Graco 24E267 User manual

3A1937C
EN
Instructions
Heated Platen Kits
For heating bulk supply of medium to high viscosity sealant and adhesive materials for
VPM systems. Not for use in hazardous locations. Intended for indoor use only.
24E267
Heated platen kit, high volume
24E268
Heated platen kit, low volume
Important Safety Instructions
Read all warnings and instructions in VPM,
Instructions manuals. Save all instructions.

23A1937C
Contents
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
System Description . . . . . . . . . . . . . . . . . . . . . . . 3
Power Requirements . . . . . . . . . . . . . . . . . . . . . 3
Component Identification . . . . . . . . . . . . . . . . . . . . 4
Kit Components . . . . . . . . . . . . . . . . . . . . . . . . . 4
Temperature Control Module . . . . . . . . . . . . . . . 5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Power Requirements . . . . . . . . . . . . . . . . . . . . . 6
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Temperature Control Module . . . . . . . . . . . . . . 16
Platen Maintenance . . . . . . . . . . . . . . . . . . . . . 17
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Common Problems . . . . . . . . . . . . . . . . . . . . . . 18
Temperature Control Module . . . . . . . . . . . . . . 21
Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Replace Platen Heaters and Sensor . . . . . . . . . 22
Replace High Power Temperature Control Module
23
Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Platen Heater Kits, 24E267 and 24E268 . . . . . 24
Heat Panel Module, 24K203 and 24K204 . . . . . 26
Heater Platen Assembly, 24C493 . . . . . . . . . . . 28
Graco Standard Warranty . . . . . . . . . . . . . . . . . . . 30
Graco Information . . . . . . . . . . . . . . . . . . . . . . . . . 30

Overview
3A1937C 3
Overview
System Description
The heated platen kit is a field installed kit to add heat to
the platen. The additional heat may change the viscosity
properties of the material and allow the material to flow
easier through the system.
The heat is controlled by Graco Control Architecture
components: High Power Temperature Control Modules
(HPTCM) and the display module. The display module
provides the user interface for the entire VPM system.
Power Requirements
A 20A (minimum) - 30A (maximum) circuit breaker must
be installed on the incoming power supply.
* Add to power requirements of VPM system. Amps
maximum per leg shown.
Voltage Wattage
Amps*
1 Heated Platen 2 Heated Platens
230 V 3,500 per Platen 17 27
400V 17 34

Component Identification
43A1937C
Component Identification
Kit Components
Key:
1 RTD Temperature Sensor
2HeaterCoil
3 Temperature Limit Switch
4 Junction Box
5 High Power Temperature Control Module (HPTCM)
6Relay
1
2
3
4
5
6

Component Identification
3A1937C 5
Temperature Control Module
Key:
1N/A
2 RTD Temperature Sensor Connection
3 Output Power Connection
4 DC Output Connection
5 Input Power Connection
6 CAN Connections
7 Rotary Selector Switch, Token Access
Adjust Rotary Switch
The rotary switch setting indicates which zone the tem-
perature control module will control in the system. The
high power module uses an 8-position rotary switch.
Set the rotary switch (S) to the specific selection accord-
ing to the settings listed in the following table.
FIG. 1: High Power Temperature Control Module Sensor Connections
1
2
3
5
4
6
LED
Signals
7
ti12352a1 ti12353a1
Setting Zone
0NotUsed
1 B (Blue) Primary Heat
2NotUsed
3 A (Red) Primary Heat
4NotUsed
5NotUsed
6NotUsed
7NotUsed
FIG. 2
High Power Module Rotary Switch Location
S
ti12360a

Installation
63A1937C
Installation
Power Requirements
Ensure that the electrical panel located within the Power Distribution Box has the correct circuit breakers for installing
the kit. If the current Power Distribution Box does not have this configuration, contact your local distributor inquiring
about a Power Distribution Box upgrade kit.
Grounding
Ground the system as instructed within this manual.
Setup
1. Access the Platen
a. Perform Remove Drum Procedure found in
VPM Instructions manuals.
b. Perform Shutdown Procedure found in VPM
Instructions manuals.
c. Thoroughly clean all material that may be found
on the top of the platen.
d. Turn off all sources of power to the machine.
To avoid serious injury or machine damage, all
electrical connections need to be done by a qualified
electrician familiar with local codes.
The equipment must be grounded to reduce the risk
of static sparking and electric shock. Electric or static
sparking can cause fumes to ignite or explode.
Improper grounding can cause electric shock.
Grounding provides an escape wire for the electric
current.

