Vallox 101 MC L User manual

Manual
MANUAL
Ventilation unit
Document
D4686
Valid from
02.10.2017
Updated
12.2.2018
Model
Vallox 101 MC R
Vallox 101 MC L
Type
3740

2
MAIN PARTS
Extract air fan
1
Supply air fan
2
Supply air filter F7
5
Heat recovery cell
3
Bypass flap
4
Supply air filter G4
6
Extract air filter G4
7
8
Post-heating radiator
(in the supply air duct)
9
Safety switch
10
Supply air heating adjustment
11
Supply/extract air flow adjustment
R model in the figure.
In the L model, the parts are mirrored
WARNING!
The unit is not intended for use by children under 8 or by persons with reduced sensory, physical or
mental capabilities, or whose lack of knowledge and experience do not ensure safe operation of the
unit. Such persons can use the unit under supervision, or by following the instructions of someone who
is responsible for their safety.
7
5
6
11
10
8
9
12
13
14
Vallox Simple Control control panel
(ordered separately)
Vallox ProControl control panel
(ordered separately)
Vallox Capto PTC EC control hood,
Vallox X-Line PTXPMC control hood, or
Vallox X-Line PTXPAMC control hood (ordered
separately)
12
14
13
Vallox X-Line PTXP MC
Vallox X-Line PTXPA MC
(optional)
Vallox Capto PTCEC
(optional)
(optional) (optional)
2
3
4
1

3
© Vallox Oy - All rights reserved
USING THE UNIT
The fan speed of the Vallox ventilation unit is adjusted
using a four-step control.
The available speed options of the control switch
are 1, 2, 3, and 4:
1. Away mode. The ventilation eciency can be
temporarily reduced when the apartment is
unoccupied.
2-3. Standard mode. In standard mode, the air inside the
apartment is replaced once every two hours.
4. Boost mode. Cooking, sauna, bathing, drying of
clothes, guests, and other similar situations can
require that ventilation be increased from the
standard setting.
The fan speed can also be controlled through a separate
Vallox control hood, the Vallox ProControl control panel,
or directly through voltage messages (0-10 V).
Vallox Simple Control control
panel
The temperature of the air blown into the apartment can
be adjusted approximately between +10°C and +30°C.
The unit has an automatic summer/winter function
(a bypass flap).
• When the adjusted temperature is between +10°C
and +30°C, the heat recovery cell is not bypassed,
i.e. the unit is in winter mode.
• In the OFF position, the unit is in the summer mode,
i.e. post-heating is turned o and the heat recovery
cell is bypassed when the outdoor temperature is
above +14°C. The heat recovery will be turned on
when the outdoor temperature falls below +12°C.
• In the AUTO position, the unit will operate as follows
around the year: The default post-heating setting
is +17°C. The unit will bypass the heat recovery cell
when the temperature of the outdoor air exceeds
+14°C. The heat recovery will be turned on when the
outdoor temperature falls below +12°C. During the
bypass, post-heating is turned o.
Adjusting supply air temperature
FAN SPEED ADJUSTMENT
ADJUSTING THE SUPPLY AIR TEMPERATURE
AND SUMMER/WINTER FUNCTION
The winter function of
the ventilation unit
The limit value has been set in the factory for freezing of
the heat recovery cell. When this limit value is exceeded,
the ventilation unit starts to defrost the heat recovery cell
by directing the outdoor air past the heat recovery cell.
The duration of the defrost cycle is 15-45 min depending
on the amount of ice accumulated in the heat recovery cell
and on the extract air flow. The factory settings ensure
optimal operation in standard living and detached house
conditions. Even though the winter operation parameters
can be adjusted for certain extreme conditions, such as
swimming pool facilities, it is always advisable to contact
Vallox maintenance services.

