GCHV CHV Mini Series User manual

Commercial AirConditioners
Service
Manual
R410A
Series

CHV Mini VRF 50/60Hz
202105 1
CONTENTS
CONTENTS
Part 1 General Information ................................................................................. 3
Part 2 Outdoor Units …………………….................................................................... 13
Part 3 Installation ............................................................................................... 91
Part 4 Troubleshooting ..................................................................................... 107

CHV Mini VRF 50/60Hz
2202105
CHV Mini Series ServiceManual

CHV Mini VRF 50/60Hz
202105 3
Part 1
General Information
Part 1 - GeneralInformation
1 Indoor and Outdoor Unit Capacities ...................................................... 4
3Nomenclature…………………..................................................................... 7
2 External Appearance.............................................................................. 5
4 Combination Ratio................................................................................. 7
5Features……………................................................................................... 8

4202105
CHV Mini Series ServiceManual
CHV Mini VRF 50/60Hz
1. Indoor and Outdoor Unit Capacities
1.1 Indoor Units
Table 1-1.1: Standard indoor unit abbreviation codes
Abbreviation
code Type
G
Wall
-mounted
UA
Floor
& Ceiling
TA
Low
ESP Short Ducted
TB
Medium
ESP Ducted
TH
High
ESP Ducted
Abbreviation
code Type
Q1
One
-way Cassette
Q2
Two
-way Cassette
Q4
Compact
four-wayCassette
QR
Round
-flow Cassette
FA
Floor Standing
Table 1-1.2: Standard indoor unit capacity range
Capacity Capacity
Q1 Q2 Q4 QR FA G UA TA TB TH
kW index
2.2 22 22 —22 ——22 —22 ——
2.8 28 28 —28 — — 28 —28 ——
3.6 36 36 —36 — — 36 36 36 ——
4.5 45 45 45 45 — — 45 45 45 ——
5.6 56 56 56 —56 —56 56 56 ——
7.1 71 71 71 —71 —71 71 71 71 71
8.0 80 —80 —80 80 —80 —80 80
9.0 90 — — — 90 — — 90 —90 90
10.0 100 — — — 100 100 — — — 100 100
11.2 112 — — — 112 — — 112 — — —
12.0 120 — — — — — — — — 120 120
12.5 125 — — — 125 — — — — — —
14.0 140 ———140 140 —140 — — —
15.0 150 — — — — — — — — 150 150
16.0 160 — — — 160 160 —160 — — —
1.2 Outdoor Units
Table 1-1.3: Outdoor unit capacityrange
Capacity 8kW 10kW 12.5kW 14kW 16kW
Model (1PH) CHV-DH080W/R1 CHV-DH100W/R1 CHV-DH125W/R1 CHV-DH140W/R1 CHV-DH160W/R1
Capacity 12.5kW 14kW 16kW
Model (3PH) GCHV-D125W/HZR1-D01 GCHV-D140W/HZR1-F01 GCHV-D160W/HZR1-F01

CHV Mini VRF 50/60Hz
202105 5
Part 1 - GeneralInformation
2. External Appearance
2.1 Indoor Units
Table 1-2.1: Standard indoor unit appearance
One
-way Cassette
Q1
Two
-way Cassette
Q2
Compact
Four-way Cassette
Q4
Round
-flow Cassette
QR
Floor
Standing
FA
Wall
-mounted
G
Floor
& Ceiling
UA
Low
ESP Short Ducted
TA
Medium
ESPDucted
TB
High
ESP Ducted
TH

