Eaton Network Shutdown Module V3 User manual

www.eaton.com
Network Shutdown Module V3
User Manual
Network Shutdown Module V3 – User Manual - 34 003 896 XU / AE

www.eaton.com
Network Shutdown Module V3
User Manual
Table of Contents
1Introduction to the EATON’s Network Solution................................................................... 3
1.1 Overview ...............................................................................................................................................3
1.2 Monitoring the UPSs over the network..................................................................................................4
1.3 Protecting the computers / servers .......................................................................................................5
1.4 Connecting the UPS..............................................................................................................................6
1.4.1 Connecting to the Network ............................................................................................................................6
1.4.2 Select Network Architecture ..........................................................................................................................6
1.4.3 Network Performances..................................................................................................................................7
2Installation............................................................................................................................... 8
2.1 Hardware Pre-requisites (Electrical and Network Connections) ...........................................................8
2.2 Software Installation Pre-requisites.......................................................................................................9
2.2.1 On the System Hosting « Network Shutdown Module V3 » ..........................................................................9
2.2.1.1 Windows Compatibilities:........................................................................................................9
2.2.1.2 Linux Compatibilities:..............................................................................................................9
2.2.1.3 Mac Compatibilities:................................................................................................................9
2.2.1.4 Standby configuration (Windows):........................................................................................10
2.2.1.5 Broadcast Message configuration (Windows): .....................................................................10
2.2.1.6 Firewall configuration (Windows & Linux) and Gateway : ....................................................10
2.2.2 On the System that Displays Web-based Graphical User Interface ............................................................10
2.3 Quick Start...........................................................................................................................................11
2.4 Software Installation Procedure ..........................................................................................................12
2.5 Application deployment and silent installation (advanced) .................................................................14
2.6 Uninstalling the Network Shutdown Module.......................................................................................14
3Minimal configuration steps ................................................................................................ 15
3.1 Introduction..........................................................................................................................................15
3.2 The IP address of the UPS that powers your server...........................................................................15
3.3 Users accounts configuration..............................................................................................................17
4Use ......................................................................................................................................... 18
4.1 Monitoring the server and the UPS(s).................................................................................................18
4.1.1 Local access ...............................................................................................................................................18
4.1.2 Remote access ...........................................................................................................................................18
4.2 System and UPS event log .................................................................................................................21
4.3 UPS Events list....................................................................................................................................21
4.4 Test the communication with the UPS ................................................................................................23
4.4.1 Simple Tests ...............................................................................................................................................23
4.4.2 Advanced tests............................................................................................................................................24
4.5 Start and stop the Shutdown Module (advanced)...............................................................................24
5Other Configuration possibilities........................................................................................ 25
5.1 Introduction..........................................................................................................................................25
5.2 Configure system parameters .............................................................................................................25
5.3 Shutdown Configuration......................................................................................................................26
5.4 Checking for Upgrades........................................................................................................................28
5.5 Events and actions (advanced configuration) .....................................................................................28
6Multi-UPS Systems...............................................................................................................30
6.1 Caution ................................................................................................................................................30
6.2 Presentation ........................................................................................................................................30
6.3 Create a multi-UPS configuration........................................................................................................33
7Appendix ............................................................................................................................... 34
7.1 Single UPS Mode compatibility ...........................................................................................................34
7.1.1 Card/Proxy compatibility..............................................................................................................................34
7.1.2 UPSs compatibility ......................................................................................................................................34
7.2 Multi-UPS Mode Compatibility list .......................................................................................................34
7.2.1 Caution........................................................................................................................................................34
Network Shutdown Module V3 – User Manual - 34 003 896 XU / AE