4
USING THE UNIT
FIREPLACE SWITCH
A switch with timer functions can be connected to the unit. The switch stops the
extract air fan when the fireplace is being used. NOTE! Starting up the extract
air fan can reduce the draw of the fireplace! In winter, this can disturb the winter
mode of the ventilation unit. The situation will return to normal soon after the
fireplace mode is turned o.
ADJUSTING THE SUPPLY AND EXTRACT AIR
RATIO
This function might be needed when the air flows are adjusted at the valves
during installation. The user does not need to adjust this function once
the valves have been adjusted, and indeed should not adjust it at all. A
potentiometer can be used to reduce the supply or extract air flow as required.
When the potentiometer is set roughly in the centre position, neither the supply
nor the extract air flow has been reduced. When the potentiometer is turned
anti-clockwise, the supply air flow is reduced, and when the potentiometer is
turned clockwise, the extract air flow is reduced.
The potentiometer for adjusting
the supply and extract air flows
TROUBLESHOOTING
Flashing
LED
Problem Correction
1 NTC sensor of the supply air from the cell
is faulty
Check the sensor and the wires, replace as required
2 NTC sensor of the extract air is faulty Check the sensor and the wires, replace as required
3 NTC sensor of the extract air is faulty Check the sensor and the wires, replace as required
4 NTC sensor of the exhaust air is faulty Check the sensor and the wires, replace as required
5 NTC sensor of the outdoor air is faulty Check the sensor and the wires, replace as required
6 The supply air fan has stopped. Check the wiring of the fan, re¸place the fan as required
7 The extract air fan has stopped. Check the wiring of the fan, replace the fan as required
8 EEPROM is faulty Replace the circuit board
Concealed installation of
the fireplace switch (optional)
TROUBLESHOOTING TABLE
If the ventilation unit is aected by any of the errors listed in the table, the unit will report the error through the error relay,
signal light, and circuit board LEDS. The number of flashes indicates the nature of the error.
The error relay can be connected to remote monitoring.
NOTE! When remote monitoring is used, the signal light of the control panel cannot be turned on.
MAINTENANCE REMINDER
If a signal light is connected to the connectors of the unit’s error relay, the unit will send a reminder of service need every
six months,. If connected, the signal light will flash every second. Sounds made by the relay can then be heard from
inside the unit. The maintenance reminder will be set o automatically when the door of the ventilation unit is opened or
the power is turned o. The maintenance reminder can also be set o manually.
The Vallox Simple Control control panel, and the
Vallox X-Line PTXP MC and PTXPA MC control
hoods, VAK 0-10 VDC:
• The low speed is turned on, then higher-lower-higher
- Low speed under 4 V
- High speed over 6 V
- The selected speed will always be turned
on for 1-5 seconds
Vallox Capto PTC EC control hood:
• The damper is closed, then open-closed-open
• Press at a 1-5 second interval.
The service reminder will only be set o if it has been activated. Refer to the maintenance instructions for the necessary
maintenance measures.

5
© Vallox Oy - All rights reserved
MAINTENANCE
The R model is shown in the figures.
In the L model, the parts are mirrored.
BEFORE BEGINNING
MAINTENANCE WORK
When you open the door of Vallox 101 MC, the safety
switch (S) cuts the power. Despite this, disconnect the
power supply plug anyway. Always disconnect the power
plug before starting maintenance on the Vallox 101 MC.
FILTERS
When the maintenance reminder becomes activated,
check the cleanliness of the filters and replace them if
required.The Vallox ventilation unit has three air filters:
• Class G4 coarse filter (A) filters insects, heavy pollen
and other relatively large foreign objects out of the
outdoor air.
• Class F7 fine filter (B) filters microscopic pollen and
dust particles out of the supply air.
• Class G4 coarse filter (C) filters the extract air and
keeps the heat recovery cell clean.
Using original Vallox filters ensures the best operation
of the ventilation unit and the best filtering results. The
filter replacement interval depends on the ambient dust
concentration. It is recommended that the filters be
replaced every spring and autumn, or at the very least
once a year.
HEAT RECOVERY CELL
Check that the heat recovery cell (D) is clean roughly
once a year when the filters are being replaced. Clean by
washing as required.
• Remove the sealing strip (E) above the heat recovery
cell in the direction of the arrow. Also remove the
extract air filter (C).
• Lift the heat recovery cell and pull it out of the unit.
IMPORTANT! Handle the cell carefully! For example, do
not lift the cell by the layers. The cell layers are very thin
and easily damaged.
If the heat recovery cell is dirty, clean it by immersing it in
water containing a small amount of a mild detergent. Rinse
the heat recovery cell clean with a water spray. When all
the water has drained from between the layers, the heat
recovery cell can be installed.
• Ensure that the lower support (F) is in place between
the knobs at the bottom of the unit before the heat
recovery cell is installed.
• Push the heat recovery cell in place. Also push the
sealing strip (E) in place so that the strip is supported
by the corner bracket (G) at the rear. Lastly, install the
extract air filter (C) in place.
S
A
B
C
E G
C
D
F

