Cellartec 1/8 Ton-SSL User manual

SSL Series Split System
Installation, Operation & Care Manual
CellarTec 1/8 Ton-SSL
CellarTec 1/4 Ton-SSL
CellarTec 1/3 Ton-SSL
CellarTec 1/2 Ton-SSL
w
ww
ww
w.
.a
ap
pe
ex
xw
wi
in
ne
ec
ce
el
ll
la
ar
rs
s.
.c
co
om
m
w
ww
ww
w.
.c
ce
el
ll
la
ar
rt
te
ec
c.
.c
co
om
m
READ AND SAVE THESE INSTRUCTIONS

- 1 -
TABLE OF CONTENTS
Important Safety Information…..........................................2
Features & Specifications…………………….….…………..3
Cellar Construction.…………………………….……………..7
Installer’s Instruction…………….…..….……..……………..8
Electrical Wiring…..…………….…..….……..……………..15
Temperature Control & Humidity Adjustment.………….20
Care Guide…………………………………………………….24
User’ Troubleshooting…….………………………………...25
Customer Support……………………………………………28
Warranty……………………………………………………….29

- 2 -
Important Safety Information
WARNING:
•DO NOT USE A GROUND FAULT INTERRUPTER (GFI).
•A DEDICATED CIRCUIT IS REQUIRED, 15 AMP FOR 1/8-1/3 Ton-SSL
AND 20 AMP FOR 1/2 Ton-SSL.

- 3 -
Features and Specifications
•CELLARTEC split cooling systems CellarTec 1/8-1/2 Ton-SSL are
designed and used to provide a cold temperature between 50~65 °F for a
properly insulated wine room at a normal environment.
•The wine room will maintain humidity of 50~70% RH even when the
environment becomes dry and humid. These temperatures and humilities
are optimized for long term storage of wine.
•SSL units consist of a condensing unit and an evaporator unit, and they
are connected by a liquid line and an insulated suction line.
•SSL condensing units can be located away from the evaporator units and
wine cellars as far as 50 feet, which will bring you quiet operation.
•SSL evaporator units provide low profile and whisper quiet operation. The
evaporator units can be installed on the ceiling in a wine cabinet or room.
The dimensions and capacities are specified as follows:
MODEL EVAP UNIT
W”xD”xH” COND UNIT
L”xD”xH”
Btu/h
CFM
(55/90°F)
BOTTLE
CAPACITY
(55/75°F) REFRIGERANT ELECTRICAL
EVAP UNIT/
COND UNIT
WEIGHT(lb)
EVAP UNIT/
COND UNIT
CellarTec
1/8 TON-
SSL
WM-
15SFCL
16.75x14.5
x4.75
WM-150SCU
18x12x14 1500/180 150
cu ft R134a 115V-60HZ-
0.4A / 115V-
60HZ-3.1A 15/30
CellarTec
1/4 TON-
SSL
WM-
25SFCL
31.75x14.5
x4.75
WM-250SCU
18x12x14 2500/275 250
cu ft R134a 115V-60HZ-
0.4A / 115V-
60HZ-5.7A 30/40
CellarTec
1/3 TON-
SSL
WM-
45SFCL
40.25x14.5
x4.75
WM-450SCU
18x12x14 4500/460 1000
cu ft R134a 115V-60HZ-
0.8A / 115V-
60HZ-6.9A 37/60
CellarTec
1/2 TON-
SSL
WM-
65SFCL
53.75x16.5
x6.75
WM-650SCU
24x18x17 6500/575 1500
cu ft R134a 115V-60HZ-
0.8A / 115V-
60HZ-12A 61/90
Parts included:
Condensing Unit (pressure control, discharge and suction valves installed) +
Filter + Sight Glass
Evaporator Unit (liquid line solenoid valve and expansion valve installed)
Temperature Controller + Air Sensor
CAUTION:
LIQUID AND SUCTION LINES MAY DIFFER FROM WHAT ARE SHOWN
HERE, PLEASE CHECK ON THE UNITS FOR PROPER INSTALLATION.

- 4 -
Fig. 1 WM15-25SFCL Evaporator Unit
Fig. 2 WM45-65SFCL Evaporator Unit
NOTE:
LEAVE MINIMUM 3” CLEARANCE FOR ELECTRICAL WIRING AND
REFRIGERATION PIPING.