Installation
3A1937C 7
2. Install Heat Coils and Thermostat Switch
Install both heat coils onto the platen as shown below.
3. Connect Ground Wires
Connect ground wires to the terminal lug and platen covers (not shown in view). Attach conduit to platen cover (not
shown) and route wires through the conduit when connections are complete.
- (6) 1/4-20 Stud
- (6) Flat Washer
- (6) Lock Washer
- (6) Nut
- (1) Thermostat
- (2) Screws
- (3) Ground Wires
- (2) Lock Wasers
- (2) Nuts
- (1) Ground Screw

Installation
83A1937C
4. Connect Power Leads
Connect leads as shown below. Route all wires through conduit when connections are complete.
5. Mount RTD
Mount RTD as shown below. Route wire through conduit when connections are complete.
- (2) “B” Leads
- (3) “A” Leads
- (1) RTD
- (1) Washer
- (1) M5 Screw

Installation
3A1937C 9
6. Attach Platen Covers
7. Mount Junction Box
NOTICE
To prevent damage to wires, ensure wires are not
pinched when assembling and securing platen cov-
ers.
- (1) Conduit
- (1) Knob
- (2) Covers
- (1) Plug
- (1) Knob
- (2) 3/8-16 Bolts
- (4) #10-32 Screws
- (4) Lock Washers
- (1) Conduit from
platen

Installation
10 3A1937C
8. Route Power Cord and Signal Cable
Route power cord and signal cable as shown below. It is recommended to start from the cube base and route to junc-
tion box.
9. Connect Leads in Junction Box
Connect “A” leads, “B” leads, ground, and signal cable within junction box.
Routing
Cord and cable to be
routed under cover

Installation
3A1937C 11
10.Mount New Electrical Panel in Power Pack Base Cube
a. Disconnect all auxiliary components (fans) from existing electrical panel.
b. Remove existing electrical panel.
c. Mount electrical panel that came with the kit into the base cube.
d. Connect power cable and signal cable (routed in previous step) to High Power Temperature Control Module
as shown below.
- (1) Power Cable
- (1) Signal Cable

Installation
12 3A1937C
11.Reconnect Auxiliary Components
Reconnect auxiliary components (fans) to the electrical panel shown below.
DC Power Pack
Fan Leads
Base Cube Fan
Leads
Power Leads

Installation
3A1937C 13
12.Route Power Cable from Distribution Box to Base Cube
Route power cable from distribution box to base cube as shown below.
Power Leads
from either “A” or
“B” breaker as
applicable
Power Junction
Connector
Ground Terminal
Ground Terminal

Installation
14 3A1937C
13.Sensor Resistance Checks
The heated platen system includes a heat sensor and
controller for each of the two optional heated zones. To
check sensor resistance:
1. Make sure the power is off and that the disconnect
switch is in the OFF position.
2. Make electrical resistance checks for the compo-
nents.
3. Replace any parts that have resistance readings
that do not comply with the ranges listed in Table 1.
NOTE: Check resistance at ambient room tempera-
ture (63°– 77°F [17°– 25°C]).
14.Heater Resistance Checks
To check heater resistance:
1. Make sure the power is off and that the disconnect
switch is in the OFF position.
2. Make electrical resistance checks for the compo-
nents. Refer to Table 2. Heater terminal pins are
connected to the HPTCM.
3. Replace any parts whose resistance readings do
not comply with the ranges listed in Table 2.
NOTE: Check resistance at ambient room tempera-
ture (63°– 77°F [17°– 25°C]).
Conduct these electrical checks with the main dis-
connect OFF.
Table 1: RTD Sensor Resistance
Zone Component Connector Pin Range (ohms)
1, 2 Platen Pin 1 to 3 1050-1100
FIG. 3: RTD Connector Pins
Conduct these electrical checks with the main power
disconnect OFF.
Table 2: Resistance Chart of All Heaters
Zone Component
Between
Terminals
Unit
Voltage
Range
(ohms)
1, 2 Platen 1 and 3 240 15 +5/-5
FIG. 4: Heater Terminal Pins
1
3

