FRIEDHELM LOH Rittal 3359 Series User manual

Enclosure cooling unit
Assembly and operating instructions
3359.xxx
3273.xxx
3382.xxx
3383.xxx
3384.xxx
3385.xxx
3386.xxx
3387.xxx

Contents
EN
2Rittal enclosure cooling unit
Contents
1 Notes on documentation .................. 3
1.1 CE labelling.................................................. 3
1.2 Storing the documents................................. 3
1.3 Symbols used in these operating instructions 3
1.4 Other applicable documents ........................ 3
2 Safety notes ..................................... 3
3 Device description ............................ 3
3.1 TÜV-tested output measurement to
DIN EN 14511 .............................................. 4
3.2 Functional description .................................. 4
3.2.1 How it works ......................................................... 4
3.2.2 Control .................................................................. 4
3.2.3 Bus mode (e-Comfort controller only) .................... 4
3.2.4 Safety devices ....................................................... 5
3.2.5 Condensation ....................................................... 5
3.2.6 Filter mats ............................................................. 5
3.2.7 Door limit switch ................................................... 5
3.2.8 Additional interface X3 .......................................... 5
3.3 Proper use, foreseeable misuse ................... 5
3.4 Scope of supply........................................... 6
4 Assembly and connection ................ 6
4.1 Choosing the installation site........................ 6
4.2 Notes on assembly ...................................... 6
4.2.1 General ................................................................. 6
4.2.2 Layout of the electronic components in the
enclosure .............................................................. 6
4.3 Fitting the cooling unit .................................. 7
4.3.1 Making the cut-outs .............................................. 7
4.3.2 Top mounting of the cooling unit ........................... 7
4.4 Connecting the condensate discharge ......... 8
4.5 Notes on electrical installation ...................... 9
4.5.1 Connection data ................................................... 9
4.5.2 Overvoltage protection and supply line load .......... 9
4.5.3 Three-phase devices ............................................. 9
4.5.4 Door limit switch ................................................... 9
4.5.5 Notes on the flicker standard ................................ 9
4.5.6 Potential equalisation ............................................ 9
4.6 Making the electrical connection ................ 10
4.6.1 Bus connection (only when interconnecting several
units with a Comfort controller) ............................ 10
4.6.2 Connection X3 for serial interface ........................ 10
4.6.3 Installing the power supply .................................. 11
4.7 Finalising assembly .................................... 12
4.7.1 Installing the filter media ...................................... 12
4.7.2 Fitting the cooling unit ......................................... 12
4.7.3 Setting the filter mat monitor ............................... 12
5 Start-up .......................................... 13
6 Operation ....................................... 13
6.1 Control using the e-Comfort controller ....... 13
6.1.1 Properties ........................................................... 13
6.1.2 Eco mode ........................................................... 13
6.1.3 Launching test mode .......................................... 14
6.1.4 General information about programming ............. 14
6.1.5 Editable parameters ............................................ 15
6.1.6 Programming overview ....................................... 16
6.1.7 Defining system messages for evaluation ............ 17
6.1.8 Setting the master/slave identifier ........................ 18
6.1.9 Evaluating system messages .............................. 18
6.1.10 Resetting the e-Comfort controller ...................... 20
7 Inspection and maintenance .......... 20
7.1 Compressed air cleaning............................ 20
8 Storage and disposal ..................... 22
9 Technical details ............................ 22
9.1 Technical specifications.............................. 22
9.2 Performance diagrams............................... 25
10 List of spare parts .......................... 26
11 Appendix ....................................... 28
11.1 Cut-out and hole sizes ............................... 28
11.1.1 Dimensions for assembly .................................... 28
11.2 Electrical wiring plan................................... 29

Rittal enclosure cooling unit 3
1 Notes on documentation
EN
1 Notes on documentation
1.1 CE labelling
Rittal GmbH & Co. KG confirms the conformity of the
cooling unit with the European Union's Machinery Di-
rective 2006/42/EC and EMC Directive 2014/30/EC. A
corresponding declaration of conformity has been is-
sued. This can be found at the end of this document, or
on the Rittal homepage.
1.2 Storing the documents
The assembly and operating instructions as well as all
other applicable documents are an integral part of the
product. They must be issued to everyone who works
with the unit and must always be available and on hand
for operating and maintenance personnel.
1.3 Symbols used in these operating in-
structions
The following symbols are used in this documentation:
This symbol indicates an "action point" and shows that
you should perform an operation or procedure.
1.4 Other applicable documents
Assembly and operating instructions in paper and digital
format are available for the unit types described here.
We cannot accept any liability for damage associated
with failure to observe these instructions. Where applica-
ble, the instructions for any accessories used also apply.
2 Safety notes
Please observe the following general safety notes when
assembling and operating the unit:
– Assembly, installation and servicing may only be per-
formed by properly trained specialists.
– Do not obstruct the air inlet and air outlet of the cooling
unit inside and outside the enclosure (see sec-
tion4.2.2 "Layout of the electronic components in the
enclosure").
– The heat loss of the components installed in the enclo-
sure must not exceed the specific useful cooling pow-
er of the cooling unit.
– The cooling unit must always be transported in a hori-
zontal position.
– Use only original spare parts and accessories.
– Do not make any changes to the cooling unit other
than those described in these instructions or associat-
ed instructions.
– Risk of burns! On cooling units with automatic con-
densate evaporation, the surface of the thermal ele-
ment will get very hot during operation, and will remain
so for some time afterwards.
– The mains connector of the cooling unit must only be
connected and disconnected with the system de-en-
ergised. Connect the protective device specified on
the rating plate.
3 Device description
Depending on the model chosen, your cooling unit may
vary in appearance from the illustrations contained in
these instructions. However, the functions are identical
in principle.
Danger!
A dangerous situation in which failure to
comply with the instructions will result in
death or severe injury.
Warning!
A dangerous situation which may cause
death or serious injury if the instructions
are not followed.
Caution!
A dangerous situation which may lead to
(minor) injuries if the instructions are not
followed.
Note:
Important notices and indication of situations
which may result in material damage.