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 2/65
7.2.2 « simple » configurations.............................................................................................................................34
7.2.3 Simple associations of the previous configurations.....................................................................................36
7.2.4 Configurations NOT supported....................................................................................................................37
7.3 Examples of Multi UPS configurations ................................................................................................38
7.4 Multi-UPS Systems and Event Management......................................................................................38
7.5 Application deployment and silent installation.....................................................................................39
7.5.1 Introduction .................................................................................................................................................39
7.5.2 Customized installation package.................................................................................................................39
7.5.3 Install the Shutdown Module in silent mode ................................................................................................40
7.5.4 Advanced installation options......................................................................................................................41
7.6 Single UPS Shutdown Sequence........................................................................................................42
7.7 Multi UPS shutdown sequence (example with Static Transfer Switch) ..............................................45
7.8 Additional information on events and actions......................................................................................46
7.8.1 Action settings Tab......................................................................................................................................46
7.8.1.1 The different actions .............................................................................................................46
7.8.1.2 Add an action ........................................................................................................................47
7.8.1.3 «System Shutdown» Action..................................................................................................47
7.8.1.4 Execute Action ......................................................................................................................49
7.8.1.5 «Send email» Action ............................................................................................................50
7.8.2 Events Tab..................................................................................................................................................51
7.8.2.1 Notification alarms..............................................................................................................51
7.8.2.2 Protection alarms................................................................................................................52
7.8.2.3 Multi UPS Systems and Notification Alarms....................................................................52
7.8.2.4 Multi UPS Systems and Protection Alarms......................................................................52
7.8.3 Test tab .......................................................................................................................................................53
7.8.4 The action parameters (execute and send email) ......................................................................................54
7.8.5 Software utilities ..........................................................................................................................................54
7.8.5.1 Shutdown.bat (Windows Script)............................................................................................54
7.8.5.2 Shutdown.sh (Linux Script)...................................................................................................55
7.8.5.3 Wait (Windows).....................................................................................................................55
7.8.5.4 Windows RunAs command or legacy mgeRunAs software utility .......................................55
7.9 FAQ and Error messages....................................................................................................................57
8Glossary ................................................................................................................................ 60
9Acknowledgements.............................................................................................................. 61
9.1 SQLite..................................................................................................................................................61
9.2 Pi3Web................................................................................................................................................61
9.3 PHP .....................................................................................................................................................61
9.4 OpenSSL.............................................................................................................................................62
9.5 Lighttpd................................................................................................................................................64
9.6 WxWidget ............................................................................................................................................64

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 3/65
1 Introduction to the EATON’s Network Solution
1.1 Overview
EATON’s Network Solution:
zprovides information on events concerning the supply of power to the computers connected to your
computer network,
zcarries out automatic shutdown of computer systems,
zmonitors and controls all the UPSs connected to the network.
As illustrated in the picture below, EATON Network Solution provides these 3 main functions:
zsupervising the UPSs over the Network,
zprotecting the computers,
zconnecting the UPS to the Network.
The functions of EATON’s Network offering

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 4/65
1.2 Monitoring the UPSs over the network
Depending on your needs, you can either use:
your Internet browser to monitor each UPS, as
Management Proxy, Management Card and
Shutdown Module include a Web server.
your company’s standard Network Management
System:
>HP-Openview,
>CA Unicenter,
>HP Insight Manager,
>IBM Tivoli Netview,
>…
To simplify integration of EATON UPSs with these
NMS, you can use one of the Network Management
System Kits for EATON devices. These kits are
available on Management Pac 2 CD-Rom (ref 66923).
the EATON supervisor "Intelligent Power Manager"

