect additional heat in the form of
the internal immersion heater, or any connected external
addition.
5SPLIT
For Home Owners
Information about the installation

Front panel, indoor module
A BI II III I II
13.43
1.0
A
5 0 . 0 ° C
- Scroll forward in the menu system.
- Increase the value of the selected
parameter
- Scroll back in the menu system.
- Reduce the value of the selected
parameter
- Select lower menu in the menu system.
- Parameter change activated
- Parameter change confirmed
During normal operation, the status lamp
lights green.
In the event of an alarm, it lights red.
The change does not need to be
confirmed with the Enter button.
Pressing the button (the change does not
need to be confirmed with the enter
button).
-Current operating mode is shown in the
display.
-Further button pressing changes
operating mode.
Press the enter button to return to the
normal display mode.
For information about the various operating
modes, see the different sections regarding
comfort settings.
Pressing the button takes you directly to
menu 1.0.
- Heating or cooling demand
"A" Heating mode
"B" Cooling mode
If the electrical addition is connected
”I” Electrical step 1
”II” Electrical step 2
”II” Electrical step 3
More than one electrical step can be connected
at the same time.
Additional heat symbol
Compressor symbol
Hot water temp.
Operating status
Extra hot water (XHW)
Menu 1.0
Normal mode
Switch
1
All control functions connected.
Shutdown
0
Only the circulation pump and
electrical addition (electrical step 2)
are operational.
Emergency mode
Hot water symbol
The heat pump charges hot water.
Temporary temperature increase in
progress.
Time based temperature increase in
progress, e.g. periodic.
"A"
"B"
A BI II III I II I II
A B
A BI II III I II I II
A B A BI II III I II
50.0°C
V a r m v attentemperatur
13.43
1.0 P
50.0°C
V a r m v attentemperatur
13.43
1.0 P13.43
1.0 P
A
50.0°C
V a r m v attentemperatur
A BI II III I II I II
A B
13.43
1.0 P
50.0°C
r tt
r tt
Circulation pump symbol
Circulation pump in operation.
With two circulation pumps (requires
accessory MG), the operating pump is
also indicated.
Climate system symbol
Heating/cooling in progress.
A BI II III I II I II
A B
A BI II III I II I II
A B A BI II III I II
50.0°C
V a r m v attentemperatur
13.43
1.0 P
50.0°C
V a r m v attentemperatur
13.43
1.0 P13.43
1.0 P
A
50.0°C
V a r m v attentemperatur
A BI II III I II I II
A B
13.43
1.0 P
50.0°C
r tt
r tt
Description of current display parameter
Information symbols
Menu number
A BI II III I II I II
A B
A BI II III I II I II
A B A BI II III I II
50.0°C
V a r m v attentemperatur
13.43
1.0 P
50.0°C
V a r m v attentemperatur
13.43
1.0 P13.43
1.0 P
A
50.0°C
V a r m v attentemperatur
A BI II III I II I II
A B
13.43
1.0 P
50.0°C
r tt
r tt
Key lock activated.
A BI II III I II I II
A B
A BI II III I II I II
A B A BI II III I II
50.0°C
V a r m v attentemperatur
13.43
1.0 P
50.0°C
V a r m v attentemperatur
13.43
1.0 P13.43
1.0 P
A
50.0°C
V a r m v attentemperatur
A BI II III I II I II
A B
13.43
1.0 P
50.0°C
r tt
r tt
Plus button
Minus button
See the section "Control – General"
Enter button
Status lamp
A BI II III I II I II
A B
A BI II III I II I II
A B A BI II III I II
50.0°C
V a r m v attentemperatur
13.43
1.0 P
50.0°C
V a r m v attentemperatur
13.43
1.0 P13.43
1.0 P
A
50.0°C
V a r m v attentemperatur
A BI II III I II I II
A B
13.43
1.0 P
50.0°C
r tt
r tt
See the section "Control – General"
See the section "Control – General"
- Turning clockwise (+) increases the
room temperature (if room sensors are
not used).
When the knob is turned menu 2.0 is
shown on the display and the value for
the current supply temperature changes.
Offset heating curve
Defrosting symbol
Defrosting in progress.
A BI II III I II
13.43
1.0
A
5 0 . 0 ° C
Displayed with all activated scheduling.
Clock
See the section "Control – Menu 7.0"
SPLIT6
For Home Owners
Front panel, indoor module