CHV Mini VRF 50/60Hz
6202105
CHV Mini Series ServiceManual
2.2 Outdoor Units
Table 1-2.2:Outdoor unit appearance
8kW 10/12.5kW 12.5/14/16kW
Model name Net dimension(mm) Net/Gross weight (kg) Power supply
CHV-DH080W/R1
Width:935
Height:702
Depth:383
47/50 220~240V/1N/50Hz
CHV-DH100W/R1
Width:1032
Height:810
Depth:445
60/65 220~240V/1N/50Hz
CHV-DH125W/R1
Width:1100
Height:870
Depth:528
85/95 220~240V/1N/50Hz
CHV-DH140W/R1
Width:1100
Height:870
Depth:528
90/100 220~240V/1N/50Hz
CHV-DH160W/R1
Width:1100
Height:870
Depth:528
90/100 220~240V/1N/50Hz
GCHV-D125W/HZR1-D01
Width:1032
Height:810
Depth:445
67.4/72.2 380~415V/3N/50Hz
GCHV-D140W/HZR1-F01
Width:1100
Height:870
Depth:528
87.5/97.4 380~415V/3N/50Hz
GCHV-D160W/HZR1-F01
Width:1100
Height:870
Depth:528
90/100 380~415V/3N/50Hz
Table 1-2.3:Outdoor unit specification

CHV Mini VRF 50/60Hz
202105 7
Part 1 - GeneralInformation
4. CombinationRatio
Table 1-4.1: Indoor and outdoor unit combinationratio limitations
Type Minimum combination ratio
Maximum combination ratio
(Standard indoor units)
CHV Mini
Series outdoor units 50% 130%
Combination ratio =
3. Nomenclature
GCHV-D125W/HZR1-D01
Box code
Refrigerant Type
R1: R410A
Power Supply
-- 220~240V, 50Hz,1Ph
Z 380~415V, 50Hz, 3Ph
Function code
H: Heat pump; C: Cooling only
Outdoor Unit
Cooling Capacity (×100W )
All DC Inverter
GCHV
Sum of capacity indexes of the indoorunits
Capacityindex of the outdoorunits

CHV Mini VRF 50/60Hz
8202105
CHV Mini Series ServiceManual
5. Features
5.1 Wide application
The All DC Inverter Mini VRF system is a highly efficient solution for small commercial buildings requiring heating and
cooling of up to 9 zones with one outdoor unit. Such as villa, restaurant, school etc.
GCHV offers various indoor units, more than 100 models of 10 types. Capacity ranges are from 2.2kW to 16kW.It is all
compliance with residential and light commercial place. Our systems can be operated up to 130%of capacity which
allows any system to be designed to the customers’ and applications’ needs.

Compressor
(Twin Rotary)structure
5.3 High performance heat exchanger
The new designed window fins enlarge the heat-exchanging area, which
decrease the air resistance, save more power and enhance heat exchange
performance.
Hydrophilic film fins and inner-grooved copper pipes optimizeheat
exchange efficiency.
5.5 Quick warm-up & cool-down design and less temperature fluctuation
Utilizing the inverter compressor benefits,
the system can reach All load quickly and
shorten warm-up or cool-down time for an
immediate comfortable air solution.
Less temperature fluctuation will create a
better living environment.
5.4 Low-operating sound design
Optimally design fan shape and new designed discharge air grille and air deflector, auxiliary withDC fan motor and
world-famous compressor, making higher air volume and lower operationsound.
5.2 High efficient DC inverter compressor
All DC inverter Mini VRF adopts highly intelligent inverter-driven compressor. This advanced technology enables the
output of the outdoor unit to be modulated by the real heat loaddemands.
This advanced system ensures precise temperature regulation and highly efficient energy usage, making a significant
contribution to the limiting the impact on the environment.
Highly Efficient DCMotor:
- Creative motor core design
- High density neodymiummagnet
- Concentrated type stator
- Wider operating frequencyrange
Better balance and Extremely LowVibration:
- Twin eccentric cams
-2 balance weights
Highly Stable Moving Parts:
- Optimal material matching rollers and vanes
- Optimize compressor drivetechnology
- Highly robust bearings
- Compactstructure
1
2
Temp.
Time
Fluctuation of room temperature
Notn-inverter
Coolingoperation
Inverter
New design Originaldesign
High efficiency inner-thread pipe,
enhance heat transfer.
CHV Mini VRF 50/60Hz
Part 1 - GeneralInformation
202105 9

