atmosphere VORTEX POWERFANS VTX-DEDPV User manual

IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
VTX-DEDPV
— USER MANUAL
VTX-DEDPV KIT
1 x Inline fan with integral control
2 x 8’’ Section of galvanized duct
4 x ADC4 clamps
1 x Grommet for tubing
1 x Mounting bracket and hardware
1 x Indicator panel
1 x 2” x 4” Indicator cover plate
1 x 50 ft (15.4 m) Communication cable
1 x Warning label for indicator cover plate

2480 BOUL. DES ENTREPRISES TERREBONNE, QUEBEC J6X 4J8
450 477.1100 | ATMOSPHERE.COM
Page : 2
READ AND SAVE THESE INSTRUCTIONS
WARNING — TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE
THE FOLLOWING :
A - Your dryer installation incorporates a dryer exhaust power ventilator (DEDPV)
incorporating a lint trap.
B - Your dryer depends on the DEDPV for its safe and ecient operation. Operating your
dryer without a functional DEDPV will result in inecient dryer operation, excess energy
consumption and a possible re hazard. See warning light on DEDPV front panel.
C - The VTX-DEDPV shall be permanently installed within the space in which the dryer
is installed. In the case of a dryer installed in an alcove provided with a door, the DEDPV
shall be installed within the alcove or be installed immediately adjacent to the doors of the
alcove. The DEDPV shall be located where it will be readily visible after the dryer is installed
without opening any doors other than those necessary to access the dryer.
WARNING — IF A CONTINUOUS ALARM SOUNDS OR A VISUAL ERROR INDICATOR IS PRESENT,
DO NOT OPERATE THE CLOTHES DRYER. CONTACT YOUR SERVICE PERSONNEL
• Do not install in an exhaust ductwork of a clothes dryer whose instructions prohibit the
installation of a clothes dryer booster fan (DEDPV).
• Do not install in an exhaust ductwork where the equivalent duct length is less than 25 ft
(7.62 linear metres).
• The VTX-DEDPV is suitable to overcome an equivalent duct length of 130 feet
(39.6 meters) of 4 inch diameter galvanized steel duct, and to maintain an air velocity
of 1200 fpm (6.10 m/s).
• Do not exhaust air in excess of 167F (75C) and do not install less than linear 4ft (1.21m)
from clothes dryer exhaust outlet.
• Do not install less than 4 linear feet (1.21 linear meters) or more than 45 linear feet (13.71
linear meters) from clothes dryer exhaust outlet.
• Insulated dryer duct shall not be used upstream of the ventilator.
• The ventilator must not be used in conjunction with high output dryers.
• For general ventilating use only. Do not use to exhaust hazardous or explosive materials
and vapors.
• The installation must comply with local electrical and mechanical building codes,
and must be inspected and accepted by local authorities having jurisdiction.
INSTALLATION GUIDELINES
TO PREVENT THE POSSIBILITY OF DRYER FAN CAVITATION AND/OR EXHAUSTING EXCESS
HEAT REQUIRED FOR THE DRYING CYCLE AND COMPROMISING DRYING TIMES, BOOSTER FAN
AIRFLOW MUST NOT EXCEED THE DRYER FAN CAPACITY.

Ⓒ 2022 ATMOSPHERE INC.
REV R-1122
Page : 3
Calculating duct run for secondary lint trap
To calculate the length of your planned duct run, measure from the dryer to external venting
point in roof or wall. For each bend or elbow add 5 feet (1.52 meter) to your total duct run calcu-
lation. The VTX-DEDPV can be used on runs up to 130 feet (39.6 meter).
Fan location
The VTX-DEDPV is to be mounted a minimum
of 4 linear feet (1.21 meter) and not more
than 45 linear feet (13.71 linear meters) from
clothes dryer exhaust outlet. A secondary lint
trap can be used where required and in appli-
cations where excessive dryer lint generation
is likely to increase the time interval between
routine maintenance of the dryer booster fan.
The VTX-DEDPV is to be attached with the 4
ADC4 clamps (included) to permit periodic
inspection of the blower. Refer to mainte-
nance instructions for inspection recommen-
dations. All duct connections should be prop-
erly sealed to prevent leakage and loss of fan
performance.
Roof exhaust
Roof exhaust
Wall exhaust

