INSTALLATION MANUAL
AIR CONDITIONER
INDOOR UNIT
Compact Cassette Type
hcstueDsiaçnarFloñapsEonailatIάkIvηλλEsêugutroP hsilgnE
eçkrüT йикссуР
PART NO. 9379124010-05
9379124010-05_IM.indb COVER19379124010-05_IM.indb COVER1 8/31/2012 10:41:42 AM8/31/2012 10:41:42 AM
AMP Air Conditioning

En-1
1. SAFETY PRECAUTIONS
Be sure to read this• Manual thoroughly before installation.
The warnings and precautions indicated in this Manual contain important information per-• taining to your safety. Be sure to observe them.
Hand this Manual, together with the Operating Manual, to the customer. Request the cus-• tomer to keep them on hand for future use, such as for relocating or repairing the unit.
WARNING This mark indicates procedures which, if improperly per-
formed, might lead to the death or serious injury of the user.
Request your dealer or a professional installer to install the indoor unit in accordance
with this Installation Manual. An improperly installed unit can cause serious accidents
such as water leakage, electric shock, or fire. If the indoor unit is installed in disregard of
the instructions in the Installation Manual, it will void the manufacturer’s warranty.
Do not turn ON the power until all work has been completed. Turning ON the power
before the work is completed can cause serious accidents such as electric shock or fire.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant
comes in contact with a flame, it produces a toxic gas.
Installation work must be performed in accordance with national wiring standards by
authorized personnel only.
CAUTION This mark indicates procedures which, if improperly per-
formed, might possibly result in personal harm to the user, or
damage to property.
Read carefully all security information before use or install the air conditioner.
Do not attempt to install the air conditioner or a part of the air conditioner by yourself.
This unit must be installed by qualified personnel with a capacity certificate for handling
refrigerant fluids. Refer to regulation and laws in use on installation place.
The installation must be carried out in compliance with regulations in force in the place
of installation and the installation instructions of the manufacturer.
This unit is part of a set constituting an air conditioner. It must not be installed alone or
with non-authorized by the manufacturer.
Always use a separate power supply line protected by a circuit breaker opera-ting on all
wires with a distance between contact of 3mm for this unit.
The unit must be correctly earthed (grounded) and the supply line must be equipped
with a differential breaker in order to protect the persons.
The units are not explosion proof and therefore should not be installed in explosive
atmosphere.
Never touch electrical components immediately after the power supply has been turned
off. Electric shock may occur.After turning off the power, always wait 5 minutes before
touching electrical components.
This unit contains no user-serviceable parts. Always consult authorized service person-
nel to repairs.
When moving, consult authorized service personnel for disconnection and installation
of the unit.
This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the appliance by a
person responsible for their safety. Children should be supervised to ensure that they do
not play with the appliance.
2. ABOUT THE UNIT
2.1. Precautions for using R410A refrigerant
WARNING
Do not introduce any substance other than the prescribed refrigerant into the refrigera-
tion cycle. If air enters the refrigeration cycle, the pressure in the refrigeration cycle will
become abnormally high and cause the piping to rupture.
If there is a refrigerant leak, make sure that it does not exceed the concentration limit.
If a refrigerant leak exceeds the concentration limit, it can lead to accidents such as
oxygen starvation.
Do not touch refrigerant that has leaked from the refrigerant pipe connections or other
area. Touching the refrigerant directly can cause frostbite.
If a refrigerant leak occurs during operation, immediately vacate the premises and thor-
oughly ventilate the area. If the refrigerant comes in contact with a flame, it produces a
toxic gas.
2.2. Special tool for R410A
WARNING
To install a unit that uses R410A refrigerant, use dedicated tools and piping materi-
als that have been manufactured specifically for R410A use. Because the pressure of
R410A refrigerant is approximately 1.6 times higher than the R22, failure to use dedi-
cated piping material or improper installation can cause rupture or injury. Furthermore, it
can cause serious accidents such as water leakage, electric shock, or fire.
Tool name Changes
Gauge manifold
The pressure in the refrigerant system is extremely
high and cannot be measured with a conventional
gauge. To prevent erroneous mixing of other refriger-
ants, the diameter of each port has been changed. It
is recommended to use a gauge manifold with a high
pressure display range of –0.1 to 5.3 MPa and a low
pressure display range of –0.1 to 3.8 MPa.
Charging hose
To increase pressure resistance, the hose material
and base size were changed.
(The charging port thread diameter for R410A is 1/2
UNF 20 threads per inch.)
Vacuum pump
A conventional vacuum pump can be used by install-
ing a vacuum pump adapter.
Be sure that the pump oil does not back flow into
the system. Use one capable for vacuum suction of
–100.7 kPa (5 Torr, –755 mmHg).
Gas leakage detector Special gas leakage detector for R410A refrigerant.
2.3. Accessories
WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or other
prescribed parts.
The use of non-prescribed parts can cause serious accidents such as the unit to fall,
water leakage, electric shock, or fire.
The following installation parts are furnished. Use them as required.• Keep the Installation Manual in a safe place and do not discard any other accessories• until the installation work has been completed.
Contents
1. SAFETY PRECAUTIONS...........................................................................................1
2. ABOUT THE UNIT......................................................................................................1
2.1. Precautions for using R410A refrigerant...........................................................1
2.2. Special tool for R410A......................................................................................1
2.3. Accessories.......................................................................................................1
2.4. Cassette grille accessories...............................................................................2
2.5. Optional parts....................................................................................................2
3. INSTALLATION WORK..............................................................................................2
3.1. Selecting an installation location.......................................................................2
3.2. Installation dimension.......................................................................................3
3.3. Installation the unit............................................................................................3
4. PIPE INSTALLATION.................................................................................................5
4.1. Selecting the pipe material................................................................................5
4.2. Pipe requirement...............................................................................................5
4.3. Flare connection (pipe connection)...................................................................5
4.4. Installing heat insulation....................................................................................6
5. ELECTRICAL WIRING...............................................................................................6
5.1. Wiring system diagram .....................................................................................7
5.2. Connection cable preparation...........................................................................8
5.3. Connection of wiring.........................................................................................8
6. REMOTE CONTROLLER SETTING..........................................................................8
6.1. Load batteries (R03/LR03 ×2) .........................................................................8
6.2.
Installing the
remote controller holder................................................................9
7. CASSETTE GRILLE INSTALLATION.........................................................................9
7.1. Remove the intake grille...................................................................................9
7.2. Installing the panel to indoor unit......................................................................9
7.3. Attach the intake grille.....................................................................................10
8. FUNCTION SETTING..............................................................................................10
8.1. Operation method...........................................................................................10
8.2. Function setting...............................................................................................10
8.3. Selecting the remote controller signal code....................................................11
8.4. Special installation methods...........................................................................12
9. TEST RUN................................................................................................................14
10. CHECK LIST ............................................................................................................14
11. OPTIONAL KIT INSTALLATION (OPTION)..............................................................14
12. CUSTOMER GUIDANCE.........................................................................................14
13. ERROR CODES.......................................................................................................15
INSTALLATION MANUAL
PART No. 9379124010-05
INDOOR UNIT (Compact Cassette Type)
9379124010-05_IM.indb 19379124010-05_IM.indb 1 8/31/2012 10:43:04 AM8/31/2012 10:43:04 AM
AMP Air Conditioning

