It is important to follow all instructions shipped with this product. This device is to be
installed by a trained electrician who is thoroughly familiar with the National Electrical Code and
will follow the NEC Guidelines as well as local codes.
This device should be considered a part of the warning system and not the entire warning
system.
The selection of the mounting location for the device, its controls and the routing of the wiring
are to be accomplished under the direction of the facilities engineer and the safety engineer. In
addition, listed below are some other important safety instructions and precautions you should
follow:
• Read and understand all instructions before installing or operating this equipment.
• Never alter the unit in any manner. Safety may be compromised if additional
openings or other alterations are made to the unit.
• Do not connect this light to the system when power is on.
• After installation, ensure that the setscrew and threaded joints are properly
tightened.
• Keep unit tightly closed when in operation.
• After testing is complete; provide a copy of this instruction sheet to all operating
personnel.
• Establish a procedure to routinely chec the light installation for integrity and
proper operation.
Failure to follow all safety precautions and instructions may result in property damage,
serious injury, or death to you or others.
I. GENERAL.
The Model 224XSTHI strobe light is a Visual Signaling Device for the Hearing Impaired for
use in Hazardous Locations and provides about 80 high intensity flashes per minute. The unit is
UL Listed for indoor use on a wall or ceiling in a nonsleeping area and complies with the TYPE 4X
(watertight and corrosion resistant) and IP66 (dust-tight and protection against heavy seas)
enclosure requirements.
For the Electrical Ratings and Light Dispersion Pattern of the Model 224XSTHI, reference
Table 1 and Figure 1.
II. INSTALLATION.
A. Unpacking.
Damaged globes can lead to explosions, which could result in serious injury or death.
After unpac ing the unit, examine it for damage that may have occurred in transit. If
the equipment has been damaged, do not attempt to install or operate the unit. File a claim
immediately with the carrier, stating the extent of damage. Carefully chec all envelopes, shipping
labels and tags before removing or destroying them.
-1-

-2-
B. Mounting.
The Model 224XSTHI strobes are designed for hearing impaired applications and should
be installed per the NFPA 70 & 72, STATE and LOCAL CODES. Alternate installation locations
and/or orientations should only be performed with the approval of the authority having jurisdiction.
Reference Figure 1 for the light dispersion pattern of the 224XSTHI.
To reduce the ris of fire or explosion, do not install in a hazardous location if the
operating temperature exceeds the ignition temperature of the hazardous atmosphere.
Refer to the product nameplate for operating temperature mar ings.
The Model 224XSTHI has provisions for mounting to _” N.P.T threaded pipe. The
conduit run from the device to the splice box shall not be larger than 10 inches. Before mounting,
ensure that mating threads are clean.
C. Electrical Connections.
To avoid electrical shoc hazards, do not connect wires when power is applied.
The DC Models Operating Voltage Range Limits are 16 – 33Vdc.
This product was only tested to its rated operating voltage range. It was not tested to
80% and 110% of these limits.
The DC units are polarity sensitive, and MAY BE DAMAGED by incorrect electrical
hoo up. When connecting the DC strobe unit to the voltage supply lines, POLARITY
MUST BE OBSERVED. In addition, damage will result if the voltage operating range of
the model is exceeded.
The 224XSTHI units are provided with five leads; two red, two blac and one green/
yellow. To achieve electrical supervision, connect one red (+) lead to the positive side of the
incoming power source and the other red (+) lead to the outgoing power source. Then connect one
blac (-) lead to the negative side of the incoming power source and the other blac (-) lead to the
negative side of the outgoing power source. If required local building codes, connect the earth
ground to the grounding screw located in the mounting hood.
III. MAINTENANCE.
To prevent receiving an electrical shoc , disconnect the fixture from the supply circuit
before opening.
High voltages are present inside the light assembly. Wait at least 5 minutes after
disconnecting power before servicing this unit.

