Always On P.O.S. Pro 600VA User manual

M1701_POS_Pro_Manual V1.0 2012-06-12
P.O.S. Pro-Series – Single Phase Input, Single
Phase Output
Uninterruptible Power Supply
P.O.S. Pro 600VA
Line Interactive UPS (PWM): 600VA with Integrated DC Power
Supply
User’s Manual

M1701_POS_Pro_Manual V1.0 2012-06-12
SAVE THESE INSTRUCTIONS
This manual contains important instructions for the P.O.S. Pro 600va UPS, and should be
followed during installation and maintenance of the UPS and batteries.
The UPS contains voltages that are potentially hazardous. Please contact our dealers or
qualified personnel for service.
Servicing of the batteries should be performed or supervised by personnel knowledgeable
with batteries and the required precautions. Keep unauthorized personnel away from
batteries.
When replacing batteries, replace with the same model number, type and rating.
CAUTION: Do not dispose of battery or batteries in a fire. The batteries may explode.
CAUTION: Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to the skin and eyes. It may be toxic.
CAUTION: A battery can present a risk of electrical shock and high short circuit current.
The following precautions should be observed when working on or with the batteries.
−Remove watches, rings, or other metal objects.
−Use tools with insulated handles.
−Wear rubber gloves and boots.
−Do not lay tools or metal parts on top of batteries.
−Disconnect charging source prior to connecting or disconnecting battery terminals.
−Determine if the battery is inadvertently grounded. If inadvertently grounded,
remove source of ground. Contact with any part of a grounded battery can result in
electric shock. The likelihood of a shock will be reduced if grounds are removed
during installation and maintenance (applicable to a UPS and a remote battery
supply not having a grounded supply circuit).
•CAUTION: To ensure the safety and performance of the UPS, never load the UPS with a
hair dryer, heater, laser printer or other types of inductive loads.

SAFETY INSTRUCTIONS
1. The UPS has its own internal energy source (battery), therefore the output receptacles may
have electricity present even though the UPS is disconnected from the utility power.
2. The DC voltage provided from the internal battery is 12VDC.
3. Isolated Ground Wire refers to the bare wire connecting electrical equipment to
ground. The isolated ground wire (green or green with yellow stripe) must meet
national wire requirements.
4. The power plug to connect with the UPS has to be equipped with a ground plug.
5. Battery must be replaced or serviced by qualified, knowledgeable, personnel.
6. Replacement battery must be the type, quantity and configured the same as the
original(s).
7. To avoid explosions, keep open flame and other heat emitting sources away from
battery.
8. Do not disassemble or damage the battery. The electrolyte is toxic and especially
harmful to the eyes and skin.
9. The battery contains high voltages and currents that are dangerous. To maintain
secure operation and performance of the UPS, the user must exercise basic and
regular maintenance. Please follow the precautions below:
1. Do not remove the UPS cover unless authorized by factory. Removing the
cover will void the warranty.
2. The UPS can only be connected to a 2-pole/3-wire plug.
3. Do not install the UPS in an environment with excessive humidity.
4. Do not allow liquids or foreign objects to get inside the UPS.
5. Allow for air circulation through the UPS. A minimum clearance of 10cm is
required on all sides.
6. Do not load the UPS with appliances such as a hair dryer, heater, vacuum,
kettle, etc.
7. Keep the UPS away from direct sunlight and heat-emitting sources.
8. Install the UPS as close as possible to the load for maximum protection.
10. Storage Requirements
1. Recharge the UPS batteries every 6 months for no less than 8 hours at a time.
2. Under a high ambient temperature environment, recharge the UPS batteries
every 3 months for no less than 8 hours at a time
11. High Voltage Risk:
1. High voltages might exist between the battery terminal and the grounding
system, if the battery circuit has not been disconnected from the UPS circuit.
Please check this voltage before connecting.
2. Disconnect the battery wires before proceeding with maintenance. High
voltages may be present between the UPS internal components and battery
even after the input power is disconnected.
M1701_POS_Pro_Manual V1.0 2012-06-12

