40SMC---N
GB - 2
Safety considerations
Installation and servicing of air conditioning equipment can
be hazardous due to system pressure and electrical
components.
Only trained and qualified service personnel should install,
repair or service air conditioning equipment.
All maintenance operations must be carried out by skilled
personnel.
When working on air conditioning equipment, observe
precautions on the literature, tags and labels attached to the
unit and other safety precautions that may apply.
Follow all safety codes.
Wear safety glasses and workgloves.
Use a quenching cloth for unbrazing operations.
WARNING:
Before performing service or maintenance operations turn off
the main power switch to unit.
Electrical discharge could cause personal injury.
The 40SMC---N unit is designed for installation with ducts.
If this is not the case, the installer must place a protection
mesh in the discharge according to the standards in force.
This unit is not suitable for use in laundry premises.
Only use original spare parts when repairing and pay special
attention when positioning the same.
They must be placed indentically to the previus ones.
These units must not be installed in an explosive
atmosphere.
These units must not be installed in an explosive
atmosphere.
The units con operate in residential, commercial and light
industrial installations which have normal radioelectrical
atmospheres consultation must be made for other applications.
WARNING:
This unit base can incorporate a drain pan.
Do not drill through base or damage to drain pan and
refrigerant circuit may result.
The air must be filtered before entering the evaporator, or the
guarantee becomes invalid. Do not use undue force or
excessive manipulation of the refrigerant connections and
pipes.Ensure that no piping touches any adjacent part.
If necessary, adjust carefullly because the guarantee does not
cover leaks due to a negligent handling of the pipes. Split
units can contain a maintenance charge. Purge before de-
soldering the plugs.
Table I: Phisical data
40SMC---N 009 012 018 024 028 036 048 060
Weight 22 22 22 36 36 36 60 60
Indoor coil
Material Aluminium/Copper
Quantity 11111111
Front surface m20,145 0,145 0,145 0,245 0,245 0,245 0,400 0,400
Fins per inch 14 14 14 14 12 14 12 14
Nº rows -tube diameter 2...3/8” 2...3/8” 3...3/8” 2...3/8” 3...3/8” 3...3/8” 3...3/8” 3...3/8”
Fan motor
Quantity 11111111
Electrical capacitor µF 4 5 4,5 5,5 6,3 8 6 8
Nom. power (1) W 80 90 100 190 220 305 420 560
Nom. cons. (1) Amp 0,36 0,40 0,45 0,85 1,0 1,35 1,90 2,50
Fan
Quantity 22222222
Diameter - lenght mm 146x176 146x176 146x176 185x240 185x240 185x240 200x240 200x240
Refrigerant
Type
R-410A R-410A R-410A R-410A R-410A R-410A R-410A
R-410A
Control Restrictor (3) Restrictor (3) Restrictor (3) Restrictor (3) Restrictor (3) Restrictor (3) Restrictor (3) Restrictor(3)
Approx. charge (2) Kg See note See note See note See note See note See note See note See note
Air filter Washable Washable Washable Washable Washable Washable Washable Washable
Quantity 11111111
DImensions mm 685x218 685x218 685x218 684x283 684x283 684x283 1172x308 1172x308
NOTES:
(1) Motor on high speed.
(2) Refrigerant charge depends on the outdoor unit to be connected.
(3) The restrictor is located into the outdoor unit.
Table II - Electrical data (cooling only) - 38GL(S) - 38BC(S) + 40SMC---N
38GL(S) - 38BC(S) 09 12 18 24 28 36 48 60
+ ++++++++
40SMC---N 009 012 018 024 028 036 048 060
Operation voltage V/Ph/Hz ❍❍❍❍❍/●❍/●❍/●●
CONSUMPTION
Nominal *kW 1,03 1,23 1,82 2,26 2,80 3,53 4,05 5,20
Amp 4,56 5,45 8,23 10,20 12,67/4,22 16,0/5,32 13,6/7,80 18,6/10,7
Máximum ** kW 1,23 1,47 2,18 2,71 3,36 4,23 4,50 6,60
Amp 5,56 6,65 9,86 12,30 15,20/5,06 19,15/6,37 15,07/8,67 23,6/13,6
On short circuit Amp 28,5 35,0 51,5 78,0 84,5/47,5 108,0/49,0 103,0/53,0 124,0/64,0
NOTES:
*Outdoor dry bulb temperature = 35oC; Indoor wet bulb temperature = 19oC.
** Outdoor dry bulb temperature = 43oC; Indoor wet bulb temperature = 23oC.
❍Outdoor unit operation voltage 230V ~ 50Hz
●Outdoor unit operation voltage 400V 3N~ 50Hz