APT 310XAC User manual

300XAC
MODULAR AC POWER SOURCES
For the following models:
310XAC, 320XAC, 340XAC, 360XAC
SAFETYCHECKLIST
KEEP unqualified/unauthorized personnel away from test area
ARRANGE test stations in a safe and orderly manner
NEVER touch products or connections during a test
STOP the test first in the event of a problem
BE SURE to use the appropriate AWG for your input and output cabling
TURN OFF the output when making any connections to the load
WARNING: THIS GUIDE WAS CREATED
FOR OPERATORS HAVING SOME FAMILIARITY
WITH AC POWER SOURCES AND HIGH
VOLTAGE/HIGH CURRENT TESTING APPLICATIONS.
AN AC POWER SOURCE PRODUCES VOLTAGES AND
CURRENTS THAT CAN CAUSE HARMFUL OR FATAL
ELECTRIC SHOCK. TO PREVENT ACCIDENTAL INJURY
OR DEATH, THESE SAFETY PROCEDURES MUST BE
STRICTLY OBSERVED WHEN HANDLING AND USING
AN AC POWER SOURCE.
Via Acquanera, 29 22100 Como
tel. 031.526.566 (r.a.) fax 031.507.984
info@calpower.it www.calpower.it

FRONTPANELCONTROLS
1.
1. POWER SWITCH: Rocker style power switch with International ON (I) and
OFF (0) markings.
2. GRAPHIC LCD: 240 x 64 monographic LCD.
3. SOFT KEYS: Multi-functional selection keys used to select parameters, select
screens, and edit parameters.
4. NUMERIC KEYPAD: Keys used to enter numeric data.
5. DELETE KEY: Used to delete text characters and numeric data.
6. ROTARY KNOB: Used to adjust the voltage/frequency output in MANUAL
Mode or DC Mode.
7. LOCK KEY: Used to lock out the front panel.
8. LOCK LED: When lit, this LED indicates the instruments front panel is locked.
9. TEST/RESET KEY: Used to turn ON/OFF output voltage, or used to reset the
instrument in the event of a failure condition.
10. TEST/RESET LED: When lit, this LED indicates output is active, or when
blinking indicates the instrument is in a failure condition.

BACKPANELCONTROLS
2.
1. SYNC OUTPUT CONNECTOR: Provides the capability to monitor a 5 VDC output
signal.
2. REMOTE OUTPUT CONNECTOR: Provides output to monitor PASS, FAIL,
Test-In-Process via relay contact closures.
3. AUTOMATED INTERFACE CARD: Interface card used to control, program, and
capture data.
4. LINKING CARD (OPT. 8): Provides input and output communication ports for
operating multiple instruments in parallel and polyphase modes.
4a. Interface Input: Connector used to attach the instrument to a master power
source. Connecting the interface cable to this port automatically designates the
instrument as a slave unit.
4b. Interface Output: Connector used to attach the instrument to a slave power
source. Connecting the interface cable to this port automatically designates the
instrument as a master unless an interface cable is also connected to the Interface
Input port (in this case the instrument is automatically configured as a slave).
5. INPUT TERMINAL POWER BLOCK: Provides input power to the instrument.
Models 310XAC and 320XAC require 90-264 VAC 1Ø, 47-63 Hz.
5a. G: Earth ground (chassis) connection.
5b. N: Neutral input screw terminal.
5c. L: Line input screw terminal.
6. OUTPUT TERMINAL POWER BLOCK: Provides output power to the DUT.
6a. Ns: Neutral sense screw terminal.
6b. N: Neutral output screw terminal.
6c. G: Earth ground (chassis) connection.
6d. L: Line output screw terminal.
6e. Ls: Line voltage sense screw terminal.