M1701_POS_Pro_Manual V1.0 2012-06-12
Table of Contents
1. INTRODUCTION 1
2. PRESENTATION 2
3. INSTALLATION 3
3.1. Unpacking and Inspection 3
3.2. Placement 3
3.3. Connect to Utility 3
3.4. Charging the Battery 3
3.5. Connecting the Loads 3
3.6. Storage Conditions 4
3.7. Extended Storage 4
4. OPERATION 5
4.1. Switching “On” the UPS 5
4.2. Switching “Off” the UPS 5
4.3. Self-Test 5
4.4. Silence the Alarm 5
4.5. Cold Start 5
4.6. Shutdown Mode 5
4.7. Green Function 6
4.8. Back-Up (Slow Alarm) 6
4.9. Low Battery (Rapid Alarm) 6
4.10. Overload (Continuous Alarm) 6
4.11. Replace Battery (Continuous Alarm) 6
5. BATTERY REPLACEMENT 7
6. TROUBLESHOOTING 8
6.1. General Problems 8
7. SPECIFICATIONS 9
7.1. DC Power Supply Specifications: 10
8. CONTACT INFORMATION 11
8.1. Additional Purchases or Upgrades 11
8.2. QA / Warranty Questions 11
8.3. Software Questions 11

M1701_POS_Pro_Manual V1.0 2012-06-12 1
1. INTRODUCTION
The P.O.S. Pro-Series is a Line Interactive UPS system that includes the newest and
latest technology enhancements. The Line Interactive technology with AVR function
(on-line voltage boost-up & buck-down) allows for a wide input voltage range of 90
to 150VAC. The P.O.S. Pro-Series UPS is ideal protection for modern Point of Sale
equipment. After the UPS has been turned “On” it will protect the load from
transients, spikes and other power aberrations. In the event of a blackout (or severe
brownout) the UPS will automatically switch to back-up mode and maintain power to
the load until the battery reaches a low voltage state. Also included with our UPS
system is a cyclic self-testing function to verify both the operation of the UPS and the
condition of the battery.
The integrated DC power supply and multiple outlet configuration allows for
complete versatility for today’s Point of Sale equipment. The adapter cord included
with every P.O.S. Pro is designed to plug directly into the printer and provide back-
up power in the event of utility loss.
Interference to Radio/TV
If this UPS causes interference to radio or television reception (this may be
determined by turning the UPS off and on), try to correct the interference by one or
more of the following measures:
1. Connect the equipment to an outlet on a different circuit from which the
receiver is connected.
2. Increase the separation between the equipment and the receiver.
3. Re-orientate the receiving antenna.

M1701_POS_Pro_Manual V1.0 2012-06-12 2
2. PRESENTATION
2.1 Front Panel
1. Multi purpose LED
This LED will be solid greed when the UPS is under normal
conditions. It will flash every two seconds when the UPS is
supplying battery power to the loads, and flash rapidly when
the battery requires replacement.
2. “ON/OFF/TEST/SILENCE” button
Press and hold the button for more than 3 seconds to turn the
UPS “ON” or “OFF”, press and hold the button less than 1
second to activate a self-test, or silence the back up alarm.
2.2 Rear Panel
3. DC printer cable
4. AC input power cord
1
2
3
4
5
67
5. Input breaker
6. Surge protected - output power receptacles
7. Backed Up - output power receptacles