- 5 -
Fig. 3 WM150-450SCU Condensing Unit
Fig. 4 WM-650SCU Condensing Unit

- 6 -
Fig. 5 Liquid Filter
Fig. 6 Sight Glass
CAUTION:
LOW AMBIENT TEMPERATURE KIT IS REQUIRED IF THE INSTALLATION
AREA WILL BE BELOW 50°F.

- 7 -
Cellar Construction
This is only a guide and shall be considered as minimum requirements.
All interior walls and floors shall have a vapor barrier and a minimum of R11
insulation. All exterior walls and ceiling shall have a vapor barrier and a minimum
of R19 insulation. The vapor barrier shall be installed on the warm side of the
insulation. All joints, door frames, electrical outlets or switches and any pipes or
vents that go through the enclosure shall be sealed to prevent air and moisture
leakage into the room. Concrete, rock, and brick are not insulation or vapor
barriers.
Doors shall be of a minimum size, insulated to at least R11 and tightly sealed
with high quality weather stripping. Be sure to seal the bottom of the door and fill
gap between the door’s frame and wall before installing the cap molding.
In order to maintain 55 °F in the wine cellar, the ambient temperature
surrounding the enclosure shall not exceed the temperature of the enclosure by
more than 25 °F. No enclosure wall shall receive direct sun or strong wind.
Lighting shall be of low wattage, with a timer to insure lights are not left on when
the enclosure is not occupied.
The cooling system will not be able to maintain the proper temperature if fresh
moisture-laden air is constantly being introduced to the enclosure. Symptoms of
this condition are; unit runs all the time with only a slight reduction in temperature
and/or water overflows from the unit. Because of the temperature difference
between the inside and outside, very small cracks can allow large amounts of
outside air to enter into the enclosure. Please be aware that moisture can pass
through solid concrete, paint and wood. Often a newly constructed room contains
fresh wood, paint, concrete and other building materials. These materials contain
large amounts of moisture. When placed into operation in this type of
environment, the system will work harder to remove this extra moisture resulting
in increased “run” time.

- 8 -
Installer’s Instruction
Federal law requires that CELLARTEC split cooling systems be
installed by an EPA certified refrigeration technician.
CELLARTEC split system is shipped as components and is ready for use only
after a certified refrigeration technician has properly installed, evacuated,
charged and tested the system. Proper installation is critical. Apex can only
warrant the quality of the components. The installation and proper operation of
the system must be warranted by the installer. Installation of the system must be
done in accordance with all state and local building and electrical codes.
The condensing unit and evaporator unit are connected by a liquid line and an
insulated suction line that are supplied by the installer. These lines must be
properly sized for the distance between the two units. After the units and the lines
are installed, the system must be pressure tested. If no leaks are found,
evacuate and charge system. Refrigerant amount will vary depending on the
length of line set.
Fig. 7 SSL Split System Installation

- 9 -
1. Condensing Unit
•Place the condensing units WM150-650SCU in a
properly ventilated location. If it is not, heat exhausted
by the condensing unit will build up and the cooling
system will not operate properly.
•Condensing unit shall be elevated to avoid possible flooding and shaded
from direct sun. It shall not be exposed to temperatures higher than 110
°F or lower than 50 °F (optional low ambient kit available).
•Leave minimum 5 feet clearance for the exhaust side and leave minimum
1 foot clearance for the fresh air intake side.
CAUTION:
IF THE CONDENSING UNIT IS EQUIPPED WITH A LOW AMBIENT
CONDITION KIT, DO NOT TURN ON THE COMPRESSOR UNTIL THE
CONDENSING UNIT HAS BEEN POWERD FOR 24 HOURS.
2. Discharge/Suction Valve Operation (Condensing unit)
Back Position: Normal operation, process and manometer port closed
Front Position: Liquid/suction line connection closed
Middle Position: All ports open for evacuation, charge and manometer reading
BACK POSITION FRONT POSITION MIDDLE POSITION
Fig. 8 ROTALOCK Valve Operation
BACK POSITION FRONT POSITION MIDDLE POSITION
Fig. 9 Base Valve Operation