How to use the front panel
All the most common settings are made from the panel
as well as control computer instructions such as comfort
etc. that you require the heat pump system to fulfil.
In order for the installation to be used optimally, certain
basic settings must have been made (see page 9). In ad-
dition the installation in general must be carried out ac-
cording to the instructions and manufacturer's recommend-
ations.
Menu 1.0 (temperature in the water heater) is normally
shown on the display.
The plus and minus buttons and the enter button
are used to scroll through the menu system as well
as to change the set value in some menus.
Menu types
Control is divided into different menu types depending
on how ”deep” into the controls you need to go.
■Normal [N]: The settings you as a customer often
need.
■Extended [U]: Shows all detailed menus except the
service menus.
■Service [S]: Shows all menus.
The menu type is changed from menu 8.1.1
Quick movement
To quickly return to the main menu from a sub menu,
press one of the following buttons:
Key lock
A key lock can be activated in the main menus by simultan-
eously pressing the plus and the minus buttons. The key
symbol will then be shown on the display.
A BI II III I II
13.43
1.0
A
5 0 . 0 ° C
The same procedure is used to deactivate the key lock.
7SPLIT
For Home Owners
Front panel, indoor module

Comfort setting heating
General
The indoor temperature depends on several factors.
■Sunlight and heat emissions from people and household
machines are normally sufficient to keep the house warm
during the warmer parts of the year.
■When it gets colder outside, the climate system must be
started. The colder it is outside, the warmer radiators
and under floor heating systems must be.
Controlling heat production
Normally, the heat pump heats the water (heating medi-
um) to the temperature required at a certain outdoor
temperature. This occurs automatically on the basis of the
collected temperature values from the outdoor temperat-
ure sensor and sensors on the lines to the climate system
(flow line sensors). Extra accessories such as room temper-
ature sensors, can influence the temperature.
However, the correct default settings must be made on
the heat pump first, see the section “Default settings”.
The temperature information that the outdoor sensor
(mounted on an exterior wall of the house) sends to the
heat pump’s control computer senses variations in the
outdoor temperature early on. It does not have to be cold
inside the house before the control system is activated, as
soon as the average outdoor temperature drops outside,
the temperature of the water to the climate system (supply
temp.) inside the house is increased automatically.
The heat pump's supply temperature (menu 2.0) will hover
around the theoretical required value, which is in brackets
on the display.
Temperature of the climate system
The temperature of the climate system in relation to the
outdoor temperature can be modified by using the "Offset
heating curve” knob on the heat pump’s front panel.
Operating status
The “Operating mode” button is used to set the re-
quired operating mode with regard to permitting/block-
ing the circulation pump and additional energy.
The change does not need to be confirmed with the
enter button.
The current operating mode is shown on the front panel
display when the button is pressed and the mode changes
when you continue to press the button.
The display returns to the normal display mode once the
enter button is pressed.
The addition is only used for anti-freeze mode, if it is deac-
tivated in the menu system. This applies to all operating
modes.
The different operating modes are:
1. ”Auto”
■HM 8-12 SPLIT automatically selects the operating
mode by taking the outdoor temperature into ac-
count. This means that the operating mode switches
between "Heating" and "Hot water". Current oper-
ating mode is shown within brackets.
■The circulation pump is permitted to operate when
there is a need.
2. ”AutoK”*
■HM 8-12 SPLIT selects operating mode automatic
(cooling can also be selected now) with regard to
the outdoor temperature. This means that the oper-
ating mode switches between "Heating", "Cooling"
and "Hot water".
■The circulation pump is permitted to operate when
there is a need.
3. "Heat" / "Heat addition"
■Only heating and cooling produced.
■The circulation pump is in operation the entire time.
■If "Heat addition" is shown the addition is permitted
to operate if necessary.
4. "Cooling"* / "Super cooling"
■If addition is permitted, "Super cooling" is displayed.
The compressor then only runs in cooling mode.
Otherwise, the mode switches to cooling or produ-
cing hot water.
■The circulation pump is in operation the entire time.
■Hot water is only produced by the immersion heater.
5. "Hot water"
■Only hot water is produced.
■Only the compressor is operational.
6. ”Add. heat only”
■Compressor blocked. The function is activated by
pressing in the ”operating mode button” for 7
seconds.
7. Deactivate the function by pressing the "Operating
mode" button for 7 seconds once again.
* To use the cooling functions, the system must be con-
structed to withstand low temperatures and "Cooling"
must be activated in menu 9.3.3.
Changing the room temperature manually
If you want to temporarily or permanently increase or
lower the indoor temperature turn the ”Offset heating
curve” knob clockwise or anticlockwise. One line approx-
imately represents a 1 degree change in room temperat-
ure.
NOTE
An increase in the room temperature may be inhib-
ited by the radiator or underfloor heating thermo-
stats, if so these must be turned up.
SPLIT8
For Home Owners
Comfort setting heating

