Rev G 3-4-15 6
OPERATION
IDLE:
In normal operation, the door being monitored is closed. The Lock Output is powered (for
magnetic lock) or not powered (for electric strike). The alarm relay is de-energized. The sounder
is quiet. No timers are running. The LED status lights are green. The alarm is armed.
REQUEST FOR ACCESS:
Contact closure at the REX input changes the state of the LOCK output (depending on the fail-
safe or fail-secure setting, the default being fail-safe) releasing the door lock. The door is now
accessible. The indicator light changes from green to amber. The door will remain accessible for
as long as the REX input contacts are closed. The REX device must be adjusted to provide
sufficient time delay for the user to initiate a request and then move to open the door. The ideal
delay time will vary by installation. If the REX contacts open before the door is opened, the
system returns to IDLE and the door is no longer accessible.
OPEN DOOR WITH VALID REX:
During the unlock period, the door may be opened. When the DPS input sees open contacts, the
indicator light changes to blinking amber. The internal door prop timer begins counting down the
pre-set prop time. If the door is still open when the prop timer expires, the system enters the
WARNING period – see below.
DOOR CLOSE WITH NO ALARM:
In normal operation the door will close before the prop timer has timed out and the system returns
to IDLE.
PROP WARNING:
If the door remains open after the prop timer has timed out, the WARNING timer begins. During
the warning phase, the sounder beeps and the indicator light flashes red. If the door is closed
during the warning period, the system returns to IDLE.
DOOR PROP ALARM:
If the door remains open when the warning timer expires, the system enters ALARM state, the
sounder tone is continuous and the indicator light is steady red. The system will remain in
ALARM state until it is reset. Note, the alarm relay is not energized during the warning period.
DOOR OPEN ALARM:
With the WARN adjustment set to zero, and the prop time set to zero, the system goes into
ALARM as soon as the door opens.