OPERATORS MANUAL
Flow Compu t er
Liqui d Version
11 1 0 4 W.Airpo rt Blv d , Suite 108 & 1 4 8
Staf f ord , Texa s 77 4 77 USA
( 281 ) 5 65 - 11 18
F ax (2 81 ) 5 65 -1 11 9

Date: 8/1/2019
WARRANTY
Dynamic Flow Computers warrants to the owner of the Smart Flow Computer that the
product delivered will be free from defects in material and workmanship for one (1) year
following the date of purchase.
This warranty does not cover the product if it is damaged in the process of being installed
or damaged by abuse, accident, misuse, neglect, alteration, repair, disaster, or improper
testing.
If the product is found otherwise defective, Dynamic Flow Computers will replace or
repair the product at no charge, provided that you deliver the product along with a return
material authorization (RMA) number from Dynamic Flow Computers.
Dynamic Flow Computers will not assume any shipping charge or be responsible for
product damage due to improper shipping.
THE ABOVE WARRANTY IS IN LIEU OF ANY OTHER WARRANTY EXPRESS
IMPLIED OR STATUTORY. BUT NOT LIMITED TO ANY WARRANTY OF
MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSE, OR ANY
WARRANTY ARISING OUT OF ANY PROPOSAL, SPECIFICATION, OR SAMPLE.
LIMITATION OF LIABILITY:
DYNAMIC FLOW COMPUTERS SHALL HAVE NO LIABILITY FOR ANY
INDIRECT OR SPECULATIVE DAMAGES (INCLUDING, WITHOUT LIMITING
THE FOREGOING, CONSEQUENTIAL, INCIDENTAL AND SPECIAL DAMAGES)
ARISING FROM THE USE OF, OR INABILITY TO USE THIS PRODUCT.
WHETHER ARISING OUT OF CONTRACT, OR UNDER ANY WARRANTY,
IRRESPECTIVE OF WHETHER DFM HAS ADVANCED NOTICE OF THE
POSSIBILITY OF ANY SUCH DAMAGE INCLUDING, BUT NOT LIMITED TO
LOSS OF USE, BUSINESS INTERRUPTION, AND LOSS OF PROFITS.
NOTWITHSTANDING THE FOREGOING, DFM’S TOTAL LIABILITY FOR ALL
CLAIMS UNDER THIS AGREEMENT SHALL NOT EXCEED THE PRICE PAID
FOR THE PRODUCT. THESE LIMITATIONS ON POTENTIAL LIABILITY WERE
AN ESSENTIAL ELEMENT IN SETTING THE PRODUCT PRICE. DFM NEITHER
ASSUMES NOR AUTHORIZES ANYONE TO ASSUME FOR IT ANY OTHER
LIABILITIES