Default setting
The basic heating is set using menu 2.1.2 and with the
“Offset, heating curve” knob.
If the required room temperature is not obtained, readjust-
ment may be necessary.
If you do not know the correct settings use the basic data
from the automatic heating control system diagram op-
posite.
A BI II III I II
13.43
1.0
A
5 0 . 0 ° C
Offset heating curve
Heating curve
2 . 1 . 2
9
Menu 2.1.2 Heating curve
NOTE
Wait one day between settings so that the temperat-
ures have time to stabilise.
Setting with diagrams
The diagram is based on the dimensioned outdoor tem-
perature in the area and the dimensioned supply temper-
ature of the climate system. When these two values
“meet”, the heating control's curve coefficient can be read.
This is set under menu 2.1.2, "Heating curve". Limitations,
which are not in the diagrams, are included in the control
system's permitted min and max temperatures.
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
- 40
UTETEMPERATUR
- 10
0
10
- 5
+ 5
30
40
50
60
70
FRAMLEDNINGSTEMPERATUR
- 20 - 30
FÖRSKJUTNING
VÄRMEKURVA (-2)
VÄRMEKURVA
30
40
50
60
70
FRAMLEDNINGSTEMPERATUR
- 40
UTETEMPERATUR
- 10
0
10 - 20 - 30
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
1514 13 12 11 10
8
7
6
5
4
3
2
1
- 40
UTETEMPERATUR
- 10
0
10
- 5
+ 5
30
40
50
60
70
FRAMLEDNINGSTEMPERATUR
- 20 - 30
FÖRSKJUTNING
VÄRMEKURVA (+2)
9
VÄRMEKURVA
VÄRMEKURVA
- 5
+ 5
FÖRSKJUTNING
VÄRMEKURVA (0)
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
- 40 °C
OUTSIDE TEMPERATURE
- 10
0
10
- 5
+ 5
30
40
50
60
70
°C
FLOW TEMPERATURE
- 20 - 30
HEATING
CURVE OFFSET (-2)
HEATING CURVE
30
40
50
60
70
°C
FLOW TEMPERATURE
- 40 °C
OUTSIDE TEMPERATURE
- 10
0
10 - 20 - 30
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
1514 13 12 11 10
8
7
6
5
4
3
2
1
- 40 °C
OUTSIDE TEMPERATURE
- 10
0
10
- 5
+ 5
30
40
50
60
70
°C
FLOW TEMPERATURE
- 20 - 30
HEATING
CURVE OFFSET (+2)
9
HEATING CURVE
HEATING CURVE
- 5
+ 5
HEATING
CURVE OFFSET (0)
HEATING CURVE
OUTSIDE TEMPERATURE
SUPPLY TEMPERATURE
OFFSET HEAT CURVE -2
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
- 40
UTETEMPERATUR
- 10
0
10
- 5
+ 5
30
40
50
60
70
FRAMLEDNINGSTEMPERATUR
