Fieldpiece S365 User manual

01
04
03
06
02
05
WARNINGS
Only use on TXV systems using
either R410A or R22.
Ensure the system is powered
OFF before installing the Charg-
ing Jacket.
Severe injury can occur if the fan
turns ON before hooks are se-
curely fastened towards the top
of the condenser.
Wear eye protection.
Only use when the ambient dry
bulb temperature is between
37°F and 70°F (3°C to 21°C.)
Using outside of this range can
damage the air conditioner/heat
pump.
Head pressure of the system
needs to remain within the
following safe ranges to avoid
damage to the compressor or
other equipment:
R22: 55psig to 300psig
R410A: 97psig to 500psig
Stop the system if the head pres-
sure approaches these limits.
Description
HVACR technicians typically
cannot charge a cooling system in
cold weather. The cold temperature
removes too much heat from the
condenser coils.
The Charging Jacket from Fieldpiece
Instruments allow you to charge aTXV
system when ambient temperatures
are between 70°F and 37°F.
It works by restricting the fan outlet
of the condenser, in eect raising the
temperature within the condsenser.
This is a more eective method than
blocking the incoming air to the
condenser coil .
Look professional and increase
your amount of possible jobs. No
more trash bags or cardboard! Do it
the right way.
Maintenance
Hand wash with cold water and
mild detergent if needed and let air
dry. Do not machine wash or dry.
Fieldpiece
Charging Jacket
OPERATOR'S MANUAL
Model S365
How to Use
TheWinter Charge Setup may
only be used for equipment for which
the air conditioning manufacturers
approve the use of the Winter
Charge Setup. Refer to (California’s)
Energy Commissions website for
the list of split system air condition
units approved by the manufacturers
to use the Winter Charge Setup. In
addition to the requirements of this
document, manufacturers may issue
additional instructions/clarication
for the equipment and procedures to
be used to conduct the Winter Charge
Setup. These additional instruction/
clarifications are also available on
the (California) Energy Commission
website.
-- California Title 24 2013 Edition
Setup
1 Power down the system.
2 Install Charging Jacket:
A. Tighten Bungie Cinch around top
of condenser fan cage making sure
not to block the airow inlet (sides.)
B. Fasten hooks securely so that the
the fan does not eject the Charging
Jacket when the system starts.
C. Always start with the top open,
then tighten the restriction string
to restrict airow as needed.
3 Make sure people and animals are
clear of the condenser, then start
the system. If using on a heat pump,
set it to cooling mode.
4 Carefully adjust the restriction
of the Charging Jacket until the
difference between the high
side and the low side pressures
is between 160psi and 220psi
(R410A) or 100psi and 145psi (R22).
Restricting airflow increases the
pressure dierence.
Check Refrigerant Charge
5 Once the system is within the
pressure dierence range, allow
the system to stabilize for 15
minutes.
6 Calculate Actual Subcooling.
(Tcondenser, saturation - T liquid line)
If your subcooling is more
than three degrees less than the
target subcooling, then you are
undercharged. (continued)
!
!
!
!
!
!
!
!
!
!
!
BUNGIE CINCH
RESTRICTION STRING