En-2
Name and Shape Q’ty Description
Operating Manual
1
Installation Manual
1
(This book)
Coupler heat insulation (Large)
1
For indoor side pipe joint (Gas pipe)
Coupler heat insulation (Small) 1For indoor side pipe joint
(Liquid pipe)
Special nut A (Large flange)
4
For installing indoor unit
Special nut B (Small flange) 4For installing indoor unit
Template
(Carton top) 1
For ceiling openings cutting
Also used as packing
Drain hose
1
For installing drain pipe
VP25 (O.D.32, I.D.25)
Hose Band
1
For installing drain hose
Drain hose insulation
1
For installing drain pipe
Remote controller
1
For air conditioner operation
Battery 2For remote controller unit
Remote controller holder 1
For installing the remote controller
Tapping screw
(M3 × 12mm) 2For mounting the remote controller
holder
Cable-tie 2For electrical wiring
Wire clamper 1For electrical wiring
(*1) This part is not furnished forAUT* series
2.4. Cassette grille accessories
Name and Shape Q’ty Description
Connector cover
1
For covering connector
Tapping Screw
(M5 × 12 mm) 4
For mounting cassette grille
Tapping Screw
(M4 × 12 mm) 1 For mounting connector cover
L angle
2
For mounting the Hook Wire to the
Cassette grille
Hook wire 2For suspending the Cassette grille
Screw [pitch small]
(M4 × 10 mm) 2
For mounting the Hook Wire (for
metals)
Screw [pitch large]
(M4 × 10 mm) 4
For mounting the L angle and Hook
wire (for resins)
2.5. Optional parts
Parts name Model No. Summary
Wired remote controller UTY-RNN*M Unit control is performed by
wired remote controller
Simple Remote Controller UTY-RSN*M For air conditioner
operation
Air outlet shutter plate UTR-YDZB Install the plate at outlet
when carrying out 3-way
direction operation
Insulation kit for High
humidity UTZ-KXGC
External connect kit UTY-XWZX For control input/output port
Fresh air intake kit UTZ-VXAA To take fresh air
Wired remote controller is recommended using simultaneous twin or triple connection.
3. INSTALLATION WORK
Especially, the installation place is very important for the split type air conditioner because
it is very difficult to move from place to place after the first installation.
3.1. Selecting an installation location
Decide the mounting position together with the customer as follows.
WARNING
Select installation locations that can properly support the weight of the indoor unit.
Install the units securely so that they do not topple or fall.
9379124010-05_IM.indb 29379124010-05_IM.indb 2 8/31/2012 10:43:06 AM8/31/2012 10:43:06 AM
AMP Air Conditioning

En-3
CAUTION
Do not install the indoor unit in the following areas:
Area with high salt content, such as at the seaside. It will deteriorate metal parts,• causing the parts to fail or the unit to leak water.
Area filled with mineral oil or containing a large amount of splashed oil or steam, such• as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit to leak
water.
Area that generates substances that adversely affect the equipment, such as sulfuric• gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to
corrode, which can cause refrigerant leakage.
Area that can cause combustible gas to leak, contains suspended carbon fibers or• flammable dust, or volatile inflammables such as paint thinner or gasoline. If gas leaks
and settles around the unit, it can cause a fire.
Area where animals may urinate on the unit or ammonia may be generated.•
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or flammable gas.
Install the indoor unit, outdoor unit, power supply cable, transmission cable, and remote
control cable at least 1 m away from a television or radio receivers. The purpose of this
is to prevent TV reception interference or radio noise. (Even if they are installed more
than 1 m apart, you could still receive noise under some signal conditions.)
If children under 10 years old may approach the unit, take preventive measures so that
they cannot reach the unit.
Install the indoor unit in a location having sufficient strength to support the weight of(1) the indoor unit.
The inlet and outlet ports should not be obstructed; the air should be able to blow all(2) over the room.
Leave the space required to service the air conditioner.(3) Locate where the air can be distributed evenly throughout the room by the unit.(4) Install the unit where connection to the outdoor unit is easy.(5) Install the unit where the connection pipe can be easily installed.(6) Install the unit where the drain pipe can be easily installed.(7) Install the unit where noise and vibration is not amplified.(8) Take servicing, etc., into consideration and leave the spaces. Also install the unit(9) where the filter can be removed.
3.2. Installation dimension
The ceiling rear height as shown in the figure.•
Strong and durable ceiling
262
or more
1,000
or more
1,800
or more
1,000
or more
Unit : mm
Floor
Obstruction
This product can be installed at a height of up to 3,000mm.• However, 7000, 9000 Btu/h model can not be installed in high places.
Perform the Function Setting on the remote control in accordance with the installed height.
(See 8.2.Function setting)
Discharge direction setting
The discharge direction can be selected as shown below.•
100 or more*
(4 directions) (3 directions)
Unit : mm
*Please ensure
sufficient
service access
during installation.
For a 3-way outlet, make sure to perform the Function Setting on the remote control.• Also, make sure to use the optional shutter plate to block the outlet.
The ceiling height cannot be set in the 3-way outlet mode. Therefore, do not change the• setting in the setting the ceiling height. (See 8.2. FUNCTION SETTING)
When the outlet is shut, be sure to install the optional Air outlet shutter plate kit.• For the details of installation, please refer to Installation Manual of kit.
3.3. Installation the unit
WARNING
Install the air conditioner in a location which can withstand a load of at least 5 times the
weight of the main unit and which will not amplify sound or vibration. If the installation
location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will come loose.
Please take care.
3.3.1. Position the ceiling hole and hanging bolts
Ceiling openings and hanging bolt installation diagram.
WARNING
When fastening the hangers, make the bolt positions uniform.
530 (Hanging bolt position)
service access
250
99
40
102
215
30
58
123
114
30
262
250
75
150~200
Drain pipe (O.D.ø26.1)
Ceiling
Control box
Liquid pipe Gas pipe
Unit : mm
540 (Hanging bolt position)
570(Indoor unit)
580 – 660 (Ceiling openings)
700 (Cassette Grille)
Min.450
Min.450
Be sure to keep sufficient space in the designated position for future maintenance.
3.3.2. Body installation
(1) Install special nut A, then special nut B onto the hanging bolt.
(2) Raise the body and mount its hooks onto the hanging bolt between the special nuts.
(3)Turn special nut B to adjust the height of the body.
WARNING
Perform final tightening by tightening the double nut firmly.
Be sure to install the body horizontally and adjust the height below the body and the
ceiling surface properly.
9379124010-05_IM.indb 39379124010-05_IM.indb 3 8/31/2012 10:43:17 AM8/31/2012 10:43:17 AM
AMP Air Conditioning

