Eguana Evolve ESS Installation and operation manual

DO 58160 Rev1
Evolve ESS
Installation & Startup Manual
For use only with battery model
LG Chem EM048126P3S7

DO 58160 Rev1
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for the Eguana Evolve™ESS –including the Power Control System (PCS)
and base model battery cabinet installation and operation. The AC Battery is expandable with the addition of up to
two more battery cabinets. Refer to the manual, “Eguana AC Battery Expansion Cabinet Installation Guide” for more
details if your system contains additional battery capacity beyond the base model. The Eguana AC Battery™
components described by this manual are intended to be used as part of an Energy Storage system and installed per
all local building codes and regulations in addition to the National Electrical Code, ANSI/NFPA 70 (for US) and
Canadian Electrical Code (for Canada).
CAUTION: Hazardous Voltages! This inverter contains hazardous voltage and energy that may be lethal. It may
only be installed by qualified personnel who have read this manual and are familiar with its operation and hazards.
The following safety procedures should be followed:
Only connect the PCS cabinet to a compatible electrical service as defined in the model specifications. The PCS must
be connected to a dedicated branch circuit in the main electrical panel.
An external disconnect switch shall be provided in the end installation by others for the AC Grid output circuit.
CAUTION! This equipment contains high energy lithium batteries. Qualified and trained personnel should wear
protective clothing and equipment when working inside the battery cabinet and/or with battery modules.
The PCS is compatible with the LG Chem battery model EM048126P3S7 only.
CAUTION! The batteries provided with this system must be charged only by the PCS included as part of the
energy storage system. Do not attempt to charge batteries with any other charger device or connect any devices
directly to the DC battery bus.
Ensure proper electrical grounding in accordance with code requirements.
Ensure proper airflow path for active cooling.
Never operate system in a manner not described by this manual.
Only qualified personnel should service this product.
Ensure all covers are securely fastened after installation is complete.
This product must be stored indoors in an environmentally conditioned location prior to installation, protected from
rain and exposure to any hazardous chemicals.
Do not attempt to operate this product if there is any physical evidence of damage to any of the cabinets or internal
components.
CAUTION! This equipment is heavy. Mechanical lifts are recommended for safe installation.

Table of Contents
1 SAFETY ...............................................................................................................................................................................................................................1
1.1 IN CASE OF EMERGENCY..............................................................................................................................................................................................1
1.2 BATTERY MODULE SAFETY PRECAUTIONS................................................................................................................................................................. 1
1.3 GENERAL SAFETY PRECAUTIONS................................................................................................................................................................................2
1.4 DISPOSAL AND RECYCLING ........................................................................................................................................................................................ 2
2 INTRODUCTION ...............................................................................................................................................................................................................3
2.1 ABOUT THIS MANUAL –TARGET AUDIENCE............................................................................................................................................................. 3
2.2 INSTALLATION PLANNING &SUPPORTING DOCUMENTS .........................................................................................................................................3
2.3 GLOSSARY ...................................................................................................................................................................................................................4
2.4 INITIAL INSPECTION OF MATERIAL LIST .....................................................................................................................................................................4
2.5 SPECIAL TOOLS &HARDWARE................................................................................................................................................................................... 4
3 INSTALLATION SITE PREPARATION........................................................................................................................................................................ 5
3.1 OVERVIEW OF PCS AND BATTERY COMPONENTS ................................................................................................................................................... 5
3.2 INSTALLATION AREA REQUIRED TO WALL MOUNT PCS AND BATTERY:...............................................................................................................5
4 PCS AND BATTERY CABINET WALL-MOUNTING INSTRUCTIONS...............................................................................................................6
5 PCS / BATTERY INTER-CABINET WIRING.............................................................................................................................................................8
5.1 BATTERY POWER CABLE CONNECTIONS....................................................................................................................................................................8
5.2 BATTERY BMS TO PCS COMMUNICATION CONNECTION.........................................................................................................................................9
6 SYSTEM ELECTRICAL WIRING ................................................................................................................................................................................... 9
6.1 AC POWER CONNECTIONS .......................................................................................................................................................................................10
6.2 CHASSIS GROUNDING...............................................................................................................................................................................................11
6.3 COMMUNICATION WIRING TO THE ENERGY MANAGEMENT SYSTEM –RJ45 PIN-OUT .......................................................................................11
7 START-UP SEQUENCE ................................................................................................................................................................................................12
8 OPERATION.....................................................................................................................................................................................................................13
9 PCS DISPLAY PANEL ...................................................................................................................................................................................................13
9.1 LED DISPLAY INDICATORS.......................................................................................................................................................................................13
9.2 PCS DISPLAY PANEL INDICATOR SUMMARY............................................................................................................................................................14
..........................................................................................................................................................................................................................................14
9.3 SERVICE BUTTON......................................................................................................................................................................................................14
9.4 BACKUP POWER OPERATION ..................................................................................................................................................................................14
9.4.1 Backup Power Display Modes ..................................................................................................................................................................15
9.5 RESTARTING THE BATTERY SYSTEM AFTER LOW BATTERY SHUTDOWN...............................................................................................................15
10 MAINTENANCE ............................................................................................................................................................................................................15
11 TROUBLESHOOTING.................................................................................................................................................................................................16
12 SERVICEABLE PARTS –BATTERY MODULE REMOVAL/REPLACEMENT ................................................................................................16
13 SPECIFICATIONS.........................................................................................................................................................................................................17
Table 1: PCS Electrical / Mechanical Ratings ...................................................................................................................................................17
Table 2: PCS Field Wiring Ratings –AWG / Torque......................................................................................................................................18
Table 3: Battery Cabinet Electrical / Mechanical Ratings ..............................................................................................................................18
Table 4: Battery Cabinet Field Wiring Ratings –AWG / Torque.................................................................................................................18
13.1 UL 1741 SA GRID SUPPORT UTILITY INTERACTIVE INVERTER SPECIFICATIONS.............................................................................................19
Table 5: UL1741 SA grid support functions. ...................................................................................................................................................19
Table 7: SA9 Low and high voltage ride through settings. ..........................................................................................................................19
Table 8: SA10 Low and high frequency ride through settings. ...................................................................................................................20
Table 9: SA11 ramp rate settings.......................................................................................................................................................................21
Table 10: SA12 specified power factor settings. ............................................................................................................................................21
Table 11: SA13 Volt VAR Mode .........................................................................................................................................................................22
Table 12: SA14 Frequency-Watt settings. ....................................................................................................................................................23
Table 13: SA15 Volt-Watt Settings...................................................................................................................................................................23
13.2 THERMAL PERFORMANCE:CHARGE /DISCHARGE CURVES................................................................................................................................24
APPENDIX A: ELECTRICAL BLOCK DIAGRAM OF INTER-CABINET WIRING...............................................................................................25

