Emotron AFR 2.0 Series User manual

Emotron AFR/AFG 2.0
AFR - Low harmonic/Regenerative Active Front End
AFG - Active Front End for renewable generation
Instruction manual
English
2019-10-14


Emotron AFR/AFG 2.0
AFR - Low harmonic/Regenerative Active Front End
AFG - Active Front End for renewable generation
Instruction manual - English
Valid from software version 4.45-097-10
Document number: 01-7318-01
Edition: r1
Date of release: 2019-10-14
© Copyright CG Drives & Automation Sweden AB 2013 - 2019
CG Drives & Automation retains the right to change specifications and
illustrations in the text, without prior notification. The contents of this
document may not be copied without the explicit permission of
CG Drives & Automation.


CG Drives & Automation 01-7318-01r1 1
Safety Instructions
Instruction manual
Read this instruction manual before using the system.
The following symbols can appear in this manual. Always
read these first before continuing:
Handling the Active front end unit
Installation, commissioning, demounting, taking
measurements, etc, of or on the active front end may only be
carried out by personnel technically qualified for the task.
The installation must be carried out in accordance with local
standards.
Opening the Active front end unit
Always take adequate precautions before opening the active
front end. Although the connections for the control signals
and the switches are isolated from the main voltage, do not
touch the control board when the active front end is
switched on.
Precautions to be taken with a
connected load (motor)
If work must be carried out on a connected load (motor) or
on the driven machine, the mains voltage must always be
disconnected from the active front end first. Wait at least 7
minutes before starting work.
Earthing
The active front end must always be earthed via the mains
safety earth connection.
Earth leakage current
Residual current device (RCD)
compatibility
This product cause a DC current in the protective
conductor. Where a residual current device (RCD) is used
for protection in case of direct or indirect contact, only a
Type B RCD is allowed on the supply side of this product.
Use RCD of 300 mA minimum.
EMC Regulations
In order to comply with the EMC Directive, it is absolutely
necessary to follow the installation instructions. All
installation descriptions in this manual follow the EMC
Directive.
Mains voltage selection
The active front end may be ordered for use with the mains
voltage range listed below.
VFXR/FDUL/AFR46: 380-460 V
VFXR/FDUL/AFR69: 480-690 V
VFXG/FDUG/AFG46: 380-460 V
VFXG/FDUG/AFG69: 480-690 V
NOTE:
Additional information as an aid to avoid problems.
CAUTION!
Failure to follow these instructions can result
in malfunction or damage to the active front
end or motor inverter.
WARNING!
Failure to follow these instructions can result
in serious injury to the user in addition to
serious damage to the active front end or
motor inverter.
HOT SURFACE!
Failure to follow these instructions can result
in injury to the user.
WARNING!
Always switch off the mains voltage before
opening the drive unit and wait at least 7
minutes to allow the buffer capacitors to
discharge.
!
CAUTION!
This active front end has an earth leakage
current which does exceed 3.5 mA AC.
Therefore the minimum size of the protective
earth conductor must comply with the local safety
regulations for high leakage current equipment which
means that according to the standard IEC61800-5-1 the
protective earth connection must be assured by one of
following conditions:
PE conductor cross-sectional area shall for phase cable
size < 16 mm2(6 AWG) be >10 mm2Cu (16 mm2Al) or
use a second PE conductor with same area as original
PE conductor.
For cable size above 16 mm2(6 AWG) but smaller or
equal to 35mm2(2 AWG) the PE conductor cross-
sectional area shall be at least 16mm2(6 AWG).
For cables >35 mm2(2 AWG) the PE conductor cross-
sectional area should be at least 50 % of the used phase
conductor.
When the PE conductor in the used cable type is not in
accordance with the above mentioned cross-sectional
area requirements, a separate PE conductor should be
used to establish this.
!

