
14
Capacitors
Remove the plug from the socket and remove the cables
from the capacitor. Discharge the capacitor, shortcircuiting
its terminal with the blade of a screwdriver.
Take an Ohmmeter and select the x 100 scale. Then
connect the sensors of the Ohmmeter to two terminals of
the capacitor.
a) If the capacitor is in order the needle will go immediately
to zero and then will indicate high resistance.
b) If the capacitor is shorted the needle will go to zero and
stop in that position.
c) To check if a capacitor with metallic body is shorted it is
necessary to put a sensor of the Ohmmeter in contact with a
terminal of the capacitor and the capacitor body. If capacitor is
shorted the instrument will indicate the electric continuity.
d) To check the capacitor polarity it is necessary to put the
Ohmmeter terminals on the capacitor terminals, verifying
that the needle goes to zero and then indicates
the maximum resistance.
Then reverse the position of the Ohmmeter sensor on
the capacitor terminals: the needle will go to zero and
then come back to the normal position.
In this way the capacitor will be discharged and then
recharged by the Ohmmeter battery.
Compressor thermal overload protection
The test of the compressor thermal overload protection
(Klixon) must be carried on before the continuity test;
remove the plug and the connection cables from the
thermal overload protection. Be sure that the protection is
cool and closed. If necessary the Klixon must be removed
from the compressor body and cooled before the test.
Fan motor
Before the test it is necessary to rotate the fans by hand to
ensure that their bearings are not seized and their wheels
do not touch the housing.
Remove the plug and check the run capacitor to be sure
that it is properly working; then:
Fig. 2Fig. 1
Capacitor To capacitor
body
To each
terminal
Capacitor
body
Capacitor Compressor
A) Leaks
Torch leak detector use
To carry out a leak test of a refrigerant circuit it is necessary to
move the sensor pipe terminal of the leak detector along all
the joints and the parts containing refrigerant.
Maximum sensitivity of the detector can be obtained by
keeping the flame high enough to get a red copper plate.
The flame is blue if there is no refrigerant in the air.
When the sensor pipe draws in air containing refrigerant the
colour of the flame changes according to the concentration
of the refrigerant in the air.
1. A small leak will cause the flame colour to switch from
blue to green.
2. A large leak will cause the flame colour to switch from
blue to violet.
Attention! Do not inhale the fumes of the leak detector when the
sensor pipe is drawing in air heavily polluted with refrigerant.
B) Electric parts
In case of a fault of any electric component, to identify the
problem and to solve it apply the procedures described on
the next pages. To carry out these tests it is necessary to
remove unit front panel.
Supply cable
Check the voltage at the terminals while the plug is
connected to the socket.
Electric conductors
Remove the plug from the socket and check the continuity
of all the conductors and jumpers.
Available power supply
Low voltage is the most common problem.
Voltage must be read by an accurate and reliable voltmeter
whenthe unit isworking inCooling Mode. Themeter sensors
must be inserted in the sensor in parallel with the unit.
Components tests
In case of a suspected electric fault first test the circuit to
identify the faulty part.
The tests must be carried on using a TESTER suitable for
troubleshooting.
Change-over switch
1. Remove the plug from the socket.
2. Insert the tester in the different positions of the change-
over switch shown in the wiring diagram to check the
continuity between the contact and the corresponding
position of the change-over switch.
This test must be carried out only when all cables are
disconnected from the change-over switch.
Room thermostat
1. Remove the plug from the socket.
2. Insert the tester according to the wiring diagram indication
and put the thermostat knob to the maximum cooling
position to check the continuity between thermostat contacts.
This test must be carried on only when all cables are
disconnected from the thermostat.
COMPONENT TESTING PROCEDURE
9