Length 285 mm / 11 7/³²”
Depth 144 mm / 5 21/32”
Height 134 mm / 5 9/32”
Weight 1.65 kg
Capacity 1.7 litres
285mm / 11 7/32”
134mm / 5 9/32”
Max. flow (@ 0 m/ft) 300 L/hr
Max. rec. head 5m
Sound level @ 1m 49 dB(A)
Pump Power supply 230 VAC, 0.8 A, 50Hz
Non Continuous 5mins on, 5mins off
Class I Appliance
Max. AC unit output 200kW - 682,000 Btu/h
Max. water temp 60º C / 140º F
Inlets/Outlets Ø21mm to Ø27mm /
6mm (1/4”) & 10mm (3/8”)
IP Protection IP24
Safety switch 3 A Normally closed
Thermal protection ✓
SPECIFICATIONS
1This pump has been designed for the removal of pH +2.2
condensate water ONLY.
2Ensure 1 Amp fuse is installed.
3Following installation of the pump the tank should
be filled with water until the motor runs. Pipes and
connections should be checked for leaks and discharge of
water checked. The operation of the safety switch should
also be checked.
4Do not use these pumps in oily or very dusty environments.
5Install hose and wiring in accordance with manufacturers
instructions. Do not use discharge hose larger than
3/8”/10mm I.D.
6Inspect pump, clean floats, and tank regularly checking for
correct operation.
7Do not use any unapproved cleaning chemicals this pump.
Operating the pump when unapproved or poorly mixed
cleaning chemicals are present will result in permanent
damage to pump and void warranty. Ensure all cleaning
chemicals are thoroughly flushed out of the pump with
clean water.
8After initial installation and/or maintenance, do not leave
site until pump has been tested for correct operation.
9When commissioning the pump, please check for debris
in the pump – remove any material that might block the
drain line or drain into the boiler pump.
10 NOISE: All Center Brand pumps operate quietly, however
under certain conditions where an extremely low ambient
noise level is present, the sound of their intermittent
operation may still be perceived as noisy. Always confirm
acceptable noise level before installing any condensate
pump in a bedroom or other noise sensitive area.
Correct sequence of operation:
1Boiler drains water which flows into pump’s tank.
2When the water lifts the float to the correct level the
pump will activate.
Fault Conditions:
In the unlikely event of a pump failure check the following:
1Power supply: Ensure power is supplied to pump.
2Hi level safety switch: Ensure hi level safety switch has not
operated. If it has, check pump performance is suited to
incoming flow rate.
3Pump is loud: Pump fixing may be loose or the connected
cables and hoses may be vibrating against a hard surface.
4Outlet Pipe: Check pipe, and outlet barb are not blocked
with debris or kinked.
AC max. unit sizing chart
Head / m L / hr kW
0 300 400
1 215 287
2 159 212
3 106 141
4 65 87
5 36 48
5.4 0 0
LITRES PER HOUR
METRES HEAD
6
5
4
3
2
1
0100
Max. rec. head 5m
200 300 400 500 600
6mm (¼”)
Information correct at the time of going to press.
PERFORMANCE
IMPORTANT
2
Boiler Condensate Pump - Installation Guide