6
MAINTENANCE
FANS
Check the cleanliness of the fans when servicing the filters
and the heat recovery cell. Clean the fans as required.
The fans are very sensitive to external impacts, and it is
recommended that they be cleaned in place rather than
removing them.
You can clean the fan blades with compressed air or by
brushing them gently. Do not remove or move the fan
blade balancing weights.
Cleaning the fans
• Remove the extract air filter (C), the sealing strip (E),
and the heat recovery cell (D) from the unit following
the instructions provided earlier. The fans can now
be cleaned. The control grille in the suction outlet of
the supply air fan (T) can be removed if it is in the way
during cleaning. To remove the grille, the supply air
fan must first be removed from the unit.
• To remove the fan, disconnect the quick connector
(H) of the supply air fan (T) and/or the extract air fan
(P) cables.
• Push the fan cables and the rubber feed through (I)
into the fan chamber.
• Remove the wing screws used to fasten the fans (J)
(3 screws per fan).
• Remove the fan from the unit by pulling it forward and
by tilting it slightly backwards at the same time.
Removing and mounting the supply air fan
attenuation grid
• Remove the mounting screws (4) of the air flow
control grille of the supply air fan and remove the
grille. You can now clean the fan. Put the control grille
back in place after cleaning.
Mounting the fans
• Ensure that the rubber feed throughs set in place
when reinstalling the fan. Fasten the fan in place with
wing screws (3 screws/fan).
E
C
P
D
S
H
S
K
S
P
H
J JI I
The R model is shown in the figures.
In the L model, the parts are mirrored.

7
© Vallox Oy - All rights reserved
MAINTENANCE
MAINTENANCE
CONDENSING WATER
In the heating season, the extract air humidity condenses
to water. In new buildings, condensation runo can form
rapidly. Condensed water must be able to freely leave
the unit. At some time before the heating season begins
(e.g. during autumn maintenance), check that the
condensing water outlets in the bottom pool are not
clogged. To check this, pour some water into the pool.
Clean as required. Water must at all times be kept out of
the electrical system.
See the condensing water connections on page 15.
291
291
147,5 147,5
R modelL model
Installation of the Vallox Silent Klick
water seal on the bottom pool
Installation of the Vallox Silent Klick
water seal on the wall.
447
598
53

8
TECHNICAL SPECIFICATIONS
Volume flow rate (dm/s)
Volume flow rate (dm/s)
Pressure loss in ducts. Total pressure (Pa)
Power, W
Supply/extract air volumes
Power table
Combined input power of the fans (kW)
Airflow specified in the ventilation plan (m/s)
SFP =
SFP rate (Specific Fan Power)
recommended value <1,8kW (m/s)
T = supply air
P = extract air
Air flow measurement points
Measurement points after the outlet collar. The fan curves
indicate the total pressure accounted for by duct losses.
TECHNICAL SPECIFICATIONS
Product title
Vallox 101 MC R
Vallox 101 MC L
Product number
4102638
4102629
HVAC code
7912117
7912118
Air volumes Supply air
Extract air
90 dm/s, 100 Pa
98 dm/s, 100 Pa
Electrical connection 230V, 50Hz 8.3A power plug
Enclosure protection class IP34
Post-heating radiator Power, 1500 W
Preheating radiator –
Additional heating radiator –
Fans Supply air
Extract air
0.115 kW, 0.9 A EC
0.115 kW, 0.9 A EC
Specific energy consumption (SEC)
in a cold climate
in a temperate climate
A+
B
Operating eciencies
Annual eciency
Supply air eciency
Specific Fan Power (SFP)
70 % A
82 %
1,0 (38 dm3/s)
Filters Supply air
Extract air
G4 + F7
G4
Heat recovery bypass Automatic
Weight 50 kg
Extract air
Supply air
0
50
100
150
200
250
300
0,0 10,0 20,0 30,0 40,0 50,0 60,0 70,0 80,0 90,0 100,0 110,0
2,7V 3,8V 4,7V
5,7V
6,5V
7,5V
8,0V
9,0V
10,0V
11,4V
0
25
50
75
100
125
150
175
200
225
250
275
300
325
350
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
2,7V
6,5V
7,5V
T9,0V
8,0V
10,0V
11,4V
5,7V
4,7V
3,8V
SFP 1,0
SFP 1,5
SFP 1,8

