manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. FEDERAL PIONEER
  6. •
  7. Power Distribution Unit
  8. •
  9. FEDERAL PIONEER USD User manual

FEDERAL PIONEER USD User manual

INSTRUCTION
MANUAL
C
-
3
-
217
-
2
FEDERAL
PIONEER
OVERCURRENT
TRIP
UNIT
TYPE
USD
March
,
1982
C
-
3
-
217
-
2
INSTRUCTION
MANUAL
FEDERAL
PIONEER
LIMITED
OVERCURRENT
TRIP
UNIT
TYPE
USD
Prepared
by
:
Dated
:
Typed
by
:
Charles
Ho
March
,
1982
dm
Courtesy of NationalSwitchgear.com
(
)
4
Courtesy of NationalSwitchgear.com
INSTRUCTION
MANUAL
C
-
3
-
217
-
2
FEDERAL
PIONEER
OVERCURRENT
TRIP
UNIT
TYPE
USD
March
,
1982
TABLE
OF
CONTENTS
1
.
Introduction
1
2
.
Description
1
General
Current
Sensors
USD
Relay
Shunt
Trip
Types
of
Solid
State
Overcurrent
Trip
Units
2.1
2.2
2.3
2.4
2.5
3
.
Operation
3
3.1
General
Overcurrent
Elements
Ground
Fault
Element
The
ZSIP
Functions
Selecting
Settings
3.2
3.3
3.4
3.5
4
.
Specifications
5
Scope
Current
Sensor
Relay
Configurations
Long
Time
Element
Short
Time
Element
Instantaneous
Element
Ground
Fault
Element
Output
Trip
Pulse
Test
Signals
Relay
Impedance
(
Burden
)
Reset
Time
Performance
in
Service
4.1
4.2
4.3
1
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
5
.
Testing
10
5.1
Secondary
Injection
5.2
Primary
Injection
Maintenance
6
.
12
6.1
General
Troubleshooting
6.2
Courtesy of NationalSwitchgear.com
:
'
<
3
*
%
fc
Courtesy of NationalSwitchgear.com
INSTRUCTION
MANUAL
C
-
3
-
217
-
2
FEDERAL
PIONEER
OVERCURRENT
TRIP
UNIT
TYPE
USD
March
,
1982
LIST
OF
FIGURES
PAGE
Functional
Block
Diagram
of
USD
Relay
Faceplate
Layout
of
USD
-
3
IR
Relay
Faceplate
Layout
of
USD
-
6
IR
Relay
Characteristics
of
the
Current
Sensors
Time
Current
Characteristics
of
USD
Relay
•
•
USD
Relay
Impedance
(
Burden
)
USD
_
Relav
Jrao
^
dance
(
Burden
)
Overcurrent
Trip
System
Connections
Remote
Indication
and
ZSIP
Connections
•
•
•
Remote
Indication
and
ZSIP
Connections
•
• •
Remote
Indication
and
ZSIP
Connections
•
•
•
Test
Connections
for
Primary
Injection
Tests
15
FIGURE
1
FIGURE
2
a
FIGURE
2
b
FIGURE
3
FIGURE
4
FIGURE
5
a
FIGURE
_
5
h
_
FIGURE
6
FIGURE
7
a
FIGURE
7
b
FIGURE
7
c
FIGURE
8
16
17
18
19
20
21
22
23
24
25
26
LIST
OF
TABLES
27
Current
Sensor
Sizes
and
Ampere
Taps
•
•
Standard
USD
Overcurrent
Relay
Models
TABLE
1
TABLE
2
28
Courtesy of NationalSwitchgear.com
1
I
'
)
L
*
•
•
•
'
•
-
Courtesy of NationalSwitchgear.com
INSTRUCTION
MANUAL
C
-
3
-
217
-
2
FEDERAL
PIONEER
OVERCURRENT
TRIP
UNIT
TYPE
USD
March
,
1982
INTRODUCTION
1
.
This
Instruction
Manual
contains
descriptive
operating
,
testing
and
maintenance
information
for
Federal
Pioneer
Limited
Solid
State
Overcurrent
Trip
Unit
,
Type
USD
for
protection
of
low
voltage
power
systems
.
2
.
DESCRIPTION
2.1
General
The
Solid
State
Over
current
Trip
System
Type
USD
protects
low
voltage
power
systems
against
damage
caused
by
overloads
and
faults
.
The
types
of
protection
offered
are
overload
,
short
circuit
and
ground
fault
.
Zone
Selective
Instantaneous
Protection
(
ZSIP
)
is
also
available
for
short
circuits
and
ground
faults
.
The
trip
unit
operates
to
open
a
low
voltage
circuit
breaker
in
accordance
with
a
set
of
programmable
time
-
current
characteristics
.
Tripping
energy
for
the
operation
of
the
circuit
breaker
is
obtained
solely
from
the
circuit
being
protected
.
Fault
indication
requires
the
use
of
control
power
.
The
components
used
for
the
measurement
of
primary
current
,
for
the
detection
of
fault
conditions
and
for
the
provision
for
trip
energy
are
semiconductors
,
capacitors
,
transformers
,
etc
.
Thus
,
except
for
the
shunt
trip
,
and
the
mechanical
relay
contacts
for
remote
fault
indication
,
the
trip
is
completely
static
.
All
parts
of
this
system
are
designed
for
conservative
loading
of
components
for
long
life
and
minimum
maintenance
.
The
extensive
use
of
digital
and
analog
integrated
circuits
make
this
trip
system
more
accurate
,
versatile
,
compact
and
reliable
than
electromagnetic
trip
divices
.
The
complete
solid
state
overcurrent
trip
system
consists
of
the
following
parts
:
a
)
the
primary
current
sensors
,
b
)
the
overcurrent
relay
,
and
c
)
the
direct
acting
shunt
trip
solenoid
.
2.2
Current
Sensors
The
current
sensors
interface
the
USD
relay
with
the
power
system
.
The
core
of
the
current
sensors
is
tape
wound
with
grain
oriented
silicon
steel
.
Three
current
sensors
for
monitoring
the
three
phase
currents
are
mounted
on
the
primary
conductors
.
The
extra
sensor
required
when
ground
fault
protection
is
provided
is
mounted
on
the
neutral
conductor
,
or
on
the
ground
strap
.
The
sensors
selected
for
a
specific
circuit
breaker
establish
the
rating
of
that
breaker
.
Each
sensor
provides