3 Device description
EN
4Rittal enclosure cooling unit
Fig. 1: Device description
Key
1Enclosure
2 Air outlet holes
3 Rating plate
4 Louvred grille for air inlet
5Display
6 X2 master-slave connection (underside of the unit)
7 X1 terminal strip (underside of the unit)
8 X3 optional serial interface (underside of the unit)
9 Dispatch bag
10 Twin-threaded bolt
11 Condenser
12 Condensate discharge
3.1 TÜV-tested output measurement to
DIN EN 14511
All TopTherm cooling units in the output range from 300
to 4000 W are tested to the latest EN 14511-1-4:2013-
12 standard by independent test institute TÜV Nord.
This means you have peace of mind about the design of
the climate control solution and you can be sure you are
getting the performance you are paying for.
3.2 Functional description
Enclosure cooling units are designed to dissipate heat
from enclosures by cooling the air inside the enclosure
and so protect the temperature-sensitive components.
It is mounted on the roof of an enclosure.
3.2.1 How it works
The cooling unit (compression refrigeration system)
comprises four main components (see fig. 2): the evap-
orator (1), the refrigerant compressor (2), the condenser
(3), and the control or expansion valve (4), which are
connected by suitable pipework.
This circuit is filled with a readily boiling substance, the
refrigerant. The refrigerant R134a (CH2FCF3) is chlorine-
free. Its Ozone Depletion Potential (ODP) is 0, making it
very eco-friendly. A filter dryer (5) which is integrated into
the hermetically sealed cooling circuit provides effective
protection against moisture, acid, dirt particles, and for-
eign bodies within the cooling circuit.
Fig. 2: Cooling circuit
In the evaporator coil (1), the liquid refrigerant is convert-
ed to a gaseous state. The energy needed for this pur-
pose is taken from the enclosure air in the form of heat,
which has the effect of cooling the enclosure air. In the
compressor (2), the refrigerant is heavily compressed,
so that it achieves a higher temperature inside the con-
denser (3) than the ambient air. This means that excess
heat may be emitted to the ambient air via the surface of
the condenser, as a result of which the temperature of
the refrigerant drops and it is converted back into liquid.
It is re-injected into the evaporator coil via a thermostatic
expansion valve (4), which causes it to cool down fur-
ther, and is then once again able to absorb the energy
from the enclosure air in the evaporator coil. The whole
cycle begins again.
3.2.2 Control
Rittal enclosure cooling units are fitted with a controller
for setting the functions of the cooling unit (display plus
extended functions, see section6 "Operation").
3.2.3 Bus mode (e-Comfort controller only)
The serial unit interface X2 allows you to create a bus
connection with up to ten cooling units using the master-
slave cable (shielded, four-wire cable, Model No.
3124.100). This allows you to implement the following
functions:
– Parallel unit control (the cooling units in the network
can be switched on and off simultaneously)
– Parallel door status message ("door open")
– Parallel collective fault message
Data is exchanged via the master-slave connection.
During commissioning, assign an address to each unit
that also includes the identifier "master" or "slave".
3
6, 7, 8
12
4
11
10
9
5
2
1
PSAH
pressure
switch
Condenser fan
Expansion valve (4)
Temperature
control
Filter dryer (5)
Internal circuit
Compressor (2)
External circuit
Evaporator fan
Evaporator coil (1)
Condenser (3)

Rittal enclosure cooling unit 5
3 Device description
EN
3.2.4 Safety devices
– In the cooling cycle, the cooling unit has a tested pres-
sure switch to EN 12 263 which is set to maximum PS
(permissible pressure); this operates via an automatic
reset device whenever the pressure drops again.
– Temperature monitoring prevents the evaporator coil
from icing over. If there is a risk of icing, the compres-
sor switches itself off and automatically switches itself
back on again at higher temperatures.
– The refrigerant compressor and the fans are equipped
with thermal winding shields to protect against excess
current and excess temperatures.
– In order to allow a reduction of pressure inside the
compressor and hence a safe restart, once it has been
switched off (e.g. upon reaching the set temperature
via the door limit switch function or via de-energising),
the device will switch back on with a delay of 180 sec-
onds.
– The device has floating contacts on the connection
pins (terminals 3 – 5), via which system messages
from the device may be polled, e.g. using a PLC (2x
normally open contacts, e-Comfort controller).
3.2.5 Condensation
At high levels of humidity and low temperatures inside
the enclosure, condensation may form on the evapora-
tor coil.
The cooling units have an automatic electrical conden-
sate evaporator. The thermal component used for this
purpose is based on self-regulating PTC technology.
Condensate arising on the evaporator coil is collected in
a tank in the internal circuit of the cooling unit. When the
water level rises, the water enters the PTC thermal com-
ponent and is evaporated (through-flow heater princi-
ple). The water vapour streams out of the cooling unit
with the airflow from the external fan.
The PTC thermal component is permanently connected
and has no switchpoint. It is protected against short-cir-
cuits with miniature fuses (F1.1, F1.2). If the fuse has
tripped, any condensation is drained off via the safety
overflow.
In the case of a malfunction or a failure in the thermal
component, the condensation water is routed out of the
unit via a drain pipe at the side or rear for safety reasons.
For this purpose, a hose must be connected to the con-
densate nozzle (see section4.4 "Connecting the con-
densate discharge"). Condensate hoses are available as
accessories (refer also to the accessories section in the
Rittal Catalogue).
3.2.6 Filter mats
The entire cooling unit condenser is covered with a dirt-
repelling, easy-to-clean RiNano coating. In many appli-
cations, therefore, the use of filter media is unnecessary,
particularly with dry dusts.
For dry, coarse dust and lint in the ambient air, we rec-
ommend installing an additional PU foam filter mat (avail-
able as an accessory) in the cooling unit. Depending on
the incidence of dust, you will need to replace the filter
mat from time to time.
For air containing oil condensate, we recommend the
use of metal filters (also available as an accessory).
These may be cleaned with suitable detergents and re-
used.
Function of the filter mat monitor (with e-Comfort
controller only):
Dirt on the filter mat is automatically determined by
measuring the temperature difference in the external cir-
cuit of the cooling unit. As the level of filter mat soiling in-
creases, the temperature difference will increase. The
setpoint value of the temperature difference in the exter-
nal circuit adapts automatically to the relevant operating
points in the performance diagrams. Hence there is no
need to readjust the setpoint value for different unit op-
erating points.
3.2.7 Door limit switch
The cooling unit may be operated with a floating door
limit switch connected. The door limit switch is not in-
cluded with the supply (available as an accessory, Model
No. 4127.010).
The door limit switch function causes the fans and the
compressor in the cooling unit to be switched off after
approximately 15 seconds when the enclosure door is
opened (contacts 1 and 2 closed). This prevents the for-
mation of condensation inside the enclosure while the
enclosure door is open. In order to prevent damage to
the unit, it is equipped with an ON delay: The evaporator
fan cuts back in with a delay of approximately 15 sec-
onds after the door has been closed, while the condens-
er fan and compressor switch on after approximately
3minutes.
3.2.8 Additional interface X3
An additional interface card may be connected to the 9-
pole SUB-D connector X3 in order to incorporate the
cooling unit into higher-level monitoring systems (availa-
ble as an accessory, interface card Model No.
3124.200).
3.3 Proper use, foreseeable misuse
The cooling unit is only intended for cooling connected
enclosures. Any other use is not permitted.
– The unit must not be installed and operated in loca-
tions which are accessible to the general public (see
DIN EN 60335-2-40, paragraph 3.119).
Note:
No external voltage may be applied to the
door contacts (terminals 1 and 2).
Note:
The electrical signals at the interface are of
an extra-low voltage (not extra-low safety
voltages to EN 60 335).

