1Installation Guide:
SimpleSox
TM
System
Thank you for selecting a SimpleSoxTM System. This guide should be helpful for installing
SimpleSoxTM. Sections of fabric will be labeled, assembled, bagged, and boxed for shipping.
Overview
Inventory
The rst step on any installation project is to check the order and familiarize yourself with what needs
to be installed. We suggest reading through this manual completely to properly educate yourself on eld
installation. Please make sure you have all the required components for the SimpleSoxTM System.
Equipment Required:
• Drill
• Screwdriver
• Tape measure
• Marker or pencil
• 5/16 nut driver
• Ladder or lift for extended heights
Available Components/Details
NOTE:
We always provide
20% more cable. There will
actually be 120’ of cable
included in the kit.
Installation Guide
Adjustable Fabric Air Dispersion System
Font is Futura Md BT
Medium Italic
Textile Air Dispersion Products
Cable Assembly Kit
(includes 2 turnbuckles, 2 thimbles,
2 eyebolts, 4 cable clamps, and
100’ of cable)
1’ Inlet Adjustable Flow
Device
(Fabric Mesh Damper)
15’ Section
2’ Adjustable
Air Outlet
5’ Section
1.5’ Section 90 Degree Elbow
0.5’ Endcap
10’ Section Cross Reducer
Twisty
2
3"
1.5”
Installation Steps
1. Review materials to conrm all parts t the pre-determined design.
2. Assess product placement area to conrm the system will t in the required space.
3. Prepare metal inlet collar for fabric connection.
4. Locate cable anchors and components.
5. Install cable end supports.
6. Install the fabric.
7. Use excess cable and cable clamps for mid-supports.
8. Install cable stops.
9. Rotate Adjustable Air Outlet (AAO) sleeves as needed.
Step 1
Review materials to conrm all parts t the pre-determined design. READ INSTRUCTIONS THOROUGHLY
BEFORE BEGINNING.
Step 2
Assess product placement area to conrm the system will t in the required space.
Step 3
Prepare metal inlet collar for fabric connection.
• Conrm inlet air supply location and size.
• SimpleSoxTM inlets are manufactured 1/2” larger than
specied to t over metal inlet collar.
• Metal collar length should be 6”–10” to secure fabric inlet.
• Edge guard (provided) should be installed on the edge of
the metal collar to reduce fabric wear on metal edge.
Step 4
Locate cable anchors/components. Tension cable
system includes 1/8” cable and hardware as shown.
Hardware kit includes: 2 turnbuckles (6” draw), 2 eyebolts, 4 cable clamps, and 2 thimbles
Cable Length = 100’ (+20’ additional)
Step 5
Install cable end supports as required. Hang cable 3” above top of System.
Edge Guard
(Supplied)
6”–10”
Suggested SimpleSoxTM Ceiling Gusset Brace:
1” x 1” angle iron or slotted channel to
attached DuctSox cable hanging system
Installation Guide:
SimpleSox
TM
System
If your SimpleSoxTM System has elbows:
Install cable as shown at right 1.5” above
top of the System.
NOTE:
The elbows are meant to be
interchangeable left or right when
connected to the SimpleSoxTM System. The
double zipper allows for this.
Cable Assembly Kit (includes 2 turnbuckles, 2 thimbles, 2 eyebolts, 4 cable clamps, and 100’ of cable)
15’ Section 2’ Adjustable
Air Outlet
5’ Section 1.5’ Section 90 Degree Elbow 0.5’ EndcapAdjustable Flow Device
(Fabric Mesh Damper)
1’ Inlet
End
Support
End
Support
3Installation Guide:
SimpleSox
TM
System
Step 6
Install the fabric.
Sample System
Step 7
To prevent “sagging,” use excess cable and cable clamps for mid-
supports every 30 feet maximum.
Step 8
Install cable stops. Once system is properly adjusted, deate the
system, pull the last snap in each straight section, and secure tension
using cable clamp to cable (will reduce ination “popping”). If the system
includes elbows, secure the last snap before elbow(s).
Cable clamps are provided to secure snaps.
Failure to install the SimpleSoxTM System correctly can void warranty.
Step 9
Rotate the Adjustable Air Outlet (AAO) sleeves as needed. All AAO settings are set on Medium. CFM
ranges are diameter specic. Please see AAO insert sheet for details.
NOTE:
When adjusting AAOs, the SimpleSoxTM System should be inated, AND the aps should be
folded back to expose the hook and loop fasteners on the AAO. Once adjustments are made, fold back
the aps to cover zippers and hook and look fasteners.
Adjustable Air Outlet
Inlet 15’ Section
5’ Section Adjustable Air Outlet 15’ Section
15’ Section 15’ Section Endcap
Adjustable Air Outlet
Adjustable Air Outlet Adjustable Air Outlet
Total Length = 76.5’
1400 CFM
at 0.5” w.g.
Secure attachments to
suspension system
(inlet section rst if not
zipped together).
Slide SimpleSoxTM inlet over collar
and position the zipper start/stop at top
center and tighten the DuctBelt.
Secure anchors with standard screws
(not provided) after start-up (to ensure
proper inated alignment).
Clip SimpleSoxTM System onto cable.
Connect sections together with zippers.
The pull (female end) of the zipper is
located towards the end away from the
inlet of the section.
1
23
30' MAX
4
Change the Direction of Airow
The 2’ main section of the AAO has four large
orices and has dual start zippers on each
end. This enables the AAO to be rotated 180
degrees, changing the direction of airow
to either down (4 & 8 o’clock) or up (10 & 2
o’clock).
Change the Volume of Airow
Each AAO has two independent adjustment
sleeves that slide and rotate over the 2’ main
section. The adjustment sleeves have both
small and medium orices and are held in
place with hook and loop fasteners. Simply
rotate the sleeves to select small and/or
medium orices. For large orices, slide the sleeves off of the 2’ main section onto the inactive sections.
This will expose the large orices and will keep the sleeves readily available if you want to decrease the
airow. Changing the number of orices activated (0, 1, 2, 3, or 4) and/or the size of each orice (small,
medium, or large) changes the volume of air discharged from the AAO. NOTE: 0.5” w.g. inlet static
pressure. See Chart below for Low, Medium (Factory Setting), and High CFM volumes for each diameter.
AAO Air Volume (CFM)
(per 4 orices)
**For more detailed instructions on adjusting the AAO, see the packing slip included with the AAO.**
Laundering Instructions
• Remove system and break down into sections
• Turn soiled side out, soak in cold water for 30 minutes
• Wash cold, gentle cycle
• Rinse thoroughly (repeat cycle if water/SimpleSox still soiled)
• Drip dry or no heat tumble dry
Diameter Low Medium High
12” 140 200 260
16” 200 280 380
20” 320 460 620
24” 380 560 760
28” 460 680 920
Factory Setting
NOTE:
For Low and Medium
Settings, reduce airflow volumes
in chart by 50% if orifices are on
one side only. High Setting is not
applicable for air dispersion on
one side.
Adjustment Sleeves:
Slide and Rotate Over 2’ Main Section
Small Orifice
Medium Orifice
2’ Main Section
Large Orifice
© 2 0 1 0 D u c t S o x C o r p .
DSSSIG0810A
?If any questions arise regarding the installation of your SimpleSoxTM System, go
to www.ductsox.com or contact us at 866-DuctSox (866-382-8769).
9866 Kapp Court
Ph: 866-382-8769 or 563-588-5300
Peosta, IA 52068
Fax: 563-588-5330
Font is Futura Md BT
Medium Italic
Textile Air Dispersion Products
www.ductsox.com