Date: 8/1/2019
CHAPTER 1: QUICK START....................................................................................................................1-1
Introduction:............................................................................................................................................ 1-1
Technical Data:........................................................................................................................................ 1-2
Parts List..................................................................................................................................................1-3
SFC332L Flow Computer: Dimensions ................................................................................................. 1-4
Starting and Installing theWindow Software:..........................................................................................1-5
System Minimum Requirements .........................................................................................................1-5
Website - DFC Configuration Software ..................................................................................................1-6
Getting acquainted with the flow computer wiring: ................................................................................ 1-8
Back terminal wiring:..........................................................................................................................1-8
Back Panel Jumper ..............................................................................................................................1-9
Memory Jumper................................................................................................................................. 1-10
INPUT/OUTPUT: Assigning and Ranging Inputs ...............................................................................1-14
Input/Output Assignment ..................................................................................................................1-14
How to assign a transmitter to an I/O point....................................................................................... 1-14
Ranging the Transmitter Inputs:........................................................................................................1-15
WIRING:...............................................................................................................................................1-16
Wiring the Analog Inputs:.................................................................................................................1-16
Wiring the analog inputs 1-4 :...........................................................................................................1-17
RTD...................................................................................................................................................1-18
Wiring Analog Output:...................................................................................................................... 1-19
Turbine Input Wiring.........................................................................................................................1-20
Turbine input wiring for passive (dry contact) pulse generators .......................................................1-23
Density Input Wiring:........................................................................................................................1-24
RS-232 Connection: ..........................................................................................................................1-25
RS-485:..............................................................................................................................................1-26
Wiring of Status Inputs:..................................................................................................................... 1-27
Wiring of Switch/Pulse Outputs:.......................................................................................................1-28
I/O Expansion:...................................................................................................................................1-29
Prover/Expansion .............................................................................................................................. 1-31
CALIBRATION Through Window Program........................................................................................1-32
Analog Input 4-20mA or 1-5 volt signal ..........................................................................................1-32
RTD Calibration:............................................................................................................................... 1-33
Calibration of Analog Output:...........................................................................................................1-34
Multi-Variable Transmitters (Model 205) –DP and Pressure...........................................................1-34
Multi-Variable Transmitters (Model 205) –RTD..............................................................................1-35
CALIBRATION Through DOS Program..............................................................................................1-36
Analog Input 4-20mA or 1-5 volt signal: ..........................................................................................1-36
RTD calibration:................................................................................................................................1-37
Calibration of Analog Output:...........................................................................................................1-38
Multi-Variable Transmitters (Model 205)- DP and Pressure ............................................................ 1-38
Multi-Variable Transmitters (Model 205)- RTD...............................................................................1-39
Verifying Digital Inputs and Outputs ....................................................................................................1-40
CHAPTER 2: Data Entry ............................................................................................................................2-1
Introduction to the SFC332L Computer Software...................................................................................2-1
Configuration File through Window Program......................................................................................... 2-1
New ..................................................................................................................................................... 2-1
Open .................................................................................................................................................... 2-1
Close.................................................................................................................................................... 2-1
Save.....................................................................................................................................................2-1
Save As................................................................................................................................................2-1
VIEW ...................................................................................................................................................... 2-2
View Drawings.................................................................................................................................... 2-2
TOOLS....................................................................................................................................................2-3
Com Settings .......................................................................................................................................2-3

Date: 8/1/2019
Meter Configuration............................................................................................................................ 2-4
Security Code .................................................................................................................................... 2-33
PID OPERATING................................................................................................................................. 2-34
CALIBRATION.................................................................................................................................... 2-34
Calibrate Mode..................................................................................................................................2-34
Parameter Overrides:.............................................................................................................................2-34
Temperature Override .......................................................................................................................2-34
Pressure Override .............................................................................................................................. 2-34
DP Override.......................................................................................................................................2-34
API/SG/Density Override.................................................................................................................. 2-34
Orifice ID Override ...........................................................................................................................2-34
Current Batch Preset..........................................................................................................................2-34
Equilibrium Pressure Override .......................................................................................................... 2-35
Alpha T E-6 Override........................................................................................................................2-35
Wedge Fa Override and Wedge Kd2 Override..................................................................................2-35
Venturi C Override............................................................................................................................2-35
End Batch ..........................................................................................................................................2-35
SYSTEM ...........................................................................................................................................2-35
HISTORICAL DATA ...........................................................................................................................2-36
VIEW, CAPTURE AND STORE ..................................................................................................... 2-36
Viewing previously captured reports.................................................................................................2-36
Exporting or Printing Reports............................................................................................................ 2-37
SCHEDULED AUTO POLLING ..................................................................................................... 2-38
CHAPTER 3: FLOW EQUATIONS........................................................................................................... 3-1
AGA3 ......................................................................................................................................................3-1
API 14.3................................................................................................................................................... 3-2
Wedge......................................................................................................................................................3-3
Venturi.....................................................................................................................................................3-4
AGA7 ......................................................................................................................................................3-5
DENSITY EQUATIONS........................................................................................................................ 3-6
Sarasota Density GM/CC ....................................................................................................................3-6
UGC Density GM/CC .........................................................................................................................3-7
Solartron Density GM/CC................................................................................................................... 3-8
Propylene Density ...............................................................................................................................3-9
Ethylene Density ................................................................................................................................. 3-9
NBS 1045 ............................................................................................................................................3-9
NIST14................................................................................................................................................3-9
DENSITY EQUATIONS (Without Live Densitometer)....................................................................... 3-10
CHAPTER 4: MODBUS DATA.................................................................................................................4-1
MODBUS PROTOCOL.......................................................................................................................... 4-1
TRANSMISSION MODE...................................................................................................................4-1
ASCII FRAMING ............................................................................................................................... 4-1
RTU FRAMING..................................................................................................................................4-1
FUNCTION CODE.............................................................................................................................4-2
ERROR CHECK ................................................................................................................................. 4-2
EXCEPTION RESPONSE.................................................................................................................. 4-2
BROADCAST COMMAND...............................................................................................................4-2
MODBUS EXAMPLES...................................................................................................................... 4-3
FUNCTION CODE 03 (Read Single or Multiple Register Points).....................................................4-3
ASCII MODE - Read Address 3076 ...................................................................................................4-3
MODBUS ADDRESS TABLE –16 BITS .............................................................................................4-5
MODBUS ADDRESS TABLE –32 BITS ...........................................................................................4-12
Last Batch/Daily Data Area...............................................................................................................4-15
Alarms and Status Codes................................................................................................................... 4-40
Previous Audit Data Area..................................................................................................................4-41
CURRENT ALARM STATUS.........................................................................................................4-44