4 Assembly and connection
EN
6Rittal enclosure cooling unit
– The unit is designed solely for stationary use.
The cooling unit is state of the art and built according to
recognised safety regulations. Nevertheless, improper
use can pose a threat to the life and limb of the user or
third parties, or result in possible damage to the system
and other property.
Consequently, the cooling unit must only be used prop-
erly and in a technically sound condition! Any malfunc-
tions which impair safety should be rectified immediate-
ly.
Proper use also includes the observance of the docu-
mentation provided, and compliance with the inspection
and maintenance conditions.
Rittal GmbH & Co. KG is not liable for any damage which
may result from failure to comply with the documenta-
tion provided. The same applies to failure to comply with
the valid documentation for any accessories used.
Inappropriate use may be dangerous. Examples of inap-
propriate include:
– Use of the cooling unit over long periods with the en-
closure open.
– Use of impermissible tools.
– Improper operation.
– Improper rectification of malfunctions.
– Use of accessories not approved by Rittal GmbH &
Co. KG.
3.4 Scope of supply
The unit is supplied in a packaging unit in a fully assem-
bled state.
Please check the scope of supply for completeness.
4 Assembly and connection
4.1 Choosing the installation site
When choosing the installation site for the enclosure,
please observe the following:
– The site for the enclosure and the positioning of the
cooling unit must be carefully selected so as to ensure
good ventilation. Depending on the siting of the unit, if
several units are installed directly adjacent to one an-
other, the distance from the wall must be at least
200 mm.
– The cooling unit must be installed and operated in a
horizontal position (maximum deviation: 2°).
– The site must be free from excessive dirt, aggressive
ambient conditions and moisture.
– The ambient temperature must be within the limits
specified on the rating plate.
– It must be possible to fit a condensate discharge (see
section4.4 "Connecting the condensate discharge").
– The mains connection data as stated on the rating
plate of the unit must be guaranteed.
4.2 Notes on assembly
4.2.1 General
– Check the packaging carefully for signs of damage.
Traces of oil on damaged packaging are an indication
of refrigerant loss and leakages. Any packaging dam-
age may be the cause of a subsequent functional fail-
ure.
– The enclosure must be sealed on all sides (IP 54). In-
creased condensation will occur if the enclosure is not
airtight.
– In order to avoid excessive condensation inside the
enclosure, we recommend installing a door limit
switch (e.g. 4127.010) which deactivates the cooling
unit when the enclosure door is opened (see sec-
tion3.2.7 "Door limit switch").
4.2.2 Layout of the electronic components in the
enclosure
Qty. Description
1 Enclosure cooling unit
1
1
1
1
1
1
1
Dispatch bag:
– Sealing plate (3273.xxx, 3383.xxx, 3384.xxx,
3385.xxx)
– Sealing frame
– Plug-in terminal strip
– Assembly and operating instructions
– Angular connector
– Screw-in nozzle
3 Blind rivet (3386.xxx, 3387.xxx)
1 Drilling template
Tab. 1: Scope of supply
Note:
Risk of condensation!
When arranging the components inside the
enclosure, please ensure that the cold air-
flow from the cooling unit is not directed at
active components. Please also ensure that
the cold airflow is not directed at the warm
exhaust airflow from active
components such as converters. This may
lead to an air short-circuit and therefore pre-
vent adequate climate control, or may even
cause the cooling unit’s internal safety de-
vices to cease cooling operation.

Rittal enclosure cooling unit 7
4 Assembly and connection
EN
Fig. 3: Never direct the cold airflow at active components
Exercise particular caution with the airflow from the
blowers of built-in electronic components (see fig. 3).
Components for targeted air routing are available as ac-
cessories – please refer to the Rittal Catalogue.
Fig. 4: Targeted air routing inside the enclosure
Fig. 5: Cover bungs
4.3 Fitting the cooling unit
The enclosure cooling unit is mounted on top of the en-
closure roof:
To this end, cut-outs must be made in the roof plate as
per the drilling template included with the supply.
4.3.1 Making the cut-outs
Affix the supplied drilling template to the roof of the en-
closure using adhesive tape.
There are dimensioning lines on the drilling template to
suit the installation type for your cooling unit.
Make the cut-outs including the line width as per the
drilling template.
Deburr the cut-outs.
4.3.2 Top mounting of the cooling unit
Affix the supplied sealing frame onto the cut out roof
plate.
Note:
When using an air duct system, care must
be taken to ensure that it is laid straight and
without kinks wherever possible. This mini-
mises the resistance to the cold airflow.
It is important to ensure even air circulation
inside the enclosure. Under no circum-
stances should air inlet and outlet openings
be obstructed, otherwise the cooling perfor-
mance of the unit will be reduced. Ensure a
suitable distance from electronic compo-
nents and other installed enclosures so that
the required air circulation is not obstructed
and prevented.
One cold air outlet from the cooling unit
must be kept open at all times when operat-
ing with the air duct, to prevent the accumu-
lation of cold air inside the unit.
Note:
When using the cover bungs, only a maxi-
mum of 1 or 2 cold air outlet openings may
be sealed, depending on the unit type.
Note:
Pre-configured, reinforced roof plates with
cut-outs to match your enclosure are avail-
able as accessories; refer to the Rittal Cata-
logue.
Caution!
Carefully deburr all cut-outs to prevent
injuries caused by sharp edges.
3273.xxx
3383.xxx
3384.xxx
3385.xxx
3359.xxx
3382.xxx
3386.xxx
3387.xxx
max. 2x max. 1x

