domat R560 User manual

domat R560 11/2018 Subject to technical changes. 1
R560
Universal analogue input module
Summary
The R560 is a microprocessor controlled, communicative module with 8 analogue
inputs with variable measuring range: voltage, resistance, temperature, current
loop). The module uses a RS485 bus for communication, and can be easily
integrated in a variety of supervision and control systems.
Application
•Building and industrial control systems –measuring of temperature,
pressure, and other values
Function
The module incorporates 8 analogue inputs. The input signals are processed and
multiplexed into a 16 bit A/D converter. Each input is rangeable separately (see
Technical data), and inputs can also be used as 0 to 20 mA current measurement
inputs if the corresponding DIP switch is activated.
The module communicates by means of RS485 data bus. The Modbus RTU
communication protocol ensures smooth and easy integration in a variety of control
and data acquisition systems. It connects to process stations (PLCs) directly or
through the M012 interface (RS485 to RS232 converter with galvanic isolation).
Removable connectors are used for all signals as well as for data line so that
mounting is fast and easy. The module has a DIN rail clip.
The communication circuits are protected against overvoltage and galvanically
isolated from other parts of the module. If the module is terminating the
communication bus, i.e. it is the first or last in line, a terminating 120 resistor may
be switched on by activating the BUS END switches. Two LEDs located inside of the
housing enable fast diagnostics –power and communication.

2 11/2018 Subject to technical changes. domat R560
All module settings are backed up in an EEPROM chip. The module is equipped with
a watchdog circuit.
See domat - Technical application notes for connection examples. R560 is a more
universal replacement of M550 (which has 8 inputs for passive sensors) and it can be
used also as a replacement of M500 (8 voltage inputs) for most of the applications.
Please note that the R560, unlike M500, has asymmetrical inputs (0 to 10 V rather
than -10...10 V).
____________________________________________________________________
Technical data
Power
10 V ÷ 35 V DC, 14 V ÷ 24 V AC
Consumption
2,5 W
Communication
Galvanic isolation
Max. bus length
Max. amount of modules on the bus
Modbus RTU RS485, 1200 ... 115200 bit/s
1 kV
1200 m
256
Number of analogue inputs
8
Input ranges
Pt1000* (-50...150 °C), 20...1600 Ohm, 20...5000 Ohm, 0...10
V, 0...20 mA
*Resistance ranges may be used for temperature
measurement with Pt100, Pt1000, Ni1000/5000 and
Ni100/6180 passive sensors. Linearisation must be done in
controllers (Domat PLC… for example) just like at e.g. MCIO2
module. In the R560 module there is recalculation to °C for
the Pt1000 sensor only.
Sampling
10 samples/s
Effective resolution
16 bit
Measurement error
The measurement deviation for all measured variables is
0.25% of the whole range.
Input impedance
>10M
SW
ModComTool 4.2.3.9 or higher parameters setting, GUI
Merbon IDE, SoftPLC IDE –predefined modbus devices
Housing
Polycarbonate box (certification UL94V0)
elbox 4
Terminals
screw terminals M3 (bus, power), M2 (AI inputs)
Dimensions
71 (l) x 90 (w) x 58 (h) mm
Protection degree
IP20 (EN 60529)
Recommended wire
0,14–1,5 mm2
Ambient temperature
External conditions: -5 –45 °C; 5 – 95 % relative humidity;
non-condensing gases and chemically non-aggressive
conditions (according to EN 60721-3-3 climatic class 3K5)
Storage: -5 –45 °C; 5 – 95 % relative humidity; non-
condensing gases and chemically non-aggressive conditions
(according to EN 60721-3-1 climatic class 1K3)

domat R560 11/2018 Subject to technical changes. 3
Standards conformity
EMC EN 61000-6-2 ed.3:2005, EN 61000-6-4 ed.2:2006 +
A1:2010 (industrial environment)
Electrical safety EN 60950-1 ed.2:2006 + A11:2009 +
A12:2011 + A1:2010 + A2:2014 + Opr.1:2012 + Z1:2016
Hazardous substances reduction EN 50581:2012
Terminals
Terminals and
connectors:
RS485 K+
port COM1 - serial link RS485, terminals K+
RS485 K-
port COM1 - serial link RS485, terminals K-
G
G power supply
G0
G0 power supply
TE
optional connection for shielding, technical ground
AIC
common terminals for AI1…AI8
AI1 … AI8
input 1 … 8
LED indication:
RUN
orange LED –system cycle (OK: LED flashes periodically 1
s ON, 1 s OFF; ERROR: LED flashes in other pattern, LED is
still ON or OFF)
TxD
red LED –RS485 transmitting data at COM1 (flashing:
transmitting data; OFF: no data traffic)
PWR
green LED –power supply (ON: power OK; OFF: no power
applied, weak or damaged power supply, …)
DIP switches:
ADR
AUTO –if all switches are OFF, the address is used
according to Modbus register 4 LSB
USER –address is set by DIP switches configuration
INIT - if are all switches ON at power-up, configuration
parameters are set to defaults
DIP 8 = bit 0; switches increase their bit weight from
right to left, see below
BUS END
Switch for bus RS485 termination (located at the RS485
connector); ON = bus end; the first and last devices on
bus should have bus end ON

4 11/2018 Subject to technical changes. domat R560
0 … 20 mA
For current measurement (0-20 mA) on individual
channels switch the particular DIP switch to ON
The 0...20 mA range must be also set over Modbus (e.g.
using Domat ModComTool)
Connection

domat R560 11/2018 Subject to technical changes. 5
Dimensions
Dimensions are in mm.
Installation
The R560 module is fixed on standard DIN rail (by snapping).
When removing the module from the DIN rail proceed as follows: Place a
screwdriver in the plastic slot which is in the middle of bottom part of the module
(1). Then push the screwdriver upwards (2). After that, the module can be removed
by tilting it upwards (3).
Addressing
The Modbus address can be set as follows:
-hardwarewise: using DIP switches. The switches increase their bit weight
from right to left, see image with example where address of 21 is set by
activation of switches 4, 6, and 8 with bit weight of 16, 4, and 1 respectively.
Valid settable range is 1 to 254. Address 0 (all switches OFF) means that the
address is set as entered in the Modbus table. Address 255 (all switches ON)
brings the module to INIT mode, where Modbus address is 1 and
communication parameters are set to N, 8, 1, see image below.
All changes apply after the module is switched off and on again.

6 11/2018 Subject to technical changes. domat R560
-softwarewise using the ModComTool software, available for free
at www.domat.cz. The default address (factory setting) is 1, default
communication parameters are 9600, 8, N, 1. Parity and stopbits can be set
in Modbus register 1005 LSB.
The software address is only active if the hardware addressing switch is set
to 0.
All changes apply after the module is switched off and on again.
Safety note
The device is designed for monitoring and control of heating, ventilation, and air
conditioning systems. It must not be used for protection of persons against health
risks or death, as a safety element, or in applications where its failure could lead to
physical or property damage or environmental damage. All risks related to device
operation must be considered together with design, installation, and operation of
the entire control system which the device is part of.

domat R560 11/2018 Subject to technical changes. 7
Changes in
versions
07/2017 –First datasheet version.
10/2017 –Added measurement error value, new image.
02/2018 –Added Safety note.
11/2018 –Minor changes.