M1701_POS_Pro_Manual V1.0 2012-06-12 3
3. INSTALLATION
3.1. Unpacking and Inspection
Examine the packaging for damage. Inform the carrier immediately if
and/or when damage is noticed. Retain the packaging for future use.
3.2. Placement
Install the UPS in a protected area with adequate airflow and free of
excessive dust. Do not operate the UPS where the temperature and
humidity is outside the specified limits.
3.3. Connect to Utility
Connect the AC input power connector (Included) to utility power.
3.4. Charging the Battery
The UPS charges its battery whenever the UPS is in LINE mode. For best
results, charge the battery for 4 hours initially before connecting the load.
3.5. Connecting the Loads
Plug the loads into the output connectors on the rear of the UPS. To use
the UPS as a master on/off switch, make sure all of the loads plugged into
the UPS are switched on.
Caution:
Never connect a laser printer or plotter to the UPS with other computer
equipment. A laser printer or plotter draws significantly more power on
start-up than when idle, and will overload the UPS. If a laser printer
or plotter requires protection against blackouts, brownouts and over-
voltage the UPS needs to be increased in size to accommodate the
inrush o
f
p
ower.

M1701_POS_Pro_Manual V1.0 2012-06-12 4
Caution:
The line current limiting feature could be rendered inoperable if
improperly installed. Make sure that the line from the wall is plugged
into the connector marked “IN”, and the device to be protected
(telephone, modem, etc.) is plugged into the connector marked “OUT”.
This surge protection device is for indoor use only; never install wiring
during a lightning storm.
3.6. Storage Conditions
Store the UPS covered and upright in a cool, dry location, with its battery
fully charged. Before storing, charge the UPS for at least eight (8) hours.
Remove any accessories in the accessory slot and disconnect any cables
connected to the computer interface port to avoid the unnecessary draining
of the battery.
3.7. Extended Storage
During extended storage periods in environments where the ambient
temperature is -15 to +30°C (+5 to +86°F), charge the UPS‘s battery every
6 months.
During extended storage in environments where the ambient temperature
is +30 to +45°C (+86 to +113°F), charge the UPS‘s battery every 3
months.

M1701_POS_Pro_Manual V1.0 2012-06-12 5
4. OPERATION
4.1. Switching “On” the UPS
With the UPS plugged in and utility power present, press and hold the
On/Off/Test/Silence Button more than 3 seconds or until the LED is lit.
The UPS will perform self-testing each time it is switched “On”.
4.2. Switching “Off” the UPS
Press and hold the On/Off/Test/Silence Button for more than 3 seconds, or
until the Line Normal or Back-Up LED turns off.
ATTENTION:In backup mode, the UPS can be automatically turned off
if none of the connected loads are operating. (Green mode; No Load shut
down function) Once the utility power returns to normal, the unit will
restart.
4.3. Self-Test
Use the self-test to verify both the operation of the UPS and the condition
of the battery. When normal utility power is present, push the
On/Off/Test/Silence Button for less than 1 second and the UPS will
perform a self-test function. During the self-test, the UPS operates in
back-up mode.
During the self-test, the UPS briefly operates the loads with battery
power (the LED flashes every 2 seconds). If the UPS passes the self-
test, it returns to on-line operation. The LED stops flashing and the
LED remains on. If the UPS fails the self-test it immediately returns
to on-line operation. The loads are unaffected when performing a
self-test. Recharge the battery overnight and perform the self-test
again. If the UPS still fails a self-test, ask our nearest dealer to
replace the battery.
4.4. Silence the Alarm
In Back Up mode, push On/Off/Test/Silence Button for less than 1 second
to silence the audible alarm. (The function is void when under condition of
"LOW BATTERY" or "OVERLOAD")
4.5. Cold Start
When the UPS is off and there is no utility power, use the cold start
feature to apply power to the loads from the UPS's battery. Press the
ON/TEST button (see Front Panel section for location of the indicator)
until the UPS beeps.
4.6. Shutdown Mode
In shutdown mode the UPS stops supplying power to the load and waits
for the return of utility power.

