thermometer. When the targeted water temperature (75° C) is reached, x the damper 4 to the lowest position by fastening the
lever of the draught regulator and choosing the length of the connecting chain. Remember: a 9 mm gap should be left between
the damper and the air supply opening. The exact size of the gap depends upon the draught of your chimney. The worse the
draught, the greater the gap should be.
• REGULATION OF THE SECONDARY AIR DAMPER
The secondary air damper 6 (Fig. 8) is set up in the factory. To inspect the positioning of the damper: loosen the xing screw
and push the shaft of the damper forward until it gets stuck. Then pull the shaft 5 mm backwards and x it with the screw.
• CONTROLLING THE TEMPERATURE OF WATER RETURNING TO THE BOILER
It is absolutely necessary to maintain the
temperature of the water returning from the
heating system to the boiler at a constant
level, no less than 65°C, as this will prolong
the lifetime of the boiler and will make the
combustion process more eective. This is
because when a constant high temperature
of water returning to the boiler is maintained,
there arises signicantly less water vapour
condensation inside the boiler. The heavy water
condensation is harmful to the boiler, because
deposits of tar, pitch and soot accumulate on the walls of the heat exchanger, causing intense metal corrosion. Moreover, the
resulting layer of soot impedes eective heat transfer and the eciency of the boiler falls.
In order to maintain the temperature, we recommend installing the small circulation circle together with a Swedish-made
thermoregulation device, “Laddomat 21-100”. Makesurethatthe“Laddomat” is supplied with the 72°Cthermostatcartridge.
The mentioned temperature is the one at which the valve of the device opens completely. However, the actual temperature
of the water returning from the system and getting into the boiler after mixing, is 5-6°C lower. The higher the temperature
of the return water is, the better it is for the boiler. Thermoregulation devices of other manufacturers could be used for
maintaining the temperature of the returning water as well.
• HEATING OUTPUT, WATER TEMPERATURE AND WATER FLOW RELATIONSHIP
Theheatingoutputsuppliedtoaheatingsystemdependsdirectlyuponthedierenceofowandreturnwatertemperatures
tandtheintensityofthewater owcirculatingthroughthe boiler.Theboiler willfailtoreachthedesiredtemperatureof the
ow water if the returning water temperature is too cold or the circulation pump is too powerful. This will happen because
the boiler will be forced to produce a larger heating output than it has been designed for. The most eective boiler operation
occurs when the dierence between the ow and return water temperatures is 13-18°C. If the boiler is forced to operate
with a 20°C or even greater temperature dierence, it will work ineectively, consume too much of fuel, and the combustion
period of one fuel load will consequently shorten. If the previously mentioned dierence of temperatures is kept less than
10°C, the fuel in the boiler will again burn ineciently and fume because of a lack of air supply. If you know the water ow
intensity near your boiler, in the above presented table you can check, what the dierence of ow and return temperatures
your boiler is capable to maintain, when operating at the nominal heating output.
Do not forget to keep the returning water temperature as high as possible, at least 65°C or even higher!
It is necessary to assure that a thermometer is installed on the returning water pipe, in order to be able to
observe this temperature at any time!
Dierence of water temperatures
t, °C
Heating output, kW
50
Water ow, l/min
11 67
12 61
13 56
14 52
15 49
16 46
17 43
18 41