Cooper Lighting DLVP Operating instructions

Application Note
DLVP
Distributed Low-Voltage Power System Troubleshooting
Lights will not turn ON
Issue Possible Causes Suggestions
Lights will
not turn ON
automatically
Vacancy Mode set on Low-voltage power
module
Low-voltage power module may be in vacancy mode. In vacancy mode, lights turn on when wallstation
button is pressed.
Vacancy Mode set on Occupancy Sensor If a sensor is being used that has an automatic/manual mode, ensure that the sensor is in automatic
mode.
Connection Issue Verify that all connections are connected to the correct ports for the accessories being used.
Lights will not
turn ON from
wallstations
Connection Issue Verify that all connections are connected to the correct ports for the accessories being used.
Microprocessor Verify that the low-voltage power module status LED is flashing. If it is flashing, press and release the
reset button and verify that lighting turns ON for 3 seconds. If there is no response, contact technical
support.
Power Interruption If the low-voltage power module status LED is not flashing, check incoming voltage and/or wiring.
If still having trouble with lighting turning ON, consult Troubleshooting Guide or call Technical Services at 1-800-553-3879
Lights will not turn OFF
Issue Possible Causes Suggestions
Lights will
not turn OFF
automatically
Occupancy Sensor Turn zone OFF using the programming remote (LVHH-01) to verify the lights will turn off.
Verify the occupancy sensor is properly sensing lack of motion, is not located within 4-6 feet of air vents,
make sensitivity adjustments if necessary.
Place occupancy sensors in test mode to verify lighting turns OFF.
Verify that the occupancy sensor is not overridden (DIP Switch 8 up).
Make sensitivity adjustments if necessary.
Quiet Time If the wallstation has a Quiet Time button, ensure that this is not activated.
Motion sensors are ignored during the 60-minute quiet time count down.
Occupancy Sensor or Time Clock
connections are not present
To turn lighting OFF automatically, the low-voltage power module requires either a vacancy command
from an occupancy sensor, OR a time clock command to automatic shutoff
(after-hours) mode.
Alert Mode If alert mode has been activated, lighting will be on and full bright until the alert is cleared. Disconnect
contact into the alert mode terminal to verify normal operation resumes. Troubleshoot the connected
system to determine the cause of the alert signal.
Lights will not
turn OFF from
wallstations
Connection Issue Verify that all connections are connected to the correct ports for the accessories being used.
Alert Mode If alert mode has been activated, lighting will be ON and full bright until the alert is cleared. Disconnect
contact into the alert mode terminal to verify normal operation resumes. Troubleshoot the connected
system to determine the cause of the alert signal.
If still having trouble with lighting turning ON, consult Troubleshooting Guide or call Technical Services at 1-800-553-3879

Distributed Low-Voltage Power System App NoteDLVP
Lights turn OFF unexpectedly
Issue Possible Causes Suggestions
Lights will not
remain ON
(Lights turn
OFF approx.
30 seconds
after the ON
command)
The controller senses that there is an
occupancy sensor connected but is not
seeing an occupied signal from the
sensor.
Verify that the occupancy sensor LEDs are flashing when motion is occurring.
Make sure that the occupancy sensor coupler is connected to the correct wires from the occupancy
sensor.
If the occupancy sensor being used has an Auto/Manual selection, verify that the occupancy sensor is in
auto mode.
Verify that a VAC model sensor is not being used.
Lights will
not remain
ON (Lights turn
OFF approx.
60 minutes
after the ON
command)
Automatic shutoff (after-hours) mode The low-voltage power module is in automatic shutoff (after-hours) mode. Verify that the system
connected to the time clock input has been programmed for the correct times. A closure indicates
automatic shutoff (after-hours) mode where 60-minute timers will run. An open state indicates normal
mode.
Lights will not
remain ON
The Occupancy sensitivity may be set to
LOW
Verify that movement in the space causes the red LED to flash.
Using the programming remote (LVHH-01) push the “HI” button.
Using the programming remote (LVHH-01) push the zone ON button to ensure the fixture has power.
If still having trouble with lighting turning ON, consult Troubleshooting Guide or call Technical Services at 1-800-553-3879
Lighting level will not raise or lower as expected
Issue Possible Causes Suggestions
Lights turn ON
but remain at a
dimmed level
(lighting does
not respond to
dimming raise
controls)
Demand Response Demand response mode may have caused light levels to automatically reduce. Check contact from
demand response system. Verify that the demand response energy options DIP switches are set for the
appropriate lighting level.
Daylighting Daylight levels may not be correct for the space. Press the reset button on the controller to verify loads
turn ON to Full ON for 3 seconds. If loads go Full ON, then resume dimmed level:
Look in the Open-loop daylight Sensor lens to determine if the green LED is ON fairly steadily. If it is, the
sensor is seeing more daylight than its range will allow. Set a new range using the LVHH-01 remote and
the advanced daylight level adjustment procedures in the installation instructions.
If the Open-loop daylight sensor’s green LED is not on, use the LVHH-01 remote to adjust daylight levels
per the advanced daylight level adjustment procedures in the installation instructions.
Check the High End trim pot to ensure it is not set all the way counter-clockwise.
Lights turn ON
but remain at a
full bright level
(lighting does
not respond to
dimming lower
controls)
Alert Mode If alert mode has been activated, lighting will be ON and full bright until the alert is cleared. Disconnect
contact into the alert mode terminal to verify normal operation resumes. Troubleshoot the connected
system to determine the cause of the alert signal.
Lights turn
ON at a full
bright level
and responds
to manual dim-
ming lower
controls but do
not appear to
dim automati-
cally from day-
lighting
Daylighting Verify that the open-loop daylight sensor is installed in a location that is not obstructed from receiving
daylight.
Verify that the open-loop daylight sensor is properly connected to the low-voltage power module per the
installation instructions.
Verify that the open-loop daylight sensor lens is oriented properly for the location it is installed in.
The sensor range may be set too high. If the sensor is located in a darker location, try reducing the sensor
range to a lower range using the instructions in the advanced daylight level adjustment section.
Use the HHPR-01 remote to adjust daylight levels per the advanced daylight level adjustment procedures
in the installation instructions.
Lights turn ON
but remain at
full bright level
Daylighting Daylight levels may not be correct for the space.
Using the personal remote (LVHH-02) or a connected wallstation, press the lower button to ensure the
light level can go lower.
Use the programming remote (LVHH-01) to adjust the daytime occupied light level.
AP503041EN page 2
December 2019
www.eaton.com/lighting