a
choice
of
at
least
two
current
ratings
.
1
Courtesy of NationalSwitchgear.com
C
-
3
-
217
-
2
INSTRUCTION
MANUAL
E
e
o
e
n
A
L
•
:
PIONEER
OVERCURRENT
TRIP
UNIT
TYPE
USD
March
,
1982
2.3
USD
Relay
The
USD
Relay
receives
information
on
the
primary
current
from
the
current
sensors
,
senses
overloads
and
faults
and
determines
when
to
initiate
tripping
in
accordance
with
independent
programmable
time
current
characteristics
.
The
power
required
to
activate
the
direct
acting
shunt
trip
solenoid
is
obtained
from
the
current
sensors
.
After
a
fault
condition
has
been
determined
,
the
relay
diverts
the
output
of
the
phase
current
sensors
,
or
the
output
of
the
neutral
sensor
from
the
monitoring
circuitry
into
an
energy
accumulating
circuit
which
generates
a
trip
pulse
.
A
single
metal
enclosure
houses
the
current
matching
transformers
,
the
power
supply
,
the
programmable
logic
,
the
programming
switches
and
the
output
trip
pulse
generator
.
The
ZSIP
system
and
optional
fault
indication
circuits
are
also
housed
in
the
same
enclosure
.
Interconnection
of
the
USD
relay
with
the
primary
current
sensors
and
the
shunt
trip
solenoid
is
accomplished
through
a
labelled
terminal
block
mounted
on
the
faceplate
of
the
relay
.
Connections
for
control
power
local
indication
,
remote
indication
and
the
ZSIP
is
accomplished
by
means
of
a
colour
coded
wiring
harness
.
The
wiring
harness
is
attached
to
a
10
pin
connector
that
plugs
and
locks
into
the
side
of
the
relay
enclosure
.
2.4
Shunt
Trip
The
shunt
trip
device
is
a
cylindrical
solenoid
which
is
mounted
in
the
circuit
breaker
in
such
a
way
that
the
plunger
is
held
in
the
reset
position
by
gravity
.
When
the
USD
relay
supplies
the
solenoid
with
a
trip
pulse
,
the
plunger
is
allowed
a
specified
distance
of
free
travel
before
striking
the
trip
lever
of
the
circuit
breaker
.
2.5
Types
of
Solid
State
Overcurrent
Trip
Units
Two
basic
types
of
Solid
State
Overcurrent
Trip
Units
are
available
.
Both
types
use
the
current
sensors
,
the
appropriate
USD
relay
and
the
shunt
trip
solenoid
.
The
first
type
provides
only
overcurrent
protection
;
being
equipped
with
instantaneous
,
short
time
and
long
time
elements
.
The
second
type
,
in
addition
to
these
functions
,
also
provides
ground
fault
protection
and
zone
selective
interlocking
protection
(
ZSIP
)
for
the
short
time
and
ground
fault
elements
.
4
The
first
type
of
trip
unit
utilizes
the
USD
-
3
solid
state
relay
.
The
second
type
utilizes
the
USD
-
6
solid
state
relay
.
This
relay
is
available
with
six
different
sets
of
pick
up
settings
for
the
ground
fault
element
.
Both
USD
-
3
and
USD
-
6
relays
are
available
with
optional
fault
indication
packages
.
2
Courtesy of NationalSwitchgear.com
INSTRUCTION
MANUAL
C
-
3
-
217
-
2
FEDERAL
PIONEER
f
OVERCURRENT
TRIP
UNIT
TYPE
USD
March
,
1982
3
.
OPERATION
3.1
General
The
functional
block
diagram
of
Figure
1
attached
,
illustrates
the
operation
of
the
USD
relay
.
Appropriate
blocks
are
eliminated
for
models
not
providing
ground
fault
protection
and
ZSIP
.
There
are
three
current
sensors
on
the
circuit
breaker
monitoring
the
primary
phase
current
.
If
ground
fault
protection
is
required
on
3
phase
4
wire
power
systems
,
a
fourth
sensor
must
be
used
.
The
current
sensors
supply
currents
to
the
relay
which
are
proportional
to
the
currents
in
the
primary
circuit
.
These
currents
are
converted
to
d
.
c
.
signals
by
means
of
a
set
of
residually
connected
auxiliary
transformers
and
a
set
of
rectifiers
.
These
signals
are
used
to
provide
energy
for
tripping
,
regulated
logic
power
supply
voltage
and
signals
proportional
to
the
gorund
and
phase
currents
.
The
relay
may
have
up
to
four
pickup
elements
;
INSTANTANEOUS
,
SHORT
TIME
,
LONG
TIME
and
GROUND
FAULT
.
Each
pickup
circuit
works
independently
of
the
other
and
triggers
its
corresponding
time
delay
circuit
.
The
instantaneous
element
has
no
intentional
time
delay
.
3.2
Overcurrent
Elements
Overload
and
short
circuit
protection
are
provided
jointly
by
the
LONG
TIME
,
SHORT
TIME
,
and
INSTANTANEOUS
elements
.
The
signal
in
the
relay
which
is
proportional
to
the
highest
of
the
three
phase
primary
current
is
compared
to
preset
values
in
each
of
the
three
elements
.
If
it
does
not
exceed
any
of
the
preset
pickup
levels
,
the
relay
continues
to
monitor
the
system
.
If
the
current
signals
exceed
a
preset
pickup
setting
,
the
respective
time
delay
circuit
will
start
timing
.
When
the
proper
time
delay
is
reached
,
the
relay
transfers
itself
into
a
fault
mode
.
The
output
from
the
phase
sensors
is
diverted
totally
into
the
energy
accumulating
circuit
.
When
enough
energy
has
been
accumulated
,
a
trip