M1701_POS_Pro_Manual V1.0 2012-06-12 6
4.7. Green Function
If the connected loads are drawing less than 20 watts, the UPS will
automatically shutdown after 5 minutes in back-up mode in order to
conserve battery power.
To disable “GREEN FUNCTION” press and hold the “On” button during
initial start-up for at least 3 seconds, until a beep-beep sound is heard.
AUDIBLE ALARM
4.8. Back-Up (Slow Alarm)
When in back-up mode, the LED flashes every 2 seconds and the UPS
sounds an audible alarm. The alarm stops when the UPS returns to line
normal operation. Press the On/Off/Test/Silence Button during back-up
mode to silence the beeping.
4.9. Low Battery (Rapid Alarm)
In back-up mode, when the battery energy runs low, the UPS beeps
rapidly until the UPS shuts down from battery exhaustion or returns to line
normal operation.
4.10. Overload (Continuous Alarm)
When the UPS is overloaded (the connected load exceeds the maximum
rated capacity of the UPS) the UPS sounds a continuous alarm to warn of
an overload condition. Disconnect non-essential loads until the UPS stops
the alarm.
4.11. Replace Battery (Continuous Alarm)
The UPS emits a continuous beep if the battery fails the self-test. See
replace battery section for battery replacement or call your dealer for
services.

M1701_POS_Pro_Manual V1.0 2012-06-12 7
5. BATTERY REPLACEMENT
1. Your battery should run anywhere from 3-5 years before it needs to be
replaced.
2. Please follow the instructions below for easy, trouble free, battery replacement.
3. Turn the UPS off (follow procedure previously mentioned)
4. Unplug the UPS from utility power source and disconnect all connected loads.
5. Disconnect AC power cord from unit.
6. Turn unit upside down and using a Phillips screwdriver, unscrew the four (4)
screws holding the top of the unit to the bottom. Put screws in a safe place for
reconnection.
7. Holding the top together firmly with the bottom, turn the entire unit right side
up.
8. Carefully lift top cover off and place it to the side. The connecting wires and
electronics will be exposed. Be careful not to touch any inner components
when changing the battery.
9. Remove the two (2) connecting wires from the battery.
10. You can now easily remove the battery from the unit
11. Place your new battery in the same position, direction and reconnect the wires.
The red wire to the positive (+) pole and black wire to the negative (-) pole.
12. Reverse steps 5, 4 and 3 (in that order) to reassemble the unit.
13. Follow start-up instructions in order to properly reconnect your equipment.
Caution:
Do not dispose of battery in a fire. Do not attempt to open the battery.
When replacing the battery use tools with insulated handles and
remove watches, rings, etc…

M1701_POS_Pro_Manual V1.0 2012-06-12 8
6. TROUBLESHOOTING
Please follow the guidelines below for common problems:
9Check UPS input plug and wiring.
9Check UPS input voltage.
Please prepare the information as follows for service personnel:
9UPS model number and serial number
9Description of problem(s) in detail.
6.1. General Problems
Problems Possible causes Solution
UPS has no reaction while
AC power is connected
Breaker at back panel open
No AC input
UPS fault
Battery failure
Replace Fuse/Switch breaker on
Check AC power
Call for service
Call service center to replace batteries
UPS has no reaction while
AC power is connected, yet
starts after pushing power
on/off switch
Breaker at back panel open
No AC input
UPS AC detecting circuit fail
Switch breaker
Check AC power
Call for service
UPS goes into back-up mode
while connected to AC power
Utility voltage or frequency
abnormal
UPS AC detecting circuit failure
Check AC power
Call for service
Battery can not provide
normal back-up power in the
event of a blackout
Battery deteriorated
Batteries not fully charged
Battery charger damaged
Charge batteries and reset
If that doesn’t work call for service
Fault LED lit
Inverter fault
Over temperature
Battery over voltage
DC bus fault
Overload fault
Call for service
Check load status
After AC connected to UPS,
alarm sounds short and fast
beeps and UPS shuts down Abnormal utility power Check input power

