Envirovent Slimline 150 User manual


SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING THIS UNIT CALL
01
01 Safety Instructions
IMPORTANT
Be sure to have read and understood these
instructions before beginning the installation
process.
PRE-INSTALLATION CHECK LIST
Make sure that the unit can physically t in to
the desired location.
SAFETY AND RECOMMENDATIONS
• This appliance can be used by children
aged from 8 years and above and
persons with reduced physical, sensory or
mental capabilities or lack of experience
and knowledge if they have been given
supervision or instruction concerning
use of the appliance in a safe way and
understand the hazards involved. Children
shall not play with the appliance. Cleaning
and user maintenance shall not be made
by children without supervision.
Installation must take place under:
• Quality requirements ventilation systems
dwellings.
• Quality requirements balanced ventilation
in dwellings.
• The regulations for ventilation of dwellings
inand residential buildings.
• The safety regulations for low-voltage
installations.
• The regulations for connection to interior
sewers in dwellings and residential
buildings.
• Any additional regulations of the local
utilities.
• The installation instructions for the Slimline
150

AFTER INSTALLING THIS UNIT PLEASE PASS ONTO END USER
DO NOT THROW AWAY
02
02 Technical Specications
Before you begin to install the heat recovery unit, check that it has been supplied complete and undamaged.
The Slimline 150 unit should include the following components:
1. Heat recovery appliance
2. Wall mounting bracket kit; - 2x suspension strips
3. Duct connecting kit; - 4x collars Ø125 mm
4. Documentation set; - 1x installation instructions
5. Connecting kit; - Mounting material collars, including 16 xing screws
- Connectors : 2-pole screw connector (eBus) and 9-pole screw connector only
for Plus version)
6. Control unit with operating manual

SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING THIS UNIT CALL
03
The EnviroVent Slimline 150 is a ventilation
unit with heat recovery with a maximum
ventilation capacity of 150 m3/h and low-
energy fans.
Slimline 150 Features:
• Steplessly adjustable air ow rates through
a control unit (supplied with appliance).
• Filter indication on the control unit / multiple
switch.
• A completely new intelligent frost
protection system. This ensures that
even at low outdoor temperatures the
appliance’s performance remains optimal
and that, if necessary, it activates the
standard preheater.
• Low sound level
• Comes as standard with automatic bypass
valve
• Constant ow control
• Low energy consumption
• High eciency
Slimline 150 is available in two types:
• Slimline 150
• Slimline 150 Plus
Compared to the Slimline 150, the Slimline
150 Plus has a more extensive control board
which increases the connection options.
These installation instructions describe both
the standard Slimline 150 and the Slimline
150 Plus.
With the aid of the supplied mounting
brackets, the Slimline 150 (Plus) can be
mounted either on the wall or on the ceiling.
For the correct position of the connection
ducts and dimensions see page 6.
When ordering an appliance always state
the correct type; subsequent conversion to
a dierent version is highly labour-intensive.
The Slimline 150 comes ready to wire into
the 230V mains fused spur.
The appliance comes as standard with a
control unit, but connection of a simple
4-way switch is possible as well.
If a 4-way switch is installed instead of a
control unit, the settings of the appliance
can only be changed with a laptop.
Connecting a combination of control unit
and multiple switch is another option.
02 Technical Specications

AFTER INSTALLING THIS UNIT PLEASE PASS ONTO END USER
DO NOT THROW AWAY
04
Supply voltage (V/Hz) 230/50 Protection degree IP30
Dimensions
(w x d x h) (mm) 1000 x 660 x 198 Duct diameter (mm) Ø125
External discharge 3/4 Weight (kg) 24.5
Filter class G4
Fan factory setting
(control unit)
MAX
4-Way switch 1 2 3
Ventilation capacity
(m3/h) 30 75 100 125 150
Permissible
resistance ducts
system (Pa)
2-6 13-38 22-66 35-105 50-150
Rated power (excl.
optional pre-heater)
(W)
11-12 19-27 27-37 38-52 53-72
Rated current (excl.
optional pre-heater)
(A)
0.14-0.15 0.20-0.28 0.27-0.35 0.36-0.47 0.49-0.64
Rated current (incl.
optional pre-heater)
(A)
2.4
Cos φ 0.34 0.42 0.44-0.47 0.46-0.48 0.47-0.49
02 Technical Specications

SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING THIS UNIT CALL
05
0
50
100
150
200
0 25 50 75 100 125 150 175
= [W]
x
36
27
19
13
9
32
23
17
12
812
14
19
27
7
9
5
Sound Power
Ventilation
capacity (m3/h) 45 75 105 150
Sound power
level Lw (A)
Static pressure
(Pa) 10 50 100 25 50 100 50 100 50 100
Housing emission
dB(A) 24 33 39 33 35 40 38 41 44 45
Duct “from
dwelling” dB(A) 27 36 42 34 37 42 40 43 46 47
Duct “to dwelling”
dB(A) 41 49 58 50 53 57 57 60 62 64
Note: In practice, the value may deviate 1 dB(A) as a result of measuring tolerances.
(Pa)
(m3/h)
Note: The value stated in the circle is the capacity per fan (in Watt)
02 Technical Specications

AFTER INSTALLING THIS UNIT PLEASE PASS ONTO END USER
DO NOT THROW AWAY
06
1. To dwelling
2. To atmosphere
3. From dwelling
4. From
atmosphere
5. Electric connections
6. Connection condensate
discharge
02 Technical Specications

SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING THIS UNIT CALL
07
1. Extract air lter
2. Indoor temperature sensor
3. Bypass
4. Condensate bin
5. Extract fan
6. Locking screw front panel
(mounted in front panel)
7. Connector X14
8. Control board
9. Connector X4
10. Condensate discharge
11. Supply air lter
12. Preheater
13. Outdoor temperature sensor
14. Heat exchanger
15. Supply fan
16. Modular connector multiple switch
17. Service connector
18. Sleeve low voltage cable
19. Sleeve cable 230V postheater or
extra preheater
20. Mains cable 230V
21. 9-pole connector (only for Plus version)
22. Connector eBus
23. Fall protection front panel
02 Technical Specications

AFTER INSTALLING THIS UNIT PLEASE PASS ONTO END USER
DO NOT THROW AWAY
08
The appliance is supplied ready to wire into
the fuse spur and operates fully automatically.
The extracted indoor air heats up the fresh,
clean outdoor air. That saves energy and
fresh air is sent to the required rooms.
The control system has four ventilation
modes. The air ow rate can be adjusted
per ventilation mode. The constant volume
control system ensures that the air ow
rate of the supply and extract fans is
always delivered despite any resistance
encountered in the ductwork.
The standard bypass valve makes it possible
to supply fresh outside air that is not heated
by the heat exchanger. Particularly during
summer nights it is desirable to supply
cooler outside air. In this mode the hot air in
the dwelling is replaced by cooler outside air
as far as possible.
The bypass valve opens and closes
automatically when a number of conditions
are satised (refer to the table below for
bypass conditions).
The operation of the bypass valve can be
adjusted in step number 5, step number 6
and step number 7 in the settings menu (see
pages 39-41).
To prevent freezing of the heat exchanger
at extremely low outdoor temperatures,
the Slimline 150 features an intelligent frost
control. Temperature sensors measure the
temperatures across the heat exchanger
and, if necessary, the preheater is switched
on. This guarantees a proper ventilation
balance, even at very low outdoor
temperatures.
If, with switched on standard preheater(s),
the exchanger temperature still starts to drop
below zero, stepless unbalance is created in
the appliance.
The user information menu shows when the
Slimline 150 frost control system is activated
(see page 19).
Bypass valve open
-The outdoor temperature is higher than 10°C and
-The outdoor temperature is lower than the indoor temperature in the
dwelling and
-The temperature in the dwelling is higher than the temperature set at step
no.5 in the settings menu
(set a standard at 22°C).
Bypass valve closed
-The outdoor temperature is lower than 10°C or
-The outdoor temperature is higher than the indoor temperature in the
dwelling or
-The temperature from the dwelling is lower than the temperature set at
step no. 5 in the settings menu minus the set temperature by the hysteresis
(tolerance) (step no. 6), this temperature is factory set at 20°C (22.0°C
minus 2.0°C).
02 Technical Specications

SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING THIS UNIT CALL
09
02 Technical Specications
The Slimline 150 is also available as a Plus
version. This version is equipped with a
dierent control board with 2 additional
connectors (X14 & X15) with more
connection options for various applications.
Only the Plus is equipped with a 9-pole
connector (connected to X15 on control
board) that is accessible from the outside of
the appliance.
If a postheater or extra preheater is
connected to connector X14 (accessible
after opening the front panel ) the installer
must feed the connected 230 Volt cable
to outside the appliance through a strain
reliever. For this strain reliever (not supplied
with the appliance) a plug must be removed
from the position where this strain relief
must be placed.
See page 32 for more information on the
connection possibilities of connectors X14
and X15.
A. 9-pole connector
B.Hole for gland to be
mounted by installer (for
sleeve cable postheater/ extra
preheater).
Slimline 150 Plus

AFTER INSTALLING THIS UNIT PLEASE PASS ONTO END USER
DO NOT THROW AWAY
10
03 Accessories
Electric post-heater
Kit wireless remote
control 4 positions (1
transmitter & 1 receiver)
Electric pre-heater
4-way switch with lter
indication; ush
mounted; modular
connection
Splitter RJ12 Service tool
CO2 sensor, ush
mounted eBus or
surface mounted
0-10V proportional
(PLUS version only)
Filter kit 1x F7 lter
RH sensor Filter kit 1x G4 & 1x F7
Transmitter wireless
remote control 2
positions (with battery)
Silencer box Ø125 mm
(2x)
Transmitter wireless
remote control 4
positions (with battery)
Silencer- / air distribution
box Ø75 mm (20x)
Receiver wireless
remote control
(for battery version)
Silencer- / air distribution
box 100 x 50 mm (12x)
Kit wireless remote
control 2 positions (1
transmitter & 1 receiver)
Silencer- / air distribution
box 130 x 60 mm (12x)
F7
G3 +F7 G4 +F7 2X G3 2x G4
G4 + Frame
F7
G3 +F7 G4 +F7 2X G3 2x G4
G4 + Frame
Please contact EnviroVent for order codes
482 mm
660 mm
200 mm
482 mm
660 mm
200 mm
482 mm
660 mm
200 mm
482 mm
660 mm
200 mm

SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING THIS UNIT CALL
11
The Slimline 150 can be mounted directly
to the wall or ceiling using the mounting
brackets supplied for that purpose.
Because of the appliance’s weight,
mounting the appliance must
always be done by two people.
For a vibration-free result the appliance must
be mounted to a solid wall with a minimum
mass of 200 kg/m2. A gypsum block or
metal stud wall will not suce. Additional
measures such as double panelling or extra
studs are required in that case. In addition,
the following aspects must be taken into
account.
• The appliance must be placed level; both
lengthwise and laterally.
• The installation room must be such that a
good condensate discharge with air trap
and pitch for condensate can be made.
Make sure that under no condition
the condensate discharge is
installed at a pitch towards the
appliance.
The appliance is only suitable for
ceiling or wall mounting! Never
mount the appliance at on the
oor because of the position of the
condensate discharge bin.
• The installation room must be frost-free.
• When mounting exible ducts, bear in
mind that it must be possible to replace
them in due course.
• Make sure there is sucient free space
at the appliance to allow cleaning of the
lters and maintaining the appliance. It
must be possible to swing the door open.
Ceiling mounting:
At least 70 cm at the underside of the
appliance and a free headroom of 1.8 m; if 70
cm free space is not available, for instance
when mounting on top of a suspended
ceiling, there must be sucient room to
partly open and remove the front panel.
The front panel can be detached after
removing a lock screw at the hinge.
Make sure the lters can always be freely
removed, so there is no frame or other
obstacle at the level of the lters!
Wall mounting:
Make sure there is a free space of at least 70
cm at the front of the appliance and a free
headroom of 1.8 m.
Make sure there is at least 20 cm free space
at the appliance side where the electric
connections are located, so connectors and
sleeves remain accessible.
04 Installation Instructions