pulse
is
supplied
to
the
shunt
trip
solenoid
.
The
LONG
TIME
element
has
the
inverse
(
I
2
t
=
constant
)
bands
.
The
SHORT
TIME
element
has
four
definite
time
bands
which
become
slightly
inverse
at
low
fault
levels
and
an
inverse
(
I
2
t
=
constant
)
band
.
The
LONG
TIME
element
has
ten
inverse
(
Inconstant
)
bands
.
The
INSTANTANEOUS
element
has
no
intentional
time
delay
other
than
that
needed
by
the
relay
to
initialize
itself
and
accumulate
trip
energy
.
All
I
2
t
functions
are
dynamic
in
behaviour
and
are
continuously
adjusting
the
time
rate
to
the
existing
maximum
phase
current
during
the
timing
operation
.
3.3
Ground
Fault
Element
The
input
signal
for
the
GROUND
FAULT
element
is
obtained
from
the
residually
connected
auxiliary
transformers
in
the
relay
.
This
allows
ground
current
detection
in
both
3
phase
3
wire
and
4
wire
systems
.
If
the
ground
current
signal
exceed
the
preset
pickup
value
,
the
ground
fault
time
delay
circuit
starts
timing
.
On
reaching
the
preset
time
delay
,
the
output
trip
circuit
is
activated
.
3
Courtesy of NationalSwitchgear.com
C
-
3
-
217
-
2
INSTRUCTION
MANUAL
FEDERAL
PIONEER
OVERCURRENT
TRIP
UNIT
TYPE
USD
March
,
1982
The
signal
output
representing
the
ground
current
is
diverted
into
the
energy
accumulating
circuit
and
ultimately
discharged
into
the
shunt
trip
solenoid
.
When
the
indication
is
provided
,
a
trip
caused
by
a
ground
fault
is
normally
registered
by
the
G
.
F
.
remotely
.
It
should
be
noted
,
however
,
that
since
ground
fault
current
is
also
phase
current
and
may
therefore
be
over
current
,
the
overcurrent
element
indicators
may
also
register
the
fault
.
The
ground
fault
element
has
5
time
bands
which
are
slightly
inverse
at
low
ground
fault
levels
,
because
of
the
time
needed
to
accumulate
trip
energy
,
and
become
definite
at
high
ground
fault
levels
.
indication
LED
,
locally
,
and
by
the
G
.
F
.
normally
open
contacts
,
3.4
The
ZSIP
Functions
Selectivity
between
the
main
breaker
and
feeder
breakers
is
conventionally
obtained
by
using
time
coordinated
trip
devices
.
The
time
delay
of
the
trip
device
furthest
downstream
is
set
to
minimum
and
it
increases
from
one
zone
to
the
next
with
the
main
breaker
'
s
trip
device
having
the
highest
time
delay
setting
.
The
disadvantage
of
this
method
is
that
as
the
fault
levels
increase
for
zones
closer
to
the
main
breaker
,
the
time
to
clear
faults
in
these
zones
increases
,
and
the
power
system
must
endure
the
high
current
fault
until
the
time
delay
expires
.
With
the
trip
devices
in
the
ZSIP
mode
,
the
trip
device
that
senses
a
fault
in
its
zone
proceeds
to
trip
immediately
.
It
also
sends
a
restraint
signal
to
the
upstream
trip
devices
and
causes
them
to
revert
to
their
time
coordinated
protection
mode
.
Therefore
instantaneous
protection
against
faults
is
provided
in
all
zones
.
In
the
USD
relay
,
the
ZSIP
is
available
on
the
SHORT
TIME
element
and
the
GROUND
FAULT
element
and
the
operation
is
based
on
the
above
concepts
.
The
transmission
of
the
SHORT
TIME
restraint
and
ground
fault
restraint
signals
is
achieved
via
one
pair
of
signal
wires
.
This
minimizes
the
number
of
auxiliary
terminals
on
the
breaker
and
the
number
of
wires
needed
for
this
purpose
.
To
achieve
transmission
of
two
singals
over
the
same
set
of
wires
,
the
USD
relay
is
equipped
with
an
encoder
which
conditions
the
outgoing
restraint
signals
and
a
decoder
to
separate
the
incoming
restraint
signals
and
restrain
the
appropriate
elements
.
3.5
Selecting
Settings
The
USD
relay
has
a
number
of
thumbwheel
switches
that
enable
the
user
to
program
the
desired
time
current
protection
profile
in
the
field
,
see
Figure
2
attached
.
The
thumbwheel
switches
are
accessible
on
the
front
panel
of
the
relay
through
a
cutout
in
the
faceplate
.
Each
switch
is
actuated
by
a
knurled
thumbwheel
and
the
selected
position
is
indicated
by
a
number
ranging
from
0
to
9
,
appearing
on
the
thumbwheel
.
The
correlation
between
the
dial
number
appearing
on
each
switch
and
the
pickup
level
or
time
delay
is
shown
on
a
table
adjacent
to
each
switch
.
The
contact
surfaces
of
these
switches
are
gold
plated
to
assure
long
lasting
and
positive
electrical
contact
.
Should
any
switch
contact
of
any
element
become
4
Courtesy of NationalSwitchgear.com
INSTRUCTION
MANUAL
C
-
3
-
217
-
2
FEDERAL
f
'
PIONEER
OVERCURRENT
TRIP
UNIT
TYPE
USD
March
,
1982
open
,
the
relay
will
automatically
operate
on
the
highest
setting
of
that
element
as
a
backup
protection
.
All
pickup
and
timing
functions
are
independent
of
each
other
.
The
selection
of
settings
are
therefore
governed
by
system
design
considerations
.
Relays
incorporating
the
ZSIP
function