M1701_POS_Pro_Manual V1.0 2012-06-12 9
7. SPECIFICATIONS
M
ODEL P.O.S. Pro 600
I
NPUT
C
apacity 600VA
V
oltage 120V, 220V +/-25%
F
requency 50 or 60Hz +/-10% (auto sensing)
O
UTPUT
V
oltage (on battery) Simulated sine wave at Line Input +/-5%
F
requency (on battery) 50 or 60Hz +/- 1Hz
D
C Outpu
t
24V/1.5A (24VDC Printer cord)
A
uto Voltage Regulation
A
VR ±13% of nominal (120V)
T
ransfer Time 2/4 milliseconds, including detection time
P
ROTECTION and
F
ILTERING
Spike Protection 480 joules, 2ms
O
verload Protection UPS automatic shutdown if overload exceeds 110% of
nominal for 60 second or 130% for 3 seconds.
U
nit Inpu
t
Fuse or circuit breaker for overload & short circuit
protection
Short Circuit UPS output cut off immediately or input fuse protection
B
ATTERY
T
ype Maintenance-free, Sealed Lead Acid
T
ypical Recharge Time 6 hours (to 90% of full capacity)
P
rotection Automatic self-test & discharge protection, replace
battery indicator
B
ac
k
-up Time 20 - 30 minutes (depending on load)
P
HYSICAL
N
et Weight kg(lbs) 6.8 (15 lbs.)
Shipping Weight kg(lbs) 7.3 (16 lbs.)
D
imension (mm)WxDxH 97x320x135 (3.8” X 12.5” X 5.3”)
I
nput Inle
t
Nema 5-15P power inlet
O
utpu
t
5 X Nema 5-15R (3 output power, 2 surge protection
only) +1 DC printer power connector
A
LARM
B
attery Bac
k
-Up Slow beeping sound (about 0.47Hz)
B
attery Low Rapid beeping sound (about 1.824Hz)
O
verload Continuous beeping sound
C
ONFORMANCE Safety cUL UL1778, CSA C22.2 and FCC Class B
Surge IEEE C62.41 CAT. A
E
NVIRONMENT
A
mbient Operation 6,000 meters max. elevation, 0-95% humidity non-
condensing 0-40°C
A
udible noise <40dBA (1 meter from surface)

M1701_POS_Pro_Manual V1.0 2012-06-12 10
Storage Condition 15000 meters max. elevation
Specifications subject to change without prior notice to reflect upgrades and improvements in technology.
7.1. DC Power Supply Specifications:
Output Voltage: 24VDC
Regulation: +/- 1%
Ripple and Noise: <150mV
Rated Current: 1.5A Continuous, 2A Surge
Capacity: 58 Watts
Protection: Overload, Over Voltage, Short Circuit
+DC GND
-DC
1. DC POWER CONNECTOR CONFIGURATION

M1701_POS_Pro_Manual V1.0 2012-06-12 11
8. CONTACT INFORMATION
8.1. Additional Purchases or Upgrades
Always On UPS Systems Inc.
Bldg 1 – 150 Campion Road,
Kelowna, BC, Canada, V1X 7S8
Phone: (250) 491-9777 Ext 451
Fax: (250) 491-9775
Email: [email protected]
Website: www.alwayson.com
8.2. QA / Warranty Questions
Always On UPS Systems Inc.
Bldg 1 – 150 Campion Road,
Kelowna, BC, Canada, V1X 7S8
Phone: (250) 491-9777 Ext 209
Fax: (250) 491-9775
Email: [email protected]
Website: www.alwayson.com
8.3. Software Questions
Always On UPS Systems Inc.
Bldg 1 – 150 Campion Road,
Kelowna, BC, Canada, V1X 7S8
Phone: (250) 491-9777 Ext 204
Fax: (250) 491-9775
Email: [email protected]
Website: www.alwayson.com
Table of contents
Other Always On UPS manuals