4 Assembly and connection
EN
8Rittal enclosure cooling unit
Fig. 6: Sealing frame on roof plate
Affix the supplied sealing plate to the bottom of the
plastic base of the cooling unit (3273.xxx, 3383.xxx,
3384.xxx, 3385.xxx).
Fig. 7: Sealing plate underneath the plastic base of the cooling
unit
Mount the cooling unit on the enclosure roof.
Screw the supplied twin-threaded bolts into the core
holes in the plastic base on the underside of the cool-
ing unit with a maximum of 5 Nm.
Secure the unit using the supplied washers and nuts.
Fig. 8: Roof plate reinforcement for the TS 8 enclosure
Accessories for roof plate reinforcement with TS:
TS roof plates
Quick-change frame
Punched rail
U nut
Fastening bracket
Threaded block
(refer also to Accessories in the Rittal Catalogue)
4.4 Connecting the condensate discharge
A condensate discharge hose (Ø 1/2˝) may be fitted to
the cooling unit.
The condensate discharge
– must be laid with a suitable and constant gradient (no
siphoning)
– must be laid without kinks
– must not have a reduced cross-section if extended
The condensate hose is available as an accessory (refer
also to Accessories in the Rittal Catalogue).
Fig. 9: Connecting the condensate discharge
Connect a suitable hose to one of the two condensate
nozzles and secure using a hose clip.
The condensate nozzle that is not required should be
sealed.
Lay the condensate hose, e.g. into a drain.
Fig. 10: Laying the condensate discharge
Note:
In order to achieve a permanent seal be-
tween the cooling unit and the enclosure,
the mounting surface should be reinforced
or supported if necessary. This is particular-
ly applicable with large roof areas.
½"

Rittal enclosure cooling unit 9
4 Assembly and connection
EN
4.5 Notes on electrical installation
When performing the electrical installation, it is important
to observe all valid national and regional regulations as
well as the provisions of the responsible power supply
company. The electrical installation may only be carried
out by a qualified electrician who is responsible for com-
pliance with the applicable standards and regulations.
4.5.1 Connection data
– The connected voltage and frequency must corre-
spond to the values stated on the rating plate.
– The cooling unit must be connected to the mains via
an all-pin isolating device, which ensures at least
3 mm contact opening when switched off.
– No additional temperature control may be connected
upstream of the unit at the supply end.
– Install the protective device specified on the rating
plate to protect the line and equipment from short-cir-
cuits.
– The mains connection must ensure low-noise poten-
tial equalisation.
4.5.2 Overvoltage protection and supply line load
– The unit does not have its own overvoltage protection.
Measures must be taken by the operator at the supply
end to ensure effective lightning and overvoltage pro-
tection. The mains voltage must not exceed a toler-
ance of ±10%.
– In accordance with IEC 61 000-3-11, the unit is in-
tended solely for use at sites with a continuous cur-
rent-carrying capacity (incoming mains power supply)
of more than 100 A per phase and with a supply volt-
age of 400/230 V. If necessary, the power supply
company must be consulted to ensure that the contin-
uous current-carrying capacity at the point of connec-
tion to the public grid is sufficient for connection of
such a unit.
– The fans and compressors in single- and three-phase
units are intrinsically safe (thermal winding protection).
The same also applies to all transformer versions and
to special-voltage units which are likewise equipped
with a transformer.
– Install the protective device specified on the rating
plate to protect the line and equipment from short-cir-
cuits (miniature circuit-breaker with appropriate char-
acteristic – e.g. "K" characteristic – or gG standard
type slow fuse, circuit-breaker for plant or transformer
protection). Select a suitable circuit-breaker in accord-
ance with the information specified on the rating plate:
Set it to the minimum specified value. This will achieve
the best short-circuit protection for cables and equip-
ment.
Example: Specified setting range 6.3 – 10 A; set to
6.3 A.
4.5.3 Three-phase devices
– The electrical connection for devices in the three-
phase version MUST be made with a clockwise rotat-
ing field.
– The three-phase version must be connected to a TN
network with star earthing via a circuit-breaker for
plant protection (current setting as per the rating
plate). Three-phase units with special voltages must
be protected with a circuit-breaker for transformer
protection (category AC-3) as per the rating plate.
– Units designed for three phase 400/460 V feature ad-
ditional monitoring of the rotary field or the absence of
a phase. If the rotary field is incorrect or a phase is ab-
sent, the unit will not run.
4.5.4 Door limit switch
– Each door limit switch must only be assigned to one
cooling unit.
– Several door limit switches may be connected in par-
allel to one cooling unit.
– The minimum cross-section for the connection cable
is 0.3 mm2for a cable length of 2 m.
We recommend the use of a shielded cable.
– The line resistance to the door limit switch must not
exceed a maximum of 50 .
– The door limit switch only supports a floating connec-
tion; no external voltages.
– The contact of the door limit switch must be closed
when the door is open.
The safety extra-low voltage for the door limit switch is
provided by the internal power pack: Current approx.
30 mA DC.
Connect the door limit switch to terminals 1 and 2 of
the connector.
4.5.5 Notes on the flicker standard
The flicker limits specified in standard EN 61 000-3-3 or
-3-11 are adhered to, provided the supply impedance is
less than approx. 1.5 .
Where necessary, the unit operator should measure the
connected impedance or consult the responsible power
supply company. If there is no way of influencing the
supply impedance and sensitive installed components
(e.g. BUS) are subjected to interference, a line reactor or
starting-current limiting device should be connected up-
stream of the cooling unit to restrict the startup current
of the cooling unit.
4.5.6 Potential equalisation
If, for EMC reasons, the unit is to be integrated into the
customer’s existing potential equalisation system, a
conductor with a larger nominal cross-section can be
connected to the potential equalisation connection point
(attachment points) on the roof-mounted cooling units.
According to the standard, the PE conductor in the
mains connection cable is not classified as an equipo-
tential bonding conductor.