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 5/65
1.3 Protecting the computers / servers
The Network Shutdown Module installed on each of the servers to be protected performs this function. Note
that the Shutdown Module is available on several Operating Systems.
The Shutdown modules:
zcontinuously wait for information from the Mgt. Proxy or Mgt. Card connected to the EATON UPS.
zwarns administrators and users if AC power fails and proceeds with graceful system shutdown before the
end of battery backup power is reached.
New functions:
The Network Shutdown Module V 3.20 offers the “mass configuration” advanced management feature
through Enterprise Power Manager 2.20.
The version V3 of the Network Shutdown Module:
zoffers a remote supervision interface through any web browser (with a secured SSL/HTTPS connection
enabled by default),
zmanages multi UPS redundant configurations (see “Multi-UPS systems” chapter )
zSeveral UPSs in parallel
>2 UPSs in Hot standby (or serial) redundancy
>2 redundant UPSs through Static Transfer Switch
>UPSs powering a server with multiple power supplies
UPSs powering servers with multiple power supplies
zmanages switchable outlets
With this version you can trigger shutdown sequences with switchable outlets.
A UPS that powers servers with load-shedding function

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 6/65
1.4 Connecting the UPS
1.4.1 Connecting to the Network
This function can be performed either through network Cards inserted in the UPS (Network Management
Card) or through a software “agent” running on a nearby PC that is called the Network Management Proxy.
Note that the Network Management Proxy is available only on Windows.
The Network Management Card or Proxy:
zmanages communication with the UPS (as well as local protection of the machine on which Proxy is
installed),
zperiodically accesses the information concerning the UPS,
zmakes this information available to the connected applications (Network Shutdown Modules, Web
Browser, Network Management Systems, Enterprise Power Manager)
1.4.2 Select Network Architecture
Below are two software and hardware architectures showing how EATON UPSs can protect several
computers. These typical examples are intended to assist you in designing your own architecture.
Connection with Network Management Card
On the diagram above, the following two types of connections are required:
zthe electrical power cables,
zthe TCP/IP communication network.

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 7/65
Connection with Network Management Proxy
On the diagram above, three types of connections are required:
za point-to-point link (serial or USB),
zthe electrical power cables,
zthe TCP/IP communication network.
1.4.3 Network Performances
The Network Management Card is designed to support a maximum of:
z35 Network Shutdown Module connections in standard secure mode
z100 connections with NSM 3.10 min. and NMC 66102/DA min. in UDP mode
Network Management Proxy, installed on a dedicated server, with at least 500 MB of Ram and a 1 GHz
CPU, is designed to support a maximum of:
z250 Network Shutdown Module connections in standard secure mode.

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 8/65
2 Installation
Note: This user manual only applies to Network Shutdown Module V3. For previous versions of Network
Shutdown Module V2.x, please read the HTML on line manual.
2.1 Hardware Pre-requisites (Electrical and Network Connections)
Connection steps
Before connecting the UPS, you must first decide on a software and hardware architecture.
Before installing the EATON Network Solution, the UPS must be set up as indicated in the steps below.
zShut down the computers to be protected by the UPS.
zConnect the UPS to a wall outlet. (For UPSs above 3kVA, please refer to the UPS installation manual).
zConnect the power cord of each computer to an outlet on the UPS. (For UPSs above 3kVA, please refer
to the UPS installation manual).
zHow to connect UPS / proxy or card / network:
>If the Mgt. Proxy is used, connect the serial or USB port on the computer and on the UPS.
>If a Network Management Card is used, insert the optional card in the UPS and connect the UPS to
the computer network.
zStart the EATON UPS, then the computers.
zSetting up the protection
>If the Mgt. Proxy is used install it on the one machine directly connected to the UPS.
>If a Network Management Card is used, it must be set up (see the Mgt. Card's user manual).
zInstall Network Shutdown Module on all the other machines that are to be protected by the UPS (supplied
with UPS battery backup power).
Note: The Mgt. Proxy manages protection of the machine on which it is installed.

