Frick XLP3 Owner's manual

Form 140.925-IOM (APR 2019)
INSTALLATION - OPERATION - MAINTENANCE
File: SERVICE MANUAL - Section 140
Replaces: Nothing
Dist: 3, 3a, 3b, 3c
XLP3 Evaporative Condenser
THIS MANUAL CONTAINS RIGGING, ASSEMBLY, START-UP,
AND MAINTENANCE INSTRUCTIONS. READ THOROUGHLY
BEFORE BEGINNING INSTALLATION. FAILURE TO FOLLOW THESE
INSTRUCTIONS MAY RESULT IN PERSONAL INJURY OR DEATH,
DAMAGE TO THE UNIT, OR IMPROPER OPERATION.
Please check www.johnsoncontrols.com/frick for the latest version of this publication.

140.925-IOM (APR 2019)
Page 2
XLP3 EVAPORATIVE CONDENSERS
INSTALLATION - OPERATION - MAINTENANCE
Table of Contents
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious
injury.
Indicates a potentially hazardous situation or practice which, if not avoided, will result in death or
serious injury.
SAFETY PRECAUTION DEFINITIONS
Indicates a potentially hazardous situation or practice which, if not avoided, will result in damage
to equipment and/or minor injury.
Indicates an operating procedure, practice, etc., or portion thereof which is essential to highlight.
WARNING
CAUTION
DANGER
NOTICE
INSTALLATION
INTRODUCTION ............................................................... 4
Safety .................................................................................4
Shipping..............................................................................4
Pre-Rigging Checks ............................................................4
Cold Weather Operation.....................................................4
Location..............................................................................4
Warranties..........................................................................4
Unit Operation....................................................................5
RIGGING & ASSEMBLY......................................................5
Rigging ...............................................................................5
Section Assembly ...............................................................5
Table 1 - Recommended Vertical Dimension and Spreader
Bar Length .....................................................................5
Wiring the Factory Terminal Box (EC Fan System Only)...... 7
OPTIONAL ACCESSORY INSTALLATION............................8
Bottom Water Outlet (Optional) .........................................8
Offset Access Platform, Perimeter Guardrail and Ladder....8
Ladder Safety Cage (Optional)..........................................10
Table 2 - Ladder Safety Cage Bolting Location and
Quantities ....................................................................10
Automatic Bearing Greasers (Optional for Belt Drive Fan
System Units Only) ...................................................... 11
Heater Control Panel (Optional)........................................ 11
FIELD CONNECTIONS......................................................13
Table 3 - Supplies for Installing Field Connections............ 13
OPERATION
SAFETY PRECAUTIONS...................................................14
START-UP PROCEDURE ..................................................15
Considerations for Initial Start-Up .................................... 15
General............................................................................. 15
Cleaning............................................................................ 15
Inspection......................................................................... 15
Start-up............................................................................ 15
EXTENDED SHUTDOWN..................................................16
PROLONGED OUTDOOR STORAGE..................................16
Storage Preparation ......................................................... 16
Motor Recommendations ................................................. 17
Electronically Commutated (EC) Motors............................ 17
Belt Drive Fan System ...................................................... 17
Maintenance Requirements During Storage...................... 18
Start-Up Preparation After Prolonged Storage................. 18
COLD WEATHER OPERATION..........................................18
Inspection and Maintenance............................................. 18
Fan Section Icing Protection............................................. 18
BASIN WATER AND INTERNAL PIPING
FREEZE PROTECTION ......................................................18
Cold Water Basin Protection............................................. 18
COIL FREEZE PROTECTION..............................................19
Minimum Operation.......................................................... 19
OPERATION CONSIDERATIONS
FOR ACCESSORIES .........................................................19
Basin Heater (Optional) .................................................... 19
Stand Alone Frick Heater Control Panel (Optional)........... 19
Operation ......................................................................... 19
VIBRATION CUTOUT SWITCH (VCOS) ............................20
Mechanical Vibration Cutout Switch (Standard)................20
Electronic Vibration Cutout Switch (Optional) ..................20
FAN CONTROL................................................................ 22
EC Fan System Fan Control............................................... 22
Independent Fan Control (Optional).................................. 22
MAINTENANCE
DETAILED COMPONENT
MAINTENANCE PROCEDURES .........................................24
Cold Water Basin..............................................................24
Table 4 - Cold Water Basin Water Levels .........................24
EC Fan System..................................................................24
Belt Drive Fan System ......................................................24
Water Distribution System and Heat Transfer Section...... 26
Water Level Control.......................................................... 27
CORROSION PROTECTION ..............................................28
Water Treatment .............................................................. 28
Corrosion and Scale Control ............................................. 28
Gray Water and Reclaimed Water..................................... 29
Chemical Treatment Requirements ................................... 29
Table 5 – Quality Guidelines for Treated Circulated Water 29
Passivation ....................................................................... 29
Biological Control ............................................................. 29
Long Term Care of Stainless Steel ....................................30
Jobsite Considerations......................................................30
System Cleaning...............................................................30
BLEED RATE....................................................................30
RECOMMENDED MAINTENANCE INTERVALS ..................32