are
equipped
with
a
screw
driver
actuated
,
3
position
,
rotary
switch
.
This
switch
,
available
on
the
faceplate
of
the
unit
,
enables
the
user
to
program
the
desired
mode
of
operation
.
The
first
position
of
the
switch
,
marked
ZSIP
means
that
both
short
time
and
ground
fault
elements
are
restrained
by
downstream
relays
to
prevent
instantaneous
operation
on
a
downstream
fault
.
The
second
position
,
marked
G
.
F
.
ZSIP
,
ST
,
TCP
(
Time
Coordinated
Protection
)
means
that
there
is
ZSIP
on
the
ground
fault
element
only
and
the
short
time
element
is
self
-
restrained
.
The
third
position
marked
TCP
means
that
both
ground
fault
and
short
time
elements
are
self
-
restrained
.
It
should
be
noted
that
the
position
of
this
switch
has
no
influence
on
the
restraint
out
signal
of
the
relay
.
This
feature
is
useful
when
the
last
relay
downstream
has
to
be
in
the
TCP
mode
while
upstream
relays
are
in
the
ZSIP
mode
.
4
.
SPECIFICATIONS
4.1
Scope
The
specifications
cover
the
USD
Solid
State
Overcurrent
Trip
System
for
use
on
the
Federal
Pioneer
Ltd
.
low
voltage
power
air
circuit
breakers
.
The
trip
unit
complies
with
the
American
National
Standard
for
trip
devices
for
a
.
c
.
low
voltage
circuit
breakers
(
ANSI
C
37.17
-
1972
)
.
4.2
Current
Sensor
Ratings
4.2
.
1
-
100
%
continuous
current
settings
are
available
at
;
3000
A
3200
A
4000
A
5000
A
6000
A
50
A
600
A
800
A
1000
A
1200
A
1600
A
2000
A
70
^
100
A
150
A
250
A
400
A
D
Courtesy of NationalSwitchgear.com
RDCTION
MANUAL
C
-
3
-
217
-
2
;
•
i
i
?
v
iCURRENT
TRIP
UNIT
TYPE
USD
1
‘
t
>
;
>
•
.
•
*
.
*
•
rvr
March
,
1982
»
•
>
.
v
.
y
V
\
}
V
••
•
*
•
*
•
v
:
sensors
available
along
with
the
taps
of
each
sensor
and
i
sizes
with
which
these
current
sensors
:
V
'
V
can
be
used
®
11
*
6
r
:
;
-
tion
characteristics
of
the
sensors
and
their
secondary
d
.
c
.
igure
3
attached
.
ations
V
X
\
y
:
i
t
y
.
H
.
*
.
options
available
with
each
model
are
detailed
in
Table
2
L
•
*
lement
0.6
X
,
0.7
X
,
0.8
X
,
0.9
X
,
1.0
X
,
1.1
X
the
up
settings
available
:
;
up
tolerance
:
+
8
%
based
on
symmetrical
sinusoidal
current
at
me
Delay
Bands
:
10
calibrated
bands
are
provided
ranging
from
l
2
t
=
72
seconds
to
I
^
t
=
1.080
seconds
(
I
in
per
unit
)
rime
delays
of
2
,
4
,
6
,
8
,
10
,
14
,
16
,
22
,
26
and
30
seconds
at
600
%
al
current
50
/
60
Hz
.
Time
Delay
Tolerance
:
+
10
%
based
on
symmetrical
sinusoidal
current
>
rt
Time
Element
Pickup
settings
available
:
2
X
,
3
X
,
4
X
,
6
X
,
8
X
,
and
10
X
the
sensor
1
-
Pickup
tolerance
:
+
8
%
based
on
symmetrical
sinusoidal
current
at
i
.
2
-
L
.
V
iSilSIii
fsglsf
1.5
.
3
-
Time
Delay
Bands
:
Four
definite
time
bands
with
nominal
time
;
of
0.11
second
,
0.25
second
,
0.33
second
,
0.45
second
and
an
inverse
band
I
2
t
8
second
(
I
in
per
unit
)
with
time
delay
of
0.55
seconds
at
600
%
rated
oidal
current
,
50
/
60
Hz
.
4.5
.
4
-
Time
Delay
tolerance
:
+
10
%
based
on
symmetrical
sinusoidal
current
i
0
/
60
Hz
.
4
*
.
/
,
•
v
-
The
SHORT
TIME
delay
in
the
ZSIP
mode
with
no
restraint
is
jproximately
50
m
seconds
regardless
of
the
SHORT
TIME
delay
setting
.
4.5
.
5
6
V
Courtesy of NationalSwitchgear.com
INSTRUCTION
MANUAL
C
-
3
-
217
-
2
FEDERAL
PIONEER
OVERCURRENT
TRIP
UNIT
TYPE
USD
March
,
1982
4.6
Instantaneous
Element
4.6
.
1
-
Pickup
settings
available
:
4
X
,
5
X
6
X
,
8
X
,
10
X
and
12
X
the
sensor
tap
setting
.
4.6
.
2
-
Tolerance
:
+
8
%
based
on
symmetrical
sinusoidal
current
at
50
/
60
Hz
.
4.6
.
3
-
The
pickup
switch
has
an
"
OFF
"
position
.
Vvhen
this
setting
is
selected
,
the
instantaneous
element
will
not
pickup
unless
the
breaker
closes
on
a
fault
that
exceeds
13
X
the
sensor
tap
setting
,
in
which
case
a
discriminator
will
initiate
tripping
.
The
discriminator
circuit
shall
activate
the
trip
pulse
generator
of
the
relay
instantaneously
provided
one
of
the
following
conditions
exists
;
a
)
The
breaker
closes
on
a
fault
of
13
X
the
sensor
setting
or
greater
and
,
b
)
A
fault
of
13
X
the
sensor
tap
setting
or
greater
occurs
while
the
breaker
is
supplying
a
load
of
less
than
0.04
X
the
sensor
tap
setting
.
If
the
breaker
closes
and
the
current
is
greater
than
0.04
X
,
but
less
than
13
X
the
sensor
tap
setting
,
the
discriminator
monitors
the
current
for
40
milliseconds
and
if
the
fault
level
of
13
X
is
not
exceeded
during
this
time
,
the
discriminator
shall
switch
itself
off
.
4.6
.
4
-
The
operating
time
of
the
relay
for
fully
offset
single
phase
faults
at
the
interrupting
capacity
of
the
circuit
breaker
with
X
/
R
6.6
,
is
33
m
seconds
.
This
operating
time
represents
the
time
taken
by
the
relay
to
energize
itself
,
sense
the
fault
,
activate
its
trip
energy
accumulating
