Epcos BR 7000 User manual

PowerFactorController
BR7000
Manual
Version 1.1 E
Power Factor
Controller
BR 7000
Auto
Program
Manual
Service
Enter
OK
Power Quality Solutions
HELP
ESC
AUTO-MODE 2/2
14
137
140
kvar
kW
kVA
Q
P
S
cos ϕ

!
CAUTIONS:
1. High voltage !
2. BR7000 may only be used indoor !
3. Make sure that the discharge time set in the controller matches
the capacitor discharge time !

CONTENTS
Section1 General p.3
Section2 Installationandinstructionsforusage p.4
Section3 Connectionalternativesmeasuringvoltage p.6
andmeasuringcurrent
Section4 Displayfunctions p.8
Section5 Displayofgridparameters p.9
Section6 PROGRAM-MODE/ Manualprogramming p.11
6.1Programminglock p.18
6.2QUICK-Program p.19
Section7 Automaticinitialization p.20
Section8 Automatictestrun p.21
Section9 HELP-function/actualassignmentofoutputs p.21
Section 10 MANUAL OPERATION p.23
Section11 SERVICEMENU/ Error storage p.24
Section12 EXPERTMODE
12.1 Expert-Mode1 p.25
12.2 Expert-Mode2 p.27
Section13 Controlprinciple p.28
Section14 Interfaces p.29
14.1 ASCII-protocol p.30
14.2 Controllercoupling p.30
14.3 Windows-softwareforPC p.31
Section15 Alarmrelay/Errormessages p.32
Section16 Display-editor p.32
Section17 OSCI-MODE p.32
Section18 Maintenanceandwarranty p.32
Appendixes/Tables:
Annex1 Troubleshooting p.33
Annex2 Technical data p.35
Annex3 Factory settings p.37
Annex4 Controlseriestable p.39
Controlserieseditor
Annex5 RegisterMODBUSprotocol p.40
Annex6 Operationdiagram p.43
- 2 - Rev.: 04.2013

Section 1: GENERAL
The power factor controller BR7000 is the consequent follow-up development of the well
provenseriesBR6000.
The main distinctive feature is the new 3-phases measuring system. Due to the 3-phases
recording of voltage and current the device allows a convenient usage as grid measuring
deviceandaspowerfactorcontroller.
All measuring values can be edited and may be displayed in big letters for easier
readability.
2 interfaces are standard. By means of the comfortable windows-software that is included
in the delivery and by using one interface for a connection to a PC the execution and
evaluation of grid measurements is possible. The second interface can be used for
customerspecificpurposes.
Used as PF-controller various control modes are available. They allow not only to control
according to the phase with the highest load or the average demand of the phases, but
also to realize a real single-phase control (balancing) or a mix of balancing and
conventionalthree-phases-control.
All well proven functions of the BR6000-series are available for the BR7000; for example
the control series editor, the automatic initialization etc. For an easy usage the concept of
graphic menu navigation has mainly been adapted. New are amongst others an
integrated help (HELP-button) and the possibility to jump back in the programming menu
byanadditionalESCape-button.
The usage of a fully graphic support display allows an additional Oscilloscope-Mode where
thephases(halfwaves)ofvoltageandcurrentcangraphicallybedisplayed.
R3 x 5 free programmable switching outputs
R1 alarm relay, 1 programmable message relay, 1 relay for the cabinet fan
ROperating voltage: 110 ... 230VAC (+/-15%)
RMeasuring voltage: 3 x 30 ... 440 VAC (L-N) / 50...760 V (L-L)
RMeasuring current: 3 x 5A / 1A
RPre-programmed control series and control series editor
RIlluminated graphic display 128 x 64 dot, graphical menu navigation
R4-quadrant-operation
RAutomatic initialization possible
RMeasuring of capacitor current possible
RThree-phase display of various grid parameters ( U, I, F, Q, P, S Delta Q ... )
RSwitch over to large display possible
RDisplay up to 31st harmonic of voltage and current
RSimultaneous graphical display 1 period of voltage and current in Osci-mode
RMonitoring of temperature and particular capacitor output
RStorage of maximum grid parameters and switching operations/switch on times of
capacitors with time stamp
RManual/automatic operation
RProgramming of fixed steps or mascing of particular outputs possible
RControl possible as 3-phase, 1-phase or mixed-mode
RDisplay of different error messages
RError storage
RComplete 2nd parameter set programmable
R2 integrated separate interfaces
RIntegrated clock, several timers possible
RIntegrated help-function/plain text
RPanel-mounted instrument 144 x 144 x 60 mm
- 3 -