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 9/65
2.2 Software Installation Pre-requisites
2.2.1 On the System Hosting « Network Shutdown Module V3 »
2.2.1.1 Windows Compatibilities:
Network Shutdown Module V3 Windows is compatible and has been tested with:
zWindows (x86) 2000 / XP (Home or Pro) / 2003 / Vista (Business or Ultimate) /
2008 (Web Server, Standard, Entreprise, Data Center) /
Windows 7
Server 2003 Appliance Edition (Tested on Iomega NAS Server)
zWindows (Xeon 64) Windows Server 2003 Standard x64 Edition
Windows Server 2008 Enterprise x64 Edition
Windows 7
Windows Vista Business x64
zWindows (AMD Opteron) IBM blade server AMD Opteron single processor for LS20 (type 8850)
Windows Server 2003
zWindows (Intel Xeon) IBM blade server Intel Xeon single processor for HS20 (type 8843)
Windows Server 2003
2.2.1.2 Linux Compatibilities:
Network Shutdown Module V3 Linux is compatible and has been tested with:
zLinux (x86/x86_64)
Debian GNU Linux: Etch, Lenny
SUSE/Novell: SLES 11, OpenSUSE 10.3, 11.2,
Redhat Enterprise Linux: RHEL 5.4, Fedore core 12
Ubuntu: 9.04, 9.10
VMWare: ESX3, 3.5, ESXi4 (NSM CLI installer)
Mandriva 2009, 2010
The Linux package is based on standard Linux mechanisms and therefore can be installed and used with
other Linux distributions. Feedbacks / test or bug reports are welcome at EATON Support.
The following list is not exhaustive. Network Shutdown Module V3 should be compatible with:
zLinux (x86/x86_64)
Debian GNU Linux: Testing,
SUSE/Novell: SLES 10, openSUSE 10.x, 11.x
Redhat Enterprise Linux: RHEL 4, 5 , Fedora core 10,11
Ubuntu: 7.10, 8.04, 8.04 LTS Server, 8.10
Others: IPCop, …
2.2.1.3 Mac Compatibilities:
Network Shutdown Module V3 Mac OSX is compatible and has been tested with:

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 10/65
zMac Intel Mac OS X 10.4, 10.5, 10.6
zMac PowerPC Mac OS X 10.4, 10.5
2.2.1.4 Standby configuration (Windows):
In Configuration Panel -> Power Option properties:
zYou must unselect the Standby configuration of your Operating System to be compliant with the
Network Shutdown Module. With the standby configuration checked your system is not protected.
zIf you want to save energy, please prefer the hibernate feature.
2.2.1.5 Broadcast Message configuration (Windows):
If the “Broadcast administrator messages / Broadcast user messages ” function is activated, on Network
Shutdown Module, you have to check that the “Messenger” Service is started.
This service is mandatory to use the broadcast messages on Windows.
2.2.1.6 Firewall configuration (Windows & Linux) and Gateway :
(Optional) To enable a remote access for supervision and configuration you will have to open the following
UDP and TCP ports of the Windows Firewall:
z4679 EATON Supervision
z4680 EATON Management (access through SSL)
These ports are reserved for EATON at IANA (Internet Assigned Numbers Authority, http://www.iana.org/).
If you use Windows, the ports are automatically opened in the Windows Firewall.
If you use a Firewall with all ports closed by default:
To enable communication between Network Shutdown Module and Network Management Card:
zPort 80 must be opened as a destination port (for output) on the machine hosting Network Shutdown
Module.
If you use a Gateway without predefined routed port:
To enable communication between Network Shutdown Module and Network Management Card:
zEnsure to route 4679 and 4680 ports with the protocol «TCP»&«UDP».
2.2.2 On the System that Displays Web-based Graphical User Interface
Important:
The Network Shutdown Module graphical interface can be accessed remotely using a simple Web browser.
Access to this interface is secured through SSL connection (default configuration) and must also be secured
through Login & password.
The Network Shutdown Module graphical interface has been tested with:
zMozilla Firefox (1.5, 2.0, 3.0) is recommended for better performance. (Firefox is mandatory for Linux)
zMicrosoft Internet Explorer V6, V7, V8
zSafari
Note: For the Web browser, we advise you against the use of the highest security level. Some configuration
screens are not useable.
Javascript and Cookies must be authorized for the selected security level.