En-4
Special nut A
After installing the
body, tighten the nuts.
Hook
Ceiling Unit : mm
30
or more
Special nut B
Hanging bolt
3.3.3. Leveling
Using a level, or vinyl hose filled with water, fine adjust so that the body is level.
Inclined installation so as the drain pipe side is higher may cause a malfunction of the float
switch, and may cause water leakage.
Vinyl hoses
Drain pipe
3.3.4. Installing drain pipe
WARNING
Do not insert the drain piping into the sewer where sulfurous gas occurs. (Heat ex-
change erosion may occur)
Insulate the parts properly so that water will not drip from the connection parts.
Check for proper drainage after installation by using the visible portion of transparent
drain port and the drain piping final outlet on the body.
CAUTION
Do not apply adhesive agent on the drain port of the body. (Use the attached drain
hose assembly to connect the drain piping)
Note: Install the drain pipe.
• Install the drain pipe with downward gradient (1/50 to 1/100) and so there are no rises or
traps in the pipe.
• Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32mm] and connect it
with adhesive (polyvinyl chloride) so that there is no leakage.
• When the pipe is long, install supporters.
• Do not perform air bleeding.
• Always heat insulate indoor section of drain pipe.
•
If it is impossible to have sufficient gradient of pipe, perform drain lift-up.
Pipe size
Drain pipe VP25 (O.D. 32 mm)
Hanging fittings 1.5 to 2 m
VP25 (O.D. 32 mm)
Downward gradient 1/100 to 1/50
Rise
PROHIBITED:
Trap Air bleeding
When lifting up drain:
• Height of inclined pipe should be less than 700 mm from the ceiling. A rise dimension
over this range will cause leakage.
• Lift up the pipe vertically at the position of 300 mm or less from the unit.
300 mm or less
VP25 (O.D. 32 mm)
local arrangement
700 mm or less
Horizontal or
upward gradient
Downward gradient
1/100 to 1/50
VP30 (O.D. 38 mm) or more
Downward gradient 1/100 to 1/50
700 mm or less
Installation procedure
1) Install the attached drain hose to the drain port of the body. Install the hose band from
the top of the hose within the shown in the figure area.
2) Use vinyl adhesive agent to glue the drain piping (PVC pipe VP25 ) to the drain hose
assembly.
(Apply color adhesive agent evenly until the gauge line and seal)
3) Check the drainage. (See separate diagram)
4) Install the heat insulation.
5) Use the attached heat insulation to insulate the drain port and hose band.
Install the knob facing upward
Attach hose band
(Accessories)
Locally installed
PCV pipe
Attach drain hose
(Accessories)
Attach heat insulation
(Accessories)
・
(a) Top view
(c) Hose opening view
Top view
(b) Side view
Hose band
19
Applying area
of adhesive 35
Unit: mm
Gauge line
4 or less
20 Transparent
visible portion
Make sure there
are no gaps
Wind the attached heat insulation
around the hose band
Make sure the alignment is
on top
5~10
20
Note)
Check for drainage
Pour about 1 liter of water from the position (see 9. TEST RUN/CHECKING DRAINAGE).
Check for any abnormalities such as strange noises and whether the drain pump functions
normally
9379124010-05_IM.indb 49379124010-05_IM.indb 4 8/31/2012 10:43:18 AM8/31/2012 10:43:18 AM
AMP Air Conditioning

En-5
4. PIPE INSTALLATION
CAUTION
Be careful that foreign matter (oil, water, etc.) does not enter the piping with refrigerant
R410A models. Also, when storing the piping, securely seal the openings by pinching,
taping, etc.
While brazing the pipes, be sure to purge with dry nitrogen gas.
4.1. Selecting the pipe material
CAUTION
Do not use existing pipes.
Use pipes that have clean external and internal sides without any contamination which
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil or water.
It is necessary to use seamless copper pipes.
Material: Phosphor deoxidized seamless copper pipes.
It is desirable that the amount of residual oil is less than 40 mg/10 m.
Do not use copper pipes that have a collapsed, deformed, or discolored portion (es-
pecially on the interior surface). Otherwise, the expansion valve or capillary tube may
become blocked with contaminants.
Improper pipe selection will degrade performance. As an air conditioner using R410A
incurs pressure higher than when using conventional refrigerant, it is necessary to
choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in the table.• Never use copper pipes thinner than those indicated in the table even if they are available• on the market.
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter [mm (in.)] Thickness [mm]
6.35 (1/4) 0.80
9.52 (3/8) 0.80
12.70 (1/2) 0.80
15.88 (5/8) 1.00
19.05 (3/4) 1.20
4.2. Pipe requirement
CAUTION
Refer to the Installation Manual of the outdoor unit for description of the length and the
diameter of connecting pipe or for difference of its elevation.
Use pipe with water-resistant heat insulation.•
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause
water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is
expected to exceed 70%, install heat insulation around the refrigerant piping. If the
expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if
the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker. If
heat insulation is used that is not as thick as specified, condensation may form on the
surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045W/(m·K) or less (at 20 °C).
4.3. Flare connection (pipe connection)
4.3.1. Flaring
Use special pipe cutter and flare tool exclusive for R410A.•
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3) Insert the flare nut (always use the flare nut attached to the indoor and outdoor units
respectively) onto the pipe and perform the flare processing with a flare tool. Leakage
of refrigerant may result if other flare nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from
entering the pipes.
B
AL
Check if [L] is flared uniformly
and is not cracked or scratched.
Die
Pipe
Pipe outside diameter
[mm (in.)]
Dimension A [mm] Dimension B-0
0.4 [mm]
Flare tool for R410A,
clutch type
6.35 (1/4)
0 to 0.5
9.1
9.52 (3/8) 13.2
12.70 (1/2) 16.6
15.88 (5/8) 19.7
19.05 (3/4) 24.0
When using conventional flare tools to flare R410A pipes, the dimension A should be ap-
proximately 0.5 mm more than indicated in the table (for flaring with R410A flare tools) to
achieve the specified flaring. Use a thickness gauge to measure the dimension A.
Width across
flats Pipe outside diameter
[mm (in.)] Width across flats of
Flare nut [mm]
6.35 (1/4) 17
9.52 (3/8) 22
12.70 (1/2) 26
15.88 (5/8) 29
19.05 (3/4) 36
4.3.2 Bending pipes
If pipes are shaped by hand, be careful not to collapse them.• Do not bend the pipes at an angle more than 90°.• When pipes are repeatedly bend or stretched, the material will harden, making it difficult• to bend or stretch them any more.
Do not bend or stretch the pipes more than 3 times.•
CAUTION
To prevent breaking of the pipe, avoid sharp bends.
If the pipe is bent repeatedly at the same place, it will break.
4.3.3. Pipe connection
CAUTION
Be sure to connect the pipe against the port on the indoor unit and the outdoor unit cor-
rectly. If the centering is improper, the flare nut cannot tightened smoothly. If the flare nut
is forced to turn, the threads will be damaged.
Do not remove the flare nut from the indoor unit pipe until immediately before connecting
the connection pipe.
Do not use mineral oil on flared part. Prevent mineral oil from getting into the system as
this would reduce the lifetime of the units.
(1) Detach the caps and plugs from the pipes.
(2) Center the pipe against the port on the indoor unit, and then turn the flare nut by hand.
Connection pipe
(Gas)
Connection pipe
(Liquid)
Indoor unit
(3) When the flare nut is tightened properly by your hand, hold the body side coupling with
a separate spanner, then tighten with a torque wrench. (See the table below for the
flare nut tightening torques.
9379124010-05_IM.indb 59379124010-05_IM.indb 5 8/31/2012 10:43:20 AM8/31/2012 10:43:20 AM
AMP Air Conditioning