BACKPANELCONTROLS
3.
7. INPUT TERMINAL POWER BLOCK: provides input power to the instrument.
Model 340XAC requires 180-284 VAC 1Ø, 47-63 Hz.
7a. L: Line input screw terminal.
7b. N: Neutral input screw terminal.
7c. G: Earth ground (chassis) connection.
8. OUTPUT TERMINAL POWER BLOCK: Provides output power to the DUT.
8a. N: Neutral output screw terminal.
8b. G: Earth ground (chassis) connection.
8c. L: Line output screw terminal.
9. EXTERNAL SENSE OUTPUT TERMINAL BLOCK: Provides screw terminals for
external voltage sense leads.
9a. L: Line voltage sense screw terminal.
9b. N: Neutral voltage sense screw terminal.

BACKPANELCONTROLS
4.
10. INPUT TERMINAL POWER BLOCK: Provides input power to the instrument. Model
360XAC requires 180-264 VAC 1Ø, 180-264 VAC 3Ø or 312-457 VAC 3Ø at
47-63 Hz.
11. OUTPUT TERMINAL POWER BLOCK: Provides output power to the DUT.
11a. N: Neutral output screw terminal.
11b. G: Earth ground (chassis) connection.
11c. L: Line output screw terminal.
12. EXTERNAL SENSE OUTPUT TERMINAL BLOCK: Provides screw terminals for
external voltage sense leads.
12a. L: Line voltage sense screw terminal.
12b: N: Neutral voltage sense screw terminal.

CHANGINGTESTMODES
5.
The 300XAC includes two test modes that change the way in which the AC power
source operates. PROGRAM Mode allows the operator to configure and run a test
using steps and memory locations within the AC power source’s menu. PROGRAM
Mode is designed for advanced testing applications. MANUAL Mode doesn’t
utilize steps and memories, allowing the operator to quickly run a test with basic test
parameters.
Turn the POWER switch to ON. From the Set screen press the “<more>” soft key and
press the “System” soft key in the next screen.
In the System Parameters Menu, you can use the up or down arrow soft keys to
highlight the AUTO RUN parameter. To change the AUTO RUN parameter, press the
“Edit” soft key.
In the next screen, the AUTO RUN parameter will be highlighted. Press the
“Change” soft key to toggle the highlighted parameter between PROGRAM and
MANUAL mode. Press the “Enter” soft key to save changes made and then press the
“Exit” soft key two times to return to the Set screen.
When the AUTO RUN parameter in the System Parameters menu is set to PROGRAM
mode, the Set screen will be displayed as follows: (See Figure 1)
(Figure 1. Set Screen)
When the AUTO RUN parameter in the System Parameters is set to the MANUAL
mode the Set screen will be displayed as follows: (See Figure 2)
(Figure 2. Set Screen)

USING THE 300XAC IN CONSTANT CURRENT MODE
1) Turn ON the OC FOLD parameter.
From the Set screen press the “<more>” soft key and press the “System” soft key in
the next screen.
In the System Parameters Menu, you can use the up or down arrow soft keys to
highlight the “OC FOLD” parameter. To change the “OC FOLD” parameter, press
the “Edit” soft key.
In the next screen, the “OC FOLD” parameter will be highlighted. Press the
“Change” soft key to set the highlighted parameter to ON. Press the “Enter” soft key
to save changes. Press the “Exit” soft key two times to return to the Set screen.
2) Program a current Hi-Limit, which represents the constant current you will
provide to the load.
From the Set screen press the “Edit” soft key.
In the next screen, the Edit Parameters Menu, you can use the up and down
arrow soft keys to highlight the “A Hi-Lmt” parameter. To change the “A Hi-Lmt”
parameter, press the “Edit” soft key.
In the next screen, the “A Hi-Lmt” parameter will be highlighted. Using the Numeric
Keypad enter the desired current limit. Press the “Enter” soft key to save changes
and then press the “Exit” soft key one time to return to the Edit Parameters Menu.
3) Program the voltage.
From the Edit Parameters Menu, use the up or down arrow soft keys to highlight the
“Voltage” parameter. To change the “Voltage” parameter, press the “Edit” soft key.
In the next screen, the “Voltage” parameter will be highlighted. Using the numeric
keypad, enter the voltage value. The voltage should be set higher than the nominal
load voltage. This allows the current to adjust to the Hi-Limit value. After you enter
the voltage, press the “Enter” soft key and then press the “Exit” soft key two times to
return to the Set screen.
CONSTANTCURRENTMODE
6.