07
10
09
12
08
11
If your subcooling is more than one
degree over the target subcooling,
you are overcharged.
EXAMPLES
Target subcooling = 12°F and your
measured subcooling is 10°F. You are
OK.
Target subcooling = 12°F and your
measured subcooling is 14°F. You are
overcharged.
Target subcooling = 12°F and your
measured subcooling is 7°F. You are
undercharged.
Please use manufacturer's target
subcooling for comparison.
Check TXV Device
7 Calculate Actual Superheat
(Tsuction - T evaporator,saturation)
8 If TXV manufacturer’s data is
available, determine the superheat
range recommended by the
manufacturer. (continued)
9 If there is no manufacturer’s data
available then a superheat between
4° and 25°F is acceptable for aTXV. If
the superheat is outside this range,
and the charge is correctly adjusted
by the subcooling method, there
may be a problem with the TXV.
Limited Warranty
In the USA, this product is warranted
against defects in material or
workmanship for one year from date
of purchase. Fieldpiece will replace or
repair the defective unit, at its option,
subject to verication of the defect.
This warranty does not apply to
defects resulting from abuse, neglect,
accident, unauthorized repair,
alteration, or unreasonable use of the
instrument.
Any implied warranties arising
from the sale of a Fieldpiece product,
including but not limited to implied
warranties of merchantability and
tness for a particular purpose, are
limited to the above. Fieldpiece shall
not be liable for loss of use of the
instrument or other incidental or
consequential damages, expenses, or
economic loss, or for any claim of such
damage, expenses, or economic loss.
Statelawsvary.The above limitations
or exclusions may not apply to you.
For Service
In the USA, call Fieldpiece
Instruments for one-price-x-all out of
warranty service pricing. Send check or
money order for the amount quoted.
Send the product freight prepaid to
Fieldpiece Instruments. Send proof of
date and location of purchase for in-
warranty service. The product will be
repaired or replaced, at the option of
Fieldpiece, and returned via least cost
transportation. Outside of the USA,
please visit www.eldpiece.com for
service contact information.
www.fieldpiece.com
© Fieldpiece Instruments, Inc 2012; v05
More Products
from Fieldpiece
Visit www.fieldpiece.com for info.
Ω
VDC
VAC
µADC
HZ
MFD
400m
400
Auto
4000m
1000
400
°C
°F
NCVMAX
MIN
TRUE RMS
BACKLIGHT
NON-CONTACT VOLTA GE
HS36
AC
AirVelocity
&Temperature
Head English
READLO BATT
ON
LCD X
100
Average
(16 sec)
Metric Real
time
AAV3
AUTO-
OFF
English Metric
Ft/min M/s
KM/hrMPH
ºF ºC
OFF
O
F
F
M
FD
NCV
VAC VDC
AAC
Hz
Hz
%
°C
°F
SC56
AUTO OFFTRUE RMS
CAT III
600V
TEMP
K-TYPE
30V
MAX
SEL
HOLD
INRUSH
T1 T2
Atmospheric
Pressure
Superheat
Subcooling
T1 T2 Direct Saturation
Target
Superheat
CALCAL
CAL CAL
Test
Pressure
AUTO
OFF
Refrigerant ON/OFF
Enter
Units
Alarm
Digital Manifold + Vacuum Gauge
SMAN3
ODDB
HH:MM:SS
Psig
Kpa
inHg
cmHg
Psig
Kpa
inHg
cmHg
SHT1
VSAT
APO
Microns
HiLo
SetStable
Alarm
IDWB
Target SH
R-
°F°C
SCT2
LSAT
°F°C
°F°C
Clear
Input Output
Recall
Enter
Save
Sync
SETUP
Target
Evaporator
Logger
Light
Exit Temp
CFM
Display
Superheat
SubcoolingCombustion
HVAC Guide
CheckMe!
Fieldpiece HG3
Data
Service
Displa
y
INPUT FORM
SET 01
Set ID:Indoor Temp
Measurement: 72.8
SET 02
SET ID:Comp Amps
Measurement: 23.6
CustomerID:__JONES123
Multimeters
Digital Refrigerant Manifolds
Accessory Heads
System Analyzer
Table of contents
Popular Air Conditioner manuals by other brands

Fujitsu
Fujitsu ASYG 09 LLCA installation manual

York
York HVHC 07-12DS Installation & owner's manual

Carrier
Carrier Fan Coil 42B Installation, operation and maintenance manual

intensity
intensity IDUFCI60KC-3 installation manual

Frigidaire
Frigidaire FAC064K7A2 Factory parts catalog

Sanyo
Sanyo KS2432 instruction manual

Mitsubishi Electric
Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Panasonic
Panasonic CS-S18HKQ Service manual

Panasonic
Panasonic CS-E15NKE3 operating instructions

Gree
Gree GWH18TC-K3DNA1B/I Service manual

Friedrich
Friedrich ZoneAire Compact P08SA owner's manual

Daikin
Daikin R32 Split Series installation manual