circuit
and
transmit
the
trip
pulse
to
the
shunt
trip
solenoid
.
4.7
Ground
Fault
Element
4.7
.
1
-
Four
pickup
ranges
are
available
which
enable
the
user
to
compose
a
trip
unit
with
the
current
sensors
CSD
-
1.5
,
CSD
-
6
,
CSD
-
8
,
CSD
-
16
,
CSD
-
20
,
CUD
-
30
,
CUD
-
32
and
CUD
-
40
,
that
will
meet
the
1200
A
maximum
pickup
requirement
of
service
protection
equipment
.
The
table
below
groups
the
current
sensors
with
the
appropriate
pickup
settings
;
7
Courtesy of NationalSwitchgear.com
INSTRUCTION
MANUAL
C
-
3
-
217
-
2
FEDERAL
PIONEER
OVERCURRENT
TRIP
UNIT
TYPE
USD
March
,
1982
Pickup
Settings
(
Multiple
of
Sensor
Tap
)
Sensor
Type
CSD
-
1.5
CSD
-
6
CDS
-
16
0.2
,
0.3
,
0.4
,
0.5
,
0.6
,
0.7
0.2
,
0.25
,
0.3
,
0.4
,
0.5
,
0.6
CSD
-
20
CUD
-
30
CUD
-
32
0.2
,
0.22
,
0.24
,
0.28
,
0.32
,
0.36
CUD
-
40
CUD
-
60
0.2
,
0.22
,
0.24
,
0.26
,
0.28
,
0.30
4.7
.
2
-
Tolerance
:
+
8
%
based
on
symmetrical
sinusoidal
current
at
50
/
60
Hz
.
4.7
.
3
-
Time
Delay
Bands
:
5
calibrated
bands
are
provided
that
are
slightly
inverse
at
low
fault
levels
and
become
definite
at
fault
levels
exceeding
500
%
rated
current
.
The
definite
time
delays
provided
are
0.08
,
0.14
,
0.20
,
0.26
,
and
0.32
seconds
.
In
the
inverse
region
these
become
0.17
,
0.23
,
0.29
,
0.35
,
0.40
seconds
with
100
%
rated
current
.
Time
Delay
tolerance
:
+
10
%
based
on
symmetrical
sinusoidal
4.7
.
4
current
at
50
/
60
Hz
.
In
the
ZSIP
mode
with
no
restraint
,
the
ground
fault
element
initiates
tripping
approximately
20
m
seconds
after
pickup
occurs
.
The
time
current
characteristics
in
Figure
4
attached
should
be
consulted
for
the
operating
time
of
the
relay
under
currents
other
than
those
specified
here
.
4.7
.
5
8
Courtesy of NationalSwitchgear.com
INSTRUCTION
MANUAL
C
-
3
-
217
-
2
FEDERAL
PIONEER
OVERCURRENT
TRIP
UNI
T
TYPE
USD
March
,
1982
4.8
Output
Trip
Pulse
The
USD
relay
provides
a
trip
pulse
output
with
a
minimum
energy
of
0.98
joules
.
This
pulse
has
an
initial
voltage
of
140
V
and
its
rate
of
decay
depends
on
the
impedance
of
the
shunt
trip
solenoid
.
This
energy
is
approximately
that
stored
in
a
100
F
capacitor
charged
to
140
V
d
.
c
.
4.9
Test
Signals
A
test
plug
is
mounted
on
the
faceplate
of
the
relay
to
provide
access
to
appropriate
signals
so
that
the
operation
of
the
relay
can
be
checked
by
means
of
a
Test
Set
or
other
metering
devices
.
The
signals
available
on
the
test
plug
are
;
PIN
#
SIGNAL
Test
Set
input
signal
t
!
1
2
3
4
Instantaneous
pickup
/
inhibit
Short
time
pickup
/
inhibit
Long
time
pickup
/
inhibit
Ground
fault
pickup
/
inhibit
Overcurrent
trip
inhibit
Logie
common
Ground
fault
trip
signal
(
delay
)
Overcurrent
trip
signal
(
delay
)
5
6
7
8
9
10
11
12
4.10
Relay
Impedance
(
Burden
)
The
impedance
of
the
overcurrent
elements
and
ground
fault
element
seen
by
the
secondary
of
the
current
sensors
at
different
current
levels
are
shown
in
Figures
5
a
and
5
b
attached
.
4.11
Reset
Time
If
a
fault
condition
disappears
and
the
current
magnitude
drops
to
95
%
of
the
pickup
level
of
any
element
,
the
relay
resets
in
approximately
30
m
seconds
.
If
the
breaker
trips
,
the
signals
to
the
relay
disappear
and
the
relay
resets
automatically
.
The
fault
indicators
,
if
used
,
must
be
reset
manually
with
the
pushbutton
on
the
relay
faceplate
.
9
Courtesy of NationalSwitchgear.com
INSTRUCTION
MANUAL
C
-
3
-
217
-
2
FEDERAL
PIONEER
OVERCURRENT
TRIP
UNIT
TYPE
USD
March
,
1982
Under
arcing
ground
fault
conditions
,
the
ground
fault
element
of
the
USD
operates
to
carry
through
the
missing
cycles
or
half
cycles
in
the
definite
time
region
and
trip
.
In
the
inverse
region
where
energy
accumulation
contributes
considerably
to
the
delay
,
the
arcing
ground
fault
is
integrated
with
time
and
a
trip
is
generated
as
soon
as
trip
energy
has
been
accumulated
.
4.12
Performance
in
Service
The
circuits
in
the
USD
relay
are
stable
and
show
excellent
repeatability
over
long
periods
of
time
.
Service
involving
frequent
operations
will
not
cause
the
characteristics
to
change
or
drift
,
since
there
are
no
mechanical
moving
parts
to
wear
.
The
USD
relay
is
compensated
for
variations
in
ambient
temperature
over
the
range
-
20
°
C
to
+
55
°
C
.
The
tolerance
over
this
temperature
range
is
+
8
%
on
the
pickup
and
+
10
%
on
the
time
delay
of
all
the
elements
.
Operation
outside
this
temperature
range
is
possible
,
factory
for
further
information
,
specifying
the
required
temperature
range
.
Consult
the
TESTING
5
.
5.1
Secondary
Injection
Testing
of
the
overcurrent
trip
system
with
secondary
injection
is
easily
accomplished
,
under
field
conditions
,
with
the
Federal
Pioneer
portable
Test
Set
Type