7.
(Option 8 Linking Card Required)
PARALLEL MODE (1Ø2W)
In Parallel Mode, two (2) or three (3) instruments may be connected together in
parallel, to increase the total current output of the system.
Linking two 300XAC sources:
Only one linking cable is needed. Connect the linking cable from the output
connector labeled “Link Output” of one 300XAC source’s linking card to the input
connector labeled “Link Input” of the second 300XAC source’s linking card.
(See Figure 3)
Linking three 300XAC sources:
Take a second linking cable and connect it from the second 300XAC source’s output
connector labeled “Link Output” on the linking card to the input connector labeled
“Link Input on the third 300XAC source’s linking card. (See Figure 3)
(Figure 3.)
LINKINGSOURCES
IMPORTANT: BEFORE YOU BEGIN MAKING CONNECTIONS, YOU MUST
ENSURE THAT THE POWER SWITCH ON THE 300XAC INSTRUMENT IS IN THE
OFF POSITION.
SLAVE
SLAVE
MASTER

In Parallel Mode, each instruments’ LINE output must be connected together at the
load. If you are linking two sources there will be two line connections. If you are
linking three sources there will be three line connections. (See Figure 4)
Also, each instruments’ NEUTRAL output must be connected together at a load. If
you are linking two sources there will be two neutral connections. If you are linking
three sources there will be three neutral connections. (See Figure 4)
(Figure 4)
Once all the linking cables and conductor connections have been made, you can
power up each individual 300XAC via the Power Switch on the front panel. Upon
power up, the 300XAC will go through an initialization screen to verify that the
additional sources are interconnected via the linking cable. If there is a proper
connection, a message will appear acknowledging that additional 300XAC sources
are linked and prompting the user to enable the additional sources.
LINKINGSOURCES
FUNCTIONMODE
The FUNCTION mode changes the output voltage configuration.
Power up all instruments. From the Set screen press the “<more>” soft key and in the
next screen press the “System” soft key.
In the System Parameters Menu, you can use the up or down arrow soft keys to
highlight the FUNCTION parameter.
When the FUNCTION parameter is highlighted, press the “Edit” soft key and use the
“Change” soft key to select the FUNCTION mode to “PARALLEL”.
To save changes made, press the “Enter” soft key and then press the “Exit” soft key
two times to get back to the Set screen.
8.
Load
Line 1
Neutral 1
Line 2
Neutral 2
Line 3
Neutral 3
MASTER
SLAVE
SLAVE

9.
FUNCTIONMODE
The FUNCTION mode changes the output voltage configuration.
Power up all instruments. From the Set screen press the “<more>” soft key and in the
next screen press the “System” soft key.
In the System Parameters Menu, you can use the up or down arrow soft keys to
highlight the FUNCTION parameter.
When the FUNCTION parameter is highlighted, press the “Edit” soft key and use the
“Change” soft key to select the FUNCTION mode to “1Ø3W” .
To save changes made, press the “Enter” soft key and then press the “Exit” soft key
two times to get back to the Set screen.
(Figure 5)
Once all the linking cables and conductor connections have been made, you can
power up each individual 300XAC via the Power Switch on the front panel. Upon
power up, the 300XAC will go through an initialization screen to verify that the
additional sources are interconnected via the linking cable. If there is a proper
connection, a message will appear acknowledging that additional 300XAC sources
are linked and prompting the user to enable the additional sources.
Load
Line 1
Line 2
Neutral
ØB
ØA
(Option 8 Linking Card Required)
POLYPHASE OUTPUT MODE (1Ø3W)
In Polyphase Mode, two (2) or three (3) instruments connected together may be used to
increase the total voltage output of the system, or change the output configuration from
1Ø to 3Ø. If two (2) instruments are interconnected 1Ø3W mode is available. This
mode allows the operator to increase the output voltage to up to 600 VAC by configuring
the two sources to output voltage at 180 degrees apart
You will only use one linking cable between the two 300XAC sources. Connect the
linking cable from the output connector labeled “Link Output” of one 300XAC source’s
linking card to the input connector labeled “Link Input” of the second 300XAC source’s
linking card. (See Figure 5)
In the configuration below, the operator must connect the NEUTRALS of both instruments
together and utilize both LINE outputs to achieve full voltage. (See Figure 5)
LINKINGSOURCES
IMPORTANT: BEFORE YOU BEGIN MAKING CONNECTIONS, YOU MUST
ENSURE THAT THE POWER SWITCH ON THE 300XAC INSTRUMENT IS IN THE
OFF POSITION.