Setup
3A1937C 15
Setup
For individual screen shot details, refer to VPM Instruc-
tions manual.
1. Make sure the power is on and that the disconnect
switch is in the ON position.
2. Navigate to Conditioning Screen 1 and select the
appropriate heater.
3. Navigate to Conditioning Screen 2 to verify proper
selection of heaters is correct.
4. Press and navigate to the component you
wish to edit the temperature setpoint and alarm.
5. Press the enter key to display the setpoint and
alarm values associated with that component.
6. Edit the setpoint and alarm values and then press
the page back button to return to the previous
screen.
1. Navigate to the Status Screen, Conditioning Con-
trol Screen.
2. Press to enter the Conditioning Control
screen.
3. Use the arrows keys to navigate to the desired
zone.
4. Press to turn the selected zone on. When a
zone is on, the button will be selected. Press the
button again to turn the zone off.
Zone
Setting Color Definition
OFF Black Dispense Disabled
Grey Dispense Allowed
ON Yellow Dispense Disabled
Green Dispense Allowed

Maintenance
16 3A1937C
Maintenance
Temperature Control Module
Clean
Keep heat sink fins clean at all times. Wipe the fins
clean with a dry cloth or clean them using compressed
air.
NOTE:
Do not use conductive cleaning solvents on the tem-
perature control modules.
Install Upgrade Token
NOTE: The Motor Control Module, Fluid Control Mod-
ule, and Temperature Control Module connection to the
system is temporarily disabled during the installation of
upgrade tokens.
To install software upgrades:
1. Use correct software token stated in the table. See
Graco Control Architecture™Module Programming
manual for instructions.
NOTE: Upgrade all modules in the system to the
software version on the token, even if you are
replacing only one or two modules. Different soft-
ware versions may not be compatible.
All data in the module (System Settings, USB Logs,
Recipes, Maintenance Counters) may be reset to
factory default settings. Download all settings and
user preferences to a USB before the upgrade, for
ease of restoring them following the upgrade.
See manuals for locations of specific GCA compo-
nents.
The software version history for each system can be
viewed in the technical support section at
www.graco.com.
FIG. 5: Clean Heat Sink Fins
ti12353a1
Heat Sink Fins
Token Application
16G365 VPM:
- High Power Temperature Control Module
FIG. 6: Remove Access Cover
ti12354a1

Maintenance
3A1937C 17
Platen Maintenance
If the platen does not come out of the pail easily when
the pump is being raised, the air assist tube or check
valve may be plugged. A plugged valve prevents air
from reaching the underside of the plate to assist in rais-
ing it from the pail.
1. Turn off main disconnect.
2. Relieve pressure and disassemble air assist valve.
Refer to Supply Systems Repair-Parts manual.
3. Clear air assist tube in platen. Clean all parts of
valve and reassemble. Refer to Supply Systems
Repair-Parts manual.
4. Remove bleed stick from platen. Push bleed stick
through bleed relieve port (T) to remove material
residue. See FIG. 7.
5. Remove platen covers. See FIG. 7.
a. Remove platen cover fasteners (70).
b. Remove both platen covers (49) and ground
wire from platen.
6. Remove any excess fluid. Use a soft wire brush on
heater coils (48). See FIG. 7.
7. Inspect platen heater blocks (43) or heater (48) for
burn or melt spots. Replace platen heater if neces-
sary. See FIG. 7.
8. Check for loose connections and damaged wires.
9. Follow steps in reverse order to reassemble platen.
NOTE: Torque platen cover fasteners (70) to 60 +/-
10 in-lbs (6.8 +/- 1.1 N•m) for 55 gallon platen.
Remove and Reinstall Platen Wipers
Refer to Supply Units Repair-Parts manual for instruc-
tions.
FIG. 7: Remove Platen Covers and Heaters
r_wm2179_313296_6a
70
Bleed
Stick
49
48
43
T