DDT
-
USD
.
The
test
can
be
done
on
a
complete
breaker
assembly
located
in
the
disconnect
position
in
the
cubicle
,
on
the
complete
breaker
on
a
work
bench
,
or
on
a
static
trip
device
completely
removed
from
the
breaker
.
It
is
not
necessary
,
however
,
to
remove
any
wiring
in
order
to
do
any
of
these
tests
.
The
type
DDT
-
USD
test
unit
permits
checking
pickup
and
timing
functions
as
well
as
the
operation
of
the
shunt
trip
solenoid
.
The
type
DDT
-
USD
test
unit
can
,
in
addition
,
check
the
functions
of
the
trip
unit
with
the
circuit
breaker
in
service
.
The
Instruction
Manual
C
-
3
-
217
-
4
of
the
test
unit
should
be
consulted
.
5.2
Primary
Injection
5.2
.
1
If
it
is
desired
to
check
the
current
sensor
operation
it
will
be
necessary
to
test
the
breaker
by
primary
current
injection
methods
.
This
involves
connecting
the
power
poles
of
the
breaker
to
a
controlled
source
of
current
.
The
advantage
of
this
system
is
that
the
entire
sensor
-
relay
-
trip
coil
system
operation
is
verified
.
The
disadvantage
is
that
suitable
equipment
required
for
such
testing
is
heavy
,
extensive
and
difficult
to
use
.
10
Courtesy of NationalSwitchgear.com
INSTRUCTION
MANUAL
C
-
3
-
217
-
2
FEDERAL
PIONEER
OVERCURRENT
TRIP
UNIT
TYPE
USD
March
,
1982
5.2
.
2
The
test
equipment
for
single
phase
tests
should
provide
50
/
60
Hz
.
sinuisoidal
current
to
the
breaker
power
pole
terminals
.
The
connectors
to
double
-
stab
poles
(
on
higher
current
breakers
)
should
be
arranged
to
divide
the
current
between
the
two
stabs
equally
.
If
complete
testing
of
all
pickup
positions
of
the
USD
is
desired
the
test
equipment
should
be
capable
of
1200
%
of
the
breaker
current
rating
for
at
least
.
04
seconds
and
600
%
of
the
current
rating
for
30
seconds
.
For
minimum
testing
the
test
equipment
should
be
capable
of
600
%
current
rating
for
at
least
2
seconds
.
This
will
enable
testing
on
all
elements
to
be
performed
on
the
lowest
settings
for
INSTANTANEOUS
PICKUP
,
SHORT
TIME
PICKUP
and
LONG
TIME
DELAY
elements
.
5.2
.
3
The
test
equipment
should
include
a
timer
which
starts
when
the
current
is
switched
on
and
stops
when
the
current
is
switched
off
(
breaker
trips
)
.
It
should
be
capable
of
measuring
time
intervals
from
.
01
seconds
to
2000
seconds
accurately
.
5.2
.
4
The
open
circuit
voltage
of
the
current
souce
must
be
at
least
10
volts
when
set
at
the
test
current
.
5.2
.
5
Test
connections
to
the
breaker
should
be
as
short
as
possible
,
otherwise
,
current
capability
will
be
limited
and
only
minimum
testing
achieved
.
5.2
.
6
Before
attempting
testing
the
USD
relay
,
the
element
and
setting
to
be
tested
must
be
decided
.
To
ensure
that
other
elements
do
not
interfere
with
the
test
it
will
be
necessary
to
set
pickup
and
/
or
delay
settings
higher
than
those
under
test
.
5.2
.
7
For
USD
-
6
types
mounted
in
drawout
breakers
removed
from
the
cubicle
it
will
be
necessary
to
connect
a
test
jumper
to
complete
the
secondary
circuit
between
the
sensors
and
the
USD
relay
terminals
since
the
current
is
normally
completed
by
a
permanent
jumper
or
external
sensor
,
depending
on
the
type
of
system
being
used
.
The
jumper
may
be
connected
to
the
contacts
of
the
rear
mounted
terminal
blocks
as
shown
in
Figure
8
.
The
actual
terminals
used
varies
from
one
breaker
to
another
,
the
requiring
use
of
the
appropriate
breaker
wiring
diagram
to
determine
actual
location
.
5.2
.
9
For
overcurrent
tests
(
not
ground
fault
)
jumper
A
only
must
be
installed
.
For
ground
fault
tests
jumper
B
only
must
be
installed
.
5.2
.
8
5.2
.
10
Alternatively
,
the
connections
may
be
made
directly
from
the
common
terminal
of
the
sensors
to
either
the
N
or
G
terminal
of
the
relay
for
overcurrent
or
ground
fault
tests
respectively
.
5.2
.
11
It
is
necessary
to
provide
120
VAC
,
2.5
VA
control
power
if
it
is
desired
to
check
indication
lamps
or
remote
outputs
.
11
Courtesy of NationalSwitchgear.com
INSTRUCTION
MANUAL
C
-
3
-
217
-
2
FEDERAL
PIONEER
OVERCURRENT
TRIP
UNIT
TYPE
USD
March
,
1982
5.2
.
12
To
check
ZSIP
functions
it
will
be
necessary
to
connect
a
RESTRAINT
signal
to
obtain
time
delay
operation
of
GROUND
FAULT
and
SHORT
TIME
elements
(
otherwise
trip
will
be
instantaneous
)
.
This
can
be
achieved
by
using
a
SELF
RESTRAINT
method
whereby
a
test
jumper
is
connected
between
RESTRAINT
OUT
and
RESTRAINT
IN
terminals
(
on
the
side
mounted
10
pin
plug
)
.
A
switch
may
be
wired
for
convenient
control
as
shown
in
Figure
8
.
5.2
.
13
For
USD
-
6
types
used
with
fixed
breakers
,
a
direct
connection
between
the
sensor
common
and
either
the
N
or
G
terminals
of
the
USD
will
allow
testing
of
overcurrent
or
ground
fault
respectively
.
5.2