- 4 -
Section 2: INSTALLATION AND INSTRUCTIONS FOR USAGE
The BR7000 is designed as panel mounting instrument in PFC-systems. This requires a
cut out of 138 x 138 mm according to DIN 43700 / IEC 61554. The controller has to be
inserted from the front and fixed with the clamps (included in delivery). The device may
only be installed by qualified personnel and may only be operated according the given
safety regulations. In addition the relevant legal and safety instructions have to be
obeyed.
The measuring input is designed for 1- and 3-phase grids with or without neutral
conductor. The maximum measuring voltage is 440V+ (L-N)/760V~(L-L).
Thesupplyvoltageis110...230V+/-15%.
Wiring connections must be suitable for the particular voltages. Input leads have to be
protected by over-current-protection devices. The supply voltage must be protected by a
fuse;itmustbepossible to switch off the supply voltagebyaseparator.
TheBR7000mustnotbeoperatedwithoutprotectiveearthcontactorconnected!
Before connecting the BR7000, it has to be checked that all connections are at zero
potential; current transformers have to be short circuited. Correct phasing of measuring
voltage and measuring current have to be checked. The measuring current circuits must
2
bewiredwith minimum 2.5mm Cu.
Terminals may only be plugged when de-energized!
Attention!
During single-phase operation the coil voltage for the capacitor contactors must be drawn
from the same phase as the measuring voltage as only the measuring voltage is
monitored. (Protection against direct re-switching of contactors during a short-term
single-phasevoltagedrop.)
The controller may only be operated when installed. The complete programming of all
application-specific parameters is done according chapter programming. Then the device
is set to automatic operation by pushing the operation mode button. The controller is now
readyforoperation.
Operating the controller without following to these operating instructions may be harmful
anddangerous!
!
!
!

BR 7000 rear view
Operating mode:
- Automatic
- Program.
- Manual oper.
- Service
- Expert Mode
- Osci - Mode
- Display Editor
ENTER/ OK
Confirmation
storage of
values
Increase
selected
parameter
HELP
opens
Help pages
Reduce
selected
parameter
Escape
previous
page/value
in the display
- 5 -
BR 7000 front view
The controller is supplied for a standard operating voltage of 110...230VAC (+/-15%), a
measuring voltage of 30...440 V~ (L-N) resp. 50...760V~ (L-L), 50/60Hz, and a
measuring current of 5A or 1A (programmable). A voltage converter is required for
differentoperatingvoltages.
Caution!
Voltages which exceed the allowed voltage range can damage the
device !
!
Power Factor
Controller
BR 7000
Auto
Program
Manual
Service
Enter
OK
Power Quality Solutions
HELP
ESC
HELP
ESC
Power factor controller BR7000
Type: BR7000-R
Meas voltage: 50 - 760VAC 50/60Hz
Supply voltage:110 - 230VAC 50/60Hz
Ser.Nr.: 0815 / 2009
P1
P2
P3
K1
K6
K11
K2
K7
K12
K3
K8
K13
K4
K9
K14
K5
K10
K15
K21
K22
K23
Meas.current
k L1 l
Supply voltage
110...230V~ Measuring voltage
30 ... 440V L-N
Output 11-15
Output 6-10
Output 1-5
Switching outputs:
Fan relay
Message relay
Alarm relay
Meas.current
k L2 l Meas.current
k L3 l
Interface 1
Contact assignment 2nd terminal at bottom
Interface 2
External input
230V~
GND B A PE
L1 N L1 L2 L3 N
The allocation of switching outputs K1…K15
to the capacitors complies to the selected
connection variant and the desired
CONTROL-MODE
(Programming/point2)
Especially in ”Mixed Mode“ where some
outputs are used for single phase capacitors,
others for 3-phase-capacitors the proper
connectionmust beassured!
In the “HELP”-menu the BR7000 directly
displays the actual correct allocation of
outputs(AUTO-MODE:Help-page 7-9).
Forexamplesalso see chapter 9.
cos ϕ

Section 3: CONNECTION ALTERNATIVES MEASURING VOLTAGE
AND MEASURING CURRENT
According to the existing grid and the desired operating mode (CONTROL-MODE
Programming)the BR7000 has to be connected accord. one of the following alternatives.
In grids without neutral conductor the connector N(PE) from meas.voltage at
the controller has to be connect with the PE of the grid !
Alternative1: measuringperformedineachphase-3currenttransformersneeded
Use: CONTROL-MODE:1-4(controlmodesseepage11)
BR7000
Alternative2: single-phasemeasuringviacurrenttransformerinL1 Valuesextrapolated(balanceassumed).
Measuring complies with conventional measuring for switching of three-phase capacitors.
Use:CONTROL-MODE5
BR7000
Alternative 3: single-phase measuring as alternative 2 , but with capacitor current measuring in the compensation
systemforcollectionofrealcapacitorcurrents.
Use:CONTROL-MODE6
BR7000
Reserve
PE
N
L2 (S)
L3 (T)
L1 (R)
( L1) ( N ) L1 L2 L3 N(PE)*
Supply voltage
110-230V~ Measuring voltage Um Meas.current
L3
Meas.current
L2
Meas.current
L1
Load site
( L1) ( N ) L1 L2 L3 N(PE)*
Supply voltage
110-230V~ Measuring voltage Um Meas.current
L3
Meas.current
L2
Meas.current
L1
L1 (R)
L2 (S)
L3 (T)
PE
N
Load site
- 6 -
( L1) ( N ) L1 L2 L3 N(PE)*
Supply voltage
110-230V~ Measuring voltage Um Meas.current
L3
Meas.current
L2
Meas.current
L1
L1 (R)
L2 (S)
L3 (T)
PE
N
L1 L2 L3 N
PFC-system