- 20 - 30
FÖRSKJUTNING
VÄRMEKURVA (-2)
VÄRMEKURVA
30
40
50
60
70
FRAMLEDNINGSTEMPERATUR
- 40
UTETEMPERATUR
- 10
0
10 - 20 - 30
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
1514 13 12 11 10
8
7
6
5
4
3
2
1
- 40
UTETEMPERATUR
- 10
0
10
- 5
+ 5
30
40
50
60
70
FRAMLEDNINGSTEMPERATUR
- 20 - 30
FÖRSKJUTNING
VÄRMEKURVA (+2)
9
VÄRMEKURVA
VÄRMEKURVA
- 5
+ 5
FÖRSKJUTNING
VÄRMEKURVA (0)
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
- 40 °C
OUTSIDE TEMPERATURE
- 10
0
10
- 5
+ 5
30
40
50
60
70
°C
FLOW TEMPERATURE
- 20 - 30
HEATING
CURVE OFFSET (-2)
HEATING CURVE
30
40
50
60
70
°C
FLOW TEMPERATURE
- 40 °C
OUTSIDE TEMPERATURE
- 10
0
10 - 20 - 30
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
1514 13 12 11 10
8
7
6
5
4
3
2
1
- 40 °C
OUTSIDE TEMPERATURE
- 10
0
10
- 5
+ 5
30
40
50
60
70
°C
FLOW TEMPERATURE
- 20 - 30
HEATING
CURVE OFFSET (+2)
9
HEATING CURVE
HEATING CURVE
- 5
+ 5
HEATING
CURVE OFFSET (0)
HEATING CURVE
OUTSIDE TEMPERATURE
SUPPLY TEMPERATURE
OFFSET HEAT CURVE 0
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
- 40
UTETEMPERATUR
- 10
0
10
- 5
+ 5
30
40
50
60
70
FRAMLEDNINGSTEMPERATUR
- 20 - 30
FÖRSKJUTNING
VÄRMEKURVA (-2)
VÄRMEKURVA
30
40
50
60
70
FRAMLEDNINGSTEMPERATUR
- 40
UTETEMPERATUR
- 10
0
10 - 20 - 30
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
1514 13 12 11 10
8
7
6
5
4
3
2
1
- 40
UTETEMPERATUR
- 10
0
10
- 5
+ 5
30
40
50
60
70
FRAMLEDNINGSTEMPERATUR
- 20 - 30
FÖRSKJUTNING
VÄRMEKURVA (+2)
9
VÄRMEKURVA
VÄRMEKURVA
- 5
+ 5
FÖRSKJUTNING
VÄRMEKURVA (0)
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
- 40 °C
OUTSIDE TEMPERATURE
- 10
0
10
- 5
+ 5
30
40
50
60
70
°C
FLOW TEMPERATURE
- 20 - 30
HEATING
CURVE OFFSET (-2)
HEATING CURVE
30
40
50
60
70
°C
FLOW TEMPERATURE
- 40 °C
OUTSIDE TEMPERATURE
- 10
0
10 - 20 - 30
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
1514 13 12 11 10
8
7
6
5
4
3
2
1
- 40 °C
OUTSIDE TEMPERATURE
- 10
0
10
- 5
+ 5
30
40
50
60
70
°C
FLOW TEMPERATURE
- 20 - 30
HEATING
CURVE OFFSET (+2)
9
HEATING CURVE
HEATING CURVE
- 5
+ 5
HEATING
CURVE OFFSET (0)
HEATING CURVE
OUTSIDE TEMPERATURE
SUPPLY TEMPERATURE
OFFSET HEAT CURVE +2
9SPLIT
For Home Owners
Comfort setting heating