Popular Fan manuals by other brands

Parrot Uncle F6291 Installation & operating instructions

Parrot Uncle

Parrot Uncle F6291 Installation & operating instructions

Triangle Engineering of Arkansas Heat Buster SEB Series owner's manual

Triangle Engineering of Arkansas

Triangle Engineering of Arkansas Heat Buster SEB Series owner's manual

Lennox LPVK-110 installation instructions

Lennox

Lennox LPVK-110 installation instructions

NuTone 696N220-R01 quick start guide

NuTone

NuTone 696N220-R01 quick start guide

Loren Cook ACE-D Installation, operation and maintenance

Loren Cook

Loren Cook ACE-D Installation, operation and maintenance

Valiant REMORA FIR350 instruction manual

Valiant

Valiant REMORA FIR350 instruction manual

Craftmade RU72AG installation guide

Craftmade

Craftmade RU72AG installation guide

Lumme LU-FN103 quick start guide

Lumme

Lumme LU-FN103 quick start guide

NMB-MAT 3115PS Specification sheet

NMB-MAT

NMB-MAT 3115PS Specification sheet

EUROLAMP RD-40DC-3 instructions

EUROLAMP

EUROLAMP RD-40DC-3 instructions

Perel CFANF45N user manual

Perel

Perel CFANF45N user manual

ERGODYNE 6090 instructions

ERGODYNE

ERGODYNE 6090 instructions

Sealey SDF9/98 instructions

Sealey

Sealey SDF9/98 instructions

Envirovent SILENT Instruction leaflet

Envirovent

Envirovent SILENT Instruction leaflet

Ellington HIR52TBC5 installation guide

Ellington

Ellington HIR52TBC5 installation guide

HSC Elite T5000 operating instructions

HSC

HSC Elite T5000 operating instructions

Trane TVR LX 4TVL0006DF000AA Technical & service manual

Trane

Trane TVR LX 4TVL0006DF000AA Technical & service manual

Carrier HRVCCLHU Product data

Carrier

Carrier HRVCCLHU Product data

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.