- 7 -
kK k K
lL l L
Feed 1 Feed 2
K L K L
Measurement via sum current converter
P.F.Controller
Current
measurement
k l
k l
Example:
C.converter 1: 1000/5A
C.converter 2: 1000/5A
Sum-current converter: 5A+5A / 5A
C.converter ratio is: 2000 /5A
Connection of current transformer / sum current transformer
When installing the current converter, care should be taken to ensure that the load
current flows through it. The outputs of the compensation network must be installed
behind the current converter (in the direction of current flow). If the is connected
upvia sum-currentconverters,the overallconversionratioisentered.
Current converter clamps should be grounded on one side!
Caution!
Current converter clamps should
be grounded on one side !
ThesecondaryclampsoftheCT
haveto be short circuited before
currentleadsareiterrupted!
BR7000
!
BR7000 in High Voltage Application
TheexampleshowstheconnectionofBR7000inHV-application.
The measuring current is taken off primary via X/1A transformer. Measuring voltage
produced via transformer 20000/100 V. In this case, the BR7000 has to be programmed
asfollows:
4 I-CONVERTER sek: X/1A
14 MEASUR.VOLTAGE: 100 V
15 V-CONVERTER:20kV/100V
L1 (R) L1 (R)
L2 (S) L2 (S)
L3 (T) L3 (T)
N
Meas.current
Im (X/1A) supply
voltage
Ub
Meas-
voltage
Um
BR 7000
PE
Meas.current Meas. voltage Um Supply voltage Ub
L1 L2 L3 L1 L2 L3 N L1 N
HIGH VOLTAGE LOW VOLTAGE
20 kV / 400 V
20000
100

Section 4: DISPLAY - FUNCTIONS
After the operating voltage has been switched on, the BR7000 briefly indicates with
descriptionandsoftware-versionbeforechangingtoautomaticoperation.
Actualvaluesand symbols of the particular operation state are shown in the display.
In the automatic operation (standard) capacitor steps are automatically switched on or
off to reach the pre-set target cos-phi. This happens when the required reactive power is
higherthanthevalueof the smallest capacitor step.
Example1:Automaticoperation
L1...L3:Individualcompensationbysingle-phasecapacitors
- 8 -
Number of switching outputs until end stop.
Here: 15 three-phase capacitors, end-stop: 15
Control direction is symbolized by a
compact arrow:
Connecting-in
Connecting-out
The connecting-in arrow is always
located after the maximum possible
number of stages (end stop)
An open arrow indicates that the
required blocking time (Discharge time)
is running before an impending
switching step
A double arrow symbolizes switching of
several branches
The sigma-sign indicates the three-
phase-value (mean-value) resp.
activated three-phase-capacitors
Alarm relay activated
(declines in case of error)
Message relay activated: “SUPPLY”
Message relay activated:“Undercurrent”
Message relay aktivated: “Harmonics”
FAN-relay: ON
The particular capacitor outputs are
permanently monitored. Inverse display
= capacitor out of range
Display of 2nd parameter-set
Supply display (i.e.generator operation)
nd
2 Target-cos phi activated by timer
nd
2 Target-cos phi activated by supply
S
A
U
H
F
2
T
é
é
Example2:Automaticoperation(Mixed Mode)
L1...L3: phasewisecompensationby
singlephasecapacitors
Σ: Three-phasecapacitorsactivated
Example3: Automaticoperation
Measuringinonephase
Controllingof15three-phase-capacitors
Σ
AUTO-MODE 1/2
cosϕ0.869 IND
cosϕ0.869 IND
cosϕ0.869 IND
cosϕ0.917 CAP
L1
L1
L2
L2
L3
L3
1 2 3 4
Σ
Σ
Σ
AUTO-MODE 1/3
AUTO-MODE 1/2
L1
L2
L3
1 2 3 4
123456789
10 11 12 13 14 15
control direction
(here: connected-in)
active capacitor
branches