4 Assembly and connection
EN
10 Rittal enclosure cooling unit
Fig. 11: Connection point, potential equalisation
4.6 Making the electrical connection
4.6.1 Bus connection
(only when interconnecting several units
with a Comfort controller)
When using several cooling units, the serial device inter-
face X2 can be used to connect up to ten cooling units
with the bus cable (Model No. 3124.100).
When interconnecting, please note the following:
– De-energise the cooling units to be connected
– Ensure proper electrical insulation
– Make sure the cables are not laid in parallel to power
lines
– Make sure that the lines are short
4.6.2 Connection X3 for serial interface
The interface card (Model No. 3124.200) may be con-
nected to X3. This is used to evaluate system messages
in a PLC, for remotely setting parameters and monitor-
ing, or for integration into the facility management sys-
tem.
Fig. 12: Connection example: Master-slave operation
Key
1 Serial interface (Model No. 3124.200)
2 Serial interface cable
3 Master-slave bus cable (Model No. 3124.100)
RTT Rittal TopTherm cooling units
X1 Supply connection/door limit switch/alarms
X2 Master/slave connection Sub-D, 9-pole
X3 Serial interface Sub-D, 9-pole
St. Sub-D connector, 9-pole
Bu. Sub-D jack, 9-pole
Adr. Address
Note:
The electrical signals at the X2 interface are
of an extra-low voltage (not extra-low safety
voltages in accordance with EN 60 335-1).
Note:
With the last slave unit in the group, do not,
under any circumstances, connect the re-
maining socket of the Y cable 3124.100 into
interface X3 of the cooling unit!
X2
CMC
I/O unit
RTT
Master
Adr.: 09
X1
X2 X3
X1
X2 X3
X1
X2 X3
X1
X2 X3
X2 X3 X2
X2
X2 X2
X2
X2
St. St. St.
Bu.
St.
Bu.
X2
Adr.: 11 Adr.: 12RTT
Slave
RTT
Slave
Adr.: 19RTT
Slave
St.
Bu.
St.
Bu.
3
2
1

Rittal enclosure cooling unit 11
4 Assembly and connection
EN
Fig. 13: Connection example: Door limit switch and master-slave operation
Key
1 Master cooling unit
2 Slave cooling units
3 2-door enclosure with two door limit switches
4 Enclosure with door limit switch
4.6.3 Installing the power supply
Complete the electrical installation as per the wiring
plan inside the cooling unit underneath the cable shaft
cover (see fig. 29 on page 22, marked with an arrow).
If you would like the system messages from the cool-
ing unit to be evaluated via the system message relay,
you should also connect a suitable low-voltage cable
to connection pins 3 – 5.
Fig. 14: Electrical wiring plan no. 1
X10
L1
L2
N
PE
12345
1
X10
X10 X10 X10 X10
X2 X2 X2 X2 X2 X2
X2
L1
PE
12345
L1
L2
N
PE
12345
L2 L3 L1
PE
12345
L2 L3 L1
PE
12345
L2 L3 L1
PE
12345
L2 L3
L1
L2
N
PE
12345
X10
23456
1
Adr.: 06 Adr.: 11 Adr.: 12 Adr.: 13 Adr.: 14 Adr.: 15
22 2 2 2
34432
Adr.: 16
3359.5xx/.6xx, 3382.5xx/.6xx, 3383.5xx/.6xx, 3384.5xx/.6xx, 3385.5xx/.6xx

4 Assembly and connection
EN
12 Rittal enclosure cooling unit
Fig. 15: Electrical wiring plan no. 3
Key
X1 Main terminal strip
X2 Master/slave connection
X3 Optional interface
K1 Relay collective fault 1
K2 Relay collective fault 2
Door Door limit switch (without door limit switch: terminal 1, 2
open)
4.7 Finalising assembly
4.7.1 Installing the filter media
The entire cooling unit condenser is covered with a dirt-
repelling, easy-to-clean RiNano coating. In many appli-
cations, therefore, the use of filter media is unnecessary,
particularly with dry dusts.
For dry, coarse dust and lint in the ambient air, we rec-
ommend installing an additional PU foam filter mat (avail-
able as an accessory) in the cooling unit. For air contain-
ing oil condensate, we recommend the use of metal fil-
ters (also available as an accessory). When used in
textile plants with heavy lint contamination, lint screens
should be used (available as an optional extra).
Pull the louvred air inlet grille off the enclosure.
Secure the filter mat in front of the condenser using the
supplied blind rivets.
Then push the louvred grille back onto the enclosure.
4.7.2 Fitting the cooling unit
Connect the connector to the rear of the display.
Place the louvred grille onto the unit at the front, and
press it down until you hear it snap into place.
Fig. 16: Connect the display and attach the louvred grille
4.7.3 Setting the filter mat monitor
Function of the filter mat monitor:
Dirt on the filter mat is automatically detected by meas-
uring the temperature difference in the external circuit of
the cooling unit (see section 6.1.6 "Programming over-
view"). As the level of filter mat soiling increases, the
temperature difference will increase. The setpoint value
3386.54x/.64x, 3387.54x/.64x
Note:
For technical data, refer to the rating plate.
AC
cos φ = 1
DC
Res. Load
I max. = 2 A
U max. = 250 V
I min. = 100 mA
U max. = 30 V
I max. = 2 A
Tab. 2: Relay contact data