CHV Mini VRF 50/60Hz
10 202105
CHV Mini Series ServiceManual
5.6 Wide operation temperature range
No matter in extremely cold winter when outdoor
temperature gets as low as -15°C or in hot summer
when temperature is up to 55°C, the Mini VRF system
will keep stable performance.
5.7 Flexible piping design
Piping Length Permitted Value
Total pipe length 100m
Longest pipelength Actual 60m
Equivalent 70m
The first distributor to the lastIDU 20m
Height differencebetween
IDU~ODU
ODU above 30m
ODU below 20m
Height difference betweenIDU~IDU 8m
Table 1-5.1: Pipingparameters
5.8 Auto address setting function
The addresses of indoor units can be set automatically by outdoor unit. It has capability to reduce artificial faults and
manual works.
Wireless or wired controller can enquire and modify the address of each indoor unit.
Outdoor unit can
distribute address
for indoor unit
automatically. Shield signal wire
Wireless or wired controller can enquire
and modify address of each IDU.
5.9 Smart electronic control design
The radiation fin is made of aluminum panels fitting together seamlessly. This helps to cool down the IPM, it has better
performance compared to air cooling for PCB.
With PFC(Power Factor Corrector) module, the power utilization rate is increased, the power factor is capable to be 98%,
lead to higher efficiency.

CHV Mini VRF 50/60Hz
Part 1 - GeneralInformation
202105 11
5.10 Easy installation
The Mini VRF can be transported by elevator which makes
installation dramatically easy, and effectively reduces time and
labor thanksto the small size.
The Mini VRF units are more compact, resulting in significant
savings in installation space. It is particularly suitable for small
offices, villas, shops,etc.
5.11 Easy maintenance
Forced cooling button makes outdoor unit run in cooling mode at any
condition, so it is very easy for you to charge refrigerant to the system
when it needs to be done. The self-diagnosis function detects
malfunctions in major locations in the system and displays the type of
malfunction and location. This allows service and maintenance to be
performed moreefficiently.
Easy totransport

CHV Mini VRF 50/60Hz
12 202105
CHV Mini Series ServiceManual

CHV Mini VRF 50/60Hz
202105 13
Part 2 - Outdoor Units
Part 2
Outdoor Units
1 Specifications ...................................................................................... 14
2Dimensions ......................................................................................... 17
3 Service Space ...................................................................................... 18
4 Piping Diagrams .................................................................................. 19
5 Wiring Diagrams ................................................................................. 20
6 Field Wiring ........................................................................................ 23
7 Capacity Tables ................................................................................... 24
8 Electric Characteristics ........................................................................ 88
9 Sound Levels ....................................................................................... 89
10 Operation Limits ................................................................................. 90

14 202105
CHV Mini Series Service Manual
CHV Mini VRF 50/60Hz
1. Specifications
Model name CHV-DH080W/R1 CHV-DH100W/R1
CHV-DH080W/NR1 CHV-DH100W/NR1
Power supply 220~240V/1N/50Hz 220~240V/1N/50Hz
220~240V/1N/60Hz 220~240V/1N/60Hz
Condition T1 T3 T1 T3
Performance
data
Cooling
Capacity
HP 3 3.6
kW 8 7.2 10 9
Btu/h 27300 24570 34100 30690
RT 2.27 2.04 2.84 2.56
Power input
kW 2.60 2.81 3.00 3.25
Rated
current A 11.8 14.2 13.6 16.4
EER
W/W 3.08 2.56 3.33 2.77
Heating
Capacity
kW 911
Btu/h 30700 37500
RT 2.56 3.13
Power input
kW 2.65 3.10
Rated
current A 12.0 14.0
COP
W/W 3.40 3.55
Max. input
consumption kW 3.96 4.40
Max. current
A18 20
Capacity adjustment
range 50%~130% 50%~130%
Max. connected indoor unit
quantity 4 5
Compressor
data
DC Inverter
compressor
Quantity
1 1
Type
Twin-rotary Compressor Twin-rotary Compressor
Brand
Mitsubishi GMCC
Model
SNB200FGMMC ATM240D57UMT
frequency
range Hz 10~120 10~120
Crankcase
heater W 25 35
Compressor
oil
Model
FV50S VG74
Original oil
volume ml 400 670
Fan
data
Fan
motor
Type
DC DC
Brand
Yongan Yongan
Model
DRN-310-75-8 DRN-310-90-8
Quantity
1 1
Insulation
class B B
Protection class
IPX4 IPX4
Power output
W75 90
Fan
blade
Material
ASG20 ASG20
Type
Axial Axial
Drive
Direct-driven Direct-driven
Fan
Quantity 1 1
Air
flow m3/h 3300 4000
Physical
data
Outdoor coil
Fin
type Hydrophilic Aluminum Hydrophilic Aluminum
Tube diameter
mm Ø7 Ø 9.52
Number of
rows 3 2
Coil length x height x
width mm 784×630×40.11 1003×750×43.3
Tube type
Inner-grooved copper tube Inner-grooved copper tube
Refrigerant
Type
R410a R410a
Volume
kg 2.0 2.6
Throttle
type EXV EXV
Dimension
(W*H*D)
Net
mm 935×702×383 1032×810×445
Packing
mm 975×770×420 1075×875×495
Weight
Net
kg 47 60
Gross
kg 50 65
Outdoor sound
level dB(A) ≤54 ≤56
Maximum operating
pressure MPa 4.5 4.5
Piping & wiring
data
Pipe size
Liquid
pipe mm Ø 9.52 Ø 9.52
Gas
pipe mm Ø 15.88 Ø 15.88
Connection
wire
Power wire size
mm23×4.0 3×4.0
Signal wire
type 3-core shielded cable 3-core shielded cable
Signal wire
size mm21.0 1.0
Operation temperature
range
Cooling
Outdoor side
°C -5~55 -5~55
Indoor
side °C 16~32 16~32
Heating
Outdoor side
°C -15~30 -15~30
Indoor
side °C 16~32 16~32