1
1 Safety
This manual contains important instructions for the Eguana Evolve ESS . The Eguana Evolve ESS components
described by this manual are intended to be used as part of an energy storage system and installed per all local
building codes and regulations in addition to the National Electrical Code, ANSI/NFPA 70 (for US) and Canadian
Electrical Code (for Canada).
Throughout this manual, the following symbols will be used to highlight important information and procedures:
Symbol
Definition
Symbol
Definition
WARNING! A dangerous voltage or other
condition exists. Use extreme caution
when performing these tasks.
Meter measurement required.
CAUTION! This information is critical to the
safe installation and or operation of the
inverter. Follow these instructions closely.
Torque rating critical to operation.
NOTE: This statement is important. Follow
instructions closely.
Login to the remote monitoring
system for operating status
1.1 In case of emergency
In all cases:
If safe to do so, switch off the AC breakers (external to the system).
Contact the fire department or other required emergency response team.
Evacuate the area, and if applicable, follow your emergency evacuation plan if others are in proximity to the
installed location.
In case of fire:
When safe, use a fire extinguisher suitable for use; including A, B, and C dry chemical fire extinguishers or
carbon dioxide extinguishers.
In case of flooding:
Stay out of water if any part of the system or wiring is submerged.
Do not attempt to operate batteries that have been submerged in water even after they have been dried.
In case of unusual noise, smell or smoke:
If safe to do so, ventilate the area.
1.2 Battery module safety precautions
This product is integrated with LG Chem EM048126P3S7 series battery modules. Refer to the LG Chem product
manual LG Chem P3S series 48V Standalone Battery Module Installation Manual, for complete safety instructions
regarding handling of battery modules.
EMS

2
1.3 General safety precautions
Important! Installation, service, and operating personnel must read this document in its entirety, and observe all safety
and installation procedures as described in this manual. Never operate system in a manner not described by this
manual.
Only qualified personnel should service this product.
Ensure all covers are securely fastened after installation is complete.
Personal Protective Equipment (PPE) in compliance with local work place safety standards must be worn when
working inside the cabinet.
Risks of Fire
Do not expose the system to temperatures exceeding 60 degrees Celsius.
Avoid installation in direct sunlight.
Do not store objects on top of the cabinet.
Do not obstruct the airflow paths of the cabinet air intake.
Do not obstruct the exhaust of cabinet exhaust.
Do not store combustible objects and corrosive chemicals directly adjacent to the system.
Risks of Shock
WARNING! Hazardous Voltages. The Inverter contains hazardous voltage and energy that may be lethal. It
may only be installed by qualified personnel who have read this manual and are familiar with its operation and
hazards.
Only connect the PCS cabinet to a compatible electrical service as defined in the model specifications. The PCS
must be connected to a dedicated branch circuit in the main electrical panel.
Ensure proper electrical grounding in accordance with code requirements.
CAUTION! Both AC and DC voltage sources are terminated inside this equipment. Each circuit must be
individually disconnected before servicing
Risks of Damage
The PCS is compatible with the LG Chem battery model EM048126P3S7 only. Do not attempt to connect any
other battery to the system.
Do not connect any other loads directly to the battery power bus.
Do not drop, tip, or puncture the cabinet during transport and installation. Visible damage to the cabinet and/or
internal components should be reported to the manufacturer immediately.
Do not store this system for periods longer than six months without a battery maintenance charge. This may
result in permanent damage to the batteries.
1.4 Disposal and Recycling
Do not dispose of the system or any of the components within the cabinet. Batteries, electronics, cables, and metal
parts are recyclable. Consult your municipal waste management authority to determine required methods of
component recycling.