En-6
CAUTION
Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order to
tighten the flare nut correctly.
Tighten the flare nuts with a torque wrench using the specified tightening method. Oth-
erwise, the flare nuts could break after a prolonged period, causing refrigerant to leak
and generate a hazardous gas if the refrigerant comes into contact with a flame.
Tighten with 2 wrenches.
Holding wrench
Connection pipe
Torque wrench
Indoor unit pipe
(Body side)
Flare nut
Flare nut [mm (in.)] Tightening torque [N·m (kgf·cm)]
6.35 (1/4) dia. 16 to 18 (160 to 180)
9.52 (3/8) dia. 32 to 42 (320 to 420)
12.70 (1/2) dia. 49 to 61 (490 to 610)
15.88 (5/8) dia. 63 to 75 (630 to 750)
19.05 (3/4) dia. 90 to 110 (900 to 1,100)
4.4. Installing heat insulation
CAUTION
After checking for gas leaks (refer to the Installation Manual of the outdoor unit), per-
form this section.
Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do
so may cause water leaks.
After checking for gas leaks, insulate by wrapping insulation around the 2 parts (gas and
liquid) of the indoor unit coupling, using the Coupler Heat Insulation.
After installing the Coupler Heat Insulation, wrap both ends with vinyl tape so that there is
no gap.
Coupler heat insulation
Coupler heat
insulation
Be sure to overlap the
insulation
No gap
Body
CAUTION
Must fit tightly against body without any gap.
5. ELECTRICAL WIRING
Cable Cable size (mm2) Type Remarks
Connection cable 1.5 (MIN.) Type 60245 IEC57 3Cable+Earth (Ground),
1φ230V
Max. Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage
drop is 2% or more.
For simultaneous multi
Conductor size (mm2) Max length (m)
Bus wire 0.3 (MIN.) 500*
*This length shall be the total extended length in the system of the group.
(Total length of bus wire and remote controller cable.)
WARNING
Electrical work must be performed in accordance with this Manual by a person certified
under the national or regional regulations. Be sure to use a dedicated circuit for the unit.
An insufficient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or fire.
Before starting work, check that power is not being supplied to the indoor unit and
outdoor unit.
Use the included transmission cables and power cables or ones specified by the
manufacturer. Improper connections, insufficient insulation, or exceeding the allowable
current can cause electric shock or fire.
For wiring, use the prescribed type of wires, connect them securely, making sure that
there are no external forces of the wires applied to the terminal connections. Improp-
erly connected or secured wires can cause serious accidents such as overheating the
terminals, electric shock, or fire.
Do not modify the power cables, use extension cables, or use any branches in the wir-
ing. Improper connections, insufficient insulation, or exceeding the allowable current can
cause electric shock or fire.
Match the terminal block numbers and connection cable colors with those of the outdoor
unit or branch box. Erroneous wiring may cause burning of the electric parts.
Securely connect the connection cables to the terminal blocks. In addition, secure the
cables with wiring holders. Improper connections, either in the wiring or at the ends of
the wiring, can cause a malfunction, electric shock, or fire.
Always fasten the outside covering of the connection cable with the cable clamp. (If the
insulator is chafed, electric leakage may occur.)
Securely install the electrical box cover on the unit. An improperly installed electrical box
cover can cause serious accidents such as electric shock or fire through exposure to
dust or water.
Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit
could result.
Install a earth (ground) leakage breaker. In addition, install the earth (ground) leakage
breaker so that the entire AC main power supply is cut off at the same time. Otherwise,
electric shock or fire could result.
Always connect the earth (ground) wire.
Improper earthing (grounding) work can cause electric shocks.
Install the remote controller cable and bus wire so as not to be direct touched with your
hand.
(1) Use ring terminals with insulating sleeves as shown in the figure below to connect to
the terminal block.
(2) Securely clamp the ring terminals to the wires using an appropriate tool so that the
wires do not come loose.
(3) Use the specified wires, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-
driver that is too small, otherwise, the screw heads may be damaged and prevent the
screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table 1 for the terminal screw tightening torques.
Strip 10 mm
Sleeve
Ring terminal
Screw with
special washer Screw with
special washer
Ring terminal Ring
terminal
Wire
Wire
Terminal block
Terminal
board
Table 1
Tightening torque
M4 screw 1.2 to 1.8 N·m (12 to 18 kgf·cm)
WARNING
Use crimp-type terminals and tighten the terminal screws to the specified torques,
otherwise, abnormal overheating may be produced and possibly cause heavy
damage inside the unit.
9379124010-05_IM.indb 69379124010-05_IM.indb 6 8/31/2012 10:43:21 AM8/31/2012 10:43:21 AM
AMP Air Conditioning

En-7
5.1. Wiring system diagram
Connection diagrams
R
W
B
**
Standard pair
Indoor unit
Indoor unit
Indoor unit Remote controller cable
*Earth (Ground) the remote controller if it has a earth (ground) line.
Red
White
Black
Wired remote
controller
Earth (Ground) line Outdoor unit
Power line
Control line
Connection cable
Wired remote controller cable
R
W
B
**
Flexible multi
Indoor unit Outdoor unit
Indoor unit
Earth (Ground) line
Power line
Connection cable
Control line
UNITA UNIT B
Red
White
Black
Wired remote controller cable
Indoor unit
Remote controller cable
*Earth (Ground) the remote controller if it has a earth ground) line.
Wired remote
controller
Flexible multi (branch box)
Indoor unit Branch box Outdoor unit
Control line Control line
Power line Power line
Indoor unit
Earth (Ground) line
Connection cable
INDOOR UNITA
INDOOR UNIT B
OUTDOOR UNIT
R
W
B
**
Red
White
Black
Wired remote controller cable
Indoor unit
Remote controller cable
*Earth (Ground) the remote controller if it has a earth ground) line.
Wired remote
controller
R
W
B
**
Simultaneous twin (18, 22, 24 type only)
Connection cable
Indoor unit (Primary)
Indoor unit
(Secondary)
Junction box (Lo-
cal purchase) Outdoor unit
Earth (Ground) line
Control line
Power line
Earth (Ground) line
Wired remote controller cable
Indoor unit (Primary)
Indoor unit
(Secondary)
Wired remote
controller
Remote controller cable
Bus wire
(Local purchase)
Red
White
Black
*Earth (Ground) the remote controller if it has a earth (ground) line.
• Connect the remote controller wires to the primary unit.
Simultaneous triple (18 type only)
Connection cable
Indoor unit (Primary)
Indoor unit
(Secondary)
Outdoor unit
Earth (Ground) line
Control line
Power line
Junction box
(Local purchase)
Earth (Ground) line
Indoor unit
(Secondary)
9379124010-05_IM.indb 79379124010-05_IM.indb 7 8/31/2012 10:43:22 AM8/31/2012 10:43:22 AM
AMP Air Conditioning