202105 15
CHV Mini VRF 50/60Hz
Part 2 - Outdoor Units
Model name CHV-DH125W/R1 CHV-DH140W/R1 CHV-DH160W/R1
CHV-DH125W/NR1 CHV-DH140W/NR1 CHV-DH160W/NR1
Power supply 220~240V/1N/50Hz 220~240V/1N/50Hz 220~240V/1N/50Hz
220~240V/1N/60Hz 220~240V/1N/60Hz 220~240V/1N/60Hz
Condition T1 T3 T1 T3 T1 T3
Performance
data
Cooling
Capacity
HP 4.5 5 5.7
kW 12.5 11.3 14 12.7 16 14.5
Btu/h 42600 38340 47800 43020 54600 49140
RT 3.55 3.20 3.98 3.58 4.55 4.10
Power input
kW 3.20 3.46 3.75 4.06 4.75 5.14
Rated
current A 14.5 17.5 17.0 20.5 21.8 25.96
EER
W/W 3.91 3.27 3.73 3.13 3.37 2.82
Heating
Capacity
kW 14 16 17
Btu/h 47800 54600 58000
RT 3.98 4.55 4.83
Power input
kW 3.52 4.00 4.40
Rated
current A 16.1 18.2 20.0
COP
W/W 3.98 4.00 3.86
Max. input
consumption kW 7.48 7.48 7.48
Max. current
A34 34 34
Capacity adjustment
range 50%~130% 50%~130% 50%~130%
Max. connected indoor unit
quantity 7 8 9
Compressor
data
DC Inverter
compressor
Quantity
1 1 1
Type
Twin-rotary Compressor Twin-rotary Compressor Twin-rotary Compressor
Brand
Mitsubishi Mitsubishi Mitsubishi
Model
MNB40FEQMC MNB40FEQMC MNB40FEQMC
frequency
range Hz 10~120 10~120 10~120
Crankcase
heater W 35 35 35
Compressor
oil
Model
FV50S FV50S FV50S
Original oil
volume ml 1100 1100 1100
Fan
data
Fan
motor
Type
DC DC DC
Brand
Nidec Nidec Nidec
Model
DR-310-180-8 DR-310-180-8 DR-310-180-8
Quantity
1 1 1
Insulation
class E E E
Protection class
IP44 IP44 IP44
Power output
W180 180 180
Fan
blade
Material
ASG20 ASG20 ASG20
Type
Axial Axial Axial
Drive
Direct-driven Direct-driven Direct-driven
Fan
Quantity 1 1 1
Air
flow m3/h 5500 5500 5500
Physical
data
Outdoor coil
Fin
type Hydrophilic Aluminum Hydrophilic Aluminum Hydrophilic Aluminum
Tube diameter
mm Ø7 Ø7 Ø7
Number of
rows 2 3 3
Coil length x height x
width mm 1145×798×38.8 1145×798×58.2 1145×798×58.2
Tube type
Inner-grooved copper Inner-grooved copper Inner-grooved copper
Refrigerant
Type
R410a R410a R410a
Volume
kg 3.0 3.8 3.8
Throttle
type EXV EXV EXV
Dimension
(W*H*D)
Net
mm 1100×870×528 1100×870×528 1100×870×528
Packing
mm 1140×965×540 1140×965×540 1140×965×540
Weight
Net
kg 85 90 90
Gross
kg 95 100 100
Outdoor sound
level dB(A) ≤56 ≤57 ≤57
Maximum operating
pressure MPa 4.5 4.5 4.5
Piping & wiring
data
Pipe size
Liquid
pipe mm Ø 9.52 Ø 9.52 Ø 9.52
Gas
pipe mm Ø 15.88 Ø 15.88 Ø 15.88
Connection
wire
Power wire
size mm23×6.0 3×6.0 3×6.0
Signal wire
type 3-core shielded cable 3-core shielded cable 3-core shielded cable
Signal wire
size mm21.0 1.0 1.0
Operation temperature
range
Cooling
Outdoor side
°C -5~55 -5~55 -5~55
Indoor
side °C 16~32 16~32 16~32
Heating
Outdoor side
°C -15~30 -15~30 -15~30
Indoor
side °C 16~32 16~32 16~32