3
2 Introduction
Throughout this manual, the following symbols will be used to highlight important information and procedures:
Symbol
Definition
Symbol
Definition
WARNING! A dangerous voltage or other
condition exists. Use extreme caution
when performing these tasks.
Meter measurement required.
CAUTION! This information is critical to the
safe installation and or operation of the
inverter.
Follow these instructions closely.
Torque rating critical to operation.
NOTE: This statement is important. Follow
instructions closely.
Login to the remote monitoring
system for operating status
2.1 About this Manual –Target Audience
This manual is intended to be used by qualified service and installation personnel for the purposes of product
installation.
This manual contains instructions for the installation and start up sequence of the Eguana Evolve™ESS; including the
PCS and master battery cabinets. This product is permanently wired to the home electrical service, and must be
installed by a licensed electrician only.
2.2 Installation Planning & Supporting Documents
Eguana offers different models of the energy management system (EMS) supplied with this product at the time of
order. Please consult the Installation Guide of the EMS ordered with this product for full installation planning details,
including conduit layout plans and sample line diagrams. The EMS manuals also describe in more detail the various
operating modes and configurations for AC coupled PV solar plus storage systems.
The battery capacity of this system can be expanded by adding additional cabinets adjacent to the master battery
cabinet. Battery expansion is not covered within this document.
A complete list of Installer resources (Evolve 0513U North America) is available at www.eguanatech.com under the
Evolve product banner.
EMS

4
2.3 Glossary
2.4 Initial Inspection of Material List
The system components supplied with your Eguana Evolve™ ESS are shown below. Each component should be
inspected visually for any damage that may have been caused by shipment. If damage is present, please contact your
local distributor.
2.5 Special tools & hardware
The following tools are required to complete the installation of the
ESS:
Torque wrench
17mm socket wrench (battery negative main power
connection).
10mm socket wrench (battery +/- module power
connections).
3/8” socket wrench (battery positive main power
connection).
RJ-45 crimp tool (EMS to PCS communication cable) and
RJ-45 connectors.
Mounting hardware for wall bracket (load bearing) –M8
(5/16”) hardware suitable for use with mounting structure.
Term
Definition
Term
Definition
AC
Alternating Current
LED
Light Emitting Diode
ARC
Auto Recovery Circuit
NC
Normally Closed
CPU
Central Processing Unit
NO
Normally Open
DC
Direct Current
PCS
Power Control System (Inverter)
EMS
Energy Management System
PE
Protective Earth
ESD
Electrostatic Discharge
PV
Photo-Voltaic
ESS
Energy Storage System
RF
Radio Frequency
GND
Ground
SOC
State Of Charge (Battery)
SOH
State of Health (Battery)
Item
Description
1
ACB05-LP PCS cabinet
2
ACB05-LB Master battery cabinet
3
Wall bracket
4
BMS –PCS high level
communication cable
5
PCS and battery cabinet levelling
brackets
6
2 ea Cabinet coupler plates
7
Cabinet coupler gasket
8
2 ea levelling bracket hole grommet
Cabinet coupler hardware (not
shown)
4 ea M4 bolts, star washers, and
locknutsM4 star washers
1
2
3
4
5
6
7
x2
x2
8
x2

5
3 Installation Site Preparation
Before installing the Evolve ESS components, read all instructions and warnings in this manual.
CAUTION! All electrical installation work should be performed in accordance with local building and electrical codes.
WARNING! Isolate the PCS from all energy sources prior to electrical installation by means of disconnects, breakers or
connectors. Failure to properly isolate either AC or DC sources may result in serious injury or death. This system will
generate an AC voltage at the off-grid terminals when DC source is applied.
CAUTION! The PCS cabinet weighs up to 145 lbs (65 kg), and the battery cabinet weighs up to 223 lbs (102 kg).
Handle with care. The wall to which the system is mounted must be load-bearing rated according to the local
building code. Mechanical lifts are recommended to position cabinets on the wall bracket.
NOTE: All interconnecting cables are limited in length, and designed specifically for adjacent cabinet mounting using
the manufactured wall brackets.
CAUTION! Do not install in direct sunlight. Battery performance is dependent upon operating ambient temperature.
Radiant heat absorbed in direct sunlight will greatly reduce the performance of the battery, and will prematurely cause
degradation of the display indicator panel on the PCS cabinet. The battery modules are rated for full power operation
between -10C to +45C.
3.1 Overview of PCS and Battery components
1. The cabinets can be installed in an indoor and outdoor non-corrosive environment (not marine environment).
2. The forced air cooling of the PCS cabinet is designed to flow air from bottom to top.
3. The PCS and Battery cabinets are rated Type 3R.
4. Wall mounting hardware not included. The load-bearing wall bracket is provisioned for M8 hardware.
Levelling brackets are provisioned for M5 hardware.
3.2 Installation Area Required to Wall Mount PCS and Battery:
The physical installation of the cabinets requires the layout planning and installation of the system components in the
available installation space. The recommended installation height is driven by the viewing angle of the display panel
on the PCS cabinet.
Figure 1: Installation clearances.