2CG Drives & Automation 01-7318-01r1
Voltage tests (Megger)
Do not carry out voltage tests (Megger) on the motor, before
all the motor cables have been disconnected from the active
front end and variable speed drive.
Condensation
If the active front end or motor inverter is moved from a
cold (storage) room to a room where it will be installed,
condensation can occur. This can result in sensitive
components becoming damp. Do not connect the mains
voltage until all visible dampness has evaporated.
Incorrect connection
The Active front end or motor inverter drive is not protected
against incorrect connection of the mains voltage, and in
particular against connection of the mains voltage to the
motor outputs U, V and W. The Active front end or motor
inverter can be damaged in this way.
Power factor capacitors for improving
cosϕ
Remove all capacitors from the motor and the motor
outputs.
Precautions during Auto-reset
When the automatic reset is active, the motor will restart
automatically provided that the cause of the trip has been
removed. If necessary take the appropriate precautions.
Transport
To avoid damage, keep the active front end and motor
inverter in its original packaging during transport. This
packaging is specially designed to absorb shocks during
transport.
IT Mains supply
The Active front end can be modified for an IT mains
supply, (non-earthed neutral), please contact your supplier
for details.
Heat warning
DC-link residual voltage
Be aware of specific parts on the Active front
end and motor inverter having high
temperature.
WARNING!
After switching off the mains supply,
dangerous voltage can still be present in the
Active front end-AFR/AFG or motor inverter-
AC drive. When opening the equipment for installing
and/or commissioning activities wait at least 7 minutes.
In case of malfunction a qualified technician should
check the DC-link or wait for one hour before
dismantling the AFR/AFG or AC drive for repair.

CG Drives & Automation, 01-7318-01r1 3
Contents
Safety Instructions ......................................... 1
Contents.......................................................... 3
1. Introduction..................................................... 5
1.1 Delivery and unpacking ............................................ 5
1.2 Using of the instruction manual............................... 5
1.3 Type code number..................................................... 5
1.4 Standards .................................................................. 6
1.5 Dismantling and scrapping....................................... 8
1.6 Glossary ..................................................................... 8
2. General description ..................................... 11
2.1 AC drive types .......................................................... 12
2.2 Emotron single drive cabinet concept ................... 14
2.3 Emotron AFR/AFG concept..................................... 15
3. Mounting ...................................................... 17
3.1 Lifting instructions................................................... 17
3.2 Cabinet mounting.................................................... 18
3.3 Mounting AFR/AFG/VSI power modules
(inside the cabinet) ................................................. 20
4. Installation ................................................... 21
4.1 Before installation................................................... 21
4.2 Connect motor and mains ...................................... 21
4.3 Cable specifications ................................................ 22
5. Control connections .................................... 23
5.1 Control board........................................................... 23
5.2 Terminal connections for AFR/AFG........................ 24
5.3 Inputs configuration with the switches.................. 25
5.4 Control connections for Emotron
FDUL/VFXR/FDUG/VFXG ........................................ 26
5.5 Connecting the control signals............................... 29
5.6 Connecting options ................................................. 30
6. Getting Started ............................................ 31
6.1 Connect the mains and motor cables.................... 31
6.2 Using the function keys .......................................... 31
6.3 Remote control........................................................ 32
7. FDUL/VFXR/FDUG/VFXG/AFR/AFG
Main features 35
7.1 Autoreset at trip ...................................................... 35
7.2 Power-up and DC-link charging .............................. 35
7.3 Automatic power supply parameter detection...... 36
7.4 Power supply synchronisation................................ 36
7.5 Start command........................................................ 36
7.6 Start on regeneration demand............................... 36
7.7 Under voltage ride through for AFR/FDUL/VFXR ....... 36
7.8 PWM modulation..................................................... 37
7.9 Active power (Energy) control ................................. 37
7.10 Limit the regeneration capability of AFR/AFG....... 37
7.11 Reactive power
(Q or cos φ) control (normally not used)................ 37
7.12 Frequency (f) control ............................................... 37
7.13 Energy actual value signals .................................... 37
7.14 Power factor calculations ....................................... 37
7.15 Fault signals ............................................................ 38
7.16 Supply voltage measurement board (SVMB)
(synchronizing/bypass option) ............................... 38
7.17 Grid code functionality............................................ 40
7.18 Brake resistor overload protection ........................ 49
7.19 Detection of open circuit ........................................ 49
7.20 Remote control functions ....................................... 49
8. EMC and Machine Directive........................ 51
8.1 EMC standards........................................................ 51
8.2 Stop categories and emergency stop .................... 51
9. Operation via the Control Panel.................. 53
9.1 Control panels ......................................................... 53
9.2 General .................................................................... 53
9.3 Control panel with 2-line display ............................ 54
9.4 Control panel with 4-line display ............................ 58
9.5 The menu structure ................................................ 62
9.6 Programming during operation .............................. 63
9.7 Editing values in a menu ........................................ 63
9.8 Copy current parameter to all sets ........................ 63
9.9 Programming example............................................ 64
10. Serial communication.................................. 65
10.1 Modbus RTU ............................................................ 65
10.2 Start and stop commands ...................................... 65
10.3 Reference signal ..................................................... 65
10.4 Description of the EInt formats .............................. 66
11. Functional description................................. 69
11.1 2-line LCD display.................................................... 69
11.2 4-line LCD display.................................................... 70
11.3 Menus ...................................................................... 71
11.4 Main Setup [200].................................................... 72
11.5 Process and Application Parameters [300] .......... 81
11.6 I/Os and Virtual Connections [500]....................... 83
11.7 Logical Functions and Timers [600] ...................... 97
11.8 View Operation/Status [700] ............................... 113
11.9 View Trip Log [800] ............................................... 119
11.10 System Data [900]................................................ 120
11.11 AFE Option [O00]................................................... 122
11.12 Grid Code Functions [G00]................................... 127
12. Troubleshooting, Diagnoses and
Maintenance ..............................................147
12.1 Trips, warnings and limits..................................... 147
12.2 Trip conditions, causes and remedial action ...... 148
12.3 Maintenance ......................................................... 153
13. Options........................................................ 155
13.1 Supply voltage measurement board (SVMB) ...... 155
13.2 Liquid cooling ........................................................ 155
13.3 I/O Board ............................................................... 155
13.4 Brake chopper....................................................... 155
13.5 EmoSoftCom.......................................................... 156
13.6 Control panel ......................................................... 156
13.7 External control panel kits (4-line) ....................... 157