Date: 8/1/2019
FLOATING POINTS............................................................................................................................4-46
Historical Batch/Daily Data Area –Meter #1 ...................................................................................4-49
Historical Hourly Data Area –Meter #1 ...........................................................................................4-50
Current Data Area–Meter #2............................................................................................................4-51
Historical Batch/Daily Data Area –Meter #2 ...................................................................................4-52
Historical Hourly Data Area –Meter #2 ...........................................................................................4-53
Programmable Floating Point Variables............................................................................................4-54

Dynamic Flow Computers SFC332L Manual Quick Start —1-1
Date: 8/1/2019
CHAPTER 1: QUICK START
Introduction:
A good flow computer must be:
User friendly
Flexible
Easy to understand and configure
Rugged
Economical to install and maintain
Accurate
The model SFC332L Smart Flow Computer incorporates all these features. We hope that your experience
with the Smart Flow Computer will be a very pleasant and friendly experience and not intimidating in any
way.
General Description: The SFC332L is a dual meter run bi-directional flow computer for the measurement
of liquid products. Using orifice plate, Venturi, turbine/PD/ultrasonic mass meter, or wedge devices, it can
meter a wide variety of products, such as crude, refined product, LPG/NGL products, products that use
table 24C, ethylene, propylene, and water. Fifty days of previous daily data, fifty previous batch data, and
fifty previous hourly data are stored in the full format type reports. The previous 100 audit trail reports and
100 alarm reports are stored. User formatted reports and user formatted ticket reports are available.
Sixteen different product files are user-configurable with easy switch feature and product scheduling for
batch operation.
Inputs/Outputs: 2 serial connections, RS-232 and RS-485, both of them Modbus ready. The RS-232 can
also be used with serial printer. Inputs: two 4 wire RTD, 4 single ended analog inputs, 4 status inputs and
1 density frequency. Outputs: 2 pulse/switch outputs; 3 switch outputs; and 2 analog outputs. Also
includes a programmable plasma display.

Dynamic Flow Computers SFC332L Manual Quick Start —1-2
Date: 8/1/2019
Technical Data:
POWER
VOLTAGE RANGE
12-30 VDC
WATTAGE
4 WATT
OPERATING CONDITIONS
TEMPERATURE
- 40 TO 185 °F
HUMIDITY
100%
HOUSING
NEMA 4X CLASS 1 DIV. 1
FEATURES
DISPLAY
PLASMA 2 LINES 16 CHARACTER
PROCESSOR
32-BIT MOTOROLA 168332 @ 16.7 MHz
FLASH ROM
4 MB @ 70 NANO SECONDS
ROM
2 MB @ 30 NANO SECONDS
FREQUENCY INPUT
3 CHANNELS
0 - 5000 Hz
WITH TURBINE DIAGNOSTIC FUNCTION
>70 mV FOR SIN WAVE
> 6 VOLTS FOR SQUARE WAVE
ANALOG INPUT
FOUR 24-BIT CHANNEL
RTD INPUTS
2 CHANNELS 4 WIRES
ANALOG OUTPUT
2 CHANNELS 12 BIT SINGLE ENDED
DIGITAL OUTPUT
OUTPUTS 1 & 2 PULSE/SWITCH 0.5 AMPS RATING
OUTPUTS 3 TO 5 ARE SWITCH OUTPUTS 0.25 AMPS
RATING
STATUS INPUTS
4 ON/OFF TYPE SIGNAL
ALL INPUTS AND OUTPUTS ARE OPTICALLY ISOLATED
SERIAL
1 RS485 @ 9600 BAUDS VARIABLE
1 RS232 @ 9600 BAUDS VARIABLE
COMMUNICATION PROTOCOL
MODBUS