140.925-IOM (APR 2019)
Page 3
XLP3 EVAPORATIVE CONDENSERS
INSTALLATION - OPERATION - MAINTENANCE
XLP3 Evaporative Condenser
with EC Fan System
XLP3 Evaporative Condenser
Factory Pre-Assembled
Lader with Safety Cage
(Optional)
Coil Connection:
Refrigerant Vapor In
Coil Connection: Refrig-
erant Liquid Out
Terminal Box
Pump
Factory Pre-Assembled
Platforms with Perimeter
Handrails (Optional)
BranchLokTM
Removal
System
Access Door
with Safety
Handle
and Step
Coil
Basin
Strainer
Internal
Walkway
EC
Fan
System
XLP3 Evaporative Condenser with EC Fan System
XLP3 Evaporative Condenser
with Belt Drive Fan System

140.925-IOM (APR 2019)
Page 4
XLP3 EVAPORATIVE CONDENSERS
INSTALLATION
INTRODUCTION
Safety
Adequate precautions appropriate for the installation and
location of these products should be taken to safeguard the
equipment and the premises from damage, and the public from
possible injury. The procedures listed in this manual must be
thoroughly reviewed prior to rigging and assembly. Read all
warnings, cautions and notes.
When the fan speed of the unit is to be changed from the factory
set speed, including the use of a variable speed device, steps
must be taken to avoid operating at or near the fan’s “critical
speed” which could result in fan failure and possible injury or
damage. Refer to “Fan Control” in the Operation section of this
manual.
WARNING
In the event of extended lifts or where hazards exist, the
lifting devices should be used in conjunction with safety
slings placed under the unit.
Shipping
Frick XLP3 Evaporative Condensers are factory assembled to
ensure uniform quality with minimum field assembly. As standard,
models ship in two sections per cell (lower and upper). Contact
your local Frick Representative for more information. For the
dimensions and weights of a specific unit or section, refer to
the submittal drawings.
WARNING
Only personnel qualied to do so should undertake the
installation, operation, maintenance, and repair of this
equipment. Proper care, procedures, and tools must be
used in handling, lifting, installing, operating, maintaining,
and repairing this equipment to prevent personal injury
and/or property damage.
Pre-Rigging Checks
When the unit is delivered to the job site, it should be checked
thoroughly to ensure all required items have been received and
are free of any shipping damage prior to signing the bill of lading.
The following parts should be inspected (if applicable for
the unit's conguration):
Sheaves,Belts, and
Bearings
Bearing Supports
Fan Motor(s)
Fan Guard(s)
Fan(s) and Fan Shaft(s)
Float Valve Assembly(s)
Water Distribution System
Coil Surface
Cold Water Basin
Accessories
Interior Surfaces
Exterior Surfaces
Spray Water Pumps
Mating Surfaces Between
Sections/ Modules
Miscellaneous Items: All bolts, nuts, washers, and sealer tape required
to assemble sections or component parts are furnished by Frick and
shipped with the unit. A checklist inside the envelope marked “Custom-
er Information Packet” indicates what miscellaneous parts are included
with the shipment and where they are packed. This envelope will be
attached to the side of the unit or located in a box inside the unit.
INSTALLATION
Unit Weights
Before rigging any unit, the weight of each section should be
verified from the unit submittal drawing. Unit print weights in-
clude the final assembled unit with all accessories. Accessory
weights (found on the respective drawing) can be deducted from
the total weight.
Anchoring
Seven-eighths inch (7/8”) diameter holes are provided in the bot-
tom flange of the basin section for bolting the unit to the support
beams. Refer to the suggested support drawing included in the
submittal for location and quantity of the mounting holes. The
unit must be level for proper operation. Anchor bolts must be
provided by others. The IBC rating is only certified with standard
anchorage locations. Using alternate anchorage locations or al-
ternate steel supports will void any IBC wind or seismic ratings.
Contact your local Frick Representative for details.
CAUTION
Unit must be properly anchored in place before operation
begins.
Cold Weather Operation
These products must be protected by mechanical and operational
methods against damage and/or reduced effectiveness due to
possible freeze-up. Refer to “Cold Weather Operation” in the
Operation section of this manual or contact your local Frick
Representative for recommended protection alternatives.
WARNING
Before an actual lift is undertaken, ensure no water, snow,
ice, or debris has collected in the basin or elsewhere in
the unit. Such accumulations will add substantially to the
equipment’s lifting weight.
Location
All evaporative cooling equipment must be located to ensure
an adequate supply of fresh air to the fans. When units are lo-
cated adjacent to walls or in enclosures, care must be taken to
ensure the warm, saturated, discharge air is not deflected and
redirected back to the air intakes. Each unit must be located and
positioned to prevent the introduction of discharge air into the
ventilation systems of the building on which the unit is located
and of adjacent buildings. For detailed recommendations on Frick
equipment layout, contact your local Representative.
NOTICE
Each unit must be located and positioned to prevent the
introduction of discharge air into the ventilation systems
of the building on which the unit is located and of adjacent
buildings.
Warranties
Please refer to the Limitation of Warranties (located in the
submittal package) applicable to and in effect at the time of the
sale/purchase of these products.