.
14
After
each
test
in
which
the
breaker
has
tripped
,
it
must
again
be
charged
and
closed
before
proceeding
with
the
next
test
.
5.2
.
15
After
the
conclusion
of
the
tests
the
relay
settings
must
be
restored
to
their
original
values
.
The
jumper
,
if
any
,
should
be
removed
from
the
auxiliary
contacts
.
The
arcing
and
main
and
main
contacts
of
the
breaker
must
be
inspected
and
serviced
as
required
by
the
breaker
Manual
C
-
3
-
233
.
5.2
.
16
Care
should
be
taken
when
using
magnetic
pickup
devices
for
measuring
current
(
eg
.
clip
-
on
ammeters
,
current
sensors
etc
)
to
ensure
that
the
readings
are
not
being
influenced
by
the
strong
magnetic
field
from
high
-
current
carrying
conductors
.
5.2
.
17
Since
the
published
characteristics
are
defined
for
ideal
testing
arrangements
,
additional
tolerances
may
be
required
to
allow
for
field
conditions
(
eg
.
wareforms
may
not
be
sinusoidal
)
.
The
trip
time
of
the
breaker
should
also
be
added
to
time
delay
measurements
(
approximately
half
a
cycle
)
when
performing
primary
current
injection
tests
.
CAUTION
Since
much
of
the
testing
involves
currents
considerably
higher
than
the
continuous
ratings
of
the
breaker
and
the
trip
device
,
care
should
be
exercised
in
not
overheating
it
.
Sufficient
cooling
time
must
be
allowed
between
tests
.
6
.
MAINTENANCE
6
J
General
Each
Solid
State
Overcurrent
Relay
is
tested
and
calibrated
before
shipment
.
It
is
ready
for
use
after
it
has
been
interconnected
with
the
rest
of
the
components
of
the
trip
unit
and
the
appropriate
settings
have
been
selected
.
The
only
maintenance
recommended
is
the
periodic
verification
that
the
relay
is
functioning
.
This
may
be
supplemented
as
desired
by
checking
the
calibration
and
inspection
for
loose
or
broken
external
wiring
.
12
Courtesy of NationalSwitchgear.com
INSTRUCTION
MANUAL
C
-
3
-
217
-
2
FEDERAL
PIONEER
OVERCURRENT
TRIP
UNIT
TYPE
USD
March
,
1982
6.2
Troubleshooting
6.2
.
1
-
Failure
to
Trip
:
Failure
of
the
circuit
breaker
to
trip
in
response
to
a
fault
may
be
caused
by
any
of
the
reasons
listed
below
.
Corrective
action
is
indicated
with
the
reason
for
failure
to
trip
.
(
a
)
Relay
set
too
high
-
check
that
the
pickup
settings
on
the
relay
are
correct
and
that
the
correct
sensor
tap
is
used
,
(
b
)
Sensors
improperly
connected
-
check
that
all
connections
are
tight
,
wiring
is
correct
and
leads
not
broken
.
Any
current
sensor
with
open
-
circuited
secondary
must
be
replaced
.
(
c
)
Shunt
trip
solenoid
open
-
circuited
-
check
that
the
wiring
to
the
trip
solenoid
is
not
broken
.
The
d
.
c
.
resistance
of
the
coil
should
be
approximately
30
ohms
.
6.2
.
2
-
Failure
to
Close
;
Failure
of
the
circuit
breaker
to
close
and
latch
mechanically
may
be
due
to
the
reasons
listed
below
.
Corrective
action
is
as
indicated
.
(
a
)
The
shunt
trip
solenoid
-
check
to
ensure
that
the
plunger
of
the
shunt
trip
solenoid
is
not
inhibited
from
resetting
.
Refer
to
the
circuit
breaker
instruction
manual
for
mechanical
mounting
details
.
(
b
)
Ensure
that
an
overload
or
short
circuit
does
not
exist
in
the
load
circuit
.
(
c
)
Check
that
there
is
no
ground
current
exceeding
the
pickup
setting
.
Check
sensor
taps
to
ensure
that
the
setting
is
properly
selected
for
the
required
load
.
Check
sensor
wiring
and
mounting
for
marked
polarity
.
A
reverse
connected
current
sensor
generates
a
high
residual
current
which
causes
the
Ground
Fault
element
of
the
relay
to
trip
the
breaker
.
Check
that
pickup
and
delay
settings
are
such
as
to
override
certain
predictable
short
term
overloads
,
such
as
;
motor
starting
,
spot
welding
,
induction
oven
feeds
,
etc
.
Nonsinusoidal
current
may
cause
premature
tripping
since
the
solid
state
relay
incorporated
peak
responding
circuits
for
pickup
.
(
d
)
(
e
)
(
f
)
If
none
of
the
above
helps
,
the
USD
relay
must
be
tested
with
a
DDT
-
USD
test
unit
,
if
one
is
available
.
It
may
then
be
decided
that
the
relay
must
be
returned
to
Federal
Pioneer
for
repairs
.
In
such
a
case
it
will
be
a
great
help
to
the
Service
Department
if
the
source
of
complaint
is
documented
and
reported
as
accurately
as
possible
.
The
element
which
fails
to
function
properly
along
with
the
13
Courtesy of NationalSwitchgear.com
INSTRUCTION
MANUAL
C
-
3
-
217
-
2
•
u
FEDERAL
PIONEER
OVERCURRENT
TRIP
UNIT
TYPE
USD
•
ft
*
March
,
1982
Also
,
the
condition
under
which
improper
etting
or
settings
must
be
noted
,
iperation
was
noted
ie
.
during
initial
testing
,
during
maintenance
,
etc
.
and
the
type
jf
testing
equipment
used
.
This
will
enable
the
quick
repair
and
return
of
the
unit
.
wmm
t
*
-
85
i
-
s
A
:
%
»
•
.
i
)
14
Courtesy of NationalSwitchgear.com