-3-
SAFETY MESSAGE TO MAINTENANCE PERSONNEL
Listed below are some important safety instructions and precautions you should follow:
• Read and understand all instructions before operating this system.
• Any maintenance to the light system must be done with the power turned off.
• Any maintenance to the light system must be performed by a trained electrician in
accordance with all applicable national and local codes in the country of use.
• Never alter the unit in any manner. Safety of the unit may be compromised if
additional openings or other alterations are made.
• The nameplate should not be obscured, it contains cautionary and/or other
information of importance to maintenance personnel. Ensure the nameplate
remains readable if the housing’s exterior is painted.
• If dome is damaged in any way, it MUST be replaced.
• After performing any maintenance, test the light system to ensure that it is
operating properly.
Failure to follow all safety precautions and instructions may result in property damage,
serious injury, or death to you or others.
A. Flash Tube Replacement.
As strobe lights are used, the flash tubes begin to dar en, causing the light output to
decrease. This dar ening is characteristic of flash tubes. The dar ening will begin near the base of
the tube and progress upward. In addition, as flash tubes age, they may have a tendency to misfire
(not fire periodically).
After extended operation, occasionally chec for flash tube degradation. Should the flash
tube misfire, have a noticeable decrease in light output, glow continuously or dar en to a point
beyond that shown in Figure 2 — it should be replaced.
High voltages are present inside the light assembly. Wait at least 5 minutes after
shutting off the power before servicing this unit.
To change the flash tube, proceed as follows:
1. Disconnect power.
2. Loosen the setscrew, located on the globe-and holder assembly.
3. Grasp the top of the dome and push down while turning the dome countercloc wise
approximately 3/4-inch (19 mm).
Effectiveness of hazardous location enclosure must be maintained. Do not damage globe
or threads while disassembling or reassembling unit. Lubricated joints exposed for long
periods of time may attract small particles of dirt or other foreign materials. Body and
cover joints should be reassembled immediately.
4. Gently lift dome away. Ensure that the gas et between the dome and base is not
lost.

-4-
5. Loosen the retaining ring fastening screws approximately 1/2-turn. The retaining
ring can then be turned countercloc wise approximately 1/2-turn. The retaining ring can then be
lifted free of the unit. The interior lens can now be removed from the unit.
6. Grasp the flash tube by its base and pull it out of the soc et, using a gentle
“roc ing” motion. Install new flash tube, ensuring that the flash tube is fully seated in the soc et.
7. Reinstall interior lens.
8. Before replacing the dome, ensure that the gas et is properly seated and shows no
signs of crac ing or other deterioration. Replace the gas et if it is damaged or shows signs of
deterioration.
9. Place the dome over the base, aligning the recesses inside the dome lip with the
four pins on the base. Push down on the dome and turn cloc wise until it loc s in place [approxi-
mately 3/4-inch (19mm)].
10. Replace the screw into the bottom of the dome.
11. Test the light for proper operation.
B. Circuit Board Replacement.
High voltages are present inside the light assembly. Wait at least 5 minutes after
shutting off the power before servicing unit.
1. Disconnect power.
2. Remove the setscrew located at the bottom of the dome.
3. Grasp the top of the dome and push down while turning the dome countercloc wise
approximately 3/4-inch (19mm).
4. Gently lift dome away. Ensure that the gas et between the dome and base is not
lost.
5. Loosen the retaining ring fastening screws approximately _ turn. The retaining
ring can then be turned countercloc wise approximately _ inch (13mm), allowing the retaining to be
lifted free of the unit. The interior lens can now be removed from the unit.
6. Remove and retain the screws and heat sin clip, which secures the power supply
circuit board to its mounting plate. Remove the power connector(s) from the P.C.B. Since some
strobes are polarity sensitive, connect matching colored wires together.
7. Secure the new circuit board to the mounting plate with the previously removed
screws and reattach heat sin clip.
8. Install flash tube as described in Section III.A. (Flash Tube Replacement). Ensure
that the flash tube is fully seated in the soc et.
9. Reinstall interior lens.
10. Before replacing the dome, ensure that the gas et is property seated and shows no
signs of crac ing or other deterioration. Replace the gas et if it is damaged or shows signs of
deterioration. Replace the gas et if it is damaged or shows signs of deterioration.
11. Place the dome over the base, aligning the recesses inside the dome lip with the
four pins on the base. Push down on the dome and turn cloc wise until it loc s in place [approxi-
mately 3.4-inch (19mm)].