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 11/65
2.3 Quick Start
To install the Network Shutdown Module in 5 minutes, please perform the following steps on a machine
running Windows 2000 / XP / 2003 / 2008 / Vista / 7, Linux or Mac OSX:
zStep 1 (Pre-requisites)
Check that following connections are operational:
>the electrical connection between the UPS and the server to protect
>the network connection between the UPS and the Network Management Card (or Proxy).
zStep 2 (Optional)
To enable the configuration and supervision remote access, Network Shutdown Module needs the 4679
and 4680 ports (UDP/TCP) to be opened in the Firewall (Automatically opened in the Windows Firewall).
zStep 3 (Software Installation)
On a Windows 2000 / XP / 2003 / 2008 / Vista / 7, Linux or Mac OSX machine, execute the “Network
Shutdown Module” package under an administrator account.
zStep 4 (Configuration)
>In the Configuration->Power devices screen,
Enter the default Login «admin» and default Password «admin»
Then click on the Add button and
>Enter the IP (or the host name) of the Network Management Card (or Proxy)
or use the following new function:
New: With the Quick Scan … button, available with version 3.10 and later, you can discover
in a few seconds the cards connected to the network and then select a card from the list.
>Save your configuration
>In the Configuration->Users window configure your password (recommended)
>For the multi-UPS configurations, please refer to chapter 6
zStep 5 (Operation)
You can now supervise the UPS state and the information concerning the protected server

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 12/65
2.4 Software Installation Procedure
This section informs on how to install Network Shutdown Module to protect the computer system.
Before starting the installation:
zit is necessary first to install a Network Management Card in the UPS or the Mgt. Proxy on a server.
zmake sure you have the necessary administrator rights to install Network Shutdown Module (for
Windows and Linux).
zit is assumed that you are aware of the installation prerequisites.
Follow these steps to install Network Shutdown Module in interactive (graphical) mode:
onnect to the EATON download area. Follow the instructions to download Network Shutdown Module
From CD ROM:
t navigator screen select "Network Solutions" and follow the instructions
C
or insert the Solution-Pac 2 CD-ROM (/HF).
zAt the firs
For Windows:
the downloaded package.
From the Web:
zExecute
From CD ROM:
zMount your CD-ROM (ex: /mnt/cdrom)
wser to discover the solutions and select
tions
zOpen Default.htm from your internet bro
"Network Solutions".
zFollow the instruc
For Lin
nd save the file to your computer.
ckage (through graphical interface)
ux:
From the web:
zDownload a
zAuthorize the execution right on the downloaded pa
or execute the command : chmod 755 nsm_linux_xx_3_xx_xx.run
zTo install execute the package (double click)
zIf necessary enter the root password
zFollow the instructions
For Mac OSX downloaded package.
From the Web:
•Execute the
Choose the installation language. The selected language will correspond to the one of the installed
accept the License Agreement for EATON Software.
le.
ule
After the installation,
n-> Power device screen,
sword «admin»
e Network Management Card (or Proxy)
n, available with version 3.10 and later, you can discover
z
product.
zRead and
zChoose the installation directory of the Network Shutdown Modu
>Windows default value is C:\Program Files\EATON\NetworkShutdownMod
>Linux default value is /usr/local/EATON/NetworkShutdownModule
>Mac OSX default value is /usr/local/EATON/NetworkShutdownModule
zComplete the installation.
>In the Configuratio
Enter the default Login «admin» and default Pas
Then click on the Add button and
>Enter the IP (or the host name) of th
or use the following new function:
New: With the Quick Scan … butto
in a few seconds the cards connected to the network and then select a card from the list.