En-8
R
W
B
**
Wired remote controller cable Wired remote
controller
Remote controller cable
Bus wire
( Local purchase )
Red
White
Black
• Connect the remote controller wires to the primary unit.
Wired remote controller is recommended using simultaneous twin or triple connection.
*Earth (Ground) the remote controller if it has a earth (ground) line.
Indoor unit (Primary)
Indoor unit
(Secondary)
Indoor unit
(Secondary)
CAUTION
Tighten the indoor unit
connection cable and power supply indoor and outdoor
unit, branch box terminal board connections firmly with the terminal board
screws. Faulty connection may cause a
fire.
If the indoor unit connection cable and power supply are wired incorrectly, the
air conditioner may be damaged.
Connect the indoor unit connection cable by matching the numbers of the outdoor,
branch box and indoor units terminal board numbers as shown in terminal label.
Earth (Ground) both the indoor and outdoor, branch box units by attaching an
earth (ground) cable.
Unit shall be earthed (grounded) in compliance with the applicable local and na-
tional cables.
CAUTION
Be sure to refer to the above diagram for do correct field wiring. Wrong wiring causes
malfunction of the unit.
Check local electrical rules and also any specific wiring instructions or limitation.
5.2. Connection cable preparation
Keep the earth (ground) wire longer than the other wires.
Power supply cable
or connection cable
20 mm
40mm or more
Earth (ground)
wire
• Use a 4-core wire cable.
5.3. Connection of wiring
(1) Remove the control box cover and install each connection wire.
Screw Control box cover
(2) After wiring is complete, secure the remote controller cable and transmission cable
with the attached the cable-tie and the clamper.
Detail(a) (a)
Wire clamper (accessory)
Bind securely
Transmission cable
Wired remote controller
cable (option)
Thread the cable-tie
through the hole and
tighten securely
cable-tie (accessory)
Cut of the excess
Wire clamper
(accessory)
Bind securely
Transmission
cable
Thread the cable-tie through
the hole and tighten securely
Wired remote
controller cable
(option)
cable-tie (accessory)
Cut of the excess
(3) Install control box cover.
CAUTION
Do not wire the remote controller cable together with or parallel to the connec-
tion cables, and power supply cables of the INDOOR UNIT and OUTDOOR UNIT,
BRANCH BOX. It may cause erroneous operation.
.
6. REMOTE CONTROLLER SETTING
Refer to the installation manual enclosed with the remote controller when the wired
remote controller (option ) is used.
6.1. Load batteries (R03/LR03 × 2)
(1) Press and slide the battery compartment lid on the reverse side to open it. Slide in the
direction of the arrow while pressing the mark.
(2) Insert batteries.
Be sure to align the battery polarities (+−) correctly.
(3) Close the battery compartment lid.
9379124010-05_IM.indb 89379124010-05_IM.indb 8 8/31/2012 10:43:24 AM8/31/2012 10:43:24 AM
AMP Air Conditioning

En-9
CAUTION
Take care to prevent infants from accidentally swallowing batteries.
When not using the Remote Controller for an extended period, remove the batteries to
avoid possible leakage and damage to the unit.
If leaking battery fluid comes in contact with your skin, eyes, or mouth, immediately
wash with copious amounts of water, and consult your physician.
Dead batteries should be removed immediately and disposed of properly, either in a
battery collection receptacle or to the appropriate authority.
Do not attempt to recharge dry batteries.
NOTE:
Never mix new and used batteries, or batteries of different types.• Batteries should last about 1 year under normal use. If the Remote Controller’s operating• range becomes appreciably reduced, replace the batteries and press the RESET button
with the tip of a ballpoint pen or other small object.
6.2.
Installing the
remote controller holder
CAUTION
Check that the indoor unit correctly receives the signal from the remote controller, then
install the remote controller holder.
Select the remote controller holder selection site by paying careful attention to the
following: Avoid places in direct sunlight. Select a place that will not be affected by the
heat from a stove, etc.
Install the remote controller with a distance of 7 m between the remote controller and• the photocell as the criteria. However, when installing the remote controller, check that it
operates positively.
Install the remote controller holder to a wall, pillar, etc., with the tapping screw.• Mount the holder.(1)
Screws
Set the remote controller.(2) Insert
Press in
To remove the remote controller (when use at hand).(3)
Slide up
Pull out
7. CASSETTE GRILLE INSTALLATION
Installation according to the Installation instruction sheet Cassette grille.• Be sure to confirm there is no gap between the panel and main unit after installing the• Cassette grille.
7.1. Remove the intake grille
(1) Slide the 2 grille hooks.
Grille hook
(2) Open the intake grille and remove.
7.2. Installing the panel to indoor unit
(1) Install the cassette grille on the indoor unit.
“DRAIN” mark “PIPE” mark
Align the stamped marks on the cassette grille to the pipe and the drain of the indoor• unit.
Screw
CAUTION
Use only the supplied screws to install the cassette grille.
Indoor unit
Sealant Ceiling
5 ~ 7
Cassette grille
No gap between ceiling and
cassette grille around entire
perimeter
9379124010-05_IM.indb 99379124010-05_IM.indb 9 8/31/2012 10:43:26 AM8/31/2012 10:43:26 AM
AMP Air Conditioning