4CG Drives & Automation, 01-7318-01r1
13.8 External control panel options (2-line)................. 157
13.9 Standby supply board option................................ 158
14. Technical Data........................................... 159
14.1 Electrical and mechanical specifications
related to model .................................................... 159
14.2 General electrical specifications.......................... 163
14.3 Operation at higher temperatures ....................... 164
14.4 Environmental conditions..................................... 164
14.5 Control signals....................................................... 165
15. Menu List and communication
information ................................................. 167
Index ........................................................... 201

CG Drives & Automation 01-7318-01r1 Introduction 5
1. Introduction
Users
This instruction manual is intended for:
• installation engineers
• maintenance engineers
•operators
• service engineers
Active front end loads
Active front end is suitable for connecting to three phase
electrical networks where it allows bi-directional power flow
to DC load or from DC power source.
Motors
Motor inverter (VSI) is suitable for use with standard 3-
phase asynchronous motors. Under certain conditions it is
possible to use other types of motors. Contact your supplier
for details.
1.1 Delivery and unpacking
Check for any visible signs of damage. Inform your supplier
immediately of any damage found. Do not install the active
front end or motor inverter if damage is found.
1.2 Using of the instruction
manual
Within this instruction manual the abbreviation "AFR" and
''AFG'' is used in the following sense:
AFR: To indicate the complete active front end for low
harmonic and regenerative applications with no grid code
support.
AFG: To indicate the complete active front end for
generation applications with full/advanced grid code
functionality.
For detail see section 2.1 page 12.
Check that the software version number on the first page of
this manual matches the software version in the active front
end. See section 11.10.1 page 120 for more information
With help of the Index and the Table of contents in this
manual, it is easy to track individual functions and to find
out how to use and set them.
1.3 Type code number
Fig. 1 gives an example of the type code numbering used on
all active front ends. With this code number the exact type
of the drive can be determined. This identification will be
required for type specific information when mounting and
installing. The code number is located on the product label,
on the front of the unit.
Fig. 1 Type code number
NOTE:
Read this instruction manual carefully before starting
installation, connection or working with the active front
end or motor inverter.
Position Configuration
1 AFE type AFR = “AFR”
AFG = “AFG”
2 Supply voltage 46=400 V mains
69=690 V mains
3Rated current (A)
continuous
-175=175 A
-
-1K5=1500 A
4 Protection class 20=IP20
54=IP54
5 Control panel
–=Blank panel
C=2-line panel
D=4-line panel
E=4-line panel + BLE
6 EMC option
E=Standard EMC
(Category C3)
F=Extended EMC
(Category C2)
I=IT-Net
7 Brake chopper option - =No chopper
B=Chopper built in
8Stand-by power supply
option
–=No SBS
S=SBS included
9 Safe stop option – =No safe stop
T=Safe stop incl.
10 Brand label A=Standard
11 Coated boards, option - =Standard boards
V=Coated boards
12 Option position 1 N=No option
P=PTC/PT100
I=Extended I/O
13 Option position 2
14 Option position 3
AFG46-175-20 C E B S – A – N N N N N - A
Position number:
123456789
10 11 12 13 14 15 16 1718