Distributed Low-Voltage Power System App Note DLVP
Lights turn ON
but remain at a
full bright level
(lighting does
not respond to
dimming lower
controls)
Alert Mode If alert mode has been activated, lighting will be ON and full bright until the alert is cleared. Disconnect
contact into the alert mode terminal to verify normal operation resumes. Troubleshoot the connected
system to determine the cause of the alert signal.
Fixtures do not
respond to open
loop daylight
sensors
Connection Issue Check to see if closed loop fixture integrated sensors are on the same system. When open loop and
closed loop fixture integrated sensors are on the same system, the open loop daylight sensors are
ignored. Remove the open loop or closed loop fixture integrated sensors so that both are not on the same
system.
If still having trouble with lighting turning ON, consult Troubleshooting Guide or call Technical Services at 1-800-553-3879
Receptacle switchpacks are not responding as expected
Issue Possible Causes Suggestions
Receptacle
switchpacks
will not turn ON
Alert Mode Alert mode turns OFF all receptacle switchpacks while the alert is active. Disconnect contact into the alert
mode terminal to verify normal operation resumes. Troubleshoot the connected system to determine the
cause of the alert signal.
Connection Issue Verify that all connections are connected to the correct ports for the accessories being used.
Power Interruption Check incoming voltage and/or wiring to the receptacle switchpacks.
Receptacle
switchpacks
will not turn
OFF
Occupancy Sensor or Time Clock
connections are not present
The receptacle switchpacks require either a vacancy command from an occupancy sensor, OR a time clock
command to automatic shutoff (after-hours) mode to turn OFF. Wallstations do not cause receptacles
to turn OFF. Ensure that one of these methods is being used to successfully integrate receptacle
switchpacks.
If still having trouble with lighting turning ON, consult Troubleshooting Guide or call Technical Services at 1-800-553-3879
Miscellaneous Issues
Issue Possible Causes Suggestions
Lighting turns
ON but is not in
the right zone
Zone Assignment Verify that fixtures have been assigned to the appropriate zone (1, 2, or 3) to meet the application.
How to know if
the integrated
sensor is work-
ing on power
up
Occupancy Sensor Energize the low-voltage power module. The light should start at 50% light level and then raise or lower
to the daylight level.
The red LED on the sensor should slow blink (ON for 2 seconds, OFF for 2 seconds) for a 1-minute duration
then blink only on occupancy.
Using the programming remote (LVHH-01) press the zone ON/OFF button to ensure the light fixture turns
ON/OFF.
One or more
lights on a
low-voltage
circuit does not
come on
Connection Issue If status light on low-voltage power module is blinking, circuit is overloaded. Remove last fixture and
cable from that circuit and press RESET button on low-voltage power module.
If still having trouble with lighting turning ON, consult Troubleshooting Guide or call Technical Services at 1-800-553-3879
AP503041EN page 3
December 2019
Cooper Lighting Solutions
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.eaton.com/lighting
For service or technical assistance:
1-800-553-3879
Canada Sales
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
P: 905-501-3000
F: 905-501-3172
© 2019 Cooper Lighting Solutions
All Rights Reserved.
Product availability, specifications,
and compliances are subject to
change without notice.
Other Cooper Lighting Power Supply manuals