(Figure 6)
Once all the linking cables and conductor connections have been made, you can power
up each individual 300XAC via the Power Switch on the front panel. Upon power up,
the 300XAC will go through an initialization screen to verify that the additional sources
are interconnected via the linking cable. If there is a proper connection, a message will
appear acknowledging that additional 300XAC sources are linked and prompting the
user to enable the additional sources. (continued on back page)
10.
A
Load
C
B
Line 1
Neutral
Neutral
Neutral
Line 2
Line 3
ØA
ØB
ØC
(Option 8 Linking Card Required)
POLYPHASE OUTPUT MODE (3Ø4W)
If three (3) instruments are interconnected 3Ø4W mode is available. This mode allows
the operator to configure the instruments for three phase operation. Each phase will
output voltage 120 degrees apart.
You will be using two linking cables between the three 300XAC sources. Connect
the linking cable from the output connector labeled “Link Ouput” of one 300XAC
source’s linking card to the input connector labeled “Link Input” of the second 300XAC
source’s linking card.
Now, take a second linking cable and connect it from the second 300XAC source’s
output connector labeled “Link Output” on the linking card to the input connector labeled
“Link Input” on the third 300XAC source’s linking card. (See Figure 6)
In the configuration below, the operator must connect the NEUTRALS of all sources
together at the load and utilize the LINE outputs to achieve full voltage. (See Figure 6)
LINKINGSOURCES
IMPORTANT: BEFORE YOU BEGIN MAKING CONNECTIONS, YOU MUST
ENSURE THAT THE POWER SWITCH ON THE 300XAC INSTRUMENT IS IN THE
OFF POSITION.

For additional information about these and other key features of the 300XAC, please consult the
full Operation and Service Manual or call us toll free +1-877-322-7693 or +1-847-367-4378
© 2011 Associated Power Technologies www.aptsources.com
300XAC-5/11
(Figure 7. Results Screen)
If you have multiple steps linked together, you will have to use the Up and Down arrow
soft keys in order to toggle through each step to review the results.
Press the “Exit” soft key to move back to the set screen.
From the Set screen, press the “Results” soft key to view the results. The screen will look
as follows:
VIEWINGTESTRESULTS
FUNCTIONMODE
The FUNCTION mode changes the output voltage configuration.
Power up all instruments. From the Set screen press the “<more>” soft key and in the
next screen press the “System” soft key.
In the System Parameters Menu, you can use the up or down arrow soft keys to
highlight the FUNCTION parameter.
When the FUNCTION parameter is highlighted, press the “Edit” soft key and use the
“Change” soft key to select the FUNCTION mode to “3Ø4W”.
To save changes made, press the “Enter” soft key and then press the “Exit” soft key
two times to get back to the Set screen.
Via Acquanera, 29 22100 Como
tel. 031.526.566 (r.a.) fax 031.507.984
info@calpower.it www.calpower.it
This manual suits for next models
4
Table of contents
Other APT AC Power Distribution manuals
Popular AC Power Distribution manuals by other brands

Monster Power
Monster Power Reference PowerCenter HTS2600 owner's manual

Ditek
Ditek DTK-HT1000 user guide

Furman
Furman ELITE-15 DM i owner's manual

Pacific Power Source
Pacific Power Source AMX Series Operation manual

Unipower
Unipower DPAC1UT-AB-I-2-590 operating manual

ADTRAN
ADTRAN NetVanta 5305 quick start guide