Section 5: DISPLAY OF GRID PARAMETERS
5.1 Display of 3 selected grid parameters
In Auto-Mode, button éleads to display mode 1. Here 3 (free selectable) grid parameters
are displayed in large letters. The selection and storage of these values is done in the
Display-Editor.
Example: Displaymode1:
Desiredvaluesselected in the
DisplayEditor(seesection16)
5.2 Display of particular grid parameters (from AUTO-MODE by pressing ENTER)
By repeated activation of the “ENTER”-button (in automatic operation) several grid
parameterscan be displayed (s. table below):
Action Display Unit in% largedisplay Bargraph 3-phase
possible possible
ENTER 1 LINEVOLTAGE V x x
ENTER 2 APPARENTCURRENT A x x x
ENTER 3 REACTIVEPOWER kvar x x x
ENTER 4 ACTIVEPOWER kW x x x
ENTER 5 APPARENTPOWER kVA x x x
ENTER 6 DIFF. kvartotarget kvar x x x
ENTER 7 FREQUENCY Hz x x
ENTER 8 TEMPERATURE °C/ °F x
ENTER 9 3.-31. HARMONICS V/ I x x x
ENTER 10 HARMONICSTHD-V/I x x x
ENTER 11 Comp.- power (onlyatrealcapacitorcurrentmeasurement)
ENTER 12 ENERGY kvarh/ kWh
ENTER 13 TIME/DATE é/êchangethedateformat
ENTER 14 Softwareversion
ENTER returnto: 1
Buttons é/êchangethedisplayformat:
Thevaluescan be displayed in their unit, in % or as large displayresp.barchart.
Examples,seenextpage.
- 9 -
AUTO-MODE 2/2
14
137
140
kvar
kW
kVA
Q
P
S

=== DISPLAY ===
Examplesofdifferentdisplays:
VOLTAGE 3-phas. CURRENT: 3-phas. REACTIVEPWR 3-phas.
HARMONICSin% TEMPERATURE °C REACTIVE PWR in%
LARGELETTERS
HARMONICSdiagram THDV/Ias bar diagram REACTIVEPOWER
LARGELETTERS
- 10 -
Repeated pressing of the "Operating Mode” key activates the various menus in sequence:
Automatic operation - Programming - Manual (manual operation)- Service - Expert
mode- OsciMode- DisplayEditorand back to Auto.
AUTO-MODE
to display operation to programming to manual operation to value buffer special functions to graphic. mode display-functions
PROGRAMMING
MANUAL-MODE
SERVICE EXPERT-MODE OSZI - MODE
DISPLAY-EDITOR
DISPLAY 7/9
8 HARMONICS [3.]
L1 V 0.4% I 0.5%
L2 V 1.4% I 0.8%
L3 V 1.4% I 0.7%
DISPLAY 3/4
TEMPERATURE
25 °C
DISPLAY 1/3
1 LINE VOLTAGE
L1-N 233 V
L2-N 233 V
L3-N 233 V
24VDC 24 V
DISPLAY 3/3
25
25
25
kvar
kvar
kvar
Q1
Q2
Q3
ANZEIGE 1/3
2 APPAR.CURRENT
L1 235 A
L2 133 A
L3 133 A
DISPLAY 1/2
3 REACTIVE POWER
L1 71 kvar
L2 23 kvar
L3 22 kvar
116 kvar
DISPLAY 2/3
3 REACTIVE POWER
L1 31 %
L2 10 %
L3 10 %
17 %
HARMONICS [V-1]
1.0%
0.5%
0% 3579
11 13 15 17 19 21 23 25 27 29 31
THD 1/2
20%
10%
0%THD V 1 2 3 THD I 1 2 3
DISPLAY 1/3

Section 6: PROGRAM-MODE (manual programming)
Pressing the button “Operation Mode“ one time switches from automatic operation to the
programmode.
The upper part of the display always shows the parameter, the adjustable values are
shown in the lower part. Editable values are generally given in square brackets. Changes
of these values can be done by the buttons é/ ê. By pressing the “ENTER-button” the
valueis stored. Pressing the “ESC”-button allows to go one stepback (without storing).
1 LANGUAGE
Thisselectsthelanguageoftheoperatingmenu
[GERMAN, ENGLISH, SPANISH, RUSSIAN, TURKISH]
2 CONTROL-MODE [1...6]
CONTROL-MODE [1]:
3-phase measuring / max. 3x5 single phase capacitors L-N
(3 current transformers needed), values displayed and calculated per phase.
Connection of measuring current and measuring voltage (refer to page 6).
Controlling is done with max. 5 outputs per phase in case of switching of single-
phasecapacitorsL-N.
Allocation of switching outputs K1…K15 to the capacitors according to the selected
connectionvariantand the desired CONTROL-MODE.
Especially in ”Mixed Mode“ where some outputs are used for single phase
capacitors, and others for 3-phase-capacitors the proper connection must be
assured!
In the HELP-function the BR7000 directly displays the correct allocation of outputs
(AUTO-MODE:Help-page7-9).
!
- 11 -
Example :
3x 5 single-phase capacitors (L-N)
Output assignment
L1 (R)
L2 (S)
L3 (T)
P1 1 2 3 4 5 P2 6 7 8 9 10 P3 11 12 13 14 15
Output 1-5 Output 6-10 Output 11-15
meas.voltage L1 meas.voltage L2 meas.voltage L3
PE
N
F1: 6,3AT F1: 6,3AT F1: 6,3AT
C1.1 (C1 at L1-N)
C1.2 (C1 at L2-N)
C1.3 (C1 at L3-N)
C2.1 (C2 at L1-N)
C2.2 (C2 at L2-N)
C2.3 (C2 at L3-N)
C3.1 (C3 at L1-N)
C4.1 (C4 at L1-N)
C5.1 (C5 at L1-N)
C3.2 (C3 at L2-N)
C4.2 (C4 at L2-N)
C5.2 (C5 at L2-N)
C3.3 (C3 at L3-N)
C4.3 (C4 at L3-N)
C5.3 (C5 at L3-N)
K1
(K2)
(K3)
(K4)
(K5)
K6
(K7)
(K8)
(K9)
(K10)
K11
(K12)
(K13)
(K14)
(K15)
C1.1
(C2.1)
(C3.1)
(C4.1)
(C5.1)
C1.2
(C2.2)
(C3.2)
(C4.2)
(C5.2)
C1.3
(C2.3)
(C3.3)
(C4.3)
(C5.3)
PROGRAM-MODE
1 LANGUAGE [1]
[ ENGLISH ]