Popular Power Distribution Unit manuals by other brands

bonitron M3460R Customer Reference Manual

bonitron

bonitron M3460R Customer Reference Manual

Pts PTS90X3X Series installation guide

Pts

Pts PTS90X3X Series installation guide

Marway Optima 833 Series Operating Guide and Reference

Marway

Marway Optima 833 Series Operating Guide and Reference

LEGRAND RARITAN PXE Quick setup guide

LEGRAND

LEGRAND RARITAN PXE Quick setup guide

CLEAR DESIGN BLADE BPDH18-4 Detail Document

CLEAR DESIGN

CLEAR DESIGN BLADE BPDH18-4 Detail Document

Honeywell 050025.17 Mounting and Connection Instructions

Honeywell

Honeywell 050025.17 Mounting and Connection Instructions

ABB RELION RET670 Commissioning manual

ABB

ABB RELION RET670 Commissioning manual

Cristec Voltage Guard-70 manual

Cristec

Cristec Voltage Guard-70 manual

ETA Systems ETA-S20 quick guide

ETA Systems

ETA Systems ETA-S20 quick guide

GE SPM Series instruction manual

GE

GE SPM Series instruction manual

Middle Atlantic Products Premium+ RackLink RLNK-P420 user manual

Middle Atlantic Products

Middle Atlantic Products Premium+ RackLink RLNK-P420 user manual

Tripp Lite PDU3VSR6H50A Specifications

Tripp Lite

Tripp Lite PDU3VSR6H50A Specifications

Sonorous Energy Saver-ES-05 operating instructions

Sonorous

Sonorous Energy Saver-ES-05 operating instructions

WTI CPM Series quick start guide

WTI

WTI CPM Series quick start guide

MGE UPS Systems Comet EXtreme Series Startup guide

MGE UPS Systems

MGE UPS Systems Comet EXtreme Series Startup guide

Behringer POWERLIGHT PL2000 user manual

Behringer

Behringer POWERLIGHT PL2000 user manual

EnerSys alpha Matrix C16 Technical manual

EnerSys

EnerSys alpha Matrix C16 Technical manual

Nordost QBASE QB4 Mark II instruction manual

Nordost

Nordost QBASE QB4 Mark II instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.