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 13/65
Power device settings
>Save your configuration
zConfigure your password (recommended)
zFor multi-UPS systems, please refer to the chapter "Multi UPS systems" .
zThe Network Shutdown Module is now configured by default. You can anyway customize the Network
Shutdown Module and for example configure your password (recommended).
zThe installed components are automatically started.
zIt is possible to test Network Shutdown Module.
zThe protection function is now active on the computer and will be run automatically each time the
computer is started.
Follow these steps to install Network Shutdown Module in console mode:
zFor Linux, if the server doesn’t have the graphical layer installed, you have to use the specific package
called nsm_linux-cli_xxx.run
zLogin as root in a terminal
zThen install the Network Shutdown Module in silent mode
Note : You can configure the Network Shutdown Module either:
zthrough the silent mode parameters (e.g.)
./<FileName> -install –silent –agentName ‘172.17.1.2’
zthrough remote access

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 14/65
2.5 Application deployment and silent installation (advanced)
After customizing the Network Shutdown Module configuration (name or IP address of Network Management
Card/Proxy, events and actions, etc.), you can build a Network Shutdown Module installation package that
contains your specific configuration.
You can then deploy this Network Shutdown Module configuration on other machines that have the same
operating system.
Network Shutdown Module application deployment
Refer to the appendix “Application deployment and silent installation”
2.6 Uninstalling the Network Shutdown Module
Windows:
zThe shortcut EATON -> Network Shutdown Module->Uninstall is used to uninstall
Network Shutdown Module.
or
zIn the Control panel, you can also run the Add/remove programs command and select
the Network Shutdown Module program.
Linux:
zThe KDE shortcut K:-> EATON -> Network Shutdown Module->Uninstall is used to
uninstall Network Shutdown Module.
zThe Gnome shortcut Applications-> EATON -> Network Shutdown Module->Uninstall
is used to uninstall Network Shutdown Module.
zIn console mode, you can execute <Installation directory>/packaging/nsmInstaller –
uninstall
<Installation directory> default value is /usr/local/EATON/NetworkShutdownModule/
Mac OSX: zThe shortcut Applications -> Utilities -> EATON -> Network Shutdown Module-
>Uninstall.command is used to uninstall Network Shutdown Module.

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 15/65
3 Minimal configuration steps
3.1 Introduction
In this chapter we describe the basic and minimal configuration steps that must be performed before using the
Network Shutdown Module.
The other and optional configuration possibilities are described later.
3.2 The IP address of the UPS that powers your server.
In the Configuration -> Power device screen, click on the Add button
Adding a power device
Then following screen appears:
>Enter the IP (or the host name) of the Network Management Card (or Proxy)
or use the following new function:
New: With the Quick Scan … button, available with version 3.10 and later, you can discover
in a few seconds the cards connected to the network and then select a card from the list.
Power device settings
From this screen, you can define the following parameters:
zNetwork Name or IP address of the Network Management Card / Proxy. This parameter must correspond
to the UPS that powers your machine.
zThe UPS Outlet that powers the server
Powershare outlets and load shedding:
You have the possibility in this page to configure the electrical dependency between one of the UPS
switchable plugs and the server hosting Network Shutdown Module.
This function is useful for the servers that must be first shut down during the autonomy sequence.

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 16/65
Load shedding configuration on UPS powershare outlets
Remark:
This load shedding function is not available if the UPS doesn’t have any switchable outlet.
Note:
For multi-UPS configurations, you have the possibility to enter several names or IP addresses (using the
[Add] button). For these advanced configurations, please refer to the Chapter « Multi – UPS systems ».

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 17/65
3.3 Users accounts configuration
Click on the Users item of the Configuration section on the left menu.
The default Login «admin» and default Password «admin» with Visualization – Management rights.
Note: For security reasons we advise you to remove this default login and to create a new login with
new access password.
User accounts configuration
You can configure several user accounts.
To add a user account:
zenter the User Login and the User password (twice),
zselect the User’s Rights level. The following levels are available:
Visualization – Management (the user will be able to access all the sections)
Visualization (the user will only access to the Supervision (*) and the About sections)
zclick on the Create new user button
(*) Remove logs function in UPS logs panel is only functional with Visualization – Management user's right.