Model name GCHV-D125W/HZR1-D01 GCHV-D140W/HZR1-F01 GCHV-D160W/HZR1-F01
GCHV-D125W/HYR1-D01 GCHV-D140W/HYR1-F01 GCHV-D160W/HYR1-F01
Power supply 380~415V/3N/50Hz 380~415V/3N/50Hz 380~415V/3N/50Hz
380~415V/3N/60Hz 380~415V/3N/60Hz 380~415V/3N/60Hz
Condition T1 T3 T1 T3 T1 T3
Performance
data
Cooling
Capacity
HP 4.5 5 5.7
kW 12.5 11.3 14 12.7 16 14.5
Btu/h 42600 38340 47800 43020 54600 49140
RT 3.55 3.20 3.98 3.58 4.55 4.10
Power input
kW 3.20 3.46 3.75 4.06 4.75 5.14
Rated
current A 6.0 7.2 7.0 8.4 8.8 10.6
EER
W/W 3.91 3.27 3.73 3.13 3.37 2.82
Heating
Capacity
kW 14 16 17
Btu/h 47800 54600 58000
RT 3.98 4.55 4.83
Power input
kW 3.52 4.00 4.40
Rated
current A 6.6 7.5 8.2
COP
W/W 3.98 4.00 3.86
Max. input
consumption kW 6.3 7.07.5
Max. current
A13 15.5 17.5
Capacity adjustment
range 50%~130% 50%~130% 50%~130%
Max. connected indoor unit
quantity 7 8 9
Compressor
data
DC Inverter
compressor
Quantity
1 1 1
Type
Twin-rotary Compressor Twin-rotary Compressor Twin-rotary Compressor
Brand
HIGHLY HIGHLY Mitsubishi
Model
ATH307CDPC8DQ ATH307CDPC8DQ MNB40FEQMC
frequency
range Hz 15~120 15~120 10~120
Crankcase
heater W 35 35 35
Compressor
oil
Model
RMM68EA RMM68EA FV50S
Original oil
volume ml 8508501100
Fan
data
Fan
motor
Type
DC DC DC
Brand
Kaibang/Yongan Yongan/Weiling Yongan/Weiling
Model
DRN-310-90-8 DR-310-180-8 DR-310-180-8
Quantity
1 1 1
Insulation
class B E E
Power output
W 90 170 170
Fan
blade
Material
ASG20 ASG20 ASG20
Type
Axial Axial Axial
Fan
Quantity 1 1 1
Air
flow m3/h 4000 5500 5500
Physical
data
Outdoor coil
Fin
type Hydrophilic Aluminum Hydrophilic Aluminum Hydrophilic Aluminum
Tube diameter
mm Ø 9.52 Ø7 Ø7
Number of
rows 2.5 3 3
Coil length x height x
width mm 1003×750×43.3
580×750×21.65 1145×798×58.2 1145×798×58.2
Tube type
Inner-grooved copper Inner-grooved copper Inner-grooved copper
Refrigerant
Type
R410a R410a R410a
Volume
kg 3.0 3.45 3.8
Throttle
type EXV EXV EXV
Dimension
(W*H*D)
Net
mm 1032×810×4451100×870×528 1100×870×528
Packing
mm 1075×875×4951140×965×540 1140×965×540
Weight
Net
kg 67.4 87.5 90
Gross
kg 72.2 97.4 100
Outdoor sound
level dB(A) ≤56 ≤57 ≤57
Maximum operating
pressure MPa 4.5 4.5 4.5
Piping & wiring
data
Pipe size
Liquid
pipe mm Ø 9.52 Ø 9.52 Ø 9.52
Gas
pipe mm Ø 15.88 Ø 15.88 Ø 15.88
Connection
wire
Power wire
size mm25×2.5 5×2.5 5×2.5
Signal wire
type 3-core shielded cable 3-core shielded cable 3-core shielded cable
Signal wire
size mm21.0 1.0 1.0
Operation temperature
range
Cooling
Outdoor side
°C -5~55 -5~55 -5~55
Indoor
side °C 16~32 16~32 16~32
Heating
Outdoor side
°C -15~30 -15~30 -15~30
Indoor
side °C 16~32 16~32 16~32
Notes:
1. The cooling conditions: indoor side 27°C(80.6°F) DB, 19°C(60°F)WB outdoor side 35°C(95°F) DB.
2. The heating conditions: indoor side 20°C(68°F) DB, 15°C(44.6°F)WB outdoor side 7°C(42.8°F)DB.
3.Sound level: measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher
as a result of ambient conditions.
4. The company reserves the right to revise product technical parameter without having to notify the clients individually.
CHV Mini VRF 50/60Hz
16 202105
CHV Mini Series Service Manual