6
4 PCS and Battery Cabinet Wall-Mounting Instructions
1. Mount the wall bracket to the wall. Use the
available slot pattern to mount to a load-
bearing structure rated for the weight of the
final system. The slots accommodate a M8
bolt diameter.
IMPORTANT! Wall-stud mounting: A
minimum of three wall studs spanned within
the width of the mounting bracket are
required. A minimum of two mounting bolts
are required per stud (top/bottom).
2. Remove the master battery cabinet from the
packaging, and stand the cabinet upright.
(not shown). Remove the front cover.
3. Assemble the lower leveling bracket. (Fully
assembled drawing shown –the last washer
and wing nut are mounted from inside the
cabinet).
4. Mount the leveling bracket to the cabinet.
Each side of the cabinet must have a rubber
washer in direct contact with the cabinet wall.
CAUTION! Battery cabinet is heavy.
Mechanical lift recommended.
5. Lift the battery cabinet onto the wall mount
bracket, aligning the wall hooks at the rear of
the cabinet with the slots on the load-bearing
face of the bracket.
6. Slide the battery cabinet towards the right
end of the bracket to allow for clearance for
the PCS cabinet.
7. From the rear side of the cabinet, spin the
lower levelling bracket (in/out) until the
cabinet is vertically plumb (level) to the wall.
Alignment
tab
Cabinet
mounting slot
Wall
mount
slot
1
3
4
7
5
6
Figure 2: Wall mount bracket and battery cabinet
installation.

7
8. Remove the PCS cabinet from its packaging and
stand upright. (not shown). Remove the front
cover.
9. Assemble and mount the leveling bracket as
shown in steps 3 and 4 above.
CAUTION! The PCS cabinet is heavy. Mechanical
lift recommended.
10. Lift the PCS cabinet onto the wall mounting
bracket.
11. Slide the PCS cabinet to the left such that it aligns
with the alignment tab on the mounting bracket.
12. From the rear side of the cabinet, spin the lower
levelling bracket (in/out) until the cabinet is
vertically plumb (level) to the wall (as shown in
step 7).
WARNING! The mounting bolts of the flange
assembly are required to be fully secured, as they
provide the chassis grounding for the battery
cabinet. Torque nuts as specified in the
specification tables provided in this manual.
13. Insert the PCS cabinet coupling gasket between
the two cabinets (lower-front). Slide the battery
cabinet towards the left until mating to the gasket.
14. Place the coupling plate inside the PCS cabinet
and insert the four mounting bolts and washers
through to the battery cabinet side.
15. Place star washers on the bolts on the battery side
of the cabinet.
16. Mount the battery cabinet side coupling plate, and
fasten with the lock nuts. Torque to 10 –15 in-lbs.
17. Continuity test: Check the continuity between the
cabinets using an Ohm meter. The test reading
must be zero Ohms at a bare metal point inside
each of the PCS and battery cabinets.
18. Optional: (This is not a load bearing anchor –
anchored conduit runs to the PCS are
satisfactory). Install screws in leveling plates for
PCS and battery cabinets by inserting a
screwdriver through the hole on the backside of
the cabinets.
19. Plug hole on back of cabinet using by inserting the
hole plug from the front side.
10
11
13
14
15
16
18
19
Optional (hardware not
included)
Figure 3: PCS cabinet and inter-cabinet coupler installation.

8
5 PCS / Battery Inter-Cabinet Wiring
The following instructions cover the interconnection wiring of the
PCS and master battery cabinet. No cable preparation is required
with battery modules pre-installed in the cabinet. Refer to
appendix A for a complete inter-cabinet wiring diagram.
Note: Overcurrent protection of the DC source is provided
internally as part of the integrated battery system. No external
DC disconnect is required.
5.1 Battery power cable connections
CAUTION! A torque wrench is required to ensure the power
cables are terminated to their specifications. Over-torque can
damage the DC breaker and/or strip the threads on the copper
bus bar posts. Under-torque can result in an arc fault hazard, and
risk of fire. Damage as a result of improper termination is not
covered by the manufacturer warranty.
1. Remove the plastic safety barrier on the power panel
assembly inside the master battery cabinet by removing
the three white plastic lug nuts on the top of the safety
barrier.
2. Route the battery cables from the PCS cabinet to the
battery cabinet.
3. Loosen the PCS DC- terminal bolt using a 17mm socket
wrench. Remove the ground cable.
4. Place the DC- cable and ground cable ring terminals
back-to-back, and mount them to the PCS DC- bus bar.
Tighten the bolt using the 17mm socket. Torque to 60
in-lbs.
5. Connect the Battery positive (+) cable to the PCS Batt+
bus bar terminal on the rear of the battery disconnect
switch using a 3/8” socket wrench. Torque to 35 in-lbs.
PCS DC-
GND
1
2
3
4
5
Plastic barrier
Figure 4: Battery power cable installation.