140.925-IOM (APR 2019)
Page 5
XLP3 EVAPORATIVE CONDENSERS
INSTALLATION
Unit Operation
Prior to start-up and unit operation, refer to the Frick Operation
& Maintenance sections in this manual.
RIGGING & ASSEMBLY
Rigging
Refer to Table 1 for the recommended vertical dimension “H”
from the lifting device to the spreader bar. In the event of ex-
tended lifts or where hazards exist, the lifting devices should
be used in conjunction with safety slings placed under the unit.
NOTICE
For weight information, refer to the submittal drawing
package.
NOTICE
Any motors or accessories shipped in the cold water basin
must be removed prior to installing the upper (mechanical
and coil casing) section.
Most single cell XLP3 Evaporative Condenser products are de-
signed to be lifted in one assembled piece as shown in Figure
1. Verify the total unit shipping weight is below 35,000 lbs
before performing a single-piece lift. A two-piece lift is shown
in Figure 2.
WARNING
Single piece lift is ONLY possible when total unit shipping
weight is under 35,000 lbs. Please refer to the shipping
weight shown on the Unit Print from submittal package.
Single piece lifting must be done using lifting ears on the
base of the upper casing section (See Figure 1).
Section Assembly
1. Remove any motors or accessories shipped in the cold water
basin. Rig the basin section. The rigging hook must be placed
above the section’s center of gravity as detailed in Figures 1 and 2.
2. Wipe down the flanges with acetone to remove dirt or mois-
ture which may have accumulated during shipment and storage.
3. Install sealer tape on the mating flange of the bottom section
to ensure an airtight seal between the top and bottom section.
Install flat butyl sealer tape (Frick part #554000) supplied with the
unit, on the mating flanges of the lower section in a continuous
line. At each corner, allow 1” overlap. See Figure 3.
CAUTION
Before proceeding, bolt the basin sections securely to the
supporting steel.
4. Lower the flexible connection on the pump discharge piping
below the elevation of the lower section before rigging the coil
casing section.
5. Lower the upper section (coil casing and mechanical) until it
is hovering 2-6” above the lower section.
6. Insert drift pins per Figure 5. Start at the corner hole and skip
every 3 or 4 holes along the length of the unit, inserting drift
pins to align the coil casing section and the lower section holes.
Repeat this process on the other side.
7. Fasten the hardware between the coil casing and lower sec-
tion per Figure 4. Lower the coil casing section the rest of the
way onto the lower section, keeping mounting holes aligned.
Figure 1 — Single-Piece Lift
L
H
Table 1 – Recommended Vertical Dimension and Spreader Bar Length
Model Number Number of
Basin Sections
Number of
Casing
Sections
Basin Section Casing Section or Single
Piece Lift
Spreader Bar
Length (L)
Minimum
Height (H)
Center of
Gravity from
Air Inlet Face
Spreader Bar
Length (L)
Minimum
Height (H)
XLP3-1012xxxx-xxxx 1 1 10' 13'-8" 4'-2" 10' 9’-2”
XLP3-1018xxxx-xxxx 1 1 10' 13'-8" 4'-2" 10' 13’-8”
XLP3-1024xxxx-xxxx 2 2 10' 13'-8" 4'-2" 10' 9’-2”
XLP3-2012xxxx-xxxx 2 2 10' 13'-8" 4'-2" 10' 9’-2”
XLP3-1036xxxx-xxxx 2 2 10' 13'-8" 4'-2" 10' 13’-8”
XLP3-2018xxxx-xxxx 2 2 10' 13'-8" 4'-2" 10' 13’-8”
XLP3-1212xxxx-xxxx 1 1 12' 13'-8" 5' 10' 9’-2”
XLP3-1218xxxx-xxxx 1 1 12' 13'-8" 5' 10' 13’-8”
XLP3-1224xxxx-xxxx 2 2 12' 13'-8" 5' 10' 9’-2”
XLP3-2412xxxx-xxxx 2 2 12' 13'-8" 5' 10' 9’-2”
XLP3-1236xxxx-xxxx 2 2 12' 13'-8" 5' 10' 13’-8”
XLP3-2418xxxx-xxxx 2 2 12' 13'-8" 5' 10' 13’-8”
Table of contents
Other Frick Air Conditioner manuals
Popular Air Conditioner manuals by other brands

Fujitsu
Fujitsu ASYG 09 LLCA installation manual

York
York HVHC 07-12DS Installation & owner's manual

Carrier
Carrier Fan Coil 42B Installation, operation and maintenance manual

intensity
intensity IDUFCI60KC-3 installation manual

Frigidaire
Frigidaire FAC064K7A2 Factory parts catalog

Sanyo
Sanyo KS2432 instruction manual

Mitsubishi Electric
Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Panasonic
Panasonic CS-S18HKQ Service manual

Panasonic
Panasonic CS-E15NKE3 operating instructions

Gree
Gree GWH18TC-K3DNA1B/I Service manual

Friedrich
Friedrich ZoneAire Compact P08SA owner's manual

Daikin
Daikin R32 Split Series installation manual