=== PROGRAM-MODE ===
CONTROL-MODE [2]: MIXED-MODE 3-phasige measuring
3 current transformers required. Values displayed and calculated per phase. Connection of
measuringcurrent andmeasuringvoltage see page6.
Controllingdone withmax.4 outputsperphase forswitching of singlephase capacitors L-N.
The rest of the outputs (min. 3, max. 12) are used for switching of three-phase capacitors
tocontrol thebaseload.
Partitioninginto single-phase/ three-phase capacitorsis done at
Programming:4ENDSTOP!
The allocation of the switching outputs to the particular capacitors can be retrieved in AUTO-
MODEon HELP-pages7…9.
CONTROL-MODE [3]:
3-phase measuring / max. 3x5 single-phase capacitores L-L
3current transformersrequired. Valuesdisplayedand calculated perphase.
Controllingdone withmax.5 outputsperphase, switchingof single phasecapacitors L-L
L1 (R)
L2 (S)
L3 (T)
Example:
3x 4 single-phase-capacitors +
3 standard 3-phase capacitors
Output assignment
3 x 4 Single-phase steps
3 Three-phase-
capacitors
P1 1 2 3 4 5 P2 6 7 8 9 10 P3 11 12 13 14 15
Output 1-5 Output 6-10 Output 11-15
meas.voltage L1 meas.voltage L2 meas.voltage L3
PE
N
K 5
(K10)
(K15)
F1: 6,3AT F1: 6,3AT F1: 6,3AT
C1.1 (C1 at L1-N)
C1.2 (C1 at L2-N)
C1.3 (C1 at L3-N)
C2.1 (C2 at L1-N)
C2.2 (C2 at L2-N)
C2.3 (C2 at L3-N)
C3.1 (C3 at L1-N)
C4.1 (C4 at L1-N)
C3.2 (C3 at L2-N)
C4.2 (C4 at L2-N)
C3.3 (C3 at L3-N)
C4.3 (C4 at L3-N)
C1Σ(C1 3-phas.)
C2Σ(C2 3-phas.)
C3Σ(C3 3-phas.)
C1Σ
( C2Σ)
( C3Σ)
K1
(K2)
(K3)
(K4)
K6
(K7)
(K8)
(K9)
K11
(K12)
(K13)
(K14)
C1.1
(C2.1)
(C3.1)
(C4.1)
C1.2
(C2.2)
(C3.2)
(C4.2)
C1.3
(C2.3)
(C3.3)
(C4.3)
L1 (R)
L2 (S)
L3 (T)
Example:
3x 5 single-phase capacitors (L-L)
Output assignment
P1 1 2 3 4 5 P2 6 7 8 9 10 P3 11 12 13 14 15
Output 1-5 Output 6-10 Output 11-15
meas.voltage L1 meas.voltage L2 meas.voltage L3
PE
N
F1: 6,3AT F1: 6,3AT F1: 6,3AT
C1.1 (C1 at L1-L2)
C1.2 (C1 at L2-L3)
C1.3 (C1 at L3-L1)
C2.1 (C2 at L1-L2)
C2.2 (C2 at L2-L3)
C2.3 (C2 at L3-L1)
C3.1 (C3 at L1-L2)
C4.1 (C4 at L1-L2)
C5.1 (C5 at L1-L2)
C3.2 (C3 at L2-L3)
C4.2 (C4 at L2-L3)
C5.2 (C5 at L2-L3)
C3.3 (C3 at L3-L1)
C4.3 (C4 at L3-L1)
C5.3 (C5 at L3-L1)
K1
(K2)
(K3)
(K4)
(K5)
K6
(K7)
(K8)
(K9)
(K10)
K11
(K12)
(K13)
(K14)
(K15)
C1.1
(C2.1)
(C3.1)
(C4.1)
(C5.1)
C1.2
(C2.2)
(C3.2)
(C4.2)
(C5.2)
C1.3
(C2.3)
(C3.3)
(C4.3)
(C5.3)