Rittal enclosure cooling unit 13
5 Start-up
EN
of the temperature difference in the external circuit
adapts automatically to the relevant operating points in
the performance diagrams. Hence there is no need to
readjust the setpoint value for different unit operating
points.
5 Start-up
Once all the assembly and installation work is com-
plete, switch on the power supply to the cooling unit.
The cooling unit starts running:
– The software version of the controller first appears for
approx. 2 seconds, then "ECO" to show Eco mode is
enabled. The internal enclosure temperature will then
appear in the 7-segment display.
You can now make your individual settings on the unit
e.g. set the temperature or assign the network identifier
etc. (refer to section 6 "Operation").
6 Operation
You can operate the cooling unit using the controller on
the front of the device (fig. 1, item 5).
6.1 Control using the e-Comfort controller
For unit types xxxx.500/.510/.540 and xxxx.600/.610/
.640.
Fig. 17: e-Comfort controller
Key
1 Programming button, also display of the set temperature
unit (degrees Celsius)
2Setbutton
3 Programming button, also display of the set temperature
unit (degrees Fahrenheit)
47-segmentdisplay
6.1.1 Properties
– Rated operating voltage:
–115Vor
–230Vor
– 400 V, 2-phase or
– 400/460 V, 3-phase
– Integral start-up delay and door limit switch function.
– Protective function to prevent icing.
– Monitoring of all motors (compressor, condenser fan,
evaporator fan).
– Phase monitoring for three-phase units.
– Master-slave function with a maximum of ten units.
One device functions as a master unit. Once the set
temperature is reached by one of the connected slave
devices or in the event of the door limit switch function,
the affected slave unit will report to the master unit that
switches all the other cooling units on or off as re-
quired.
– Switching hysteresis: adjustable within the range 2 –
10 K, preset to 5 K.
– Visualisation of the current internal enclosure temper-
ature and all error messages in the 7-segment display.
– Using an interface card (Model No. 3124.200), the unit
may be incorporated into higher-level remote monitor-
ing systems.
The cooling unit operates automatically, i.e. after switch-
ing on the power supply, the evaporator fan (see fig. 2)
will run and circulate the internal enclosure air.
The compressor and condenser fan are regulated by the
e-Comfort controller.
The e-Comfort controller has a 7-segment display
(fig. 17, item 4). After switching on the power supply, the
current software version initially appears on this display
for approx. 2 seconds together with the symbol to show
Eco mode is enabled, followed by a preset option (e.g.
t10) or the temperature.
In regular operation, the display shows both the temper-
ature (in degrees Celsius or Fahrenheit – users may
switch between the two) and any error messages.
The current internal enclosure temperature is usually dis-
played permanently. In the event of an error message,
this alternates with the temperature display.
The unit is programmed using buttons 1 – 3 (fig. 17). The
relevant parameters also appear in the display.
6.1.2 Eco mode
All Rittal TopTherm cooling units with e-Comfort control-
ler from firmware 3.2 have the energy-saving eco mode,
which is enabled in the delivered state.
The eco mode is used to save energy in the heat ex-
changer if there is no thermal load, or there is a low ther-
mal load in the enclosure (e.g. standby operation, no
production or weekend).
During this process the evaporator fan in the internal cir-
cuit is switched off as appropriate if the actual internal
enclosure temperature drops to 10 K below the speci-
fied setpoint temperature. To ensure the internal tem-
perature is reliably measured during this process, the fan
starts cyclically for 30 sec. every 10 minutes (see fig. 18).
If the internal temperature drops to a range 5 K below
the setpoint set again, the fan switches back to contin-
uous operation.
Note:
The oil must be collected in the compressor
in order to ensure effective lubrication and
cooling.
Do not operate the cooling unit for at least
30 minutes after assembling the equipment.
12
43

6 Operation
EN
14 Rittal enclosure cooling unit
If required, eco mode can be disabled on the control dis-
play. For this purpose switch the parameter from 1 to 0
in the programming level (see tab. 3). The fan then runs
continuously.
Fig. 18: Eco mode
6.1.3 Launching test mode
The e-Comfort controller is equipped with a test function
whereby the cooling unit commences cooling operation
independently of the set temperature or door limit switch
function.
Simultaneously press buttons 1 and 2 (fig. 17) for at
least five seconds.
The cooling unit will commence operation.
Test mode is completed after approximately 5 minutes.
The unit switches off and changes to normal operation.
6.1.4 General information about programming
Using buttons 1, 2 and 3 (fig. 17) you can change
24 parameters within the preset ranges (min. value –
max. value).
Tables 3 and 4 show the parameters which can be al-
tered. Fig. 20 on page 16 shows which buttons must be
pressed.
In principle, the programming is identical for all editable
parameters.
To enter programming mode:
Press button 2 ("Set") for approx. 5 seconds.
The controller is now in programming mode. While in
programming mode, if you do not press any buttons for
approx. 30 seconds, the display will first flash, then the
controller will switch back to normal display mode. "Esc"
in the display indicates that any changes made have not
been saved.
Press the programming buttons (°C) or (°F) to
switch between the editable parameters (see tables 3
and 4).
Press button 2 ("Set") to select the displayed parame-
ter for editing.
The current value of this parameter is displayed.
Press one of the programming buttons (°C) or
(°F).
"Cod" will appear in the display. In order to be able to
change a value, you must enter the authorisation code
"22".
Keep the programming button (°C) held down until
"22" appears.
Press button 2 ("Set") to confirm the code.
You can now alter the parameter within the preset limits.
Press one of the programming buttons (°C) or
(°F) until the required value appears.
Press button 2 ("Set") to confirm the change.
You can now alter other parameters in the same way.
There is no need to re-enter the authorisation code "22".
To exit programming mode, press button 2 ("Set")
again for approximately five seconds.
"Acc" will appear in the display to indicate that
the changes have been saved. The display then switch-
es back to regular operation (internal enclosure temper-
ature).
You can also program the e-Comfort controller using a
diagnosis software package (Model No. 3159.100),
which is supplied with a connection cable to the PC. The
cable connector on the rear of the e-Comfort controller
display serves as an interface.
Note on switching hysteresis:
With a low hysteresis and short switching
cycles, there is a risk that cooling may not
be adequate or that only partial sections of
the enclosure are cooled. If the cooling unit
is oversized and compressor run times are
too long < 1 minute, the switching hystere-
sis to protect the cooling unit is automatical-
ly increased (see message "LH" in
section6.1.9 "Evaluating system messa-
ges").
Note on temperature settings:
With the e-Comfort controller, the tempera-
ture is preset at the factory to +35°C.
In order to save energy, and due to the risk
of increased condensation, do not set the
temperature lower than that actually neces-
sary.
Note on useful cooling power:
Interactive performance diagrams for calcu-
lating the useful cooling power may be
found at www.rittal.com.
ON
Status
internal fan
Internal
temperature
Time
Setpoint
-5°C
Setpoint
-10°C
OFF
10 min.
30 sec.
10 min.