AFTER INSTALLING THIS UNIT PLEASE PASS ONTO END USER
DO NOT THROW AWAY
12
Placing the appliance for ceiling mounted
04 Installation Instructions
Appliance disconnecting from
mounting bracket
Condensate discharge

SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING THIS UNIT CALL
13
Placing the appliance for wall mounted
Condensate discharge
Appliance disconnecting from
mounting bracket
04 Installation Instructions

AFTER INSTALLING THIS UNIT PLEASE PASS ONTO END USER
DO NOT THROW AWAY
14
Detachable coupler
Detachable coupler
The Slimline 150 must always be tted with a
condensate discharge. The condensate must
be discharged through a drainpipe. EnviroVent
recommend using KITCONDENSATE-BK.
The condensate discharge connection
with 3/4” mail thread (not supplied with
the appliance) must be screwed into the
appliance’s condensate bin by the installer.
Important:
Always install a detachable coupler
in the condensate discharge line as
closely as possible to the appliance,
otherwise the condensate bin cannot
be removed from the appliance for
service purposes.
The condensate discharge line can be mounted
to it, preferably glued, if necessary using a square
bend. The installer can glue the condensate
discharge to the appliance in the desired
position. The drain must discharge under the
water level in the U-trap. Use a condensate
discharge line with a diameter of 32 mm.
Particularly for ceiling mounting, make sure
the condensate discharge is below the level
of the condensate bin in the Slimline 150.
Before connecting the condensate discharge
to the appliance, pour water into the U-trap to
create an air trap.
Note: Add a teaspoon of oil to prevent drying
out. Alternatively use a non return valve in
place of the U-trap.
04 Installation Instructions
Recommended
(KITCONDENSATE-BK)

SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING THIS UNIT CALL
15
The appliance can be connected to an
easily accessible fused spur. The electric
installation must comply with the wiring
regulations.
The appliance
Make allowance for the 375 W preheater; if in
addition also a postheater or extra preheater
is installed, the rated power increases to
447W.
Warning
The fans and control board carry
a high voltage. Always remove
the voltage from the appliance by
isolating power when working on
the appliance.
The control unit that comes as standard with
the appliance must be connected to the
eBus connector. This (detachable) 2-pole
eBus connector is mounted on the outside
of the appliance (see page 33).
Cables to be connected by installer
(wire diameter at least 0.34 mm2)
04 Installation Instructions

AFTER INSTALLING THIS UNIT PLEASE PASS ONTO END USER
DO NOT THROW AWAY
16
Warning
When working on the appliance,
always remove the voltage from the
appliance by rst switching it o
through software and then isolating
the power.
Connecting
Software
S1.03.03
08:0 0 2 3 :0 0-
08 :30
23.01.12Sonntag
FILTER
Sunday
05 Control Display
Switching the appliance ON/OFF

SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING THIS UNIT CALL
17
05 Control Display
General explanation of control unit
The control unit display shows what the operating
mode of the appliance is. Settings in the control
unit software of the Slimline 150 can be called
up and changed with the aid of the operating
keys. Ex factory the control module is set for the
English language. In the setting menu control
unit, (see page 21) you can choose a language.
View on display
When the Slimline 150 is in operating mode,
the control unit display indicates a number of
dierent values:
08:0 0 2 3 :0 0-
08 :30
23.01.12Sonntag
FILTER
1. Right-hand setting knob 2. Return-key 3. Key appliance selection
Air ow rates can be changed by
rotating the ‘Right-hand setting
knob’. Pressing the ‘Right-hand
setting knob’ takes you to the Main
Menu (Main Menu) of the Slimline
appliance (see page 19).
Press the Return key () to leave
any selected menu/ (temporary)
ventilation mode and the appliance
will return to operating mode.
With the appliance selection key
you can choose to what appliance
the control unit is connected.
4. Key manual control 5. Info-key 6. Left-hand setting knob
After pressing the key manual
control () the operation of the
timer program “overruled. The
display shows on the location of
the actual time block the message
‘manual’. The unit continues to
operate in this manual setting until
it is cancelled by pressing the
‘Return’ key ().
Pressing the ‘Info-key’ () takes
you to the ‘User information menu’
(see page 19).
The left hand button on the control
panel has no function.
08 :0 0 2 3 :00-
08 :30
23.01.12Sonntag
FILTER
Sunday

AFTER INSTALLING THIS UNIT PLEASE PASS ONTO END USER
DO NOT THROW AWAY
18
05 Control Display
1. Flow rate indicator 2. eBus connection indicator 3. Fan indicator
The display shows a bar chart
(ow rate indicator) of the current
ventilation rate.
This eBus indicator appears when
the eBus connection is active; if it
is not visible, no communication is
possible between the control unit
and the Slimline appliance.
This ventilation indicator appears
when the fans in the appliance are
running.
4. Fault symbol 5. Filter message 6. Current time block
This fault symbol appears when an
appliance fault has occurred.
When the text “Filter” appears on
the control unit display, the lters in
the appliance must be cleaned or
replaced.
This indicates in what
(preprogrammed) time interval the
appliance is. When the manual
control key () is activated, the
time interval picture disappears
and is replaced by the message
“Manual”. When the ventilation ow
rate is modied temporarily using
the right-hand setting knob, the
time interval picture disappears
and is replaced by the message
“Temporary”.
7. Current day 8. Appliance selection 9. Current date (day/month/
year) and time
The current day is shown at this
position.
Pressing the appliance selection
key calls up a menu in which the
appliance can be selected that is
connected to the control unit.
The current date and time are
shown at this position. It is
important for proper performance
of the appliance that the time is set
correctly.
A
B123
The supply and extract
fans are running at
30 m3/h or they are
stopped (step 1)
The supply and extract
fans are running in
ventilation mode 1
(step 2)
The supply and extract
fans are running in
ventilation mode 2
(step 3)
The supply and extract
fans are running in
ventilation mode 3
(step 4)
A = Flow rate indicator
B = 4-way switch

SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING THIS UNIT CALL
19
05 Control Display
User information menu
Pressing the info key (
) on the control unit calls
up current values. Modifying values or settings
is not possible in this menu.
Readout Value
1Airow rate 30 m3/h
2Airow rate /
Ventilation mode 1 75 m3/h
3Airow rate /
Ventilation mode 2 100 m3/h
4Airow rate /
Ventilation mode 3 125 m3/h
5Bypass diuser Open or
Closed
6 Frost protection active ON or
OFF
7
Most recent fault message (see
page 25 for explanation fault
codes)
Exxx
Main menu
Pressing the right-hand setting knob on the
control unit takes you to the MAIN MENU.
In this main menu you can use the right-hand
setting knob to select one of the 4 available
menus (rotate to select and press to conrm)
including:
• Service menu (Service menu, see page 20)
• Settings menu control unit (Settings control
unit, see page 21)
• Settings menu appliance (Settings appliance,
see page 22)
• Information menu installer (Information install,
see page 23 )
08 :0 0 2 3 :00-
08 :30
23.01.12Sonntag
FILTER
Other manuals for Slimline 150
1
Table of contents
Other Envirovent Ventilation manuals