=== PROGRAMM-MODE ===
CONTROL-MODE [4]:
3-phase measuring / max. 15 three-phase capacitors
3 current transformers required. Connection of measuring current and measuring voltage
referto page6.
Values displayedand calculatedper phase.
Controlling done with max. 15 outputs according to maximum or mean-value of the reactive
power
CONTROL-MODE [5]:
1-phase measuring / max. 15 three-phase capacitors
Only2 currenttransformerin L1required
Connectionof measuringcurrentand measuringvoltagesee page 6
Values extrapolatedto allphases (balance assumed)
Measuringcomplies withconventionalmeasuring forswitching of three-phasecapacitors.
CONTROL-MODE [6]:
1-phase measuring / max. 15 three-phase capacitors
with capacitor current measurement
According variant 5, but the free current inputs (L2 or L3) are used for capacitor current
measurementfor realmonitoringof capacitors.
Connectionof measuringcurrentand measuringvoltagesee page 6!
- 13 -
L1 (R)
L2 (S)
L3 (T)
Example:
15 standard 3-phase capacitors
P1 1 2 3 4 5 P2 6 7 8 9 10 P3 11 12 13 14 15
Output 1-5 Output 6-10 Output 11-15
meas.voltage L1 meas.voltage L2 meas.voltage L3
PE
N
K1 K2 K15
F1: 6,3AT F1: 6,3AT F1: 6,3AT
C1 ( 3-phase)
C6 ( 3-phase)
C11 ( 3-phase)
C2 ( 3-phase)
C7 ( 3-phase)
C12 ( 3-phase)
C3 ( 3-phase)
C8 ( 3-phase)
C13 ( 3-phase)
C4 ( 3-phase)
C9 ( 3-phase)
C14 ( 3-phase)
C5 ( 3-phase)
C10 ( 3-phase)
C15 ( 3-phase)
C1 C2 C15
....

=== PROGRAMM-MODE ===
3 I-CONVERTER PRIM [1000]A/X (5...13000)A
Selectstheprimarycurrentofthecurrentconverter.
SequentialadjustmentofL1...L3.
viathe é/êkeys. SaveandcontinuewithENTER
4 I-CONVERTER SEC 1000A/[5]A (1/ 5 A )
Thissetsthesecondarycurrentofthecurrentconverter.
Selection via é/ê. Saveand continue with ENTER
5 END STOPP
Programming of the maximum number of active
capacitorbranches.
Depending on the selected operation mode the
maximum number of connected capacitors at the output
groups L1…L3 and (if available) for the output groups Σ
(three-phasecapacitors)areset.
The visible symbols of the capacitors correspond to the
connectedoutputs.
Inputvia é/ê.Saveand continue with ENTER
6 CONTROL SERIES [1] (1...20+ED)
The ratio of the capacitor branch powers determines the
control series, the power of the first capacitor always
beingassignedthevalue1.
Selection of desired control series consecutively for
L1…L3andfor Σ(three-phaseoutputs).
If the required control series should not be present, the
user may define a special one in control series “ED” ( see
Annex4:Control-serieseditor)
7 CONTROL PRINCIPLE
The control preference may be selected here:
SEQUENTIAL connection
LOOP connection
INTELLIGENT loop connection (defaultsetting)
COMBINED CHOKE
SeeSection13foranexplanationofthe controlmodes.
Selectionwithé/ êkeys.
Saveand continue with ENTER
8 POWER 1st STAGE [0.01...255.99] / [10...2550]kvar
To determine the controller's response sensitivity, the
dimensions of the smallest capacitor (stage 1) must be
known. They are entered in two steps in kvar. The
integral kvar values (before the comma) are initially
selectedviatheé/êkeysandsavedwithENTER.
The positions after the comma are then selected, again
viatheé/êkeys.
If the capacitor value is below the response sensitivity, a
warning will occur ( indication of “!” in the display )
- 14 -
PROGRAM-MODE
7 CONTR.PRINC. 3]
[ INTELLIGENT ]
PROGRAM-MODE
3 I-CONVERTER PRIM
[ 1000]A / 5 A
1000]A / 5 A
1000]A / 5 A
L1
L2
L3
PROGRAM-MODE
8 POWER 1.STAGE
[ 25].00 kvar
25 .00 kvar
25 .00 kvar
L1-N
L2-N
L3-N
PROGRAM-MODE
6 CONT.SERIES L1-N
12333
12333
12333
[ 3]
3
3
L1-N
L2-N
L3-N 1 2 3 4 5
PROGRAM-MODE
5 END STOP L1-N
[ 5]
5
5
L1-N
L2-N
L3-N 1 2 3 4 5