6Introduction CG Drives & Automation 01-7318-01r1
1.4 Standards
The active front ends and variable speed drives described in
this instruction manual comply with the standards listed in
Table 1. For the declarations of conformity and
manufacturer’s certificate, contact your supplier for more
information or visit www.cgglobal.com or
www.emotron.com.
1.4.1 Product standard for EMC
Product standard EN(IEC)61800-3, second edition of 2004
defines the:
First Environment (Extended EMC) as environment that
includes domestic premises. It also includes establishments
directly connected without intermediate transformers to a
low voltage power supply network that supplies buildings
used for domestic purposes.
Category C2: Power Drive System (PDS) of rated
voltage<1.000 V, which is neither a plug in device nor a
movable device and, when used in the first environment, is
intended to be installed and commissioned only by a
professional.
Second environment (Standard EMC) includes all other
establishments.
Category C3: PDS of rated voltage <1.000 V, intended for
use in the second environment and not intended for use in
the first environment.
Category C4: PDS or rated voltage equal or above 1.000 V,
or rated current equal to or above 400 A, or intended for use
in complex systems in the second environment.
The active front end complies with the product standard
EN(IEC) 61800-3:2004 (Any kind of metal screened cable
may be used). The active front end is designed to meet the
requirements according to category C3.
By using the optional “Extended EMC” filter the active
front end fulfils the requirements according to category C2.
For the distributive regeneration applications, Emotron
AFG also complies with TR-61000-3-15.
15 Option position,
Communication
N=No option
D=DeviceNet
P=Profibus
S=RS232/485
M=Modbus/TCP
E= EtherCAT
A=Profinet IO 1-port
B=Profinet IO 2-port
G= EtherNet/IP 2-port
16 Software type A=Standard AFR/AFG
17 CE Approved -
18 Cooling type L=Liquid cooled
A=Air cooled
Position Configuration
WARNING!
In a domestic environment this product may
cause radio interference, in which case it
may be necessary to take adequate
additional measures.
WARNING!
The AC drive, complying with category C3, is
not intended to be used on a low-voltage
public network which supplies domestic
premises; radio interference is expected if
used in such a network. Contact your supplier
if you need additional measures.

CG Drives & Automation 01-7318-01r1 Introduction 7
Ta b l e 1 St a n d a rd s
Market Standard Description
European
EMC Directive 2014/30/EU
Low Voltage Directive 2014/35/EU
WEEE Directive 2012/19/EU
Grid connection of
generators 2016/631/EC
All
EN 60204-1 Safety of machinery - Electrical equipment of machines
Part 1: General requirements.
EN(IEC) 61000-6-2
EN(IEC) 61000-6-4
Electromagnetic compatibility (EMC)
Part 6-2: Generic standards - Immunity standard for industrial environments.
Part 6-4: Generic standards - Emission standard for industrial environments.
EN(IEC)61800-3:2004
Adjustable speed electrical power drive systems
Part 3: EMC requirements and specific test methods.
EMC Directive: Declaration of Conformity and CE marking
IEC/TR 61000-3-15
Electromagnetic compatibility (EMC) -
Part 3-15: Limits assessment of low frequency electromagnetic immunity and
emission requirements for dispersed generation system in LV network.
EN(IEC)61800-5-1 Ed.
2.0
Adjustable speed electrical power drive systems Part 5-1.
Safety requirements - Electrical, thermal and energy.
Low Voltage Directive: Declaration of Conformity and CE marking
IEC 60721-3-3
Classification of environmental conditions. Air quality chemical vapours, unit in
operation. Chemical gases 3C2, Solid particles 3S2.
Optional with coated boards
Unit in operation. Chemical gases Class 3C3, Solid particles 3S2.
IEC-50549
IEC-50549-1
Requirements for generating plants to be connected in parallel with
distribution networks
Part 1: Connection to a LV distribution network above 16 A.
IEC-50549-2
Requirements for generating plants to be connected in parallel with
distribution networks
Part 2: Connection to a MV distribution network.
IEC-62116
IEC 62116:2014
Utility-interconnected photovoltaic inverters - Test procedures of islanding
prevention measures.

