
n
LIMIT SWITCHES
Normally closed limit switch (LS) completes the control circuit.
Should the leaving-air temperature rise above the maximum
allowable temperature, the limit switch opens and the control circuit
"breaks." Any interruption in the control circuit instantly closes the
gas valve and stops gas flow to the burners and pilot. The blower
motor continues to run until LS resets.
When the air temperature at the limit switch drops to the
low-temperature setting of the limit switch, the switch closes and
completes the control circuit. The direct-spark ignition system
cycles and the unit returns to normal heating operation.
Table 4--LED Indications
STATUS CODE
Normal Operation 2
Hardware Failure
Fan On/Off Delay Modified 2
Limit Switch Fault
Flame Sense Fault
Four Consecutive Limit Switch Faults
Ignition Lockout Fault
Induced-Draft Motor Fault
Rolloat Switch Fault
Internal Control Fault
Temporary Lock-Out 1 hr auto reset 1
NOTES:
LED INDICATION
On
Off
1 Flash
2 Flashes
3 Flashes
4 Flashes
5 Flashes
6 Flashes
7 Flashes
8 Flashes
9 Flashes
i, This code indicates an internal processor fault that will reset itself ill one hr.
Fault Call be caused by stray RF signals ill tile strueture or nearby. This is a UL
requirement.
2. LED indicates acceptable operation. Do not ehange ignition control board.
3. When W1 is energized the burners will remain oil fur alninilnum of 60 see.
4. If more thanone error mode existsthey willbe displayed on the LED ill se
quellce.
ROLLOUT SWITCH
The function of the rollout switch is to close the main gas valve in
the event of flame rnllout. The switch is located above the main
burners. When the temperature at the rollout switch reaches the
maximum allowable temperature, the control circuit trips, closing
the gas valve and stopping gas flow to the burners. The indoor
(evaporator) fan motor (IFM) and induced draft motor continue to
run until switch is reset. The IGC LED will display FAULT CODE
7.
Step 3---START-UP COOLING AND MAKE ADJUST-
MENTS
Complete the required procedures given in the Pre-Start-Up
section befnre starting the unit. Do not jumper any safety devices
when operating the unit. Do not operate the compressor when the
outdoor temperature is below 40°F (4.4°C) (unless accessory
low-ambient kit is installed). Do not rapid-cycle the compressor.
Allow 5 minutes between on cycles to prevent compressor damage.
CHECKING COOLING CONTROL OPERATION
Start and check the unit for proper cooling control operation as
follows:
1. Place room thermostat SYSTEM switch in OFF position.
Observe that blower motor starts when FAN switch is placed
in ON position and shuts down when FAN switch is placed
in AUTO position.
2. Place SYSTEM switch in COOL position and FAN switch
in AUTO position. Set cooling control below room
temperature. Observe that compressor, condenser fan, and
evaporator blower motors start. Observe that cooling cycle
shuts down when control setting is satisfied. The evaporator
fan will continue to run for 30 sec.
3. When using an auto-changeover room thermostat, place
both SYSTEM and FAN switches in AUTO positions.
Observe that unit operates in Heating mode when
temperature control is set to call for heating (above room
temperature) and operates in Cooling mode when
temperature control is set to call for cooling (below room
temperature).
IMPORTANT: Three-phase, scroll compressors are direction
oriented. Unit must be checked to ensure proper compressor
3-phase power lead orientation. If not corrected within 5 minutes.
the internal protector will shut off the compressor. The 3-phase
power leads to the unit must be reversed to correct rotation. When
turning backwards, the difference between compressor suction and
discharge pressures may be dramatically lower than normal.
CHECKING AND ADJUSTING REFRIGERANT CHARGE
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
When evaluating the refrigerant charge, an indicated
adjustment to the specified factory charge must always be very
minimal. If a substantial adjustment is indicated, an abnormal
condition exists somewhere in the cooling system, such as
insufficient airflow across either coil or both coils.
The refrigerant system is fully charged with R-22 refrigerant and
is tested and factory sealed. Allow system to operate a minimum of
15 minutes before checking or adjusting charge.
NOTE: Adjustment of the refrigerant charge is not required unless
the unit is suspected of not having the proper R-22 charge.
A refrigerant charging label is attached to the outside of the service
access door. The charging label and the tables shown refer to system
temperatures and pressures in cooling mode only.
018 Model Only
The charging chart (see Table 6) includes the required liquid line
temperature at given discharge line pressures and outdoor ambient
temperatures.
An accurate subcooling thermocouple or thermistor-type
thermometer and a gauge manifold are required when using the
subcooling charging method for evaluating the unit charge. Do not
use mercury or small dial-type thermometers because they are not
adequate for this type of measurement.
Proceed as follows:
1. Remove caps from low- and high-pressure service fittings.
2. Using hoses with valve core depressors, attach low- and
high-pressure gauge hoses to low- and high-pressure
service fittings, respectively.
3. Start unit in Cooling Mode and let unit run until system
pressures stabilize.
4. Measure and record the fnllowing:
a. Outdoor ambient-air temperature (°F (°C)db).
b. Liquid line temperature (°F (°C).
c. Discharge (high-side) pressure (psig).
5. Using "Cooling Charging (;harts," compare outdoor-air
temperature (°F (°C) db) with the discharge line pressure
(psig) to determine desired system operating liquid line
temperature (See Table 6).
6. Compare actual liquid line temperature with desired liquid
line temperature. Using a tolerance of-+ 2°F. (-+1.1°C) add
refrigerant if actual temperature is more than 2°F (1.1°C)
higher than proper liquid line temperature, or remove
refrigerant if actual temperature is more than 2°F (1.1°C)
lower than required liquid line temperature.
18