Readjusting the default settings
If the required room temperature is not obtained, readjust-
ment may be necessary.
Cold weather conditions
■When the room temperature is too low, the “Heating
curve” value is increased in menu 2.1.2 by one increment.
■When the room temperature is too high, the “Heating
curve” value is decreased in menu 2.1.2 by one incre-
ment.
Warm weather conditions
■If the room temperature is low, increase the “Heating
curve offset” setting by one step clockwise.
■If the room temperature is high, reduce the “Heating
curve offset” setting by one step anti-clockwise.
SPLIT10
For Home Owners
Comfort setting heating

Comfort setting cooling
General
The condition in order for cooling to be activated is that
"On" is selected in menu 9.3.3 Cooling system.
NOTE
The climate system must manage cooling operation.
Settings must be made by the installer when commis-
sioning the system.
If a room sensor is connected, it starts and stops cooling
together with the outdoor temperature. The lowest current
supply temperature is set in menu 2.2.4.
Cooling operated from the outdoor sensor in
operating mode AutoK
If the cooling system is set to "On" in menu 9.3.3 and the
outdoor temperature is greater or equivalent to the set
start temperature for cooling in menu 8.2.4, cooling starts.
Cooling stops when the outdoor temperature drops below
the set value minus the set value in menu 8.2.5.
The current supply line temperature is determined from
the selected cooling curve in menu 2.2.2 and the offset
for cooling curve, menu 2.2.1. Limitations, which are not
in the diagram, are included in the control system's permit-
ted min temperature.
NOTE
HM 8-12 SPLIT is condensation insulated for cooling
operation down to a supply temperature of + 7 °C.
0
0
C
20 C
30
5
10
20
Beräknad
framlednings-
temp.
Utetemp.
40
15
Utetemperatur
Be räknad framledningstemperatur
20 30 40
20
10
0
k = 1
k = 2
k = 3
k=1
k=2
k=3
+ 5
- 5
FÖRSKJUTNING
KYLKURVA (0)
Outside temperature
Calculated flow
temperature
Cooling curve offset (0)
Controlling cooling mode using the room
sensor
If RFV SPLIT is present, the condition for cooling is that the
room temperature has exceeded the set room temperature
(menu 6.3) by the set value in menu 8.2.5 and that the
outdoor temperature is equal to or exceeds the set outdoor
temperature value (menu 8.2.4).
When the room temperature has dropped below the set
room temperature in menu 6.3 by the set value in menu
8.2.5 or the outdoor temperature falls below the set value
in menu 8.2.4 by the set value in menu 8.2.5, cooling
switches off.
11SPLIT
For Home Owners
Comfort setting cooling

Comfort setting hot water
The water heaters are coil models and are heated by circu-
lating water, which is heated by the heat pump.
During “normal” consumption it is enough to run the heat
pump’s compressor to supply the different tapping points
of the house with hot water. The temperature of the hot
water in the water heater then varies between the set
values.
Under section 1.0 [N] Hot water temp. on page 53 there
is a complete description of menu settings for hot water
temperatures.
Available volume
300
350
48 50 52 54 56 58 60 62 64
Tappvarmvarmvattenvolym, 40 °C [l]
Stopptemperatur varmvarmvatten [°C]
0
50
100
150
200
250
HEV 300 AMS 10-8
10 l/min
12 l/min
14 l/min
16 l/min
Domestic hot water volume, 40 °C (litre)
Stop temperature hot water °C
10 l/ min
12 l/ min
14 l/ min
16 l/ min
300
350
48 50 52 54 56 58 60 62 64
Tappvarmvarmvattenvolym, 40 °C [l]
Stopptemperatur varmvarmvatten [°C]
0
50
100
150
200
250
HEV 300 AMS 10-12
10 l/min
12 l/min
14 l/min
16 l/min
Domestic hot water volume, 40 °C (litre)
Stop temperature hot water °C
10 l/ min
12 l/ min
14 l/ min
16 l/ min
0
100
200
300
400
500
600
48 50 52 54 56 58 60 62 64
Tappvarmvarmvattenvolym, 40 °C [l]
Stopptemperatur varmvarmvatten [°C]
HEV 500 AMS10-8
10 l/min
12 l/min
14 l/min
16 l/min
Domestic hot water volume, 40 °C (litre)
10 l/ min
12 l/ min
14 l/ min
16 l/ min
Stop temperature hot water °C
0
100
200
300
400
500
600
48 50 52 54 56 58 60 62 64
Tappvarmvarmvattenvolym, 40 °C [l]
Stopptemperatur varmvarmvatten [°C]
HEV 500 AMS10-12
10 l/min
12 l/min
14 l/min
16 l/min
Domestic hot water volume, 40 °C (litre)
Stop temperature hot water °C
10 l/ min
12 l/ min
14 l/ min
16 l/ min
Prioritizing
If the water within the water heater requires heating, the
heat pump prioritises this and shifts to hot water mode
with the entire heat pump output.
In this mode, there is no heating or cooling.
Prioritizing can be affected via settings in the front panel.
See "1.0 [N] Hot water temp." on page 53.
Extra Hot Water
In all ”Extra hot water” functions, the temperature of the
hot water increases temporarily. The temperature is first
increased to an adjustable level by the compressor (menu
1.5) and then the electric additional heat increases until
the stop temperature is reached (menu 1.4).
Temporary ”Extra hot water” is activated manually, whilst
time based extra hot water is activated using the settings
made in the control computer.
When:
■”A” appears above the
A BI II III I II
13.43
1.0
A
5 0 . 0 ° C
icon, temporary extra hot
water is active.
■””B” appears above the
A BI II III I II
13.43
1.0
A
5 0 . 0 ° C
icon, when time based extra
hot water is active.
SPLIT12
For Home Owners
Comfort setting hot water