- 10 -
1 - Process & Manometer; 2 – Receiver Discharge)/Compressor Suction
3 – Liquid Line/Suction Line; 4 - Pressure Control
3. Evaporator Unit
•The WM15-65SFCL evaporator units shall be installed for ceiling mount
with the air supply towards horizontally and air return on the bottom.
•Supply air flow shall be unobstructed for at least 12” for free installation or
2” for deflector installation and return air shall be unobstructed for 6”.
•There is a gravity drain line and the unit shall be installed level or with a
slight angle toward the drain connection. If rise-up is needed, a
condensation pump must be used.
4. Thermostat and Air Sensor
CAUTION:
USE 18 GAUGE THERMOSTAT WIRE.
•The thermostat with a built-in air sensor can be installed in the wine room
5 ft above the floor in an area with good air circulation at average temp.
•If the thermostat is mounted outside the wine room, a remote air sensor is
required inside the wine room. The air sensor can be located in a well
circulated or in the return air area, but not the supply air or air dead area.
5. Piping, Evacuating, Charging and Starting
CAUTION:
•ALWAYS USE THE SUPERHEAT AND SUBCOOLING, PRESSURE
READINGS TO CHARGE REFRIGERANT PROPERLY, THE LISTED
CHARGES ARE FOR REFERENCE ONLY.
•CHARGE 15% MORE REFRIGERANT IN THE SUMMER IF THE UNIT IS
EQUIPPED WITH A LOW AMBIENT CONDITION KIT.
NOTES:
•THE VALVE CONNECTION SIZES OF CONDENSING UNIT AND THE LINE
CONNECTION SIZES OF EVAPORATOR UNIT ARE NOT NECESSARY
THE SAME AS THE ABOVE LISTED LINE SIZES.
•IF THE CONDENSING UNIT IS INSTALLED ABOVE THE EVAPORATOR
UNIT, USE THE SUCTION LINE ONE LISTED SIZE SMALLER.
•EXPANSION AND SOLENOID VALVES ARE INSTALLED ON LIQUID LINE.
•The installation order starts from condensing unit (including the receiver,
discharge valve), liquid line filter-drier, moisture-liquid indicator/sight glass,
liquid line, to evaporator unit (including liquid line connection, solenoid
valve, expansion valve, and suction line connection), returning to insulated
suction line, suction valve and then condensing unit.

- 11 -
•Charge the system after pipe brazing, leak testing and evacuating. Liquid
must always be charged into the hide side.
•Use inverted siphons to prevent liquid from flooding back to the
compressor and aid oil returning to the compressor.
•The subcooling at the condensing unit shall be around 10°F. The charge
may be complete when there are no more bubbles forming in the sight
glass.
•Head pressure: 125-150 psig at 70-90 °F ambient temperatures.
•The evaporator’s constant pressure expansion valve is set around 35-
40°F at factory. This pressure setting gives a dew point to maintain the
humidity for storing wine.
•Suction pressure: adjust the AXV to 30-35 psig.
•The temperature split across the evaporator shall be 8-10°F at 55°F wine
room temperature.
•The superheat at the evaporator unit shall be around 9-18°F under low -
high heat load at normal ambient temperatures.
•If the superheat is high, check the subcooling first to know if the refrigerant
charge is sufficient. If the charge is not sufficient, add more refrigerant. If
the charge is good, then increase the evaporator suction pressure by
turning the hex nut (5/16”) clockwise.
•If the superheat is low, then decrease the evaporator suction pressure by
turning the hex nut (5/16”) counter-clockwise.
Fig. 10 Expansion Valve
The line sizes and refrigerant charges are listed as follows.
MODEL REFRIGERATION
LINES LIQUID
LINE SUCTION
LINE DRAIN
LINE CHARGE
CellarTec 1/8
TON-SSL <= 50 FT 1/4" OD 3/8” OD 1/2” OD R134a/
15 OZ
CellarTec 1/4
TON-SSL <= 50 FT 1/4" OD 3/8” OD 1/2” OD R134a/
19 OZ
CellarTec 1/3
TON-SSL <= 50 FT 1/4" OD 1/2” OD 1/2” OD R134a/
26 OZ
CellarTec 1/2
TON-SSL <= 50 FT 1/4" OD 1/2” OD 1/2” OD R134a/
32 OZ

- 12 -
6. Use of the adjustable pressure control (if applicable for pump-down)
Suction pressure setting: Cut out=5 psig; Cut in=25 psig; Differential=20 psig
Head pressure setting: Cut out=230 psig; Cut in=150 psig; Differential=80 psig
It may need to adjust the setting in the field to get the right cycle time.
A. Single Control
Fig. 11 Single Adjustable Pressure Control
B. Dual Control
Fig. 12 Dual Adjustable Pressure Control
7. Use of the encapsulated low pressure control (if applicable)
Fixed suction pressure setting: Cut in = 32 psig; Cut out = 10 psig