9
© Vallox Oy - All rights reserved
TECHNICAL SPECIFICATIONS
SOUND VALUES
Sound power level in the supply air duct
by octave band Lw, dB
Sound power level in the extract air duct
by octave band Lw, dB
Adjustment position V / Air flow dm3/s Adjustment position V / Air flow dm3/s
Adjustment position 2.7 V 3.8 V 4.7 V 5.7 V 6.5 V 4.5 V 8.0 V 9.0 V 10.0 V 11.4 V 2.7 V 3.8 V 4.7 V 5.7 V 6.5 V 4.5 V 8.0 V 9.0 V 10.0 V 11.4 V
Air flow dm3/s 8.6 15 16.9 37.7 45.1 53.5 57.3 67.4 73.3 82.3 11.3 24.4 34.3 45.6 55.6 65.9 72.6 83 91.5 99.2
Air flow m/h 30.96 54 60.84 135.72 162.36 192.6 206.28 242.64 263.88 296.28 40.68 87.84 123.48 164.16 200.16 237.24 261.36 298.8 329.4 357.12
Medium
frequency
of the
octave
band Hz
63 *56 *58 *63 67 70 72 75 77 79 80 62 *53 *56 *58 *61 64 67 68 70 71
125 52 62 63 65 67 69 71 74 76 78 52 58 58 61 64 67 69 70 73 74
250 44 52 57 64 70 66 70 71 72 74 35 45 50 57 60 60 62 62 62 63
500 40 49 53 58 61 64 65 69 71 74 *27 *34 40 44 48 51 53 55 57 62
1000 32 41 46 51 55 58 60 63 67 68 *16 *23 28 33 36 39 42 44 46 48
2000 *24 34 40 47 51 55 57 61 63 65 *14 *17 *23 29 32 36 38 41 43 44
4000 *23 *25 31 38 43 48 50 55 57 60 *16 *16 *17 *21 *24 *28 31 34 36 39
8000 *21 *21 *23 30 35 41 44 51 53 56 *20 *20 *20 *20 *20 *21 *22 *24 26 29
LW,dB
LWA, dB(A)
*58 *64 67 71 74 75 78 80 82 84 62 *59 61 64 67 69 72 73 75 77
41 50 54 60 64 65 67 70 73 75 39 43 45 50 54 55 57 58 59 62
Sound pressure le Vel, in decibels (A) coming through the en Velope from the room in which the unit is installed (10m2 sound absorption)
Adjustment position / air flows (supply/extract)
Adjustment position 2.7 V 3.8 V 4.7 V 5.7 V 5.9 V 7.5 V 8.0 V 9.0 V 10.0 V 11.4 V
Air flow dm3/s 13/15 21/24 29/32 39/41 43/46 55/58 60/62 69/72 76/78 84/85
Air flow m/h 46.8/54 75.6/86.4 104.4/115.2 140.4/147.6 154.8/165.6 198/208.8 216/223.2 248.4/259.2 273.6/280.8 302.4/306
LpA, dB (A) *21 *26 30 36 38 42 43 46 48 50
Dimensions and duct outlets
Duct outlets
L model
Inner diameter of the female collar: ø 125 mm
1. Exhaust air out
2. Outdoor air to the unit
3. Supply air to the apartment
4. Exhaust air from the apartment to the unit
R model
Inner diameter of the female collar: ø 125 mm
1. Supply air to the apartment
2. Exhaust air from the apartment to the unit
3. Exhaust air out
4. Outdoor air to the unit
485
38
447
The installation space required
by the Vallox elbow is 47 mm.
See Condensing water connections, p. 15
598
53
500
447
The installation space required
by the Vallox Silent Click water seal
is 73 mm. See Condensing
water connections, p. 15
136,50
461,50
598
104
322
~ 596
154,50
443,50
125
13
24