2480 BOUL. DES ENTREPRISES TERREBONNE, QUEBEC J6X 4J8
450 477.1100 | ATMOSPHERE.COM
Page : 4
STEP 1 — Install the mounting bracket on both side of
the fan
REMARQUE : Fan mounting can be done at any angle
however, vertical mounting is recommended to reduce
condensation buildup in the fan. If a horizontal installa-
tion is necessary and condensation buildup may pose a
problem, a 1/4” (6 mm) hole drilled in the bottom of the
housing (along with an NPT insert (by others) and drain
tubing) may be installed to allow condensation to drain.
STEP 2 — Mount the fan
Using wood screws provided, attach the mounting
bracket to a support beam at the selected location. For
proper operation, the control box (located on the fan)
needs to be positioned to provide access to the indica-
tor panel RJ12 female connector and the tubing con-
nections.
STEP 3 — Install acces duct on inlet and oulet and se-
cure with ADC4
Install the 8 ” long cleanout duct using the ADC4 duct
clamps. See dimensional data on next page.
STEP 4 — Install acces duct on inlet and oulet and secure with ADC4
Drill a 1/4 inch diameter hole in the inlet duct wall 4 to 8 inches from the inlet of the fan. Carefully
insert the grommet into the hole.
Do not connect the tubing in such a manner as to allow condensation from the duct to collect in
the tubing. Mark the opposite end of the pressure tubing ½ inch from the edge and insert into
the grommet until the marking is reached.
Indicator panel
The VTX-DEDPV is equipped with a remote mounted low voltage operation indicator panel. This
panel contains a RGB LED that will indicate proper operation of the booster fan. In the event of a
problem with the system, it will indicate the nature of the problem.
INSTALLATION INSTRUCTIONS
Fan Installation VTX-DEDPV

Ⓒ 2022 ATMOSPHERE INC.
REV R-1122
Page : 5
MORE —
INSTALLATION INSTRUCTIONS
IMPORTANT — The dryer duct in which the VTX-DEDPV is installed must terminate with a dryer
exhaust hood with a apper or have a backdraft damper installed near the exterior termination.
Lenght of the unit
when assembled
27.5’’ (698 mm)
1/4’’ hole
(6.35mm)
Acces ductADC4
Indicator panel installation
STEP 1 — Selecting panel location
The VTX-DEDPV indicator panel mounts near the dryer
in a location that will be visible to the operator of the
dryer. The indicator panel is supplied with 50 feet (15.2
meter) of cable. Ensure that the indicator panel and
booster fan are located to allow their connection with
this cable.
STEP 2 — Connection and mounting panel
The indicator panel is a low voltage device that is not
required to be installed in an electrical junction box. If
provided with clearance for the cable and terminal block
it can be mounted to a wall using appropriate fasteners.
If installer chooses to mount indicator panel in a single
gang junction box (by others), it should not be installed
in a box that contains high voltage wiring or devices.
Both end of the 50 foot (15.2 meter) cable have a RJ12
male connector.
STEP 3 — Warning label
Install waining label sticker next to the indicator panel. The VTX-DEDPV is equipped with a re-
mote mount, low voltage, operation indicator panel. This wall-mounted indicator panel contains

2480 BOUL. DES ENTREPRISES TERREBONNE, QUEBEC J6X 4J8
450 477.1100 | ATMOSPHERE.COM
Page : 6
a RGB LED that is intended to visually alert the occupant of any detected faults.
STEP 4 — Connect indicator panel cable to the fan
Connect both end RJ12 of the 50 foot (15.2 meter) cable, one end to the fan jonction box female
connector and one end the the female connector on the back of the indicator panel.
VTX-DEDPV Calibration procedure
IMPORTANT — Make sure all of the following are performed before supplying power to the
VTX-DEDPV. Conrm the VTX-DEDPV and the entire duct system is completely installed and clear
of lint. (Required for proper calibration)