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 18/65
4 Use
4.1 Monitoring the server and the UPS(s)
4.1.1 Local access
From the system where the Network Shutdown Module is installed,
zYou can use the following shortcut:
For Windows: Start -> Programs -> EATON -> Network Shutdown Module -> Supervision
For Linux (KDE): K-> EATON -> Network Shutdown Module -> Supervision
For Linux (Gnome): Applications -> EATON -> Network Shutdown Module -> Supervision
For Mac OSX: Applications -> Utilities -> EATON -> Network Shutdown Module->Supervision.command
zYou can also use the icon in the task bar:
To access to this interface:
ZDouble-click on the icon or
ZRight click the icon in the task bar to access to the item
“Network Shutdown module Status”
4.1.2 Remote access
zFrom a remote machine, you can type the following URL in a Web browser for
>secured SSL access:
https://< name or IP address of computer hosting NSM>:4680/
>or for non secured access:
http://< name or IP address of computer hosting NSM>:4679/
Note: The Web server is “case sensitive” for the URL.
zAccept the SSL Certificate (by clicking on Yes)
Accepting the SSL Certificate
To install the certificate on IE7 for Vista, you need
to perform the following steps:
>Run IE as an administrator (Right-click the
desktop icon)
>Visit the NSM site.
>Click through the certificate error
>Click the "Certificate Error" button in the
address bar.
>Click View Certificate
>Click Install Certificate
>Unlike on XP, you must click the “Place all
certificates in the following store” radio button,
and choose the “Trusted Root Certification
Authorities” store. If you don’t do this, the
certificate goes in your personal store, and it
isn’t trusted by IE.

www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE Page 19/65
zEnter the Login and Password (optional)
zThe following page appears:
Server and UPS supervision
Section « Information on the protected server»
zServer name / IP address:
The Network name of the machine hosting the Network Shutdown Module and its IP address.
zOperating system:
The operating system of the machine hosting the Network Shutdown Module.
zContact / Location:
The location of the machine hosting the Network Shutdown Module
the contact person for the machine hosting the Network Shutdown Module.
These values can be configured in the System page.
Section concerning the UPS that powers the protected server
zThis icon represents the status of the power device. It can have following
values: Critical/Alert/Normal
zName/ IP address: The Network name (or IP address) of the device.
zDevice: The commercial product name.
zLink: Link to the device Web site (if available).
zContact / Location: The device contact. (value of syscontact object or can also be configured in the
Device page).
The device location. (value of syslocation object or can also be configured in the Device page).
Status
zCommunication: Device communication status (OK / Network Communication Failure / device
Communication Failure).
zPower source: AC Power / Battery.
Table of contents
Popular Software manuals by other brands

Juniper
Juniper JUNOS SOFTWARE 10.2 - SOFTWARE INSTALLATION AND UPGRADE GUIDE... Upgrade guide

Navman
Navman S-Series NavDesk 2009 user manual

Autodesk
Autodesk 00128-051462-9340 - AutoCAD 2008 - PC manual

GRASS VALLEY
GRASS VALLEY AURORA EDIT 7 datasheet

Garmin
Garmin MapSource user manual

Brocade Communications Systems
Brocade Communications Systems 8 Administrator's guide

Primera
Primera Discribe5 user manual

Novell
Novell CLIENT FOR LINUX 2.0 manual

Autodesk
Autodesk AUTODESK SHOWCASE 2011 - SYSTEM REQUIREMENTS Hardware

Red Hat
Red Hat ENTERPRISE LINUX 4 - DEVELOPER TOOLS GUIDE manual

Vertical
Vertical Xcelerator IP Application note

Fujitsu
Fujitsu Remote Management user guide