8Introduction CG Drives & Automation 01-7318-01r1
1.5 Dismantling and scrapping
The enclosures of the drives are made from recyclable
material as aluminum, iron and plastic. Each drive contains
a number of components demanding special treatment, for
example electrolytic capacitors. The circuit boards contain
small amounts of tin and lead. Any local or national
regulations in force for the disposal and recycling of these
materials must be complied with.
1.5.1 Disposal of old electrical and
electronic equipment
This information is applicable in the European Union and
other European countries with separate collection systems.
This symbol on the product or on its packaging indicates
that this product shall be taken to the applicable collection
point for the recycling of electrical and electronic
equipment. By ensuring this product is disposed of correctly,
you will help prevent potentially negative consequences for
the environment and human health, which could otherwise
be caused by inappropriate waste handling of this product.
The recycling of materials will help to conserve natural
resources. For more detailed information about recycling
this product, please contact the local distributor of the
product.
1.6 Glossary
1.6.1 Abbreviations and symbols
In this manual the following abbreviations are used:
Table 2 Abbreviations
Abbreviation/
symbol Description
AC drive Frequency converter
AFE Active front end (electronics, control board
and power module part)
AFG Active front end for generation with full/
advanced grid code functionality
AFR Low harmonic/regenerative front end with no
grid support
AID
Anti-Islanding detection
BLE Blue tooth
Comm
Command sourced from serial communication
CP Control panel, the programming and
presentation unit on the AC drive
DFE Diode front end
DPF
Displacement power factor
EInt Communication format
FDUG Complete power drive train, including AFG
and VSI (FDU)
FDUL Low harmonic FDU drive, including AFR and
VSI (FDU)
FRT
Fault-ride through
GC
Gride Code
Int Communication format (Integer)
Keyb Command sourced from keyboard
LCL-filter Inductance - Capacitance - Inductance
type filter
LFSM-O
Limited frequency sensitivity mode -
over-frequency
Long Communication format (4 byte integer)
OFRT
Over-frequency ride-through
OVRT
Over-voltage ride-through
PLL Phase locked loop
ROCOF Rate of change of frequency
SVMB
Supply voltage measurement board
THD Total harmonic distortion
UFRT
Under-frequency ride-through
UInt Communication format (Unsigned integer)
UVRT
Under-voltage ride-through

CG Drives & Automation 01-7318-01r1 Introduction 9
1.6.2 Definitions
In this manual the following definitions for current, torque
and frequency are used:
VFXG Complete power drive train, including AFG
and VSI (VFX)
VFXR Regenerative VFX drive, including AFR and
VSI (VFX)
VSI Voltage source inverter (motor inverter)
The function cannot be changed in run mode
Table 3 Definitions
Name Description Quantity
IIN Nominal input current of AFR/AFG ARMS
INOM Nominal output current of VSI ARMS
IMOT Nominal motor current ARMS
PNOM Nominal power of VSI kW
PMOT Motor power kW
TNOM Nominal torque of motor Nm
TMOT Motor torque Nm
fOUT Output frequency of VSI Hz
fMOT Nominal frequency of motor Hz
nMOT Nominal speed of motor rpm
ICL Maximum output current ARMS
Speed Actual motor speed rpm
Torque Actual motor torque Nm
Table 2 Abbreviations
Abbreviation/
symbol Description

