916SA: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
12
MAXIMUM EQUIVALENT VENT LENGTH - Ft. (M)
NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows. Use Deductions
from Maximum Equivalent Vent Length to determine allowable vent length for each application.
1. 40K Inducer Outlet Restrictor disk (P/N 337683-401; 1.25-in. (32 mm) Dia.) shipped in the loose parts bag or available through Replacement Components required under 10-ft. (3 M)
TEVL in all orientations. Required for installations from 0 - 2000 ft. (0 to 610 M) above sea level. Failure to use an outlet restrictor may result in flame disturbances or flame sense
lock-out.
2. 26K (shipped in loose parts bag) & 60K Inducer Outlet Restrictor disk (P/N 337683-401; 1.25-in. (32 mm) Dia. available through Replacement Components) required for less than 5-ft.
(1.5 M) TEVL in downflow and horizontal orientations only. Required for installations from 0 - 2000 ft. (0 to 610 M) above sea level.
3. 120K & 140K Inducer Outlet Restrictor disk (P/N 337683-402; 1.50-in. (38 mm) Dia. available through Replacement Components) required for less than 5-ft. (1.5 M) TEVL in downflow
and horizontal orientations only. Required for installations from 0 - 2000 ft. (0 to 610 M) above sea level.
A13110
Deductions from Maximum Equivalent Vent Length - Ft. (M)
NOTE:
1. Use only the smallest diameter pipe possible for venting. Over-sizing may cause flame disturbance or excessive vent terminal icing or freeze-up.
2. NA - Not allowed. Pressure switch will not close, or flame disturbance may result.
3. Vent sizing for Canadian installations over 4500 ft (1370 M) above sea level are subject to acceptance by local authorities having jurisdiction.
4. Size both the combustion air and vent pipe independently, then use the larger size for both pipes.
5. Assume the two 45_ elbows equal one 90_ elbow. Wide radius elbows are desirable and may be required in some cases.
6. Elbow and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
7. The minimum pipe length is 5 ft. (2 M) linear feet (meters) for all applications.
8. Use 3-in. (76 mm) diameter vent termination kit for installations requiring 4-in. (102 mm) diameter pipe
Unit Size 26,000 240,000 1 60,000 280,000 100,000 3120,000 140,000 3
Altitude
(feet)
Pipe Dia.
(in) 1 ½ 2 1 ½ 2 2 ½ 1
½2 2 ½ 3 1 ½ 2 2 ½ 3 4 2 2 ½ 3 4 2 ½ 3 4 2 ½ 3 4
0-2000 70 200 40 155 185 20 100 175 200 15 55 130 175 200 20 80 175 200 10 75 185 5 65 155
2001-3000 65 190 35 150 175 95 165 185
10
49 125 165 185 15 75 165 185 70 175
N/A
60 140
3001-4000 60 175 30 135 160 16 90 155 175 115 155 175 155 175 5 65 165 120
4001-4500 55 160 25 130 155
15
85 150 170 44 110 150 165
10
70 170
N/A
60 160 50 110
4501-5000 125 145 80 145 165 145 160 65 150 165 45 100
5001-6000 50 145 20 120 130 75 140 155 41 100 135 150 140 155 155 35 80
6001-7000 45 135 15 110 120 13 70 130 145
N/A
38 90 125 140 60 135 145 50 140 30 65
7001-8000 40 120 10 100 110 10 65 120 135 36 120 125
N/
A
55 125 135 46 130 25 45
8001-9000 35 110 90 95 5 60 115 125 33 80 110 115 50 115 125 43 120 15 30
9001-10000 30 95 5 80 85 N/
A55 105 115 30 75 100 105 45 100 115 39 115 10 15
Maximum Equivalent Vent Length - Meters
Unit Size 26,000 240,000 160,000 280,000 100,000 3120,000 140,000 3
Altitude
(meters)
Pipe Dia.
(mm) 38 51 38 51 64 38 51 64 76 38 51 64 76 102 51 64 76 102 64 76 102 64 76 102
0-610 21.3 60.9 12.1 47.2 56.3 6.0 30.4 53.3 60.9 4.5 16.7 39.6 53.3 60.9 6.0 24.3 53.3 60.9 3.0 22.8 56.3 1.5 19.8 47.2
611-914 19.8 57.9 10.6 45.7 53.3 28.9 50.2 56.3
3.0
14.9 38.1 50.2 56.3 4.5 22.8 50.2 56.3 21.3 53.3
NA
18.2 42.6
915-1219 18.2 53.3 9.1 41.1 48.7 4.8 27.4 47.2 53.3 35.0 47.2 53.3 47.2 53.3 1.5 19.8 50.2 36.5
1220-1370 16.7 48.7 7.6 39.6 47.2
4.5
25.9 45.7 51.8 13.4 33.5 45.7 50.2
3.0
21.3 51.8
NA
18.2 48.7 15.2 33.5
1371-1524 38.1 44.1 24.3 44.1 50.2 44.1 48.7 19.8 45.7 50.2 13.7 30.4
1525-1829 15.2 44.1 6.0 36.5 39.6 22.8 42.6 47.2 12.4 30.4 41.1 45.7 42.6 47.2 47.2 10.6 24.3
1830-2134 13.7 41.1 4.5 33.5 36.5 3.9 21.3 39.6 44.1
NA
11.5 27.4 38.1 42.6 18.2 41.1 44.1 15.2 42.6 9.1 19.8
2135-2438 12.1 36.5 3.0 30.4 33.5 3.0 19.8 36.5 41.1 10.9 36.5 38.1
NA
16.7 38.1 41.1 14.0 39.6 7.6 13.7
2439-2743 10.6 33.5 27.4 28.9 1.5 18.2 35.0 38.1 10.0 24.3 33.5 35.0 15.2 35.0 38.1 13.1 36.5 4.5 9.1
2744-3048 9.1 28.9 1.5 24.3 25.9 NA 16.7 32.0 35.0 9.1 22.8 30.4 32.0 13.7 30.4 35.0 11.8 35.0 3.0 4.5
Pipe Diameter (in): 1-1/2 2 2-1/2 3 4
Mitered 90º Elbow 8 (2.4) 8 (2.4) 8 (2.4) 8 (2.4) 8 (2.4)
Medium Radius 90º Elbow 5 (1.5) 5 (1.5) 5 (1.5) 5 (1.5) 5 (1.5)
Long Radius 90º Elbow 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9)
Mitered 45º Elbow 4 (1.2) 4 (1.2) 4 (1.2) 4 (1.2) 4 (1.2)
Medium Radius 45º Elbow 2.5 (0.8) 2.5 (0.8) 2.5 (0.8) 2.5 (0.8) 2.5 (0.8)
Long Radius 45º Elbow 1.5 (0.5) 1.5 (0.5) 1.5 (0.5) 1.5 (0.5) 1.5 (0.5)
Tee 16 (4.9) 16 (4.9) 16 (4.9) 16 (4.9) 16 (4.9)
Concentric Vent Termination NA 0 (0.0) NA 0 (0.0) NA
Standard Vent Termination 0 (0.0) 0 (0.0) 0 (0.0) 0 (0.0) 0 (0.0)
Long Medium Mitered
Concentric
Standard 2-in., 3-in., or
optional 4-in. termination.
ELBOW CONFIGURATIONS VENT TERMINAL CONFIGURATIONS