9
5.2 Battery BMS to PCS communication connection
The communication cable can be routed with DC power cables. Take care that the communication cable is routed
through the inter-cabinet coupler so that there is no stress or tension on the terminations. This cable is terminated
with RJ-50, 10-pin connectors.
1. PCS cabinet: Terminate the cable (p/n 801003338) at the BMS CAN port, as shown in figure 5, above-left.
2. Battery cabinet: Terminate the cable at the rear battery module BMS port as shown above-right.
6 System Electrical Wiring
Note: This product is capable of providing utility interactive and islanded back up power, and can be AC coupled to a
utility interactive photovoltaic inverter. Wiring methods must be in accordance with local electrical codes. The installer
is responsible for ensuring that over-current protection is installed and sized appropriately for the AC grid and off-grid
output circuits, in accordance with the National Electrical Code, ANSI/NFPA 70, Canadian Electrical Code and local
codes.
All field wiring connections to the battery system are at the PCS
cabinet only. The diagram (left) indicates the knockout locations for
conduit entry into the PCS; categorized as AC power and signal
level circuits.
IMPORTANT! Drilling holes anywhere in the battery or PCS
cabinet renders the warranty null and void. Use the knockouts
provided at the bottom face of the PCS cabinet only! Do not drill
holes anywhere in the battery system. Use conduit fitting reducers,
if applicable.
BMS In port
Figure 5: PCS - BMS high level communication wire installation. Left –PCS cabinet termination. Right –Battery cabinet
termination.
PCS cabinet –bottom view
AC power
Signal
Figure 6: PCS cabinet knockout detail.

10
6.1 AC power connections
This battery system contains two independent AC power connection ports; one port dedicated for an electrical utility
connection, marked “AC Grid”, the other port dedicated for backup operation, marked “AC Load”. This product’s primary
application is intended for utility interconnection, and must be connected to a utility electrical service supplying split
phase 240/120 Vac, 60 Hz. The backup operation of this product is a secondary application, and is intended to supply
emergency backup operation only.
Note: The PCS provides galvanic separation between AC
and DC Sources.
CAUTION! To reduce the risk of fire, connect only to a
dedicated circuit provided with appropriate branch circuit
over-current protection in accordance with local electrical
codes.
WARNING! Improper connection of the wiring panel may
result in equipment damage and cause personal injury.
Disconnect all AC and DC Sources prior to installation.
CAUTION! The AC grid and load ports are independent
circuits, controlled internally by an automatic bypass and
transfer switch. Each port must be connected to
electrically isolated panels. Tapping line or neutral wires
from the main electrical panel to the backup panel may
result in permanent damage to the product.
AC Grid Port:
1. Open the spring clamp terminals on the AC
circuit board at the port marked “AC Grid”.
2. Terminate the AC grid connection wires as
follows: “L_Grid” = Line, “N_Grid” = Neutral, and
“PE” = Ground.
3. Close the spring clamp terminals, ensuring levers
are fully engaged.
AC Load Port:
1. Open the spring clamp terminals on the AC
circuit board at the port marked “AC Load”.
2. Terminate the wires at “L_AC load” (Line),
“N_AC load” (neutral), and “PE_AC load”
(protective earth).
3. Close the spring clamp terminals, ensuring levers
are fully engaged.
Figure 7: AC wiring.

11
6.2 Chassis Grounding
In this section, “Chassis Ground” is referred to as “ground” or “grounding” unless otherwise mentioned.
The AC and DC grounding are intended to provide a low impedance signal path at all frequencies.
DC Ground Wiring Installation: The PCS cabinet is shipped with ungrounded DC power terminals within the inverter.
However the default setting for DC grounding is set for DC negative to ground. This is to indicate that the DC negative
terminal of the inverter is grounded within the PCS system. The DC negative ground is completed once terminated in
the master battery cabinet, as the battery module DC bus is pre-wired with negative grounded battery modules. .
AC Ground Wiring Installation: The AC power grounding is achieved through the PE terminals of the AC grid
connectors on the AC Filter Board, as shown in section 6.1.
Note: The field ground wire rating applies to the AC circuit only. The DC source loop is internal to the battery
cabinet, and is rated accordingly.
Lightning Grounding: The inverter has built-in lightning protection. In order for the lightning protection to be effective,
the grounding for lightning currents must be provided via low impedance path from AC Filter Board to System Ground
and further to the building Ground/Earthing point.
6.3 Communication Wiring to the Energy Management System –RJ45 Pin-out
The Evolve ESS communicates with the energy management system using the Modbus protocol over an RS-485
network. Shielded twisted pair cable is required.
Note: The EMS panel supplied with the ESS includes a 10 ft factory prepared cable. Should the installation require
further separation between the EMS panel and the Evolve PCS cabinet (ACB05U-LP), a cable can be prepared using
CAT 5 shielded wire, with an RJ-45 connector terminated at the PCS end only. Connect the shield to the EMS end
only.
Terminate the cable as shown:
EMS
PCS
PCS: RJ-45 Pin
G+shield
G
3
A
A
4
B
B
5
1
Figure 8: RJ-45 pinout for EMS to PCS communication cable.