- 13 -
Fig. 13 Fixed Pressure Control
8. Use of the condenser fan control (if applicable for low ambient kit)
Head pressure setting: Cut in=170 psig; Cut out=120 psig; Differential=50 psig
It may need to adjust the setting in the field to avoid fan short cycle.
9. Use of the crankcase heater (if applicable for low ambient kit)
The crankcase heater is installed around the lower part of the compressor and
shall be turned on all the time. The heater is self-regulated.
10.Pressure, Superheat and Subcooling Readings
CAUTION:
THE VALVES MUST BE IN THE MIDDLE POSITIONS TO READ PROPERLY.
Complaint Possible Causes
a. High suction pressure and low head pressure
b. High suction pressure and low head pressure
Low superheat and low subcooling
c. High suction pressure and high head pressure
Low superheat and high subcooling
d. High to normal suction pressure and high head pressure
Low subcooling
e. High suction pressure and high head pressure
Low subcooling
f. High suction pressure and high head pressure
High superheat
g. Low suction pressure and low head pressure
High superheat and low subcooling
h. Low suction pressure and low to normal head pressure
High superheat and high subcooling
i. Low suction pressure and low head pressure
Low subcooling
j. Low suction pressure and low head pressure
Low superheat and low subcooling
k. Low suction pressure and low to normal head pressure
High superheat and normal to high subcooling
a. Compressor may be bad
b. Expansion valve opened, too
much oil
c. Overcharge
d. Non-condensable gas
e. Air restricted, dirty condenser,
bad condenser fans
f. High room temperature, high
evaporator load
g. Undercharge
h. Liquid line restricted after
receiver, solenoid valve
restricted
i. Suction line restricted
j. Air restricted at evaporator,
evaporator iced
k. Evaporator restricted

- 14 -
l. Low suction pressure and normal head pressure
High superheat and normal subcooling
m. Low suction pressure and high head pressure
High superheat and high subcooling
n. Low suction pressure and high head pressure
High superheat and high subcooling
o. low to normal suction pressure and high head pressure
High to normal superheat and high subcooling
l. Expansion valve restricted
m. Both evaporator and condenser
restricted
n. Liquid line restricted before
receiver
o. Condenser restricted
11.Condensing Unit Troubleshooting
Unit not running
a. Incorrect power supply
b. Incorrect or loose wirings
c. Failed components
d. Liquid refrigerant in the compressor
e. Low pressure switch shutting down the system
a. Check for proper voltage
b. Check all wirings and connections
c. Check start relay, start capacitor, overload
protector, compressor.
d. Call service for OEM information
e. Check for system restriction or low
refrigerant

- 15 -
Electrical Wiring
CAUTION:
•USE 14 GAUGE WIRE FOR POWER LINE WIRING.
•USE 18 GAUGE WIRE FOR THERMOSTAT AND SENSOR.
•IF EQUIPPED WITH LOW AMBIENT CONDITION KIT, USE LOW AMBIENT
TEMPERATURE WIRING DIAGRAMS. TURN OFF THE COMPRESSOR
BEFORE POWER THE CONDENSING UNIT. ONLY TURN ON THE
COMPRESSOR AFTER THE CONDENSING UNIT HAS BEEN POWERED
FOR 24 HOURS.
Fig. 14 Thermostat Installation

- 16 -
Fig. 15 CellarTec 1/8-1/3 Ton-SSL Wiring Diagram

- 17 -
Fig. 16 CellarTec 1/2 Ton-SSL Electrical Wiring Diagram

- 18 -
Fig. 17 Low Ambient Temperature
CellarTec 1/8-1/3 Ton-SSL Electrical Wiring Diagram

- 19 -
Fig. 18 Low Ambient Temperature
CellarTec 1/2 Ton-SSL Electrical Wiring Diagram
This manual suits for next models
3
Table of contents
Other Cellartec Air Conditioner manuals
Popular Air Conditioner manuals by other brands

Toshiba
Toshiba TCB-SIR41U-E installation manual

Panasonic
Panasonic CS-BE25TKE-1 operating instructions

LG
LG Art Cool LA240HSV installation manual

Frigidaire
Frigidaire FFRE153WA1 Use & care guide

National Comfort Products
National Comfort Products NCPAH Series installation guide

Mitsubishi Heavy Industries
Mitsubishi Heavy Industries SRK20ZSX-W Service manual