Rittal enclosure cooling unit 15
6 Operation
EN
6.1.5 Editable parameters
See also fig. 20 on page 16.
Progr.
level
Display
screen
Parameter Min.
value
Max.
value
Factory
setting
Description
1 St Internal enclosure
temperature set-
point Ti
20°C 55°C 35°C The internal enclosure temperature setting is
preset at the factory to 35°C (95°F) and may be
altered within a range of 20 – 55°C (68 – 131°F).
68°F 131°F 95°F
2 Fi Filter mat monitor-
ing
10°C 60°C 99
(= off)
To enable filter mat monitoring, the display
should be set to a minimum of 10 K (18°F)
above the temperature difference shown in pro-
gramming mode "Fi"; filter mat monitoring is dis-
abled at the factory (99 = off).
18°F 108°F 178
(= off)
3 Ad Master-slave iden-
tifier
0 19 0 See section 6.1.8 "Setting the master/slave
identifier".
4 CF Switch between
°C/°F
0 1 0 The temperature display can be switched be-
tween °C (0) and °F (1). The LED displays the
current unit of temperature.
5 H1 Setting for switch-
ing difference (hys-
teresis)
2 K 10 K 5 K The cooling unit is preset in the factory to a
switching hysteresis of 5 K (9°F). This parameter
should only be changed in consultation with us.
Please contact us for advice.
4°F 18°F 9°F
6 H2 Differential for error
message A2
3 K 15 K 5 K If the internal enclosure temperature exceeds
the set value by more than 5 K (9°F), then error
message A2 (internal enclosure temperature too
high) appears on the display terminal. If neces-
sary, the differential may be altered here within
the range of 3 – 15 K (5 – 27°F).
5°F 27°F 9°F
26 ECO Eco-mode opera-
tion
0 1 1 Eco mode OFF: 0 / Eco mode ON: 1
27 PSO Changing the au-
thorisation code
0 15 0 This parameter allows you to change the "22"
authorisation code (factory setting).
The new code results from the sum of 22 +
PSO.
Tab. 3: Editable parameters

6 Operation
EN
16 Rittal enclosure cooling unit
6.1.6 Programming overview
Fig. 19: Programming overview
= 5 sec.
= 5 sec.

Rittal enclosure cooling unit 17
6 Operation
EN
6.1.7 Defining system messages for evaluation
System messages are shown on the display screen of
the e-Comfort controller via the displays A1 to A20 and
E0.
A more detailed explanation of the system messages
may be found in section 6.1.9 "Evaluating system mes-
sages".
See also fig. 19 on page 16.
The system messages A1 – A19 may also be evaluated
via two floating system message relays. In this way, one
of the two system message relays may be allocated to
each system message.
System message relays with normally open contact, see
wiring diagrams at section 4.6.3 "Installing the power
supply":
– Terminal 3: NO (normally open, relay 2)
– Terminal 4: C (connection of the supply voltage to the
system message relay)
– Terminal 5: NO (normally open, relay 1)
The definition NO refers to the de-energised state. As
soon as power is applied to the cooling unit, both sys-
tem message relays (relay 1 and 2) energise.
This is the normal operating state of the cooling unit. As
soon as a system message occurs or the power supply
is interrupted, the corresponding relay will drop out and
open the contact.
The RiDiag II software (available as an accessory, Model
No. 3159.100) allows you to invert the system message
relay circuit.
In the normal operating state the two relays will then
drop out. If a system message occurs, the relevant relay
will energise and the contact will close.
Progr.
level
Display
screen
Min.
value
Max.
value
Factory
setting
Type or location of fault
7 A1 0 2 0 Enclosure door open
8 A2 0 2 0 Internal temperature of enclosure too high
9 A3 020 Filtermonitoring
10 A4 0 2 0 Ambient temperature too high/low
11A5 020 Icinghazard
12 A6 0 2 1 PSAHpressure switch
13 A7 0 2 2 Evaporator coil
14A8 021 Condensatewarning
15 A9 0 2 1 Condenser fan blocked or defective
16 A10 0 2 1 Evaporator fan blocked or defective
17A11022 Compressor
18A12021 Condenser
19 A13 0 2 1 Ambient temperature sensor
20 A14 0 2 1 Icing temperature sensor
21 A15 0 2 1 Condensate warning temperature sensor
22 A16 0 2 1 Internal temperature sensor
23 A17 0 2 1 Phase monitoring
24A18020 EPROM
25A19020 LAN/Master-Slave
Tab. 4: System messages that can be evaluated via relays
Note:
This setting can only be made using the
RiDiag II software.

6 Operation
EN
18 Rittal enclosure cooling unit
Program system messages with the value
0: System message is not sent to the system mes-
sage relay, but merely appears in the display
1: System message is evaluated by relay 1
2: System message is evaluated by relay 2
6.1.8 Setting the master/slave identifier
When several cooling units are connected together
(maximum ten), one of the cooling units must be defined
as the "master" and the others as "slaves". For this pur-
pose, assign a corresponding identifier (address) to
each cooling unit which will enable the cooling unit to be
identified in the network.
If one of the slave units reaches the set temperature or if
the door limit switch function is activated, the affected
slave unit will report to the master unit, which then deac-
tivates all the other cooling units.
On the master cooling unit (00 = factory setting), set
the number of slave units present in the network:
– 01: Master with 1 slave cooling unit
– 02: Master with 2 slave cooling units
– 03: Master with 3 slave cooling units
– 04: Master with 4 slave cooling units
– 05: Master with 5 slave cooling units
– 06: Master with 6 slave cooling units
– 07: Master with 7 slave cooling units
– 08: Master with 8 slave cooling units
– 09: Master with 9 slave cooling units
On the slave cooling unit (00 = factory setting), set its
own address:
– 11: Slave cooling unit no. 1
– 12: Slave cooling unit no. 2
– 13: Slave cooling unit no. 3
– 14: Slave cooling unit no. 4
– 15: Slave cooling unit no. 5
– 16: Slave cooling unit no. 6
– 17: Slave cooling unit no. 7
– 18: Slave cooling unit no. 8
– 19: Slave cooling unit no. 9
Fig. 20: Master/slave connection (example)
For further connection examples, see section4.6.1 "Bus
connection (only when interconnecting several units with
a Comfort controller)".
For details of how to set the identifier, see section6.1.5
"Editable parameters" or section6.1.6 "Programming
overview", parameter "Ad".
6.1.9 Evaluating system messages
In the e-Comfort controller, system messages are indi-
cated by a number in the display.
Following the appearance of messages A03, A06 and
A07 and after rectifying their cause, you will need to re-
set the e-Comfort controller (see section 6.1.10 "Reset-
ting the e-Comfort controller").
Notes:
– Only one unit may be configured as mas-
ter, and its identifier must match the num-
ber of connected slave units.
– The slave units must have different identi-
fiers.
– The identifiers must be numbered in as-
cending order without any gaps.
Master
02
Slave
11
Slave
12
Display
screen System message Possible cause Measures to rectify the fault
A01 Enclosure door open Door open or door limit switch incor-
rectly positioned
Close door, position door limit switch cor-
rectly, check connection if necessary
A02 Internal temperature of
enclosure too high
Cooling capacity inadequate/unit un-
dersized. Error as a consequence of
messages A03 to A17.
Check cooling capacity
A03 Filter monitoring Filter mat soiled Clean or replace;
reset the e-Comfort controller
A04 Ambient temperature
too high/low
Ambient temperature outside permis-
sible operating range (+10°C to
+60°C)
Raise or lower the ambient temperature
(e.g. heat or ventilate the room)
A05 Icing hazard Operational display in case of icing
hazard.
Evaporator coil fan may be mechani-
cally blocked, defective, or cold air
outlet obstructed.
Set the enclosure interior temperature to a
higher value. Check the evaporator fan;
release or exchange if necessary.
Tab. 5: Troubleshooting with the e-Comfort controller