NOTE
”Extra hot water” usually means that the electrical
addition has been activated and therefore increases
the electrical consumption.
”Extra hot water” can be activated in three different
ways:
1. Periodic time based extra hot water
■Interval between increases is selected in menu 1.7.
Menu 1.8 shows when the next increase is due.
■The increased temperature is maintained by the
electrical addition for one hour.
2. Schedule time based extra hot water
■The start and stop times for the day of the week that
the increase is required are set in the sub menus for
menu 7.4.0.
■The increased temperature is maintained by the
electrical addition for the selected period.
3. Temporary extra hot water
■The current ”extra hot water” mode is shown on the
display (A) when the button is pressed and by
pressing the button again the mode changes
between 3 hours and standby mode.
■The increased temperature is maintained by the
electrical addition until the period of time has ex-
pired.
13SPLIT
For Home Owners
Comfort setting hot water

Maintenance
HM 8-12 SPLIT and L8 SPLIT/L12 SPLIT require minimal
maintenance after commissioning.
SPLIT contains many components and is why monitoring
functions are integrated to help you.
If something abnormal occurs, a message appears about
malfunctions in the form of different ”alarm” texts in dis-
play.
Checking the safety valves
The installation has been equipped with a safety valve for
the water heater as well as a safety valve for the climate
system by the installer.
The climate system's safety valve
EHZK 90 SPLIT
LEK
XL18
XL19
QM1
The climate system's safety valve (FL2) is close to EHZK 90
SPLIT or by the hot water tank. See illustration.
VVS 300 SPLIT/VVS 500 SPLIT
LEK
LEK
BP5
FL2
The climate system's safety valve (FL2) must be completely
sealed. Checks must be carried out regularly as follows:
■Open the valve.
■Check that water flows through the valve. If this does
not happen, replace the safety valve.
■Close the valve again.
■The climate system may need to be refilled after checking
the safety valve, see the section “Filling the climate sys-
tem”. Contact your installer for refilling the climate sys-
tem.
Safety valve domestic water
The safety valve for domestic water sometimes releases a
little water after hot water has been tapped. This is be-
cause the cold water, which enters the heater to replace
the hot water, expands when heated causing the pressure
to rise and the safety valve to open.
Also check the safety valve for domestic water regularly.
The appearance and location of the safety valve differs
between different installations. Follow the cold water pipe
to locate the safety valve. Contact your installer for inform-
ation.
Pressure gauge in EHZK 90 SPLIT, WWS 300
SPLIT, WWS 500 SPLIT
The working range of the climate system is normally 0.5 –
1.5 bar when the system is closed, depending on the height
of the system. Check this on the pressure gauge (BP5).
SPLIT14
For Home Owners
Maintenance