Ⓒ 2022 ATMOSPHERE INC.
REV R-1122
Page : 7
• Conrm the dryer is o and cool.
• Conrm all lint traps are empty of lint and reinstalled in their proper position.
• Conrm the dryer is empty of clothing.
• Conrm the door on the dryer is closed.
• Supply power by plugging in the power cord or cycling the power circuit that supply the
VTX-DEDPV
NOTE — Within 10 seconds of the VTX-DEDPV dryer booster being supplied power, it will come
on and run for up to 15 - 20 seconds. This is a calibration period and will only happen when the
VTX-DEDPV is rst powered, LED is ashing blue during calibration mode and after calibration
mode motor and LED will shut o. The VTX-DEDPV is now calibrated and the clothes dryer can be
used.
NOTIFICATION PANEL STATUS MODE
CALIBRATION MODE (Flashing blue LED)
PROPER VENTING MODE (Steady green LED)
When the VTX-DEDPV is on, the green LED will be continuously on.
PRESSURE FAULT MODE (Flashing orange LED) If at anytime during the calibration or operating
cycle of the VTX-DEDPV and the dryer there is excessive pressure sensed, the notication panel
will ash the orange LED. The VTX-DEDPV will continue to operate to try to clear the blockage.
Stop the dryer immediately and have the vent system inspected by someone qualied to do so.
The power to the VTX-DEDPV will need to be removed to clear the fault condition and turn the
VTX-DEDPV motor o. The VTX-DEDPV calibration cycle will need to be performed. (See trouble-
shooting for complete details)
CIRCUIT FAILIURE MODE (Flashing pink LED).
If at anytime during the calibration or operating cycle the VTX-DEDPV is not fonctionning proper-
ly due to a circuit or motor failiure stop the dryer immediately, turn o power of the VTX-DEDPV
and contact the manufacturer.
TEMPERATURE FAULT MODE (Flashing red LED) The VTX-DEDPV has a non-resettable thermal
fuse link which will trigger when exhaust temperatures exceed 196°F. This is a safety feature de-
signed to prevent the VTX-DEDPV from operating during abnormal/dangerous drying conditions.
Call technical support for authorization before opening the electrical compartment; check resis-
tance across the thermal overload protector.
RECOMMENDED MAINTENANCE
Depending on use, but at least once a year, we recommend cleaning the dryer exhaust vent. On
an annual basis, make sure that exhaust hood apper or backdraft damper is clean of lint and
moves freely. The VTX-DEDPV motor is maintenance free. If the VTX-DEDPV is acting erratically,
perform the calibration procedure.
Fan impeller may accumulate lint. Periodic inspection, based upon dryer usage, should be per-
formed to ensure that the fan impeller is not obstructed or loaded with lint.

2480 BOUL. DES ENTREPRISES TERREBONNE, QUEBEC J6X 4J8
450 477.1100 | ATMOSPHERE.COM
Page : 8
To inspect and clean the impeller :
• Disconnect the incoming power supply at the source.
• Loosen the ADC4 fast clamps and remove the 8-inch extender ducts from the fan inlet
and outlet; remove any lint buildup on the impeller and near the outlet.
• Reconnect the duct to the fan. Turn power supply back on to recalibrate the unit.
WARNING — Do not blow into the pressure sampling tube in the direction of the circuit board.
The pressure sensor is a very sensitive device that can be destroyed if subjected to the pressure
created by someone blowing strongly into it.
TROUBLESHOOTING
IMPORTANT — All faults are indicated by a dierent colored LED light or no lights on notica-
tion panel. Faults must be investigated as outlined below and must only be cleared once a thor-
ough investigation of the dryer vent system and dryer has been performed by someone qualied
to do so. Perform VTX-DEDPV calibration procedure to clear any faults once investigation is com-
pleted.
No indicator light | VTX-DEDPV not operating when dryer runs.
• The VTX-DEDPV is interlocked to the dryer by sensing the pressure inside the exhaust
duct when the dryer turns on. Replace the tubing if damage is observed.
• Dryers are equipped with operating temperature controls that monitor drying
temperatures. Normal exhaust temperatures should not exceed 167°F. If the safety
thermal fuse in the VTX-DEDPV trips, the dryer is operating outside its limits. Contact
the dryer manufacture and replace the VTX-DEDPV.
• If the dryer is operating and there is no green LED on the notication panel, stop the
dryer immediately and have the vent system inspected by someone qualied to do so.
PRESSURE FAULT MODE (Flashing orange LED)
If at anytime during the calibration or operating cycle of the VTX-DEDPV and the dryer there is
excessive positive pressure of +0.16” W.C. sensed for over four minutes, the notication panel will
ash the orange LED. Stop the dryer immediately and have the vent system inspected by a per-
son qualied to do so. This is an indication of excessive back pressure in the vent system.