10
ELECTRICAL CONNECTIONS
INTERNAL ELECTRICAL CONNECTION
LINE:Phase
NEUTRAL:Neutral
SLI:Safety switch phase feed
SNI:Safety switch neutral feed
SLO:Safety switch phase to the circuit board
SNO:Safety switch neutral to the circuit board
SFL:Phase to supply air fan
SFN:Neutral to supply air fan
EFL:Phase to extract air fan
EFN:Neutral to extract air fan
FSO:Fireplace switch feed
FSI:Fireplace switch output
AHL:Post-heating phase
AHN:Post-heating neutral
PHL:Additional heater phase
PHN:Additional heater neutral
BL:Damper motor phase A
BL1:Damper motor phase B
BN:Damper motor neutral
E/I:Error relay feed
E/O:Error relay output
Freezing level adjustment
Fireplace switch
M
1
2
3
Programming connector
Safety / door switch
Belimo damper
motor 230VAC
VAK
remote
monitoring
E/I
E/O
When remote monitoring is used
Leave the signal LED of the external
control panel or cooker hood
disconnected.
Also disconnect the short circuit link
between connectors 3 and 5
from the female side of the control
panel connector.
Post-heating control
PWM level adjustment
4
5
6
Protective earth to a separate block
7
8
9
1
Supply
air fan
2
3
Extract
air fan
4
5
LINE
NEUTRAL
SLI
SNI
SLO
SNO
SFL
Extract air NTC
Outdoor air NTC
Supply air to the apartment NTC
Exhaust air NTC
Supply air from the cell NTC
SFN
EFL
EFN
FSO
FSI
AHL
AHN
PHL
PHN
230V 50 Hz
BL1
BL
BN
E/I
E/O
9. GND / -
8. Supply fan PWM
7. Supply fan tacho
6. GND / -
5. Extract fan PWM
4. Extract fan tacho
3. GND / -
2. 11,4 VDC / +
1. Control signal S
1
DIP Switch
Up Down
1. Post-heating
Electric
VKL
2. Additional heating
Electric
MLV
3. Type of the unit
Bypass
Supply fan stop
4. Extra
An external 0-10VDC voltage supply can be
connected to the S and GND signals
of the control signal for fan control.
234
DIP switch
ERROR RELAY
(potential-free)
*Fan neutral to FSI when
the fireplace switch is used
LED
*Without the fireplace switch, the fan neutral is connected to EFN
With the fireplace switch, the fan neutral is moved to FSI
1234
LED
-
+
S
1 2 3 4 5
1 2 3 4 5
Error relay
90 °C
130 °C
R1
T1 T2
Electric
post-heating
radiator 1500 W
7034800A

11
© Vallox Oy - All rights reserved
ELECTRICAL CONNECTIONS
EXTERNAL ELECTRICAL CONNECTION
with Vallox Capto PTC EC control hood.
EXTERNAL ELECTRICAL CONNECTION
with the Vallox Simple Control control panel / Vallox PTXP MC, Vallox PTXPA MC
cooker hood
S
+
-
LED
Simple Control
S
S
+
+
-
-
Control signal S
11.2 VDC / +
GND / -
Error relay / LED
LED LED
Internal connection
of the ventilation unit
S
+
-
LED
PTXP MC, PTXPA MC
7034500A
ALARM
TACHO
GND
0-11V
PIEZO
+ -
DAMP
IN OUT
MODE
IN OUT
F ALARM
RS 485
A B GND
N
L
DAMPER
1 2 3
LIGHT
N L
FAN
N L
EC roof fan
Tacho
-
S
MC
VENTILATION UNIT
Five terminal
connector**
GND
S
GND
S
MC
VENTILATION UNIT
Four terminal
connector
MV
VENTILATIONUNIT
GND
AN/I
RM/I
RM/O
E/I
LED / E/O
PROGRAMMING
CONNECTORS OF
THE MOTHERBOARD
CONTACT DATA:
GUARD FUNCTION:
NORMAL SITUATION = OPEN
ACTIVATED = CLOSED
HOUSE AUTOMATION:
NORMAL SITUATION = OPEN
ERROR SITUATION
(HOOD OR VENTILATION UNIT) = CLOSED
ACTIVATED GUARD FUNCTION = FLASHING
POSITION OF THE DAMPER:
DAMPER CLOSED = CONTACT OPEN
DAMPER OPEN = CONTACT CLOSED
* External error data is connected in the place
of the short circuit link of the mother board
** Disconnect the short circuit link between connectors
3 and 5 from the MC unit’s control panel connector
IN OUT
PE
EXTRA
DAMPER POSITION
CONTACT DATA
GUARD FUNCTION
CONTACT DATA
HOUSE AUTOMATION
CONTACT DATA
3 POTENTIAL FREE CONTACT
DATA 24VDC/5A
*NOTE!