10 Introduction CG Drives & Automation 01-7318-01r1

CG Drives & Automation 01-7318-01r1 General description 11
2. General description
The Emotron active front end (AFE) is a regenerative active
front end unit designed to be used either in combination
with Emotron motor inverter (VSIs) i.e. VFX/FDU or
without Emotron motor inverter (VSIs). The main objective
of the Emotron AFE is to rectify the supply AC voltage into
DC voltage to be fed to or regenerated from the VSIs. This
is achieved with the minimal impact on the supply by the
control of the active rectifier module which provides
sinusoidal input currents with a very low harmonic content,
typically a THD(I) below 5%. Different variants of
Emotron active front end drives are:
AFR: Regenerative, low harmonic active front end
without Emotron motor inverter.
AFG: Regenerative, low harmonic active front end
without Emotron motor inverter. AFG offers full/
advance grid support functionality.
FDUL: Non-regenerative, low harmonic drive including
active front end (AFR) together with Emotron
motor inverter FDU.
VFXR: Regenerative, low harmonic drive including active
front end (AFR) together with Emotron motor
inverter VFX.
FDUG: Regenerative, low harmonic drive including active
front end for generation (AFG) together with
Emotron motor inverter FDU. FDUG offers full/
advance grid support functionality.
VFXG: Regenerative, low harmonic drive including active
front end for generation (AFG) together with
Emotron motor inverter VFX. VFXG offers full/
advance grid support functionality.
CAUTION!
Always consult CG Drives & Automation
before connecting an Emotron AFR/AFG to a
standard VSI.
!

12 General description CG Drives & Automation 01-7318-01r1
2.1 AC drive types
2.1.1 Standard AC drive (as
comparison)
A standard AC drive consists of a rectifier module and an
inverter module. The rectifier module (front-end) consists of
a 6-pulse diode bridge, i.e. diode front-end (DFE) while the
inverter module (VSI) consists of IGBTs with anti-parallel
free wheeling diodes, see Figure 2. The main advantages of
DFEs are the simple and robust design together with their
high efficiency, i.e. low losses. The main disadvantages are
unidirectional power flow and the high harmonic content in
the line current, typically THD 30- 40%.
Fig. 2 Standard AC drive.
2.1.2 AC drive with AFR or AFG
(FDUL/VFXR/FDUG/VFXG)
An AFE unit is basically a VSI towards the supply (via a
filter) where the IGBTs are used as an active rectifier, see
Figure 3. The main advantages are inherent 4Q-operation,
i.e. bi-directional power flow, and sinusoidal supply
currents, i.e. low harmonics, regeneration and improved
power factor.
The AFE unit is controlled in such a way to keep the energy
between motor and supply in balance. This is achieved by
controlling the DC-link voltage (Udc). Other features are
the possibility for reactive power compensation and boosted
DC-link voltage.
Fig. 3 VSI with AFR/AFG.
AFE
VSI
AFR/AFG = AFE + LCL-filter
FDUL/VFXR = AFR + VSI (FDU/VFX)
AFR/AFG
FDUG/VFXG = AFG + VSI (FDU/VFX)

CG Drives & Automation 01-7318-01r1 General description 13
2.1.3 AFR
AFR consists of Emotron power electronic module (AFE)
connected to grid through LCL filter as shown in Figure 4.
The main objective of the Emotron AFR is to rectify the
supply AC voltage into the DC voltage to be fed to or
regenerated from the VSIs (motor inverter). It also keeps the
harmonic content of the current exchanged with grid at low
level, maintaining the THD(I) below 5%. AFR offers
standard AFE functionality such as:
-Activepowercontrol.
- Reactive power control.
- Low harmonic operation.
Fig. 4 AFR
2.1.4 AFG
AFG is an AFE variant that offers full/advance grid code
functionality. This variant (AFG) is dedicated for generation
applications where generated energy (through DC-link) is
fed into the utility grid. AFG consists of Emotron power
electronic module (AFE) including voltage measurement
board and brake chopper switch (optional) connected to
grid through LCL filter as shown in Figure 5. Main objective
of AFG is to feed in generated power from DC-link to
utility grid fulfilling the grid code requirements. AFG offers
standard AFE functionality along with full grid support
features such as:
• Grid voltage and frequency (U, F) protection.
• Reactive power (Q) control.
• Anti-islanding protection.
• Grid fault ride through (FRT) capability.
Fig. 5 AFG
AFE VSI
AFR= AFE + LCL filter
AFR
LCL
AFE
Udc
NOTE:
Supply voltage measurement board is mandatory
requirement for fulfilling the basic and advanced grid
code functionality. AFG has internal supply voltage
measurement board (SVMB) connected to K2.
ILCL
AFE
AFG
Udc+
Udc
Udc-
R
line