Rittal enclosure cooling unit 19
6 Operation
EN
A06 PSAHpressure switch Ambient temperature too high Lower the ambient temperature;
reset the e-Comfort controller
Condenser soiled Clean the condenser;
reset the e-Comfort controller
Filter mat soiled Clean or replace;
reset the e-Comfort controller
Condenser fan defective Replace;
reset the e-Comfort controller
E-valve defective Repair by refrigeration engineer;
reset the e-Comfort controller
PSAHpressure switch defective Refrigeration engineer to exchange
reset the e-Comfort controller
A07 Evaporator coil Lack of refrigerant;
Sensor in front of or behind condenser
defective
Repair by refrigeration engineer;
reset the e-Comfort controller
A08 Condensate warning Condensate discharge kinked or
blocked
Check condensate drainage; correct any
kinks or blockages in the hose
Only for units with optional conden-
sate evaporation
Check the evaporation unit, replace if neces-
sary
A09 Condenser fan Blocked or defective Clear the blockage; replace if necessary
A10 Evaporator fan Blocked or defective Clear the blockage; replace if necessary
A11 Compressor Compressor overloaded
(internal winding protection)
No action required;
Unit switches on again independently
Defective
(check by measuring the winding re-
sistance)
Replace by a refrigeration engineer
A12 Condenser tempera-
ture sensor
Open or short-circuit Replace
A13 Ambient temperature
sensor
Open or short-circuit Replace
A14 Icing temperature sen-
sor
Open or short-circuit Replace
A15 Condensate warning
temperature sensor
Open or short-circuit Replace
A16 Internal temperature
sensor
Open or short-circuit Replace
A17 Phase monitoring For three-phase devices only: Incor-
rect rotary field/phase absent
Swap two phases
A18 EPROM error New board installed incorrectly Software update needed (only following
board installation with more recent software):
Enter the programming level with Code 22;
press button 1 and confirm with "Set" until
"Acc" appears. Next, disconnect the unit
from the mains and reconnect.
A19 LAN/Master-Slave Master and slave not connected Check setting and/or cable
Display
screen System message Possible cause Measures to rectify the fault
Tab. 5: Troubleshooting with the e-Comfort controller

7 Inspection and maintenance
EN
20 Rittal enclosure cooling unit
6.1.10 Resetting the e-Comfort controller
After the occurrence of faults A03, A06 and A07, you will
need to reset the e-Comfort controller.
Press buttons 1 () and 3 () (fig. 17) simultaneously
for 5 seconds.
The system messages disappear and the temperature
display is shown.
7 Inspection and maintenance
The cooling circuit is designed in the form of a mainte-
nance-free, hermetically sealed system. The cooling unit
is filled with the required quantity of refrigerant at the fac-
tory, checked for leaks, and subjected to a functional
test run.
The installed maintenance-free fans are mounted on ball
bearings, protected against moisture and dust, and fit-
ted with a temperature monitor. The life expectancy is at
least 30,000 operating hours (L10, 40°C). The cooling
unit is thus largely maintenance-free. All that may be re-
quired from time to time is to clean the components of
the external air circuit using a vacuum cleaner or com-
pressed air if they become visibly dirty. Any stubborn,
oily stains may be removed using a non-flammable de-
tergent, such as degreaser.
Maintenance interval: 2,000 operating hours. Depending
on the level of contamination in the ambient air, the
maintenance interval may be reduced to suit the air pol-
lution intensity.
Sequence of maintenance measures:
– Check the level of dirt.
– Filter soiling? Replace the filter if necessary.
– Cooling membranes soiled? Clean if necessary.
– Activate test mode; cooling function OK?
– Check noise generation of compressor and fans.
7.1 Compressed air cleaning
Fig. 21: Disconnect the mains plug
A20 Voltage drop Error display not shown Event is stored in the log file
E0 Display message Connection problem between the dis-
play and the controller board
Reset: Switch power supply off, then switch
on again after approx. 2 sec.
Cable defective; connection loose Replace the boards
OL Overload Ambient parameters or heat loss outside the applicable limits
LH Low Heat Minimal heat loss in enclosure.
b07 Leak in the cooling cir-
cuit
Sensor B3 and B4 swapped over Swap the sensors
rSt Reset Manual device reset required, see section 6.1.10 "Resetting the e-Comfort controller".
Display
screen System message Possible cause Measures to rectify the fault
Tab. 5: Troubleshooting with the e-Comfort controller
Warning!
The unit is live.
Switch off the power supply before
opening, and take suitable precautions
against it being accidentally switched
back on.
Caution!
Never use flammable liquids for clean-
ing.
This manual suits for next models
40
Table of contents
Popular Air Conditioner manuals by other brands

Friedrich
Friedrich 0 Installation and operation manual

Daikin
Daikin FBQ60BV1 Operation manual

Panasonic
Panasonic S-20LM3HPQ Installation and operation manual

Unitary products group
Unitary products group Sunline 2000 DM180 installation manual

Fedders
Fedders A6K32E7B user manual

Daikin
Daikin RKS22MVLT Removal Procedure