Troubleshooting
18 3A1937C
Troubleshooting
Before performing any troubleshooting procedure:
1. Perform Pressure Relief Procedure found in vpm
Instructions manuals.
2. Turn main power OFF.
3. Allow equipment to cool.
Try the recommended solutions in the order given for
each problem, to avoid unnecessary repairs. Also,
determine that all circuit breakers, switches, and con-
trols are properly set and wiring is correct before assum-
ing there is a problem.
Common Problems
Problem Cause Verification Solution
Heating is slow. Heater defective. Measure resistance of
heater.
Follow Heater Resistance
Checks, page 14.
Low power. Measure voltage across cir-
cuit breakers. Voltage
should measure between
190 and 275 Vac.
1. If voltage is lower than
expected, use electrical
schematic to locate
faulty wiring or connec-
tion.
2. Have a qualified electri-
cian service electrical
components.
Heating over shoots. Shorted module. Verify for given zone that
temperature does not
increase when zone is dis-
abled.
Verify RTD wire or heater
power cord is attached to
correct heat module.
Replace module.

Troubleshooting
3A1937C 19
Missing module. Modules not on network. Verify attached modules
through Advanced Setup
screens 4 and 5.
Enter Setup screen and
scroll to Advanced Setup
screens 4 and 5. These
screens lists all compo-
nents corresponding soft-
ware revision number on
network.
Cable disconnected. Verify all green LEDs are
illuminated and yellow
LEDs are flashing.
Reconnect/replace faulty
cable.
Module with wrong rotary
switch setting.
Verify rotary switch is set
correctly.
1. Remove power from
unit.
2. Remove access cover
and visually check
rotary switch setting.
3. If incorrect, set to cor-
rect setting. See
Adjust Rotary Switch,
page 5, for selector
switch locations.
4. Replace access cover.
Problem Cause Verification Solution

Troubleshooting
20 3A1937C
No heat. Tripped circuit breaker. Visually check circuit
breaker for a tripped condi-
tion.
Determine cause of tripped
circuit breaker. Then repair
fault and reset main circuit
breaker.
Low power. Measure voltage across cir-
cuit breakers. Voltage
should measure between
190 and 275 Vac.
1. If voltage is lower than
expected, use electrical
schematic to locate
faulty wiring or connec-
tion.
2. Have a qualified electri-
cian service electrical
components.
Cable unplugged/loose
wire.
Check for loose or discon-
nected wires and plugs.
Attach plug/wire.
Circuit breaker tripped. Visually check circuit
breaker for a tripped condi-
tion.
Determine fault that caused
circuit breaker to trip.
Repair fault, and reset cir-
cuit breaker.
Zone not enabled. Verify zone is enabled on
Heat Run screen.
Enter Setup screen and
enable correct zone.
Incorrect temperature set
point.
Verify zone has a correct
temperature setting on
Heat Run screen.
Enter Setup and enter cor-
rect temperature.
Bad heater. Measure resistance of
heater.
1. Unplug suspected
heater zone from
heater module.
2. Follow Heater Resis-
tance Checks, page
14.
3. If resistance is outside
allowable value,
replace heater(s).
Contactor not closing. Turn on heat for zone A1 or
B1and ensure contactor
closes.
1. Verify that there are no
other error conditions
that would prevent
heater from starting.
2. Replace contactor.
Problem Cause Verification Solution
This manual suits for next models
1
Table of contents
Popular Range manuals by other brands

Frigidaire
Frigidaire PLGF390D Factory parts catalog

GE
GE Profile JB988KHCC Dimensions and installation information

Viking
Viking VGSC3674BSS use and care manual

Frigidaire
Frigidaire FGFS56FSA Use & care manual

Frigidaire
Frigidaire FEFL64DSG Service data sheet

GE
GE JGBP86SEMSS Dimensions and installation information