12
7 Start-up Sequence
CAUTION! Powering the Evolve ESS requires a specific start-up procedure. Please follow the steps below.
CAUTION! If the battery disconnect has been placed in the OFF position at any time during operation, wait one
minute before returning to the ON position. Rapid cycling (less than one minute) of the battery disconnect can cause
damage to the pre-charge circuit.
CAUTION! During the first start-up sequence after installation, the battery modules may require a battery
maintenance cycle to balance the SOC. This maintenance cycle requires a grid connection so that the PCS can be
commanded to charge the batteries. The PCS battery SOC alarm light will flash yellow if maintenance and/or other
battery faults are present. This procedure may take from a few minutes to a few hours, depending on the difference in
battery module SOC. Please refer to the PCS Service Manual for more information.
1. Remove the front cover from the battery cabinet
adjacent to the PCS cabinet.
2. Press the [Power] button (see above, label #8) on
the master battery module. The master battery
module has communication wired from the battery
BMS port (label #4) to the PCS [BMS in] port.
WARNING! When the batteries are turned ON, the battery
voltage will be present at the power panel assembly bus bar
where the battery modules are terminated.
This step may take up to one minute.
3. Verify that the indicators are as shown in “Normal
Operation” as shown below.
Battery Power Button
Operation
Turn Batteries ON: Press and Release
the power button on the module designated
as the Master module
(PCS connected com cable).
Turn Batteries OFF: Press and hold 5
seconds the power button of any module
designated as a Slave Module. If all modules
do not shut off, repeat individually for each
module.
Figure 9: Battery BMS interface.

13
Green indicator: The left indicator indicates normal operation when solid green.
Blue indicators (SOC): In normal operation, the four indicators on the right show the module’s state of charge (SOC).
Each indicator represents 25% of a full charge. If the SOC value is 50%, the three rightmost indicators are on solid
BLUE. The blue indicators of the slave modules look as below.
Whereas, the leftmost blue indicator on the master module flashes.
Also, verify that the module with the left-most flashing blue SOC indicator corresponds to the module which has
communication wired from the BMS to the PCS [BMS in] port.
Caution! If the battery module other than the module designated as a master has a flashing SOC light at startup, shut
down all battery modules by holding the [Power] button for 5 seconds. In this state, it may be necessary to shut down
battery modules individually. After all modules are OFF. Repeat steps 2 and 3.
4. Turn ON the Battery disconnect switch inside the battery cabinet.
5. The PCS module will initialize, indicated by a brief flash of all LEDs on
the display panel, followed by a status of the battery and PCS. Refer
to section 9.2 for indicator status of the PCS.
6. Turn ON the AC breaker at the main electrical panel to the PCS.
8 Operation
The Evolve ESS is fully automated. The EMS will be programmed to connect the system to the grid after AC and DC
sources are applied. The operating states can also be viewed on the PCS display panel. For more details on system
operation, refer to the Evolve ESS Owner’s Manual.
9 PCS Display Panel
9.1 LED Display Indicators
The PCS cabinet is equipped with a display panel that provides
indication of the following:
Battery Operating State
PCS Operating State
(out of) Service Indicator
Refer to section 9.2 for a complete definition of indicator states.
To conserve energy, the LEDs will turn off after 5 minutes from
being activated. They can be re-activated by pressing the
service button.
EMS
Figure 10: Battery breaker
disconnect turn ON.
Figure 11: PCS display panel.
Battery SOC
Service button
PCS Operating Mode
Service Mode

