8
Technical features and dimensions
4
5
6
7
8
440
550
660
770
900
2.1 - TECHNICAL FEATURES
• MODULEX is a compact, gas fired, Low NOx, condensing
boiler, made up by one sectional boiler body,
This boiler body consists of two or more modules (from 4 to
8), which cannot be separated from each other, being un-
der the same protecting casing, and are set to operate se-
parately or in cascade. These modules are connected to a
single smoke exhaust manifold and are controlled by a
single microprocessor (BMM), which manages completely
the temperatures from the point of view, both operational
and safety. This version is suitable for only central heating
CAUTION: These devices are not suitable for the
production of water for human consumption
• Efficiency at full load with temperature 30/50°C = 101,1%.
At part load (30% of the nominal) with 30°C return tempe-
rature = 107,2%.
• Efficiency Class:
• Each module, is composed of a combustion chamber, me-
tallic fiber pre-mix burner, modulating fan, gas valve, igni-
tion electrode, flame detection, NTC sensor for manage-
ment control (BMM), local temperature control and afety
thermostat.
• Each single boiler is equipped with NTC sensors for global
temperature control on the flow and return manifolds.
• Integral, non allergic, synthetic wool insulation.
• Total premix burner, modulating burner with a radiant “me-
tal sponge” (NIT). Premix antechamber combustion. Auto-
matic backflow valve, preventing gas in the place of instal-
lation.
• Fully pre-mixed, radiating, modulating, metallic sponge
burner, Automatic no return diaphragm for separation from
combustion chamber.
• Nominal input, per module: max. 108 kW, min. 22 kW.
• Noise level at maximum output: lower than 50 dBA.
• Modules configuration possibilities:
•Possible cascade installation of 2 or more Modulex
•Heating Operation: setting of instantaneous output by a
main microprocessor, with a comparison parameters pre-
setting between the requested temperature (or calcula-
ted by the outer compensator) and the global flow tem-
perature.
2TECHNICAL FEATURES
AND DIMENSIONS
• Logic of operation:
A) Output sharing on as many modules as possible at min.
load (down to 22 kW) for the max. efficiency..
B) Automatic operation hour splitting-up system for each
module to guarantee the best homogeneous use.
C) D.H.W. production, via a storage tank loading pump or a
three way diverting valve, controlled by a priority sensor
through the E 8 heating controller.
D) Output check of each module for any calibration and/or
assistance by secret access code.
• Possibility of controlling the output of each single module.
•
Heating request control: temperature set point
andmodulation level.
•
Monitoring of boiler and temperature status.
•
Alarm control.
•
Parameters setting.
•
Relay for control of the operation of a pump at constant
flow rate.
•
0÷10V analogical output for control of a modulating pump.
•
Emergency operation: it avoids C.H. system shut down
caused byan interruption in communication with the boiler
plant’s automation system: : (in case of remote control of
the complete boiler house):
•
Input for “Constant setpoint”: 82°C, maximum output 50%.
•
Alarm reset input.
•
Alarm relay signal.
• Gas connecting pipes, flow/return water pipes, arranged
for any connection (by the opposite end).
• Integral easily removable panel set (painted steel panels).
• Smoke exhaust pipe, adjustable on the right, the left and
behind the heating system.
• Condensate collecting tank equipped with drain siphon
and stainless steel smoke chamber.
• Built-in air vent.
• Weights and dimensions are limited (see table at par. 1.2)
•Instrument panels secreted (POP-UP)
SENSORS supplied with the boiler:
• 00262208 outdoor temperature sensor
• 00262209 flow temperature sensor for mixed zone
• 00262210 boiler temperature sensor
• 00262211 D.H.W. storage temperature sensor
Optional accessories:
•00262603 Sensor (Solar) PT1000
•00262829 Acid condensate inhibitor 1500 kW
•00361044 Cleaning kit bodies
•00361332 Kit thermoregulation E8
•00361358 Remote control kit BM8
•00361359 Kit custody thermoregulation
•00361545 Kit expansion module E8
•Primary circuits: COMPO S - PREMO S - PREMO C -
COMPO S RINGBOXCOVER. - Safetydevices -, see cap.
3.10
•00361997 Mixing header
• 0036..... gas terminal Support kit
• 0036....... Boiler support Kit 10 cm