En-10
(2) Connect the connector.
Wire (louver): WHITE
Wire (display): WHITE
Wire (louver): RED
Indoor unit side
Arrange the wires as illustrated below.•
(3)Attach the connector cover.
Screw Connector cover
7.3. Attach the intake grille
The installation is the reverse of “REMOVING THE INTAKE GRILLE”.
The intake grille can be rotated and installed 4 ways to suit the user’s preference.
CAUTION
The louver angle cannot be changed if the power is not on. (If moved by hand, it may
be damaged.)
The grille assembly is directionally relative to the air conditioner body.
Install so that there is no gap between the grille assembly and the air conditioner body.
The cassette grille equips with an accessory to prevent the grill completely open. Be
sure to read the INSTALLATION SHEET included with the cassette grille before instal-
lation.
8. FUNCTION SETTING
CAUTION
Confirm whether the wiring work for outdoor unit has been finished.
Confirm whether the cap for electric control box on the outdoor unit is close.
This procedure changes to the function settings used to control the indoor unit according• to the installation conditions. Incorrect settings can cause the indoor unit malfunction.
After the power is turned on, perform the “FUNCTION SETTING” according to the instal-• lation conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting• Value.
Settings will not be changed if invalid numbers or setting values are selected.• Refer to the installation manual enclosed with the remote controller when the wired• remote controller (option) is used.
8.1. Operation method
While pressing the FAN button and SET TEMP. (• ) simultaneously, press the RESET
button to enter the function setting mode.
STEP 1
Selecting the Remote Controller Signal Code
Use the following steps to select the signal code of the remote controller.
(Note that the air conditioner cannot receive a signal code if the air conditioner has not
been set for the signal code.)
The signal codes that are set through this process are applicable only to the signals in
the FUNCTION SETTING. For details on how to set the signal codes through the normal
process, refer to SELECTING THE REMOTE CONTROLLER SIGNAL CODE.
(1) Press the SET TEMP. ( ) ( ) button to change the signal code between
.
Match the code on the display to the air conditioner signal code. (initially set to ) (If
the signal code does not need to be selected, press the MODE button and proceed to
STEP 2.)
(2) Press the TIMER MODE button and check that the indoor unit can receive signals at
the displayed signal code.
(3) Press the MODE button to accept the signal code, and proceed to STEP 2.
The air conditioner signal code is factory-set to A .
Contact your retailer to change the signal code.
The remote controller resets to signal code A when the batteries in the remote controller
are replaced. If you use a signal code other than signal code A, reset the signal code
after replacing the batteries.
If you do not know the air conditioner signal code setting, try each of the signal codes
() until you find the code which operates the air conditioner.
STEP 2
Selecting the Function Number and Setting Value
(1) Press the SET TEMP. ( ) ( ) buttons to select the function number. (Press the
MODE button to switch between the left and right digits.)
(2) Press the FAN button to proceed to setting the value. (Press the FAN button again to
return to the function number selection.)
(3) Press the SET TEMP. ( ) ( ) buttons to select the setting value. (Press the MODE
button to switch between the left and right digits.)
(4) Press the TIMER MODE button, and START/STOP button, in the order listed to
confirm the settings.
(5) Press the RESET button to cancel the function setting mode.
(6) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.
Function number
Setting value
CAUTION
After turning off the power, wait 30 seconds or more before turning on it again. The
FUNCTION SETTING doesn’t become effective if it doesn’t do so.
8.2. Function setting
(1) Filter sign
The indoor unit has a sign to inform the user that it is time to clean the filter. Select the
time setting for the filter sign display interval in the table below according to the amount
of dust or debris in the room. If you do not wish the filter sign to be displayed, select the
setting value for “No indication”.
9379124010-05_IM.indb 109379124010-05_IM.indb 10 8/31/2012 10:43:29 AM8/31/2012 10:43:29 AM
AMP Air Conditioning

En-11
(¡... Factory setting)
Setting description
Function number Setting value
Standard (2,500 hours)
11
00
Long interval (4,400 hours) 01
Short interval (1,250 hours) 02
¡No indication 03
(2) Ceiling height
Select the setting values in the table below according to the height of the ceiling.
(¡... Factory setting)
Setting description
Function number Setting value
¡Standard
(2.7 m [9 ft]) 20 00
High ceiling
(3.0 m [10 ft]) 01
* However, 7000, 9000 Btu/h model can not be installed in high places.
(3) Outlet directions
Select the setting values in the table below for using a 3-way outlet. (¡... Factory setting)
Setting description
Function number Setting value
¡4-way 22 00
3-way 01
(4) Cooling room temperature correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be selected as shown in the table below. (¡... Factory setting)
Setting description
Function number Setting value
¡Standard
30
00
Slightly lower control 01
Lower control 02
Warmer control 03
(5) Heating room temperature correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be changed as shown in the table below. (¡... Factory setting)
Setting description
Function number Setting value
¡Standard
31
00
Lower control 01
Slightly warmer control 02
Warmer control 03
(6) Auto restart
Enable or disable automatic system restart after a power outage. (¡... Factory setting)
Setting description
Function number Setting value
¡Yes 40 00
No 01
* Auto restart is an emergency function such as for power failure etc. Do not start and stop
the indoor unit by this function in normal operation. Be sure to operate by the control unit,
or external input device.
(7) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed using the Wired remote controller temperature sensor
(¡... Factory setting)
Setting description
Function number Setting value
¡No 42 00
Yes 01
* If setting value is “00”:
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01”:
Room temperature is controlled by either indoor unit temperature sensor or remote
controller unit sensor.
(8) Wireless remote controller signal code
Change the indoor unit Signal Code, depending on the wireless remote controllers.
(¡... Factory setting)
Setting description
Function number Setting value
¡A
44
00
B01
C02
D03
(9) External input control
“Operation/Stop” mode or “Forced stop” mode can be selected. (¡... Factory setting)
Setting description
Function number Setting value
¡Operation/Stop mode 46 00
(Setting forbidden) 01
Forced stop mode 02
Setting record
•Record any changes to the settings in the following table.
Setting Setting Value
(1) Filter sign
(2) Ceiling height
(3) Outlet directions
(4) Cooler room temperature correction
(5) Heater room temperature correction
(6) Auto restart
(7) Indoor room temperature sensor switching function
(8) Wireless remote controller signal code
(9) External input control
After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.
8.3. Selecting the remote controller signal code
[When using the wireless remote controller]
When 2 or more air conditioners are installed in a room and the remote controller is
operating an air conditioner other than the one you wish to set, change the signal code
of the remote controller to operate only the air conditioner you wish to set (4 selections
possible).
When 2 or more air conditioners are installed in a room, please contact your retailer to set
the individual air conditioner signal codes.
Confirm the setting of the remote controller signal code and the printed circuit board
setting.
If these are not confirmed, the remote controller cannot be used to operate for the air
conditioner.
Selecting the Remote Controller Signal Code
Use the following steps to select the signal code of the remote controller. (Note that the
air conditioner cannot receive a signal code if the air conditioner has not been set for the
signal code.)
(1) Press the START/STOP button until only the clock is displayed on the remote control-
ler display.
(2) Press the MODE button for at least 5 seconds to display the current signal code
(initially set to ).
(3) Press the SET TEMP. (▲) (▼) button to change the signal code between
. Match the code on the display to the air conditioner signal code.
9379124010-05_IM.indb 119379124010-05_IM.indb 11 8/31/2012 10:43:31 AM8/31/2012 10:43:31 AM
AMP Air Conditioning