Emptying the coil in the water heater
The water heater is of the coil type and the pressure in the
domestic coil can be released by closing off the incoming
water and opening the hot water tap. However, some
water may remain in the domestic coil. Drain by removing
the cold water connection XL3 on the water heater.
Emptying the vessel
Contact your installer if the vessel in EHZK 90 SPLIT, WWS
300 SPLIT, WWS 500 SPLIT needs emptying.
Maintenance of L8 SPLIT/L12 SPLIT
L8 SPLIT/L12 SPLIT is equipped with control and monitor-
ing equipment, however some exterior maintenance is
still necessary.
Make regular checks throughout the year that the inlet
grille is not clogged by leaves, snow or anything else.
During the cold months of the year, check to make sure
that there isn't a build up of ice or frost under L8 SPLIT/L12
SPLIT. Strong wind combined with heavy snowfall can
block the intake and exhaust air grilles. Make sure that
there is no snow on the grilles.
Also check that the condensation water drain under L8
SPLIT/L12 SPLIT is not blocked.
If necessary the outer casing can be cleaned using a damp
cloth. Care must be exercised so that the heat pump is not
scratched when cleaning. Avoid spraying water into the
grilles or the sides so that water penetrates into L8
SPLIT/L12 SPLIT. Prevent L8 SPLIT/L12 SPLIT coming into
contact with alkaline cleaning agents.
!
WARNING!
Rotating fan in L8 SPLIT/L12 SPLIT.
Saving tips
Your SPLIT installation produces heat and hot water ac-
cording to your needs. It also attempts to carry out all re-
quirements with all available ”aids” from the control set-
tings made.
The indoor temperature is naturally affected by the energy
consumption. Therefore, take care not to set a temperature
higher than necessary.
Other known factors that affect the energy consumption
are, for example, hot water consumption and the insula-
tion level of the house, as well as the level of comfort you
require.
Also remember:
■Open the thermostat valves completely (except in the
rooms that are to be kept cooler for various reasons, e.g.
bedrooms).
Thermostat valves in the radiators and floor loops can
negatively affect the energy consumption. They slow the
flow in the climate system, which the heat pump wants to
compensate with increased temperatures. It then works
harder and consumes more electrical energy.
15SPLIT
For Home Owners
Maintenance

Dealing with comfort disruption
Use the following list to find and remedy any heating or
hot water problems.
ActionCauseSymptom
Check and replace blown fuses.Circuit or main MCB tripped.Low hot water temperature or a lack of
hot water. Check and replace any blown circuit and
main fuses.
Heat pump and immersion heater do not
heat.
Reset the earth circuit-breaker, if the earth
circuit-breaker trips repeatedly, call an
electrician.
Possible earth circuit-breaker tripped.
Set the switch to 1.Switch(SF1) set in 0 mode.
Wait a few hours and check if the hot
water temperature rises.
Large hot water demand.
Adjust the start temperature setting in
menu 1.2.
Too low start temperature setting on the
control system.
Reset the earth circuit-breaker, if the earth
circuit-breaker trips repeatedly, call an
electrician.
Possible earth circuit-breaker tripped.Low room temperature.
Check and replace any blown circuit and
main fuses.
Heat pump and immersion heater do not
heat.
Adjust the setting.Incorrect setting of "Curve slope", "Heating
curve, offset" and/or "Cooling curve, off-
set".
Check and replace blown fuses.Circuit or main MCB tripped.
Change operating mode to ”Auto” or
"AutoK".
Heat pump in incorrect operating mode
”Hot water” or "Cooling".
Switch off one/several of the power con-
sumers.
The current limiter has restricted the cur-
rent because many power consumers are
being used in the property.
Adjust the setting.Incorrect setting of "Curve slope", "Heating
curve, offset" and/or "Cooling curve, off-
set".
High room temperature.
Change operating mode to ”AutoK”.Heat pump in incorrect operating mode.
Adjust the settings. Check menu 2.2.1,
2.2.2 and 8.2.4.
Incorrect settings for cooling.
Wait 30 minutes and check if the com-
pressor starts.
Minimum time between compressor starts,
alternatively time after power switch on
not achieved.
The compressor does not start.
See section ”Alarms”.Alarm tripped.
Activate operating mode ”Only additional
heat”.
Alarm cannot be reset.
Check and replace any blown circuit and
main fuses.
Display not lit.
Check that the circuit breaker to the in-
door unit is not off.
Check that the switch (SF1) is in normal
position (1).
SPLIT16
For Home Owners
Dealing with comfort disruption
This manual suits for next models
5
Table of contents
Popular Air Conditioner manuals by other brands

Mitsubishi Electric
Mitsubishi Electric Mr.Slim PEA-M200 installation manual

Mitsubishi Electric
Mitsubishi Electric Mr. SLIM SLZ-M15FA2.TH Technical & service manual

Panasonic
Panasonic S-22MZ1H4A operating instructions

Panasonic
Panasonic S-20LM3HPQ Installation and operation manual

Fedders
Fedders A6K32E7B user manual

Gorenje
Gorenje VG Series User and installation manual