46 440 01 1050 06
Specifications are subject to change without notice.
CIRCULATION AIR BLOWER DATA (CFM#)
*9UHX060F12 (1)(2) * Denotes Brand
Exterrnal Static Pressure
(in wc/Pa)
Speed
Tap HI MED H MED L LO
in wc Pa CFM L/s CFM L/s CFM L/s CFM L/s
0.1 25 1478 697 1204 568 901 425 703 332
0.2 50 1418 669 1154 545 864 408 649 306
0.3 75 1350 637 1103 521 818 386 588 277
0.4 100 1280 604 1053 497 765 361 538 254
0.5 125 1201 567 993 469 720 340 488 230
0.6 149 1116 527 924 436 672 317 459 217
0.7 174 1023 483 846 399 620 293 408 193
0.8 199 931 439 764 361 558 263 365 172
0.9 224 825 389 683 322 489 231 317 150
1 249 730 345 590 278 428 202 233 110
*9UHX080J12 (1)(2) * Denotes Brand
Exterrnal Static Pressure
(in wc/Pa)
Speed
Tap HI MED H MED L LO
in wc Pa CFM L/s CFM L/s CFM L/s CFM L/s
0.1 25 1456 687 1326 626 1123 530 976 461
0.2 50 1440 680 1312 619 1112 525 941 444
0.3 75 1420 670 1280 604 1085 512 909 429
0.4 100 1379 651 1241 586 1043 492 870 411
0.5 125 1325 625 1209 571 1002 473 818 386
0.6 149 1261 595 1155 545 952 449 784 370
0.7 174 1208 570 1082 511 893 421 714 337
0.8 199 1115 526 1001 472 792 374 640 302
0.9 224 1007 475 868 410 702 331 567 268
1 249 830 392 746 352 608 287 491 232
NOTE: (1) Data Based on Bottom Only or One Side return.
(2) Gray area is above maximum temperature rise range.
# CFM −Cubic Feet Per Minute airflow. Filter required for each
return−air inlet.
Airflow perfomance includes 1” (25.4mm) washable [600 FPM (3.0
m/s) max] filter media.
*9UHX080J16 (1)(2) * Denote Brand
Exterrnal Static Pressure
(in wc/Pa)
Speed
Tap HI MED H MED L LO
in wc Pa CFM L/s CFM L/s CFM L/s CFM L/s
0.1 25 2032 959 1690 798 1246 588 922 435
0.2 50 1952 921 1650 779 1250 590 898 424
0.3 75 1874 884 1601 756 1226 579 872 412
0.4 100 1785 842 1533 723 1187 560 838 395
0.5 125 1688 797 1462 690 1151 543 806 380
0.6 149 1593 752 1381 652 1090 514 769 363
0.7 174 1482 699 1287 607 1014 479 711 336
0.8 199 1360 642 1182 558 918 433 643 303
0.9 224 1231 581 1053 497 790 373 570 269
1 249 1052 496 850 401 678 320 488 230
*9UHX100L20 (1)(2) * Denotes Brand
Exterrnal Static Pressure
(in wc/Pa)
Speed
Tap HI MED H MED L LO
in wc Pa CFM L/s CFM L/s CFM L/s CFM L/s
0.1 25 2240 1057 2137 1008 1993 941 1820 859
0.2 50 2163 1021 2062 973 1934 913 1768 834
0.3 75 2083 983 1992 940 1872 883 1722 813
0.4 100 2002 945 1916 904 1801 850 1656 782
0.5 125 1912 902 1833 865 1723 813 1590 750
0.6 149 1821 859 1745 824 1636 772 1513 714
0.7 174 1727 815 1654 781 1547 730 1426 673
0.8 199 1618 764 1551 732 1437 678 1325 625
0.9 224 1502 709 1430 675 1315 621 1199 566
1 249 1356 640 1275 602 1159 547 1047 494
MAX CFM’s for Factory Washable Filters
Filter Size (in/mm) CFM L/s
14″X 25″/ 356 x 635 1400 661
16″X 25″/ 406 x 635 1600 755
20″X 25″/ 508 x 635 2000 944
24″X 25″/ 610 x 635 2500 1180
Max CFM based on 600 FPM (3.0 m/s)
NOTE: Disposable filters are typically rated at 300 FPM (1.5 m/s). These filters