12
ELECTRICAL CONNECTIONS
EXTERNAL ELECTRICAL CONNECTION
with Vallox ProControl control panel
EXTERNAL ELECTRICAL CONNECTION
With an external control panel
Wiring between the control panel and the ventilation unit, NOMAK 2x2x0.5+0.5
Ventilation unit cable Control panel connector
S Y1
+ leave disconnected
- G0
LED S/DI2
CONTROL PANEL
G 24 VAC feed S/DI2 Error relay
G0 0 VAC G0 0 VAC
Y1 10V, control voltage
of the ventilation unit
Y2
DI1 Boost at the cooker hood
A1 24VAC 1A, intermediate
relay control
Y3
A2
Y4
U1 0...10V, humidity boost
A+ RS-485
B- RS-485
C RS-485 Common
RH%
optional
946147
Nomak
2x2x0,5+0,5
0...10V
LED
G
G0
Y1
Y2
DI1
A1
Y3
A2
Y4
U1
A+
B-
C
S/DI2
G0
Vallox Procontrol
949034
S
LED
S
+
+
-
-
B term
CONFIG
Control signal S Cooker hood
or boost switch
11.2 VDC / +
GND / -
DISTRIBUTION
BOARD
L N
24V
Error relay / LED
Nomak 2x2x0,5+0,5 Modbus
RS-485
Nomak
2x2x0,5+0,5
Cable types specified in the drawing are indicative
2x0.5
2x0.5
Internal connection
of the ventilation unit
The phase of 24VAC feed is connected
to the control panel connector G and
the neutral to the connector G0
Control signal S
GND / -
An external 0-10 VDC
voltage can be
connected to the S
and GND connectors
for fan control.
External control panel
S
S
+
+
-
-
GND / -
LED LED
Internal connection
of the ventilation unit
Control signal S
11.2 VDC / +
Error relay / LED

13
© Vallox Oy - All rights reserved
INSTALLATION
INSTALLATION SITE
Vallox 101 MC must be installed in a location where the
temperature remains above +10°C. When the unit is
installed without a protective enclosure, the location
must be chosen so that its noise does not cause any
disturbance. Such locations include storage premises and
technical spaces.
NOTE!
Remember to make a service door in the finished ceiling
so that the connection cables can be accessed. The
service door should be located roughly 500mm from the
unit door.
162
12
21
20 60
2030 30
20
60
11
20
3030
11
84 84
35 30 35
ø7 14 kpl 550
30
25
25
30°
Wall mounting plate
283 164
6
604
Bottom edge of
the wall mounting plate
The top surface of the side panel of the unit can
be installed against the finished ceiling surface.
When the wall mounting plate is used, it must be
observed that the ventilation unit will rise roughly
10mm above the final installation height!
The outer diameter
of the duct is 12mm
Wall mounting
Mount the Vallox 101 MC on the wall with a mounting plate,
as shown in the adjacent figure. Make sure that the unit is
horizontally level after mounting.
Wall structure
The wall structure must be observed in the mounting.
Avoid mounting the unit on hollow, echoing intermediate
walls and on bedroom walls, or take measures to prevent
conduction of noise.