14
9.2 PCS display panel indicator summary
9.3 Service Button
The service button can be used to wake the LED display, and either place the system into or out of service mode, as
well as cycle through various operating modes. If the system has gone into service mode, the user can attempt to
bring the system back into normal operation using the service button.
Note: It is recommended to login to the EMS via web browser and retrieve the service code from the system prior to
attempting to clear the service mode.
Refer to section 11 –Troubleshooting if the service button does not perform the action requested.
9.4 Backup Power Operation
This system will provide backup power to dedicated electrical circuits within the home via a permanently wired
electrical sub-panel, referred to as the backup panel. Backup power is limited in rating and duration, both of which are
dependent on the nature of the loads connected to the system, and the availability of the solar PV supply. This system
is designed to reliably provide power to a refrigerator, home lighting, home electronics, and small appliances.
NOTE: This product is not an uninterrupted power source (UPS). Following a utility outage, a four second power
interruption will occur before the backup power source commences. As a result of this interruption, a desktop or
portable UPS is recommended if continuous operation is desired for any electronic devices.
IMPORTANT! Surge rated loads, ie) power tools, portable air conditioners, may cause an overload shutdown.
Equipment of this type that is connected to the backup panel should be inspected and tested regularly as per
manufacturer suggested schedules. Permanent damage to the battery system and/or your equipment may occur if
exposed to chronic overloading cycles.
LED
Mode
Definition
State of charge. Each LED represents 20%
SOC. Solid = battery idle.
Charge = flash right. Discharge = flash left.
Low battery.
Sleep / Standby mode.
Grid timing mode.
Grid synchronization mode. Ten second test
before grid connect mode.
Grid connected mode.
System OK.
System out of service.
User initiated service mode.
Observed state
Action
Service button command
All panel lights off
Wake panel display
Press and release
Service light on
Exit service mode
Press and hold 5 seconds
Blink
Flash
Solid

15
IMPORTANT! Portable extension cords connected to a backup circuit should be limited to 10 meters.
IMPORTANT! This product does not support automatic gas generator integration. Do not attempt to connect a gas
generator to the battery system. If generator support is required, consult your installer regarding a separate manual
transfer to your backup electrical panel.
NOTE: The power output / surge rating will be further limited when the battery is below 10% SOC.
9.4.1 Backup Power Display Modes
Display
Definition
Battery status LEDs indicate the following:
Charge = flash right. Discharge = flash left.
PCS and service lights off.
Low SOC shutdown in backup mode. See section 5.2 to restart the system.
Low SOC shutdown initiated while out of service. See troubleshooting –section 7,
“service light on in backup mode”.
9.5 Restarting the battery system after low battery shutdown
The system will shutdown when the battery reaches a critically low level during backup operation.
To restart the system:
IMPORTANT! Ensure there is adequate sunlight for the solar PV system to charge the battery before restarting
the system. If the battery system is installed without a PV system connected to the backup panel, do not attempt to
restart the system. Wait for the utility power to return.
1. Press and hold the service button for 5 seconds.
The backup power will restart, allowing the PV system to
reconnect* and begin charging the battery. The system will continue to operate if the battery charges to its minimal
normal operating range. If the battery does not charge within 15 minutes of restart, the system will shut down to
preserve the battery.
*PV system reconnect time is approximately 5 minutes.
Note: If necessary, the load circuits can be shut off inside the backup panel to increase the battery charge rate. Do not
shut off the PV circuit.
10 Maintenance
The Evolve ESS is a maintenance free product. Regularly scheduled inspection of the airflow path for the active
cooling fans on the bottom side of the PCS cabinet is all that is required. This inspection should occur on an annual
basis, or coincide with PV inspection.

16
If the fan ventilation holes are obstructed with dust / debris, a soft-bristled brush can be used to wipe them clean. For
heavy soiling use a soft, dry brush. Do not use any solvents, scouring, or corrosive materials to clean the unit. Never
remove or unplug connections or plugs during cleaning.
11 Troubleshooting
System faults are reported and logged in the monitoring system. All fault logs are also accessible remotely by your
installer.
IMPORTANT! Contact an Eguana service representative as recommended below only after any of the following
conditions are present on the front display of the inverter panel, and the recommended actions do not resolve the
issue.
Condition
Definition
Service light ON in
grid mode
System is prevented from normal operation due to internal fault. Notify service personnel.
Service light ON in
backup mode
If the system faults into service in backup operating mode, there may be an overload condition
which prevents the system from operating safely. If the battery charge level is greater than
20% (one or more Green LEDs), reduce the load by shutting off circuits in the backup electrical
panel, then press and hold the service button 5 seconds to resume backup power operation. If
the battery low SOC shutdown mode is displayed, shut off all load circuits (keep PV ON) in the
backup panel, and do not attempt to resume backup operation until adequate sunlight is
present to provide a solar charge of the battery.
All panel lights
flashing
System is attempting to communicate with the battery modules. Notify service personnel if this
condition persists more than 30 minutes.
All panel lights OFF
after service button
wake command
This indicates loss of both AC And DC power sources to the PCS. Check the circuit breaker in
the main electrical panel for the energy storage system.
Online monitoring
system not
accessible
Check the internet connection. If connection is via wi-fi, reboot the wireless router, and make
sure the login user and password have not been changed since time of original installation.
Check power to the energy management system via the orange indicator light on the right side
of the panel. Note: the energy management system may lose power after an extended utility
outage where there is not enough solar generation to maintain battery system power.
Note: monitoring system servers may occasionally be down for service. If first attempts are not
successfully, try again the following day before contacting your installer.
12 Serviceable Parts –Battery module removal/replacement
The battery modules within the battery cabinet are removable and/or replaceable. To replace or remove the battery
modules:
1. Follow section 5 in this manual to disconnect the inter-cabinet cabling.
2. Refer to the 68006 Battery Module Field Assembly Guide for instructions on removing the battery modules.
Assembly and disassembly are the reverse order.