Ⓒ 2022 ATMOSPHERE INC.
REV R-1122
Page : 9
WIRING DIAGRAM

2480 BOUL. DES ENTREPRISES TERREBONNE, QUEBEC J6X 4J8
450 477.1100 | ATMOSPHERE.COM
Page : 10
WARRANTY
Ten (10) Year Warranty
This warranty supersedes all prior warranties
DURING ENTIRE WARRANTY PERIOD — Atmosphere will repair or replace any part which has
a factory defect in workmanship or material. Product will need to be returned to the Atmosphere
factory, together with a copy of the purchase invoice and identied with RMA number.
FOR FACTORY RETURN YOU MUST :
• Have a Return Materials Authorization (RMA) number. This may be obtained
by contacting Atmosphere at [email protected]. Please have the purchase
invoice available.
• The RMA number must be clearly written on the outside of the box or it will be refused.
• All parts and/or product will be repaired/replaced and shipped back to buyer.
No credit will be issued.
OR
The distributor may place an order for the warranty part and/or product and will be invoiced.
The distributor will receive a credit equal to the invoice only after product is returned, prepaid,
and veried to be defective.
ATMOSPHERE WARRANTY TERMS DOES NOT PROVIDE FOR REPLACEMENT WITHOUT CHARGE
PRIOR TO INSPECTION FOR A DEFECT. REPLACEMENTS ISSUED IN ADVANCE OF DEFECT IN-
SPECTION ARE INVOICED AND CREDIT IS PENDING INSPECTION OF RETURNED MATERIAL.
DEFECTIVE MATERIAL RETURNED BY END USERS SHOULD NOT BE REPLACED BY THE DISTRIB-
UTOR WITHOUT CHARGE TO THE END USER, AS CREDIT TO DISTRIBUTORS ACCOUNT WILL BE
PENDING INSPECTION AND VERIFICATION OF ACTUAL DEFECT BY ATMOSPHERE.
THE FOLLOWING WARRANTIES DO NOT APPLY :
• Damages from shipping, either concealed or visible. Claims must be led with freight
company.
• Damages resulting from improper wiring or installation.
• Damages or failure caused by act of God, or resulting from improper consumer
procedure, such as :
1. Improper installation
2. Improper maintenance.
3. Misuse, abuse, abnormal use, or accident, and incorrect electrical connections.
4. Removal or any alteration made on the Atmosphere label control number
or date of manufacture. Any other warranty, expressed, implied or written, and to
any consequential or incidental damages, loss or property, revenues, or prot, or
costs of removal, installation or reinstallation, for any breach of warranty.

Ⓒ 2022 ATMOSPHERE INC.
REV R-1122
Page : 11
WARRANTY INVALIDATION
The user must keep a copy of the purchase invoice to verify purchase date.
This warranty gives you specic legal right, and is subject to an applicable consumer protection
legislation. You may have additional rights which vary from state to state.
LIMITATION OF WARRANTY AND LIABILITY
This warranty does not apply to any Atmosphere product or part which has failed as a result of
misinstallation or abuse, incorrect electrical connections or alterations made by others, or use
under abnormal operating conditions or misapplication of the product or parts. Atmosphere will
not approve any payment for any repair not made by us or our authorized agent without prior
written consent. The foregoing shall constitute our sole and exclusive warranty and our sole
exclusive liability, and is in lieu of any other warranties, whether written, oral, implied or statutory.
There are no warranties which extend beyond the description on the page hereof. In no event,
whether as a result of breach of contract, or warranty or alleged negligence, defect incorrect
advice or other causes, shall Atmosphere be liable for special or consequential damages, includ-
ing but not limited to, loss of prots or revenue, loss of use of equipment or any other associated
equipment, cost of capital, cost of substitute equipment, facilities or services, downtime costs or
claims of customers of purchase for such damages. Atmosphere neither assumes or authorizes
any person to assume for it any other liability in connection with the sale of product(s) or part(s).
Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damag-
es so the above limitations and exclusions may not apply to you.
WARNING — ATMOSPHERE reserves the right to make technical changes. For up-to-date docu-
mentation, please refer to www.atmosphere.com
Table of contents
Popular Fan manuals by other brands

Progress Lighting
Progress Lighting AirPro CALERA installation manual

Uberhaus
Uberhaus 70395007 Operator's manual

Timco Tools
Timco Tools 103093364 instruction manual

Ansult
Ansult 012904 operating instructions

Ebmpapst
Ebmpapst D4D225-CC01-02 operating instructions

Ebmpapst
Ebmpapst W4E300-DS72-02 operating instructions