En-12
(4) Press the MODE button again to return to the clock display. The signal code will be
changed.
If no buttons are pressed within 30 seconds after the signal code is displayed, the sys-
tem returns to the original clock display. In this case, start again from step 1
The air conditioner signal code is set to A prior to shipment.
Contact your retailer to change the signal code.
The remote controller resets to signal code A when the batteries in the remote controller
are replaced. If you use a signal code other than signal code A, reset the signal code
after replacing the batteries.
If you do not know the air conditioner signal code setting, try each of the signal codes
() until you find the code which operates the air conditioner.
8.4. Special installation methods
This possible only the wired remote controller (Option)
CAUTION
When setting DIP switches, do not touch any other parts on the circuit board directly
with your bare hands.
Be sure to turn off the main power.
8.4.1. Simultaneous multi-system operation
By combining with an outdoor unit, 2 units for twin and 3 units for triple indoor units, can• be switched ON/OFF simultaneously.
Wiring method(1)
Refer to 5.ELECTRICAL WIRING for wiring procedure and wiring method.• The indoor unit is connected the outdoor unit using a transmission cable is “primary”.• Connect the remote controller wire to the primary unit.•
Twin type ( 18, 22, 24 type only )
Outdoor
unit
Indoor
unit 1
Indoor
unit 2
Remote
controller [primary] [secondary]
Triple type ( 18type only )
Outdoor
unit
Remote
controller
: Transmission cable, Power supply cable : Power supply cable
: Bus wire: Remote controller cable
Indoor
unit 1
[primary]
Indoor
unit 2
[secondary]
Indoor
unit 3
[secondary]
Set the R.C. address (DIP switc h setting )(2) Set the R.C. address of each indoor unit using the DIP switches on the indoor unit
circuit board. (See the following table and figure.)
The DIP switches are normally set to make the R.C. address 00.
Indoor unit R.C. address DIP SWITCH No.
1234
100 OFF OFF OFF OFF
201 ON OFF OFF OFF
302 OFF ON OFF OFF
DIP switches
Example :
R.C. address 02
ON
Circuit board in the control box of indoor unit.
NOTE
Be sure to set the R.C. address sequentially.
Set the primary and secondary (Remote controller setting)(3) Turn on all of the indoor units.1. Set the “primary” and “secondary” settings.2.
(Set the indoor unit that is connected to the outdoor unit using a transmission cable
as the “primary”.)
Function Number
Setting Value
Primary 51 00
Secondary 01
After completing the function settings, turn off all of the indoor units, and then turn3. them back on.
If error code 21, 22, 24 or 27 is displayed, there may be an incorrect setting.* Perform the remote controller setting again.
Twin type ( 18, 22, 24 type only )
00 01
00 01
R.C address
Primary/Secondary setting
(DIP switch setting)
(Function number 51)
Out door
unit
Remote
controller Indoor
unit 1
[primary]
Indoor
unit 2
[secondary]
Triple type ( 18type only )
00 01 02
00 01 01
R.C address
Primary/Secondary setting
(DIP switch setting)
(Function number 51)
Out door
unit
Remote
controller
: Transmission cable, Power supply cable : Power supply cable
: Bus wire: Remote controller cable
Indoor
unit 1
[primary]
Indoor
unit 2
[secondary]
Indoor
unit 3
[secondary]
9379124010-05_IM.indb 129379124010-05_IM.indb 12 8/31/2012 10:43:32 AM8/31/2012 10:43:32 AM
AMP Air Conditioning

En-13
8.4.2. Group control system
CAUTION
Group control cannot be used when using it by the flexible multi type.
A number of indoor units can be operated at the same time using a single remote controller.
(1) Wiring method (indoor unit to remote controller)
123
123
123 123 123
Indoor
unit 1
Bus wire
Remote
controller cable
Remote controller
When earth (ground) wire is necessary
Indoor
unit 2Indoor
unit 3Indoor
unit 4
Set the R.C. address (DIP switch setting)(2) Set the R.C. address of each indoor unit using the DIP switches on the indoor unit
circuit board. (See the following table and figure.)
The DIP switches are normally set to make the R.C. address 00.
Indoor unit
R.C. address
DIP SWITCH No.
1234
①00 OFF OFF OFF OFF
②01 ON OFF OFF OFF
③02 OFF ON OFF OFF
④03 ON ON OFF OFF
⑤04 OFF OFF ON OFF
⑥05 ON OFF ON OFF
⑦06 OFF ON ON OFF
⑧07 ON ON ON OFF
⑨08 OFF OFF OFF ON
⑩09 ON OFF OFF ON
⑪10 OFF ON OFF ON
⑫11 ON ON OFF ON
⑬12 OFF OFF ON ON
⑭13 ON OFF ON ON
⑮14 OFF ON ON ON
⑯15 ON ON ON ON
NOTE
Be sure to set the R.C. address sequentially.
00 01 02 03
R.C address
(DIP switch setting)
Remote
controller
: Transmission cable, Power supply cable : Power supply cable
: Bus wire: Remote controller cable
Outdoor
unit 1
Indoor
unit 1
Indoor
unit 2
Indoor
unit 3
Indoor
unit 4
Outdoor
unit 2
Outdoor
unit 3
Outdoor
unit 4
Settings when simultaneous Multi is included
Set the refrigerant circuit address (Remote controller setting)(3) Turn on all of the indoor units.1. * Turn on the indoor unit with the R.C. address 00 last.
(Within 1 minute)
Set the refrigerant circuit address.2. Assign the same number to all of the indoor units connected to an outdoor unit.
(The unit is factory-set to “00”)
Refrigerant circuit address
Function Number Setting Value
00
02 00
〜
15
01
〜
14
15
Set the “primary” and “secondary” settings. (Remote controller setting)(4)
(Set the indoor unit that is connected to the outdoor unit using a transmission cable as the
“primary”.)
Function Number
Setting Value
Primary 51 00
Secondary 01
After completing the function settings, turn off all of the indoor units,
and then turn them back on.
* If error code 21, 22, 24, or 27 is displayed, there may be an incorrect
setting. Perform the remote controller setting again.
NOTE
When different indoor unit models are connected using the group control system, some• functions may no longer be available.
If the group control system contains multiple units that are operated simultaneously, con-• nect and set the units as shown below.
Auto-changeover operates under the same mode with model R.C. address 00.• It should not be connected to any other Gr that is not of the same series (A**G only).•
R.C address
Standard
pair Standard
pair Simultaneous
twin Simultaneous
triple
Refrigerant circuit
address setting
Primary/Secondary setting
(DIP switch setting)
(Function number 02)
(Function number 51)
Remote
controller
: Transmission cable, Power supply cable : Power supply cable
: Bus wire: Remote controller cable
Outdoor
unit 1
Outdoor
unit 2
Outdoor
unit 3
Outdoor
unit 4
Indoor
unit 1
Indoor
unit 2
Indoor
unit 3
Indoor
unit 4
Indoor
unit 5
Indoor
unit 6
Indoor
unit 7
8.4.3. Dual remote controllers
2 separate remote controllers can be used to operate the indoor units.• The timer and self-diagnosis functions cannot be used on the secondary unit of remote• controller.
Wiring method (indoor unit to remote controller)(1)
123123
1 2 3
Indoor unit
Secondary unit
Primary unit
Remote controller cable
Remote
controller
Remote
controller
When earth (ground) wire
is necessary
Remote controller DIP switch 1 setting(2) Set the remote controller DIP switch 1-No. 2 according to the following table.
DIP SW 1-No. 2
Primary unit OFF
Secondary unit ON
9379124010-05_IM.indb 139379124010-05_IM.indb 13 8/31/2012 10:43:33 AM8/31/2012 10:43:33 AM
AMP Air Conditioning