17
13 Specifications
Table 1: PCS Electrical / Mechanical Ratings
Model
ACB05U-LP (contained in Evolve 0513U)
Grid : Charging
Grid : Discharging
Off Grid
Maximum DC Voltage
80 V DC
Operating DC Voltage Range
40 to 80 V DC
Operating DC Voltage Range at 100% Output Power
40 to 80 V DC
Maximum DC Current
100 A
125 A
125 A
AC Power Factor*
0.8 lagging to 0.8 leading, adjustable
N/A
Operating Voltage Range (default)
105.6 to 132 V AC for L1-N and L2-N
N/A
Operating Voltage Range (with ride-through)
60.0 to 132 V AC for L1-N and L2-N
Operating Frequency Range (default)
59.3 –60.5 Hz
N/A
Operating Frequency Range (with ride-through)
50.0 –66.0 Hz
N/A
Number of Phases
Split Phase
Nominal Output Voltage*
120 V AC for L1-N and L2-N or 240 V AC L1-L2
Normal Output Frequency*
60 Hz
Maximum Continuous Output Current
20.8 A for L1and L2
Maximum Continuous Output Power (total)
5000 W
Maximum Allowed Overload Condition (as percentage of
maximum continuous current)
100%
100%
100-120 % - 30 minutes
120-170 % - 5 seconds
Maximum Output Overcurrent Protection
60 A for AC Grid, 60 A for AC Load
Maximum AC Short-circuit Current
404 Apk-pk (< 5 ms), 8.0 Arms
Maximum Synchronization In-rush Current
1.7 Arms
Protective Class (I, II, or III)
Class I
Over-Voltage Category (OVC I, II, III, or IV)
OVC III
Pollution Degree
3
Lightning protection
IEEE 62.41.2, location category B, low exposure
Normal Operation Temperature Range / Humidity
-40 to +50 °C (limited by battery, see below)
Normal Operation Humidity
Max 95% (non-condensing)
Maximum Full Power Operating Ambient
40 °C
50 °C
Enclosure Rating
Type 3R
Dimensions
20.8”W x 30.8”H x 15.6”D (529 x 783 x 397 mm)
Weight
145 lbs (65 kg)
Default Trip Limits: UL1741 (IEEE 1547.1)
Low Volt Trip (adj.), Volts
Default
110 V AC (L1-N or L2-N)
N/A
Min/Max
105 - 115 V AC (L1-N or L2-N)
N/A
Low Volt Trip (adj.), time
Default
117 cycles (1.95 Sec.)
N/A
Min/Max
14 - 117 cycles (1.95 Sec.)
N/A
High Volt Trip (adj.), Volts
Default
132 V AC (L1-N or L2-N)
N/A
Min/Max
125 - 132 V AC (L1-N or L2-N)
N/A
High Volt Trip (adj.) time
Default
57 cycles (0.95 Sec.)
N/A
Min/Max
14 - 57 cycles (0.95 Sec.)
N/A
Undervoltage: (Very Low) Trip Limit
< 60 V AC (L1-N or L2-N)
N/A
Undervoltage: (Very Low) Trip Time
≤ 10 cycles (0.16 Sec)
N/A
Overvoltage: (Very High) Trip Limit
> 144 V AC (L1-N or L2-N)
N/A
Overvoltage: (Very High) Trip Time
≤ 10 cycles (0.16 Sec)
N/A
Under Frequency
Trip Limits
(Adjustable)
Min
59.3 Hz
N/A
Default
59.3 Hz
N/A
Max
59.8 Hz
N/A
Over Frequency
Trip Limits
(Adjustable)
Min
60.2 Hz
N/A
Default
60.5 Hz
N/A
Max
60.5 Hz
N/A
Frequency Trip Limit Accuracy
0.1 Hz
N/A
Frequency Trip Time Accuracy
0.1 Sec
N/A
Voltage Trip Limit Accuracy
2%
N/A
Voltage Trip Time Accuracy
0.043 Sec
N/A
Compliance
Safety
UL 1741SA, UL 1998, UL 9540
This manual suits for next models
1
Table of contents
Popular Audio & Video Accessories manuals by other brands

HDTV Supply
HDTV Supply WolfPack Series Integrator guide

Megasat
Megasat 74236 Installation instruction

P3 International
P3 International Kill A Watt operating instructions

MadMapper
MadMapper miniMAD user guide

SENEC
SENEC SENEC.Home Li Series user manual

Eguana Technologies
Eguana Technologies Evolve 0513 Installation & start?up guide