Clima Flex Two-pipe One-way Cassette CLIFC-W 201506
4
5. Specifications
Model CLIFC-C1- 300
300 400
400 600
Air flow H/M/L m3/h 510/450/400 630/560/500 1000/880/800
H/M/L CFM 300/270/240 370/330/300 590/520/470
Cooling Capacity H/M/L kW 3.04/2.79/2.56 3.79/3.58/3.38 5.709/4.85/4.36
Water flow rate H L/h 520 650 982
Water pressure drop H kPa 14 20 20.2
Heating Capacity H/M/L kW 5.13/4.69/4.04 6.41/5.86/5.11 9.6/8.36/7.48
Water pressure drop H kPa 9 16 18.1
Power supply V/Ph/Hz 220-240/1/50
Power input H W 32 40 125
Electric heater capacity W 750 750 /
Sound pressure level H/M/L dB(A) 36/34//32 37/35/34 42/39/37
Fan motor Type Low noise 4-speed fan motor
Quantity 1
Fan Type Cross fan Centrifugal fan
Quantity 1 4
Coil Row 2 3
Max. Working pressure MPa 1.6
Diameter mm Φ7 Φ8
Panel
Dimensions W×H×D mm 1180x25x465 1420×10×755
Packing W×H×D mm 1232x107x517 1500×110×870
Net weight kg 3.5 9
Gross weight kg 5.2 12
Body
Dimensions W×H×D mm 1054x169x425 1200×198×655
Net weight */A kg 12.8/13.1 32.6
Packing W×H×D mm 1155x245x490 1380×265×720
Gross weight */A kg 16.6/17.1 36.3
Pipe
connection Water inlet/outlet pipe inch G1/2 RC3/4
Drain pipe mm ODΦ25 ODΦ20
Notes:
1. H: High fan speed; M: Medium fan speed; L: Low fan speed.
2. Cooling conditions: entering water 7°C, temperature rise 5°C, entering air temperature
27°C DB/19°C WB.
Heating conditions: entering water 50°C, entering air temperature 20°C DB, the same water
flow as the cooling conditions.
3. Noise is tested in a semi-anechoic test room.
4. * for models without electric heater, Afor models with electric heater.