14
INSTALLATION
Ceiling mounting by using
a ceiling mounting plate
(optional)
The unit can be equipped with an optional ceiling
mounting plate. The ceiling mounting plate must be
fastened on rafter frames or other frame structure with
M8 thread bars. The bars must be fastened so that they
withstand the weight of the unit.
The ceiling mounting plate must be fastened horizontally
to make sure that the unit is level. The ceiling mounting
plate must be fastened so that there is a 10 mm gap
between its rear edge and the finished wall. This way
the ventilation unit will be installed as close to the wall as
possible. The top edge of the white covering strip of the
ceiling mounting plate can be installed against the finished
ceiling. Alternatively, a concealed mounting method can
be used, in which case the finished ceiling can be 30mm
or less from the top edge of the white covering strip.
The ceiling mounting plate is fastened to the M8 thread
bars with the mounting supplies delivered with the
mounting plate. NOTE! The end of the thread bars must
be 5mm or less below the fastening nut (more detailed
instructions are provided with the ceiling mounting plate).
Installing the ventilation unit to the ceiling
mounting plate
Remove the unit door. Lift the unit and take the wires
through the opening in the ceiling mounting plate. Lift
the ventilation unit against the ceiling mounting plate so
that it locks in place. The unit has become locked on the
ceiling mounting plate when the two operating levers on
the mounting plate have been restored to the same level
with the white covering strip of the ceiling mounting plate
(more detailed instructions are provided with the ceiling
mounting plate).
Ceiling mounting plate (optional)
The top edge of the white covering strip of the ceiling mounting plate can be installed against the finished ceiling. Alternatively,
a concealed mounting method can be used, in which case the finished ceiling can be 30mm or less from the top edge of the
white covering strip.
The minimum distance from
the finished rear wall is 10mm
The recommended distance from
the finished side wall is 10mm
598
10 10
598
Finished wall Finished wall
Concealed installation
of the ceiling mounting plate
on the ceiling, max. 30mm.
483
453
53
53
Finished ceiling
Water seal Silent Klick
Installation
space of t
he water seal
73mm
Installation
space of
the elbow
47mm
Concealed installation
of the ceiling mounting plate
on the ceiling, max. 30mm
483
453
38
38
Finished ceiling
Elbow
10
Finished wall

15
© Vallox Oy - All rights reserved
INSTALLATION
The delivery includes the Vallox Silent Klick water seal.
A pipe will be connected to the water seal that leads the
water that is condensed from the extract air to the floor
drain (not directly into the sewer). The pipe must not rise
after the water seal. The ventilation unit must be installed
straight to ensure that condensing water can exit the unit
unobstructed.
Installation of the Vallox Silent Klick
water seal on the bottom pool
Installation of the Vallox Silent
Klick water seal on the wall.
The elbow underneath the unit
takes
less space than the water seal.
47
38 73
53
Elbow
Installation height 38mm, installation space 47mm,
outer diameter of the duct 12mm
Vallox Silent Klick water seal
Installation height 53mm, installation space 73mm,
outer diameter of the duct 12mm
Location of the condensing water outlets,
R and L models
If the Vallox Silent Klick water seal does not fit into the unit
directly, the elbow can be installed at the bottom, and the
water seal can be installed on the wall. This installation
method requires that there is a 47mm space underneath
the unit. The elbow requires a 38mm space when
installed.
291
291
147,5 147,5
RmodelLmodel
Installation of the Vallox Silent Klick water seal on the wall
CONDENSING WATER CONNECTIONS
Installation of the Vallox Silent Klick
water seal on the bottom pool
Attic floor penetration plate (optional)
When an attic floor penetration plate is used, the tightness of the vapour barrier has to be ensured.
The attic floor penetration plate can
be fastened on the finished rear wall.
Finished wall
15 15
The minimum distance
from the side walls is 15mm.

© Vallox - All rights reserved
www.vallox.com
Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND
Customer Service +358 10 7732 200 | Aftersales +358 10 7732 270
D4686 |12.2.2018|PDF
EXPLODED VIEW AND PARTS LIST
(Type 3740)
NO.Part Product number
1 Supply / extract air fan ....................................................................................935450
2 Supply air fan attenuation grid......................................................................935451.
3 Wall mounting plate......................................................................................3080700
4 Water seal Vallox Silent Klick .....................................................................3292500
5 Filter (F7 + G4, supply).....................................................................................978225
6 HR cell .................................................................................................................933260
7 Lower support for the HR cell .....................................................................4102504
8 Upper support for HR cell ........................................................................... 3467200
9 Filter frame (extraction) ...................................................................................978226
10 Filter (G4, extract) ............................................................................................. 978227
NO.Part Product number
11 Bypass flap assembly.................................................................................... 4102523
12 Damper motor ....................................................................................................930621
13 Post-heating resistor........................................................................................942220
14 Door ................................................................................................................... 4102334
15 Mounting screw of the door ...........................................................................990712
16 Motherboard......................................................................................................949035
17 Safety switch...................................................................................................... 948370
18 Glass tube fuse 320 mA slow 5x20 mm....................................................952486
19 NTC sensor (specify the sensor reference number in the order).........946140
R model in the figure.
In the L model, the parts
are mirrored
EXPLODED VIEW
1
15
67
2
8
10
9
11
12
13
1415
17
161819
This manual suits for next models
3
Other Vallox Ventilation manuals