Dynamic Flow Computers SFC332L Manual Quick Start —1-3
Date: 8/1/2019
Parts List
Part
Description
332-01P
Controller (CPU) Board for SFC332/1000 w/prover option.
332-02
Terminal (BP) Board for SFC332/1000.
332-03
Analog Board for SFC332/1000.
332-04
Display (LCD) for SFC332/1000.
332-05
Rosemount Interface Board for SFC1000.
332-06
Prover Option for SFC332/1000.
332-07
Enclosure for SFC332/1000.
332-08
Mounting Bracket w/captive screws for SFC332/1000 Boards.
332-09
Adapter between SFC1000 and Rosemount 205.
332-10
Center portion of housing for SFC332/1000 enclosure.
332-11
Glass Dome Cover for SFC332/1000 Enclosure.
332-12
Blank Dome Cover for SFC332/1000 Enclosure.
332-13
O-ring for SFC332 Enclosure.
332-14
External I/O Expansion.
332-15
Battery Replacement for SFC332/1000.
332-16
1/2 Amp 250V Fuse for SFC332/1000.
332-17
EPROM for SFC332/1000 (set of two).
RS232
External RS232 Connection for all models.

Dynamic Flow Computers SFC332L Manual Quick Start —1-4
Date: 8/1/2019
SFC332L Flow Computer: Dimensions

Dynamic Flow Computers SFC332L Manual Quick Start —1-5
Date: 8/1/2019
Starting and Installing theWindow Software:
System Minimum Requirements
In order to install this software product the following requirements must be met:
Windows Operating System (Win95, Win98, Win98SE, win2000, WinNT, WinXP, Vista,
Windows 7, Windows 8, Windows 10)
For Windows NT, 2000, XP or Vista: Administrator level access to create an ODBC system DNS.
Minimum disk space available: 16 MB.
1 Serial Communication Port
If your computer meets these requirements, you can run the setup file downloaded from our website

Dynamic Flow Computers SFC332L Manual Quick Start —1-6
Date: 8/1/2019
Website - DFC Configuration Software
Step 1. Go to our website WWW.DYNAMICFLOWCOMPUTERS.COM
Step 2. Click on the “Downloads”
Step 3. Select either Windowsor
DOS software based on Step 2.
Step 4. On the new screen
presented to you click on the
application that you are trying to
download. Once you hit the link it
will ask you if you want to run or
save the file in your computer.
Select SAVE. (See illustration 1)

Dynamic Flow Computers SFC332L Manual Quick Start —1-7
Date: 8/1/2019
Step 5. The file will start to
transfer to your computer. The
download time depends on your
Internet connection speed and the
type of application that being
downloaded.
Step 6. When the download if
finish. Press the OPEN button to
start the setup process. (See
Illustration)
Step 7. Follow the steps in the
application setup.

Dynamic Flow Computers SFC332L Manual Quick Start —1-8
Date: 8/1/2019
Getting acquainted with the flow computer wiring:
Back terminal wiring:
The back terminal wiring indicates the overall positions of the terminal plugs and their functions. Though
the back panel’s jumpers are also shown, refer to the next drawing, “Back Panel Jumpers”, for information
on their settings and functions.
The Smart Flow Computer receives its power via the two topmost pins on Terminal P1, on the left of the
terminal board. Also on Terminal P1 are, from top to bottom, inputs from the two turbines and the RS-485
serial connection.
To the right (P4), from top to bottom, are status input 1, density frequency input, and switch output 1 and 2.
Terminal P3, at the lower bottom, handles analog inputs and outputs. These are, in order from right to left,
analog inputs 1-4 and analog outputs 1 and 2.
Terminal P5, top middle, is the RTD terminal block, "100 platinum RTD input".

Dynamic Flow Computers SFC332L Manual Quick Start —1-9
Date: 8/1/2019
Back Panel Jumper
In this illustration, a jumper is “ON” when the jumper block is used to connect the jumper’s to wire prongs.
“OFF” means the jumper block is completely removed or attached to only one of the two wire prongs.
Note: R11 and R3 could have a vertical orientation instead of a horizontal
orientation on certain Smart Flow Computer models.

