Det-Tronics Q9033 User manual

DESCRIPTION
The Q9033 Mounting Arm is an approved accessory for
installation of X-Series flame detectors. It allows easy
pan and tilt adjustments for sighting of the detector.
The optional Collar Attachment is used in conjunction
with the Mounting Arm to add a third dimension for
detector sighting by allowing it to also be rotated.
The Collar attachment is recommended for use in
applications that require the detector to be panned to
extreme angles.
In a typical installation, the detector is pointed down.
When a detector is pointed down, panning to either side
of center results in some degree of rotation — the greater
the pan amount, the greater the rotation. See Figure 1.
Since the cone of vision of the X3301/X3302 is not round,
but truncated on the upper half, rotation results in an
unbalanced field of view. The Collar Attachment enables
the detector to be adjusted level to the horizon, thereby
ensuring a balanced field of view.
FEATUR ES
Mounting Arm
• Compatible with all X-Series flame detectors
• FM and DNV performance approved for use with
X-Series detectors
• Allows easy detector sighting
• Heavy duty, Aluminum or Stainless Steel
construction
• Vibration and resonant frequency resistant
Collar Attachment
• Compatible with all X-Series flame detectors
• FM performance approved with X-Series detectors
• Adds increased versatility to the Mounting Arm
• Allows rotation of the detector to ensure optimum
detector performance
• Stainless steel construction (suitable for use with
either aluminum or stainless steel detectors and
mounting arms)
INSTRUCTIONS
Q9033 Mounting Arm
and Collar Attachment
1.2 ©2020 Carrier. All rights reserved. Rev: 6/20 95-8686
Q9033B Mounting Arm
with Collar Attachment

95-868621. 2
INSTALL ATION
MOUNTING ARM (Required)
1. Determine the best mounting location for the
detector following the guidelines in the detector
instruction manual.
NOTE
Refer to the detector instruction manual
for detailed information regarding detector
positioning, orientation, and mounting.
2. Install the Mounting Arm using 1/4 inch (M6) bolts
with a length of at least 1 inch (25 mm). Refer to
Figures 2 and 3 for dimensions.
NOTE
Ensure that the mounting surface is suitable to
hold the weight of the detector and mounting arm.
3. If a Collar Attachment is being used, proceed with
step 4. If no Collar Attachment will be used, go to
step 6.
Figure 2—Q9033 Mounting Arm Dimensions in Inches (cm)
4.0
(10.2)
4.0
(10.2)
3.0
(7.6)
3.0
(7.6)
4X ø0.42
(1.1)
E2069
NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.
13.1
(33.4)
10.6
(27.0)
2.63
(6.68)
2.0
(5.08)
6.5
(16.5)
1.75
(4.44)
.81
(2.06)
DETECTOR NOT PANNED
NO COLLAR ATTACHMENT
DETECTOR PANNED
COLLAR ATTACHMENT INSTALLED
DETECTOR LEVELED TO HORIZON
B2599
VIEWING WINDOWS
ALIGNED TO HORIZON
DETECTOR PANNED
NO COLLAR ATTACHMENT
VIEWING WINDOWS
NOT ALIGNED TO HORIZON
WITH DETECTORS POINTED DOWN,
PANNING RESULTS IN ROTATION
VIEWING WINDOWS
ALIGNED TO HORIZON
Figure 1–X3301 Detectors Mounted with and without Collar Attachment

395-86861. 2
COLLAR ATTACHMENT (Optional)
NOTE
Prior to installing the collar attachment, note the
location of the Mag oilabel. Apply the magnet to
the detector housing at this location to initiate a
mag oitest. The collar attachment will cover the
label, but will not interfere with the mag oitest.
4. The Collar Attachment assembly is made up of
two halves — one installed on top, and the other
under the detector bulkhead. With the four socket
cap screws (provided) held in place with O-rings
as shown in Figure 4, place the top half in position
on the detector. Then place the bottom half under
the detector and tighten the screws using a 5 mm
hex wrench (not included). Do not fully tighten the
screws at this time.
5. Using the 5 mm hex wrench, remove the bulkhead
plug from the top half of the collar attachment and
install it in the detector bulkhead mounting hole (to
prevent corrosion). See Figure 5.
ATTACH DETECTOR TO MOUNTING ARM
6. Raise the detector to insert the large bolt on the
Mounting Arm into the detector bulkhead or the
Collar Attachment (see Figure 6).
NOTE
It is possible that two people may be needed
to complete this step, especially when dealing
with the heavier stainless steel ame detector
models.
7. Aim the detector at the area to be protected, then
use a 14 mm hex wrench to tighten the detector
mounting bolt and clevis bolts just tight enough to
hold the detector in this position. See Figure 7.
A2600
COLLAR
BOTTOM HALF
COLLAR
TOP HALF
O-RING (4X)
SOCKET CAP
SCREWS (4X)
BULKHEAD
PLUG
Figure 4–Collar Attachment Assembly, part #011385-001 shown
INSTALL PLUG IN
BULKHEAD MOUNTING HOLE
A2603
Figure 5–Correct Installation of Collar Attachment to Detector
A2601
Figure 6– Connecting a Detector with Collar Attachment
to Mounting Arm
Figure 3— Q9033 Mounting Arm with Collar Attachment
Dimensions in Inches (cm)
A2604
NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.
11.2
(28.5)
10.6
(27.0)
2.63
(6.68)
2.0
(5.08)
6.5
(16.5)
NOTENOTE
Socket cap screws enter from the bottom in part
#011385-002.

95-8686
DETECTOR ALIGNMENT
8. If a Collar Attachment is used, ensure that the detector
viewing windows are correctly aligned (parallel) with
the horizon. See Figure 8. Adjust as necessary, then
tighten the four collar screws.
9. For optimum alignment accuracy, attach a Q1201C
Laser Holder with Laser to the detector. Align the
detector following the procedure in the Q1201C
instruction manual (number 95-8596). When correct
alignment is achieved, u
se a 14 mm hex wrench
to tighten the detector mounting bolt and the two
clevis bolts.
ORDERING INFORMATION
When ordering, please specify:
Part Number Description
007290-001 Q9033B Mounting Arm -
Stainless Steel
007290-002 Q9033A Mounting Arm -
Aluminum
011385-001 Collar Attachment (screws enter
from the top of the assembly)
011385-002 Collar Attachment (screws enter
from bottom of the assembly)
007255-001 Q1201C Laser Holder for X-Series
Flame Detectors
006097-001 Laser
103578-001 Anti-Seize Grease
For assistance in ordering a system to meet the needs
of a specific application, please contact:
Detector Electronics Corporation
6901 West 110th Street
Minneapolis, Minnesota 55438 USA
Operator: (952) 941-5665 or (800) 765-FIRE
Customer Service: (952) 946-6491
A2602
VIEWING WINDOWS
ALIGNED TO HORIZON
Figure 8–Optimal Alignment of Viewing Windows
(X3301 with Collar Attachment)
A2598
DETECTOR MOUNTING BOLT
CLEVIS BOLTS (2X)
Figure 7–Location of Three Bolts on Mounting Arm
(Shown without Collar Attachment)
Corporate Office
6901 West 110th Street
Minneapolis, MN 55438 USA
www.det-tronics.com
Phone: +1 952.941.6665
Toll-free: +1 800.765.3473
Fax: 952.829.8750