En-14
9. TEST RUN
CHECK ITEMS
Is operation of each button on the remote controller normal?(1) Does each lamp light normally?(2) Do not air flow direction louvers operate normally?(3) Is the drain normal?(4) Is there any error noise and vibration during operation?(5)
Do not operate the air conditioner test run for a long time.•
CHECKING DRAINAGE.
To check the drain, remove the water cover and fill with 1 liter of water as shown in the
figure.
The drain pump operates when operating in the cooling mode.
Drain pipe Wire cover Screw
Watering pot
• Test running
When the air conditioner is run by pressing the remote controller test run button,
the OPERATION and TIMER lamps flash slowly at the same time.
[Operation method]
For the operation method, refer to the operating manual.• The outdoor unit may not operate depending on the room temperature.• In this case, press the TEST RUN button on the remote controller while the air condi-
tioner is running. (Point the transmitter section of the remote controller toward the air
conditioner and press the TEST RUN button with the tip of a ball-point pen, etc.)
Transmitter section
TEST RUN button
To end test operation, press the remote controller START/STOP button.• (When the air conditioner is run by pressing the TEST RUN button, the OPERATION
Lamp and TIMER Lamp will simultaneously flash slowly.)
[Using the wired remote control] (Option)
For the operation method, refer to the operating manual.• Stop the air conditioner operation.(1) Press the MODE button and the FAN button simultaneously for 2 seconds or more to(2) start the test run.
Test run display
Press the START/STOP button to stop the test run.(3)
If “C0” appears in the R.C. address display, there is a remote controller error. Refer to the
installation manual included with the remote controller.
R.C. address Error code Content
Incompatible indoor unit is connected
Indoor unit ↔remote controller com-
munication error
10.CHECK LIST
Pay special attention to the check items below when installing the indoor unit(s). After
installation is complete, be sure to check the following check items again.
CHECK ITEMS If not performed
correctly CHECK
BOX
Has the indoor unit been installed
correctly? Vibration, noise, indoor unit
may drop
Has there been a check for gas
leaks (refrigerant pipes)? No cooling, No heating
Has heat insulation work been
completed? Water leakage
Does water drain easily from the
indoor units? Water leakage
Are the wires and pipes all con-
nected completely? No operation, heat or burn
damage
Is the connection cable the speci-
fied thickness? No operation, heat or burn
damage
Are the inlets and outlets free of any
obstacles? No cooling, No heating
After installation is completed, has
the proper operation and handling
been explained to the user?
11.OPTIONAL KIT INSTALLATION (OPTION)
WARNING
Regulation of cable differs from each locality, refer in accordance with local rules.
This air conditioner can be connected with the following optional kits.
Option type Connector No.
Fresh air intake CN6
External input CN102
External output CN103
Wired Remote Controller
-
Fresh air intake kit
Wired Remote Controller
External output kit
External input kit
12.CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating manual:
Starting and stopping method, operation switching, temperature adjustment, timer, air(1) flow switching, and other remote controller unit operations.
Air filter removal and cleaning, and how to use the air louvers.(2) Give the operating and Installation Manuals to the customer.(3) If the signal code is changed, explain to the customer how it changed (the system(4) returns to signal code A when the batteries in the remote controller unit are replaced).
*(4) is applicable to using wireless remote controller.
9379124010-05_IM.indb 149379124010-05_IM.indb 14 8/31/2012 10:43:35 AM8/31/2012 10:43:35 AM
AMP Air Conditioning

En-15
13.ERROR CODES
If you use a wireless remote controller, the lamp on the photo detector unit will output error
codes by way of blinking patterns. If you use a wired type remote controller, error codes
will appear on the remote controller display. See the lamp blinking patterns and error
codes in the table. An error display is displayed only during operation.
Error display Wired
remote
controller
Error code
Description
OPERA-
TION lamp
(green)
TIMER
lamp
(orange)
ECONO-
MY lamp
(green)
●(1) ●(1)
◊
Serial communication error
●(1) ●(2)
◊
Wired remote controller
communication error
●(1) ●(5)
◊
Check run unfinished
●(2) ●(1)
◊
R.C. address or Refrigerant circuit
address setting error
[Simultaneous Multi]
●(2) ●(2)
◊
Indoor unit capacity error
●(2) ●(3)
◊
Combination error
●(2) ●(4)
◊
Connection R.C. address• error (indoor secondary unit)
[Simultaneous Multi]
Connection R.C. address error• (indoor unit or branch unit) [Flex-
ible Multi]
●(2) ●(7)
◊
Primary unit, secondary unit set-
up error [Simultaneous Multi]
●(3) ●(1)
◊
Power supply interruption error
●(3) ●(2)
◊
Indoor unit PCB model
information error
●(3) ●(5)
◊
Manual auto switch error
●(4) ●(1)
◊
Inlet air temp. sensor error
●(4) ●(2)
◊
Indoor unit Heat Ex. Middle temp.
sensor error
●(5) ●(1)
◊
Indoor unit fan motor error
●(5) ●(3)
◊
Drain pump error
●(5) ●(7)
◊
Damper error
●(5) ●(15)
◊
Indoor unit error
●(6) ●(2)
◊
Outdoor unit main PCB model
information error or
communication error
●(6) ●(3)
◊
Inverter error
●(6) ●(4)
◊
Active filter error, PFC circuit error
●(6) ●(5)
◊
Trip terminal Lerror
●(6) ●(10)
◊
Display PCB microcomputers
communication error
●(7) ●(1)
◊
Discharge temp. sensor error
●(7) ●(2)
◊
Compressor temp. sensor error
●(7) ●(3)
◊
Outdoor unit Heat Ex. liquid temp.
sensor error
●(7) ●(4)
◊
Outdoor temp. sensor error
●(7) ●(5)
◊
Suction Gas temp. sensor error
●(7) ●(6)
◊
2-way valve temp. sensor error• 3-way valve temp. sensor error•
●(7) ●(7)
◊
Heat sink temp. sensor error
●(8) ●(2)
◊
Sub-cool Heat Ex. gas inlet• temp. sensor error
Sub-cool Heat Ex. gas outlet• temp. sensor error
●(8) ●(3)
◊
Liquid pipe temp. sensor error
●(8) ●(4)
◊
Current sensor error
●(8) ●(6)
◊
Discharge pressure sensor error• Suction pressure sensor error• High pressure switch error•
●(9) ●(4)
◊
Trip detection
●(9) ●(5)
◊
Compressor rotor position
detection error (permanent stop)
●(9) ●(7)
◊
Outdoor unit fan motor 1 error
●(9) ●(8)
◊
Outdoor unit fan motor 2 error
●(9) ●(9)
◊
4-way valve error
●(9) ●(10)
◊
Coil (expansion valve ) error
●(10) ●(1)
◊
Discharge temp. error
●(10) ●(3)
◊
Compressor temp. error
●(10) ●(4)
◊
High pressure error
●(10) ●(5)
◊
Low pressure error
●(13) ●(2)
◊
Branch boxes error
[Flexible Multi]
Display mode ●: 0.5s ON / 0.5s OFF
◊
: 0.1s ON / 0.1s OFF
( ) : Number of flashing
[Troubleshooting with the indoor unit display]
ECONOMY Lamp
(GREEN)
TIMER Lamp
(ORANGE) OPERATION Lamp
(GREEN)
MANUALAUTO
[Troubleshooting at the remote controller LCD]
This is possible only on the wired remote controller.
[Self-diagnosis]
If an error occurs, the following display will be shown.
(“Er” will appear in the set room temperature display.)
R.C. address Error code
EX. Self-diagnosis
9379124010-05_IM.indb 159379124010-05_IM.indb 15 8/31/2012 10:43:37 AM8/31/2012 10:43:37 AM