Dynamic Flow Computers SFC332L Manual Quick Start —1-10
Date: 8/1/2019
Memory Jumper

Dynamic Flow Computers SFC332L Manual Quick Start —1-11
Date: 8/1/2019
Steps to clear memory through removing the memory jumper
(1) Turn off the power, move the jumper to the next two pins, wait for 5 seconds
(2) Put the jumper back
Memory cleared and Flow Computer ID is set to 1, 9600 baud rate, RTU mode

Dynamic Flow Computers SFC332L Manual Quick Start —1-12
Date: 8/1/2019

Dynamic Flow Computers SFC332L Manual Quick Start —1-13
Date: 8/1/2019

Dynamic Flow Computers SFC332L Manual Quick Start —1-14
Date: 8/1/2019
INPUT/OUTPUT: Assigning and Ranging Inputs
Input/Output Assignment
We will now configure your SFC332L Flow Computer’s inputs and outputs. The flow computer allows the
user to configure the inputs and outputs. (I.e. Analog #1 is pressure for Meter #1). The flow computer will
not use the unassigned inputs.
How to assign a transmitter to an I/O point
1Click “Configure Device”, configuration menu is prompted
2On configuration menu, click “Input Assignment”
3Enter assignments for DP, temperature, pressure, density and spare inputs.
4Assignment (1-n). Assignments 1-4 are analog inputs attached
to terminal of the back panel. These inputs accept 4-20mA or 1-5
volts input and are suitable for temperature, pressure, density, or spare inputs. An assignment
5 is strictly RTD (temperature) input only for the meter, densitometer or spare. Assignment 7
indicates a density frequency input; it is assigned automatically once you choose live density
frequency input in the setup menu at density type Assignment 10 (module 1) is for
Rosemount multi-variable module only. DP, pressure, and temperature for the meter can be
assigned. When a frequency type primary element is hooked to the flow computer, the Multi
Variable pressure and temperature can be used and the DP becomes a spare input that could
be assigned for strainer differential.

Dynamic Flow Computers SFC332L Manual Quick Start —1-15
Date: 8/1/2019
Ranging the Transmitter Inputs:
1. Enter the range values: after assigning the inputs scroll down the transducer inputs
assignment menu to scale the 4-20mA. Enter the value at @4mA and @20mA. Enter both
values similar to the way the transmitter is ranged. 1-5 volts is equivalent to 4-20mA. Enter
the 1 volt value at the 4mA, and 5 volt value at 20mA. When the Multi Variable is used the 4-
20 ma scale has no effect on anything and does not need to be configured for that input. The
reason is simply that the flow computer gets the data via digital communication from the
transmitter in engineering units, and therefore a scale is not needed. Normal pressure range is
0-3626, temperature –40 to 1200, DP –250 to 250, or -830 to 830 inches of water.
2. Enter the high and low limits: high limits and low limits are simply the alarm points in
which you would like the flow computer to flag as an alarm condition. Enter these values
with respect to the upper and lower range conditions. Try to avoid creating alarm log when
conditions are normal. For example: If the line condition for the pressure is between 0 to 500
PSIG, then you should program less than zero for low pressure alarm, and 500 or more for
high pressure alarm. High limits are also used in the SCALE for the Modbus variables. The
high limit is equalent to 32767 or 4095. The low limit is not used for calculating the scale.
The scale starts at zero to wherever the high limit value.
3. Set up the fail code: Maintenance and Failure Code values tell the flow computer
to use a default value in the event the transmitter fails. The default value is stored in
Maintenance. There are three outcomes: the transmitter value is always used, no matter
what (Failure Code = 0); the Maintenance value is always used, no matter what
(Failure Code = 1); and the Maintenance value is used only when the transmitter’s
value indicates that the transmitter has temporarily failed (Failure Code = 2).
RTD inputs will skip 4-20 mA assignment because RTD is a raw signal of 50(ohms) to 156. Readings
beyond that range require a 4-20 mA signal to the flow computer or using the built in Rosemount Multi
Variable transmitter. The Rosemount Multivariable has a range of –40-1200 degrees Fahrenheit.
Density coefficients for raw frequency inputs are programmed in this menu. The menu will only show
parameters relevant to the live density selected (i.e., Solartron or UGC, etc.).