- 15 -
=== PROGRAM-MODE ===
9 TARGET COS PHI [ 0.98 ind ] ( 0.3 ind ... 0.3 cap )
By setting the target cos phi, the power factor to be
attainedviathePFcorrectionisdefined.
SequentialsettingofL1...L3viaé/ê,
Saveand continue with ENTER.
10 TARGET 2nd cosPhi [ NO ] ( 1...3 )
1:NO (no2nd targetcosPhi,
continuewith14)
2: Timer ( 2nd cos-phi- activatedby timer,
schedulerwith12,13)
3:Energysupply (2ndtargetcos-phi- activatedby
energy-supply)
11 TARGET 2nd cosPhi [ 0.9 IND ] (0.3 ind ... 0.3 cap )
Setpointforthe2ndtargetcosPhi
(onlyavailableifselectedunder10)
12 SWITCH ON TIME ϕ2 [ HH:MM:SS ]
Switch-ontimeofthetimerforthe2ndtarget-cosphi
(onlyavailableifselectedunder10)
13 SWITCH OFF TIME ϕ2 [ HH:MM:SS]
Switch-offtimeofthetimerforthe2ndtarget-cosphi
(onlyavailableifselectedunder10)
14 MEASURING VOLTAGE L-L [400]V ( 50...760) V
Programmingof measuring voltage.
The values programmed here always refer to the
L-L voltage in the system !
Selectionvia é/ê. Save/ continue with ENTER
15 V-CONVERTER [NO] (300V-77kV / 440V )
When a measuring-voltage converter (e.g. for HV-
measurement) is used, its conversion ratio is to be
programmedhere.
Selectionvia é/ê. Save/ continue withENTER
16 CONNECTING TIME:[40]sec. (1sec....20min.)
The time between connecting the capacitors to increase
the momentary network capacitance. It should be noted
that in practical operation the real connection time is
affectedbythedischargetime(lockingtime).
Selectionvia é/ê. Save/ continue withENTER
17 DISCONNECT TIME:[40]sec. ( 1 sec. ... 20min.)
The time between disconnecting the capacitors to
reducethemomentarynetworkcapacitance.
Selectionvia é/ê. Save/ continue with ENTER
PROGRAM-MODE
12 SWITCH ON TIME ϕ2
ON [16]: 00 MO-FR
OFF 07 : 00 MO-FR
PROGRAM-MODE
15 V-CONVERTER
PRIMARY SECONDARY
[20000V] / 100V
PROGRAM-MODE
10 TARGET 2nd cos ϕ
[ TIMER ]
PROGRAM-MODE
9 TARGET cos ϕ
[ 0.98 IND]
PROGRAM-MODE
16 CONNECTING TIME
C-ON [40]s
C-OFF 40 s
C-DIS 60 s

=== PROGRAM-MODE ===
18 DISCHARGE TIME: [ 60 ] sec. (1sec....20min.)
This is the time for which an individual output is blocked
between disconnecting and connecting. It depends on
the discharge device of the capacitor. The discharge
time of a conventional system without fast discharge
resistors or reactors should not be adjusted to less than
thedatasheetvalueof the used capacitor.
Selection with buttons é/ ê. Save /Continue with
ENTER
19 ALARM TEMPERATURE [ 55 ] °C ( 20...80 )°C
The alarm temperature programmed here is the
temperature at which a stepwise disconnection of the
capacitors is performed. After 10 min. the standard
alarm relay of the controller (K21) will respond. At the
same time, the display shows the cause of the alarm
(overtemperature).
When the temperature drops again, the required
branchesare automatically re-connected in steps.
Selectionwith é/ê.Save/ Continuewith ENTER
20 FAN TEMPERATURE [30]°C ( 15...70)°C
Threshold for the fan relay (K23) for control of a
cabinetfan.
21 MESSAGE RELAY [Supply ] ( 1...3 )
The message relay (K22) can be programmed for one
ofthefollowingoptions as required:
1 - OFF
2 - Supply: Messagewhenactivepowerissupplied.
3- Under current:
Message when the measuring current is not met. Signal
is generated when the current value drops below the
responsesensitivityofthecontroller.
4 - Harmonics:
Message when the limiting value of the total harmonic
distortion factor (THD-V) is exceeded. This value can be
parameterizedunder ”38 Harmonics” (in %).
5 - ERROR - System current measuring
6 - ERROR - Com1 (interfaceerror)
7 - ERROR - Com2 (interfaceerror)
8 - ERROR - Com1/2 (interface error)
- 16 -
S
U
H
E
E
Display:
Display:
Display:
Display:
Display:
PROGRAM-MODE
18 DISCHARGE TIME
C-ON 40 s
C-OFF 40 s
C-DIS [60]s
PROGRAM-MODE
19 ALARM TEMPERATURE
[ 55°C]
PROGRAM-MODE
21 MESSAGE RELAY [2]
[ HARMONICS ]