14 General description CG Drives & Automation 01-7318-01r1
2.2 Emotron single drive cabinet concept
2.2.1 FDUL/VFXR/FDUG/VFXG
(single drive) applications
The Emotron low harmonic and regenerative AC drive i.e.
FDUL/VFXR/FDUG/VFXG is comprised by an AFR or
AFG unit i.e. AFE and filters and a VSI, i.e. Emotron VFX
or FDU. The concept is designed as a cabinet solution, see
Figure 6.
Fig. 6 Single drive in cabinet
where
• Cabinet - IP54 cabinet with door fans
• Q1 - Main switch *
• K1 - Main contactor *
•RFI-EMCfilter
•LCL-LCLfilter
• F2 - MCB (Miniature circuit breaker) for pre-charge
circuit
• AFE - Emotron AFE module with 24V standby supply
board, voltage measurement board (optional), brake
chopper switch (optional) and integrated pre-charge
circuit (K2,D2,R2)
• AFR/AFG - Emotron AFE and filters
• VSI - DC-voltage fed VSI module, i.e. Emotron VFX or
FDU
• CB - Control board
• SBS - Standby supply board
• Lo - Output coil
* For larger units, Q1 Main switch and K1 Main contact are
replaced by Q1 Motorized circuit breaker.
2.2.2 Common DC-bus applications
For common DC-bus applications, the cabinet will contain
only the AFR/AFG part of Figure 6, i.e. all except the VSI &
Lo.
AFR/AFG
CB CB
SBS
AFR/AFG = AFE + LCL
FDUL/VFXR = AFR + VSI (FDU/VFX)
FDUG/VFXG = AFG + VSI (FDU/VFX)
NOTE:
For AFG/FDUG/VFXG, supply voltage measurement
board (SVMB) is mandatory. It is mounted and
connected internally to K2.

CG Drives & Automation 01-7318-01r1 General description 15
2.3 Emotron AFR/AFG concept
Emotron also offers only AFR/AFG solution for the
applications where complete FDUL/VFXR/FDUG/VFXG
drive train is not required. In this concept, the DC power
load/source is connected to the DC-terminals of AFR/AFG.
AFR/AFG consists of AFE power electronic module and
LCL filters as main components along with other necessary
components. AFR/AFG concept is shown in Figure 7.
Fig. 7 AFR/AFG concept
where
• Cabinet - outer cabinet (for example IP54)
• Q1 - Main switch *
• K1 - Main contactor *
•RFI-EMCfilter
•LCL-LCLfilter
• F2 - MCB (Miniature circuit breaker) for pre-charge
circuit
• AFE - Emotron AFE module with 24V standby supply
board, voltage measurement board (optional for AFR
and mandatory for AFG), optional brake chopper switch
and integrated pre-charge circuit (K2, D2, R2)
• AFR/AFG - Emotron AFE and filters
• DC source/load - External DC power source or load
based on the application.
• CB - Control board
• SBS - Standby supply board
* For larger units, Q1 Main switch and K1 Main contact
are replaced by Q1 Motorized circuit breaker.
Cabinet DC
source/load
Q1 K1
F2
RFI L2
AFR/AFG AFE
Udc
K2 D2 R2
CB & PPU
C
DC+
DC-
NOTE:
For AFG/FDUG/VFXG, supply voltage measurement
board (SVMB) is mandatory. It is mounted and
connected internally to K2.

16 General description CG Drives & Automation 01-7318-01r1
This manual suits for next models
2
Table of contents
Popular Industrial Electrical manuals by other brands

Smartrise
Smartrise M1000-INDUCTION Startup manual

Murata
Murata GRM1885C1H8R2CA01 Series Reference sheet

schmersal
schmersal AZM400 operating instructions

Murata
Murata GQM1555C2D8R0WB01 Series Reference sheet

Murata
Murata GRT188C81A106ME13 Series Reference sheet

Murata
Murata GRM0225C1E9R9BA03 Series Reference sheet

LEGRAND
LEGRAND Wattstopper DSW-100 installation instructions

Murata
Murata GJM0335C1E1R6CB01 Series Reference sheet

Toshiba
Toshiba CV-10HA instruction manual

Murata
Murata GRT155R61C224ME01 Series Reference sheet

Murata
Murata GRM0225C1E9R7BA03 Series Reference sheet

Murata
Murata GRM0335C1H7R7CA01 Series Reference sheet