-5-
12. Replace the screw into the bottom of the dome.
13. Test the light for proper operation.
C. Cleaning Enclosure.
NOTE
Maintenance procedures sometime require fixtures to be hosed down for good house-
eeping. The circuit must be turned OFF and fixture globe MUST be allowed to cool to
ambient room temperature before cleaning.
The fixture should be cleaned periodically to maintain maximum light output. Only
mild, non-abrasive cleaning agents should be used. The dome should be regularly inspected for
scratches and chips, and if damaged, must be replaced.
D. Service.
Federal Signal will service your equipment and provide technical assistance with any
problems that cannot be handled locally by Federal Signal’s Distributor or Manufacturer Represen-
tative.
If any unit returned to Federal Signal for service, inspection, or repair must be
accompanied by a Return Material Authorization number with a brief explanation of the service
being requested and/or the nature of the malfunction. This R.M.A. can be obtained from the local
Federal Signal Distributor or Manufacturer’s Representative.
Address all communications and shipments to:
Federal Signal Corporation
Electrical Products Division
Service Department
2645 Federal Signal Drive
University Par , IL 60466-3195
E. Replacement Parts.
Description Part Number
Exterior Dome, Clear 24Vdc K8444291B-15
Interior Lens, Clear K8550C095A
Flash Tube/Trigger Coil Assy. K8107177A
Gas et K8444286B
Circuit Board Assy. K2001202C-01
In-Rush Board Assy. K2001918A

-6-
Table 1
Electrical Ratings
Operational Voltage 24V dc
On-Axis Candelas 15
Flashes/minute 75
Frequency, Hz DC
Inrush Current, A 2.0
Max. DC Operating Current, A 0.75
1
Vertical Lig t Dispersion Pattern
Degrees UL Min. per UL1971
0°15.00
5-30°13.50
35°9.75
40°6.90
45°4.05
50°4.05
55°3.30
60°2.70
65°2.40
70°2.25
75°1.95
80°1.80
85°1.80
90°1.80
ON AXIS VERTICAL
0°
15°
30°
45°
60°
75°
90°
ON AXIS HORIZONTAL
0°15°30°45°
290A416
7
60°
75°75°
90°90°
60°
45°30°15°
Horizontal Lig t Dispersion Pattern
Degrees UL Min. per UL1971
0°15.00
5-25°13.50
30-45°11.25
50°8.25
55°6.75
60°6.00
65°2.40
70°5.25
75°5.25
80°4.50
85°3.75
90°3.75
Model 224XSTHI Signaling Device for the Hearing Impaired Light
Dispersion Pattern per UL1971.

2561694D
REV. D Prin ed 9/04
Prin ed in U.S.A.
2
A. New flash tube.
B. Used flash tube tends to discolor in areas shown, and should be replaced.
290A4168
A
B
Table of contents
Popular Industrial Electrical manuals by other brands

Murata
Murata GQM2195C2E1R3WB12 Series Reference sheet

Murata
Murata GRM2195C1H113JA01 Series Reference sheet

Murata
Murata GRJ216R72A472KE01 Series Reference sheet

Murata
Murata GRM2165C2A131JA01 Series Reference sheet

ABB
ABB GSC Series Installation and maintenance guide

Murata
Murata GRM0335C2AR70BA01 Series Reference sheet

Balluff
Balluff BTL6-V1 E-M Series user guide

Murata
Murata GRM1555C1H561JA01 Series Reference sheet

Murata
Murata GRM0225C1ER50BA03 Series Reference sheet

Murata
Murata GRM0335C2A390JA01 Series Reference sheet

hager
hager univers N UK31LH1FM Mounting instructions

Murata
Murata GRM0335C1H6R8CA01 Series Reference sheet