=== PROGRAM-MODE ===
22 EXTERNAL INPUT [ NO ] ( 1...5 )
Setting of the desired action upon applying a control
voltageof110...230V~attheexternalinput.
1- NO (no action)
2- 2nd parameter set (switch over to 2nd parameter set).
This selection simultaneously activates the following
points 23…36 for programming of the values of the
2ndparameterset.
3 - External error (Displayofanerrormessage)
4 - Coupling operation parallel
(Inputforsignalofcoupling switch)
5 - Coupling operation Master/Slave
(Inputforsignalofcoupling switch)
Description of coupling operation s. section 14.2.
Couplingoperationonly possible inCONTROL-MODE 4-6.
6 - Remote - Switch ON
7 - Remote - Switch OFF
8 - Remote - Stopp
Programming of 2nd parameter set
(only active if 22 EXTERNAL INPUT is set to 2nd parameter set)
As a standard, the values of the 2nd parameter set equal the
values of the normal parameter set. Menu entries 23...36 permit a
systematic change of the 2nd parameter set. Possible applications
are for example: changing of target cos-phi, switch-over of current
transformeror switch-over the switching times.
By triggering a 110...230V~ signal at the external input, the
2nd parameter set is activated with following values:
The programming of the 2nd parameter set is performed
equivalent to the programming of the 1st set parameters (3-18)
37 HARMONICS [ 7 ]% (0,5...25,5)%
Threshold value THD-V (in%). In case this value is exceeded a
message will be displayed. THD-V ist the ratio of the geometric
sum of unequal harmonics to the 1st harmonic. In any case, a
warning will be displayed. Warning via message relay will only be
23. I-converter prim
24. I-converter sec
25. End stop
26. Control serie
27. Control principle
28. Power 1st stage
29. Target cos-Phi nominal value
30. 2nd target cos-Phi NO/supply/Timer
31. 2nd target cos-Phi nominal value
32. Switch on time target cos-Phi-2
33. Switch off time target cos-Phi-2
34. Connecting time
35. Disconnecting time
36. Discharge time
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
22
PROGRAM-MODE
37 HARMONICS
THD-V [ 7.0]%
2
PROGRAM-MODE
29 TARGET cos ϕ
[ 0.98 IND]
PROGRAM-MODE
22 EXT. INPUT [2]
[ 2.PARAMETER SET]
2
2
2
PROGRAM-MODE
23 I-CONVERTER PRIM
[ 1000]A / 5 A
1000]A / 5 A
1000]A / 5 A
L1
L2
L3

=== PROGRAM-MODE ===
38 CLOCK [HH:MM], DATE [DD.MM.YY]
Setsystem-timeanddate
(Due to an internal battery the time will be kept even in
caseofpowerloss)
Selectionwith é/ê.Save/continuewith ENTER
39 CONTRAST [6] ( 0...10)
Adjustmentofdisplaycontrastforbestreadability
Selectionwith é/ê.Save/continuewith ENTER
40 BASIC SETTINGS [NO] (YES/NO)
When selecting YES and confirmated with ENTER, all
parameters are set back to the basic settings of the
panel builder (optimum values for the system if
the controller has been delivered together with the PFC-
system). If the controller has been delivered ex works,
thispointcorrespondstothe defaultsettings.
ATTENTION: All user settings get lost !
Section 6.1: PROGRAMMING LOCK
As a protection against unauthorized changes of the system
parameters, the BR7000 is equipped with a programming lock.
This can be activated in the EXPERT MODE. When the lock is active,
allparameterscan be checked but not changed.
Alternatives:
Lockactive/Notactive/ Automaticactivationafter24h
- 18 -
PROGRAM-MODE
38 CLOCK
[ 15]: 27
MONDAY
05.03.2013
PROGRAM-MODE
40 BASIC SETTINGS
[NO ]
EXPERT-MODE
7 OPERATING LOCK
[NO ]

Section 6.2: QUICK-PROGRAM
The QUICK-PROGRAMM-MODE can be activated from the menu ”PROGRAMMING“ by
pressingthebutton“é"andis used for fastprogrammingof the BR7000.
The list hereafter contains the most important parameters for programming in short
form. For most applications the input of these values is already sufficient. Input is done
likefornormalprogramming:
1 CONTROL-MODE [1...6]
2 I-CONVERTER PRIM [1000]A/X (5...13000)A
Selection of primary current of the current transformer of the system.
Programmingis done consecutively for L1…L3.
3 I-CONVERTER SEC 1000A/[5]A (1/ 5 A )
SecondarycurrentoftheCTofthesystem.
4 END STOP
Programmingof the maximum number of active capacitor branches.
5 CONTROL SERIES [1] (1...20+EDITOR )
The ratio of the capacitor branch power determines the control series, the
powerofthe1stcapacitoralwaysbeing assigned the value 1.
6 POWER 1st STAGE [0.01 ... 255.99]kvar
To determine the controller's response sensitivity, the dimensions of the
smallest capacitor in the system (stage 1) must be known. Input in kvar is done
intwosteps (beforethecomma/afterthecomma).
7 TARGET COS PHI [0.98ind] (0.3ind ...0.3cap)
Setting the target cos-phi determines the power factor that should be achieved
byPFC.
8 CONNECTING TIME: [ 40 ] sec. ( 1 sec. ... 20min.)
This refers to the time between the connections of capacitors to increase the
actualsystemcapacitance
9 DISCONNECTING TIME: [ 40 ] sec. ( 1 sec. ... 20min.)
This refers to the time between disconnecting of capacitors to decrease the
actualsystemcapacitance.
10 DISCHARGE TIME: [ 60 ] sec. (1sec....20min.)
This is the time for which an individual output is locked between its
disconnectingandconnecting.
Detaileddescriptioncanbefoundinchapter6(PROGRAMMING) page 11 ff.
- 19 -
Other manuals for BR 7000
1
Table of contents
Other Epcos Controllers manuals