EST EA752-2 Assembly instructions

© 2014 UTC Fire & Security. All rights reserved. 1 / 2 P/N 501-153600-0-06 • REV 06 • ISS 06MAR14
EA752-2 Monitored Dual Output Module
Installation Sheet
Description
The EA752-2 provides two conventional output circuits (Circuit
1 and Circuit 2) for operating polarized sounders, visual
indicators, and controls for ancillary equipment. Output 1 and
Output 2 share the same address and therefore switch on and
off at the same time.
The module comprises a front plate and a backbox. The front
plate houses the electronic components and plugs into the
backbox. The backbox provides the screw terminals for
connecting the field wiring.
The bicolor LED on the front plate indicates the status of the
module (off = normal condition, red = active condition, amber =
fault condition). There is space provided next to the LED to
attach an address label, if desired.
WARNING: This module will NOT operate without electrical
power. As fires frequently cause power interruption, we
suggest you discuss further safeguards with your local fire
protection specialist.
Installation
1. Remove the front plate from the backbox.
2. Drill out center hole in the backbox and run wires into the
module.
3. Remove appropriate knockouts on the backbox for
mounting to a conduit box. Mount the backbox to the
conduit box.
4. Make all wiring connections as shown in the wiring
diagram (Figure 2).
5. Set the address switch for the module. See “Address
switch settings” below (Figure 1).
6. Attach the address label to the indent that is on the front of
the module.
7. Secure the front plate to the backbox with the two screws
provided.
Address switch settings
SW1 is used to assign device addresses. Each switch segment
has a decimal value as shown in Figure 1.
The sum of all the switch segments in the ON position
determines the device address. You can set the device
address to any value between 001 and 127 that is not used by
another device on the same loop. For example, to select a
device address of 007 you must set SW1-1, SW1-2, and SW1-
3 to the ON position and the remaining switch segments to the
OFF position.
Figure 1: Address switch settings
Address
ON
OFF
Front plate - rear view
64
32
16
8
4
2
1
FUSES 1.0 A
Device address = 007
ON
1 2 3 4 5 6 7
1 2 4 8 16 32 64
Wiring
Field wiring connections are shown in Figure 2.
Run the wires through a hole in the backbox and connect them
to the screw terminals as shown.
Specifications
Application Indoor use
Power supply requirements
External power supply
Loop power
Max line drop
22 to 30 VDC
20 volt pulsed analogue loop
2V
Current
Standby
Activated
600 µA
700 µA
IP rating 42
Mounting Surface
Construction Moulded ABS
Colour White
Dimensions (W × H × D) 120 × 120 × 40 mm
Gross weight 310 g
Initiating device circuits (IDC)
Output current
EOL resistor value
1 A at 24 VDC per circuit
2.2 KΩ
Operating environment
Temperature
Relative humidity
−10 to +70°C
20 to 95% noncondensing
Storage temperature −10 to +70°C

2 / 2 P/N 501-153600-0-06 • REV 06 • ISS 06MAR14
Figure 2: Wiring diagram
Notes
1. Screened cable.
2. EOLR required if circuit is not used.
3. Terminal marking (plus/minus)
indicates signal polarity when the
circuit is active. The polarity
reverses when the circuit is not
active.
4. Signal source must be CE and
EN54-4 compliant. The jumper must
be connected.
5. Each output circuit provides up to 1
A at 24 VDC. Each output circuit
has a 1 A fuse. Fuses are monitored
by the panel.
6. Devices connected to the output
circuit must be polarized as shown.
If non-polarized devices are used,
insert a 1N4002/7 diode in the
positive leg of each device, with the
stripe facing the device. For
inductive loads (relays etc), fit a
Bipolar Transient Protector
(P/N 235196P) across the coil.
7. Attach the supplied ferrites to cables
as shown in Figure 2 (internal to the
module).
8. The following ferrite core needs to
be fitted to all cables (externally to
the module): TDK ZCAT3055-1330.
Regulatory information
This section includes both regulatory information and a
summary on the declared performance according to the
Construction Products Regulation 305/2011. For detailed
information refer to the product Declaration of Performance.
Certification
Certification body 0370
Declaration of
Performance number 360-5221-0199
Year of first CE marking 10
Product Identification EA752-2
Intended use See DoP point 3
Essential characteristics See DoP point 9
Manufacturer Gulf Security Technology Co.,Ltd
80, Changjiang East Road,
QETDZ, Qinhuangdao,
Hebei Province, China 066004
Authorized EU manufacturing
representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert,
Netherlands
European Union directives 1999/5/EC (R&TTE directive): Hereby,
UTC Fire & Security declares that this
device is in compliance with the essential
requirements and other relevant
provisions of Directive 1999/5/EC.
2002/96/EC (WEEE directive): Products
marked with this symbol cannot be
disposed of as unsorted municipal waste
in the European Union. For proper
recycling, return this product to your local
supplier upon the purchase of equivalent
new equipment, or dispose of it at
designated collection points. For more
information see: www.recyclethis.info.
Contact information
For contact information, see www.utcfssecurityproducts.eu.