2. Dimensions
CHV-DH080W/R1
CHV-DH100W/R1
GCHV-D125W/HZR1-D01
CHV-DH125W/R1
CHV-DH140W/R1
CHV-DH160W/R1
GCHV-D140W/HZR1-F01
GCHV-D160W/HZR1-F01
CHV Mini VRF 50/60Hz
Part 2 - Outdoor Units
202105 17

3. Service Space
3.1 Single unit installation
>300
>600
>2000
Air outlet
Air inlet
Air inlet
>300
3.2 Parallel connect the two units or above
>600
CHV Mini VRF 50/60Hz
CHV Mini Series Service Manual
18 202105

Oil separator: It is used to separate oil from high pressure & temperature gas refrigerant that is pumped out from
compressor. The separation efficiency is up to 99%, it makes the oil return back to each compressor very soon.
Gas-liquid separator: It is used to store the liquid refrigerant and oil, it can protect the compressor from liquid hammer.
4-way valve: Closed in cooling mode and open in heatingmode.
Electronic expansion valve: The opening is of the valve is regulated according to the discharge air temperature of
compressor, used to regulating refrigerantflow.
High Pressure Switch: When the discharge pressure of compressor is 4.5Mpa or higher, the protection
switch will be triggered, and if the discharge pressure is down to 3.5MPa, the protection switch will be recovered.
Low Pressure Switch: When the gas pressure back to compressor is 0.05Mpa or lower, the protection switch will be
triggered, and if the discharge pressure is down to 0.15MPa, the protection switch will be recovered.
4. PipingDiagrams
Electronic
expansion Evaporator
valve
Highpressure
switch Electronic
Condensor
expansion
valve
Oil seperator
Oil return
capilary
Compressor
Low Low
pressure pressure
switch liquid
accumulator can
CHV Mini VRF 50/60Hz
Part 2 - Outdoor Units
202105 19
This manual suits for next models
8